Professional Documents
Culture Documents
April 2014
ComAp a.s..
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Tel: +420 266 790 611, Fax: +420 266 316 647
Technical support hotline: +420 266 790 666
Copyright © 2014 ComAp a.s
E-mail: info@comap.cz, www.comap.cz
Table of Contents
Table of Contents ...............................................................................................................................................2
General guidelines ..............................................................................................................................................3
What is described in this manual? .................................................................................................................3
Used abbreviations ........................................................................................................................................3
SynchroScope mode ..........................................................................................................................................4
Safety requirements .......................................................................................................................................6
Default configuration ......................................................................................................................................7
HW note ..............................................................................................................................................................8
Worldwide there are dozens of different Marine certifications with different requirements and rules.
Purpose of this manual is explanation of notes/condition from our Marine certificates and illustration of
recommended solution. The manual contains recommendations and conditions which were mentioned by
certification engineer during certification process and they condition validation of certification. For completely
certification of ship is necessary to comply all rules of a relevant Marine certification.
At each part this document is specified type of Marine certification, for which is this part relevant.
Used abbreviations
GL: Separate synchroniser is required. (for synchronisation process and closing the breaker is neccesary to
double check of synchronism - from two independent equipment/ controllers.
IGS-NT
BO: GCBCloseEna SynchroScope
application
3xVG
3xVB
GCB
BUS
3x 3x
3xVB
3xVG
BO: GCBCloseEna
BO: GCBCloseEna
IGS-NT
Gen-set
BI: GCB Disable or
Generator
controller
IGS-NT controller in „SynchroScope application“ all the time evaluates voltages and frequency from right and
left side and in case of synchronism binary output „GCBCloseEna“ is activated.
(Binary output „In synchronism" is activated in case of synchronism only, binary output „GCBCloseEna is
active in case of synchronisation and in case of dead bus)
This binary output (GCBCloseEna) is connected to the main gen-set/generator controller to binary input
„GCB disable“ for blocking the closing the breaker without double check of synchronisation.
Binary output for control of breaker is secured/blocked by signals from both controllers (close the breaker is
possible when the conditions for closing the breaker have been met in both controllers (voltages in
synchronism or no voltage on the bus).
No voltage on bus (dead bus) and closing the breaker to dead bus occurs in case of black out on the ship
only.
Double check in case of synchronisation process before closing breaker is strictly required for
certification of ships according to Germanischer Lloyd certification.
In primary controller must be connected signal GCBCloseEna from SynchroScope to binary input
GCB Disable for ensure double check of synchronisation.
For bigger engines is necessary to use additional, independent equipment for Emergency stop, Over speed,
Low oil pressure and Over current protection.
The maximal wire length for Binary (Analog) inputs and outputs should be less than 10 meters, otherwise the
separation relay or additional protection has to be used.
12 3
I-RB16 ( I-RB8 )
K17 K18
+PWR BOUT
BO 1
BO 6
BO 8
BO 9
BO 2
BO 3
BO 4
BO 5
BO 7
IS-NT (IG-NT)
+24VDC
0 VDC
BI 10
BI 11
BI 12
BI 13
BI 14
BI 15
BI 16
BI 1
BI 6
BI 8
BI 9
BI 2
BI 3
BI 4
BI 5
BI 7
- +
In the case of longer distance wires the additional protection has to be used for Signal inputs and
Outputs close to controller terminals. Protection is available on request in ComAp.
IG-NT or IS-NT
14DK390 14DK220
3x 14DK390
1N4007
IG-NT or IS-NT
controller
+24VB from battery
+24VB
0VB
-24VB from battery
The I-LBA (low battery adaptor) module is to be used when power supply voltage dip up to 200ms is
required. The up to 100ms supply voltage dip is acceptable by IG-NT or IS-NT controller itself.
IS-NT (IG-NT)
+24VDC
0 VDC
Default configuration
Default configuration can be modified using the GenConfig-3.0 (or higher) PC tool. Please take care of
following items that are included in default configuration file:
- The function "Virtual Peripheries" shall not be used for marine application.
- An automatic start of the generator after acknowledgement of alarm shall be prevented (Basic settings:
FltResGoToMAN = ENABLED).
- Common alarm contacts interfacing the machinery alarm system shall be re-triggered in case of occurring
new alarm" (BO5 = Alarm flashing).
Override function
The “Sd override” (Shut-down override) function is included in default configuration on Binary input BI7.
Active Override is indicated by a " ! " mark on the display and on Binary output BO4 Common SdOvr.
The default Override function blocks all protections except the Overspeed, Emergency stop and all Analog or
Binary protections configured as SD Override. It is strongly recommended to modify names of such values to
begin with letters SDO (e.g. SDO BearingTmp for Bearing temperature).
Warning
Peripheral modules Inteli AIN8, Inteli AIN8TC and Inteli IO8/8 meet the test of Electrostatic discharge
(norm IEC 61000-4-2), but based on the condition of this norm for equipment placed in switchboard, these
modules were not tested of Electrostatic discarge.
Sign ESD must be placed inside switchboard.
Some controllers and accessories contain varistors in power supply modul for increased endurance against
surges and interference.