Professional Documents
Culture Documents
Ancillary Services
For Potential AS
Providers
SYSTEM REQUIREMENTS
Energy Supply
Serve the energy
demand of consumers
Ancillary Services
Ancillary Services are support services necessary to sustain the
transmission capacity and energy that are essential in maintaining
the power quality, reliability, and security of the grid.
110
115
120
125
130
135
140
145
2:57:32 PM
2:58:48 PM
3:00:04 PM
3:01:20 PM
3:02:36 PM
3:03:52 PM
3:05:08 PM
3:06:24 PM
3:07:40 PM
3:08:56 PM
3:10:12 PM
3:11:28 PM
3:12:44 PM
3:14:00 PM
3:15:16 PM
3:16:32 PM
3:17:48 PM
3:19:04 PM
3:20:20 PM
Time
3:21:36 PM
3:22:52 PM
3:24:08 PM
3:25:24 PM
3:26:40 PM
3:27:56 PM
3:29:12 PM
3:30:28 PM
3:31:44 PM
3:33:00 PM
3:34:16 PM
3:35:32 PM
3:36:48 PM
3:38:04 PM
3:39:20 PM
3:40:36 PM
3:41:52 PM
59.65
59.75
59.80
59.90
60.00
60.05
60.15
60.25
60.30
60.35
60.40
59.70
59.85
59.95
60.10
60.20
frequency
Illustration of Regulating Reserve Response
Grid frequency
The generator providing RR mirrors the change in grid frequency, in order to maintain the frequency as close to 60Hz as possible.
Regulating Reserve
Technical Requirements to become an RR provider
Primary Response RR operate in an automatic frequency sensitive mode or Free Governor Mode with deadband of
+/-0.15Hz with maximum response time of 5 seconds and sustainable for 25 seconds
Secondary Response RR operate in an Automatic Generation Control (AGC) of the SCADA/EMS of the National
Control Center or manual adjustment of load with specific instructions from the SO. Maximum response time is 25
seconds and sustainable for 30 minutes
Generating units shall be fitted with a fast-acting speed-governing system to provide frequency control under
normal operating conditions.
Speed governing system shall have an overall speed-droop characteristic of 5% or better. For thermal plants, 5%
speed-droop; for hydro, 3% speed-droop is required.
Generating unit’s speed governing system shall have a ramp rate of at least 5MW/minute.
The speed governing system shall be capable of accepting raise and lower signals from its AGC.
A generating unit that is already scheduled for RR cannot be scheduled for CR, DR or RPS on the same interval.
Pmin of the generating unit shall not be part of the RR capacity. Generating unit must already be
spinning/synchronized to the grid at the start of its RR schedule.
Contingency Reserve
Functions of CR
Provides generating capacity necessary to respond to infrequent, but usually large,
failures of generating units and/or transmission tie lines.
Generating unit shall also ensure that the rate of occurrence of frequency
fluctuation does not exceed the level set out in the PGC.
No generating unit shall be assigned a CR level greater than 20% of the total
required CR for any particular hour to avoid a single point of failure.
Total CR capacity per grid shall be equivalent to the largest generating unit online,
which includes its scheduled capacity for energy supply plus its scheduled capacity
for AS, if any. This is computed on an hourly basis.
Illustration of Contingency Reserve Response
DEMAND GENERATION DEMAND GENERATION DEMAND GENERATION
C
R
C D C D D
R R R R R
C D
R R
D C
R R
UNDERVOLTAGE OVERVOLTAGE
230 kV
Below 207kV 207kV – 218.5kV 241.5kV – 253kV Above 253kV
(218.5kV – 241.5kV)
Reactive Power for Voltage Control
• High demand results to low voltage on the load side due to an increase in current
flow.
• Low voltage may result to tripping of generators, overheating of motors and poor
performance of electrical equipment (e.g. flickering or dimming of light bulbs)
• Extremely low demand, on the other hand, results to overvoltage
• Overvoltage may result to low power factor, insultation failure of electrical
equipment and transmission lines and automatic tripping of transmission
equipment
• Reactive Power adjusts voltage levels to within +/-5% of the nominal voltage
• Sources of reactive power include: generators, capacitors, reactors/inductors,
synchronous condensers
RPS ADJUSTS VOLTAGE
The abovesaid rates are for the Capacity Payment (CP) of the Firm Capacity, which is in essence the “reservation fee” for the
generating unit as it will be dedicated for Ancillary Service once scheduled, and can no longer be traded for energy supply. The
formula shall be:
There is an additional payment for Incidental Energy (IE) which will cover the cost of Variable O&M and actual fuel consumed
for the dispatch of Ancillary Service (“G”). Any energy revenue from the WESM will be deducted in order to avoid double
compensation. The formula shall be: