User’s Manual
Version: V1.4
Release date: 2021-9-1
BOM CODE
BEG1K075G is an bidirectional AC/DC module developed by Shenzhen Infypower Technology Co., Ltd. for V2G, energy
storage, smart grid and other applications. It’s an energy storage conversion module, which can realize AC and DC Stream
bidirectional conversion function, with the advantages of high-efficiency, high-power-density and high-reliability.
1.1 Model
BEG 1K 075
1.2 Structure
Appearance
Front panel
Size parameters, as shown in Figure 1-3 below:
There are indicator lights on the front panel of the bidirectional module, as shown in Fig. 1-4 and Fig. 1-5. Refer to Table 1-1 for
the instructions of the indicator lights.
Module model
Dial switch of address(According to screen print on the panel, the right side
refers to low significant bit while the left side refers to high significant bit,
and default of 0)
Note: The dial code is a binary 8421 code format, and the high and low bits are arranged from right to left,the high is in the left; The DIP switch is
down, indicating 0, and it is up, indicating 1. Please see the example and the conversion information table in Figure 1-6 as follow. The maximum effective
address of the dial code is 60.
Fig. 1-6 Front panel DIP switch information and conversion information
Vo+ Vo-
PE N A B C
Fig. 1-7 Schematic Diagram for Definition of Three-phase AC Input Mode Port
Rect-Input Characteristic
24000
22000
20000
18000
DC Output Power(W)
16000
14000
12000
10000 45C
8000
6000
4000
2000
0
200 250 300 350 400 450 500 550
AC Input(V)
Fig. 1-9 Correlation curve between the output power and the input voltage of three-phase AC input in the rectification mode
When the module works in the on-grid inverter mode, the relationship between output power and input voltage is shown in
Figure 1-10.
When the input voltage is between 300Vdc and 1000Vdc, the module can output a maximum power of 22kW. when the input
voltage is between 200Vdc and 300Vdc, the module can still work normally, but in the limited power mode. The relationship
between module output power and DC input voltage is shown in Figure 1-10.
Inv-Output Characteristic
24000
22000
20000
18000
AC Output Power(w)
16000
14000
12000
45C
10000
8000
6000
4000
2000
0
0 100 200 300 400 500 600 700 800 900 1000
DC Input(V)
Fig. 1-10 Correlation curve between the output power and the input voltage DC input in the on-grid inverter mode
Rect-Output Characteristic
1000
950
900
850
800
750
Rect-Output voltage
700
650
600 <=45C
550
500
450 Limit
400
350
300
250
200
150
100
50
0
0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 55.0 60.0 65.0 70.0 75.0
Rect-Output Current(I)
Fig. 1-11 Correlation curve between the output voltage and the output current of the module in the rectification mode
Over 55°C, the module shall be used by derating with the power limiting linearly.
14000
12000
10000
8000
6000
4000
2000
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Ta
When the Module works in rectification mode and input voltage is less than 260Vac or more than 535Vac, the protection
indicator light is on and the module stops working, without output. Meanwhile, this condition will be transmitted to the monitoring
module. When the input voltage returns to the normal range, the alarm disappears and the module returns to the standby state.
10.Protection of input overvoltage/ voltage shortage in on-grid inverter mode
When the Module works in on-grid inverter mode and input voltage is less than 200Vdc or more than 1020Vdc, the protection
indicator light is on and the module stops working, without output. Meanwhile, this condition will be transmitted to the monitoring
module. When the input voltage returns to the normal range, the alarm disappears and the module returns to the standby state.
11.Output overvoltage protection in rectification mode
When the Module works in rectification mode, the overvoltage protection points can be set by the monitoring module:
The voltage setting range is 200Vdc to 1020Vdc and the factory default is 1020Vdc. Manual intervention is required when a
voltage-shortage protection alarm occurs. Manual intervention methods include resetting the module through the monitoring
module or removing the module from the system.
After the external output is overvoltage, when the output voltage returns to normal, the module returns to the standby state.
12.Protection of output overvoltage/ voltage shortage in on-grid inverter mode
When the Module works in on-grid inverter mode and three-phase output voltage is less than 260Vac or more than 535Vac, the
protection indicator light is on and the module stops working, without output. Meanwhile, this condition will be transmitted to the
monitoring module. When the input voltage returns to the normal range, the alarm disappears and the module returns to the standby
state.
13.Over-temperature protection
BEG1K075G Bidirectional AC/DC Module User’s Manual
8 Bidirectional AC/DC Module BEG1K075G
The environmental over-temperature protection point is 78°C±3°C. When the internal temperature is too high, the module will
protect the shutdown. After the temperature is restored, the module will resume work, and the output current and voltage will return
to the default value.
14.Protection of internal bus fault
When the internal bus voltage of the module is beyond the overvoltage/ voltage shortage protection point, the module will be
powered off automatically. At this time, there is no output from the module and the fault indicator light is on.
15. Short circuit protection
When the module is short-circuited, the protection shuts down, the red indicator on the panel is on; and the "module failure" is
reported to the monitoring which can query the current alarm information of the module through the protocol. Short-circuit
protection requires manual intervention. Manual intervention methods include: resetting the module through the monitoring module,
or disconnecting the module from the system to reset.
16.Interruption of background communication
When the module communication is interrupted for more than 10S, the module is shut down and protected, no voltage output,
and the protection indicator flashes. When the communication of the module is restored within 10S~20S, the protection indicator
returns to normal, and the module resumes work according to the default parameters. If the communication interruption time
exceeds 20S, the module will return to the standby state after the communication is restored.
17.Protection against fan fault
When the fan fails, the module will generate a fan failure alarm and the fault indicator will flash. At this time, the module shuts
down and no voltage is output. After the fault is eliminated, the module returns to the standby state.
18.Monitoring performance
The bidirectional module is equipped with DC CAN bus.
Refer to Table 1-2 for the list of the monitoring information.
2.1 Installation
The bidirectional module shall be installed according to the following steps:
1. Grasp the handle of the bidirectional module with one hand and hold the bidirectional module with the other hand to insert
the module into corresponding position of the cabinet.
2. Push the bidirectional module into the slot slowly.
3. Tighten the two set screws on the panel of the bidirectional module and fix the module on the cabinet.
4. Install the bidirectional module in the cabinet successively from left to right.
2.2 Application
The bidirectional module can operate when the system is powered on after it is installed in the system cabinet.
Application environment
1. Overvoltage category for installation: Overvoltage category II.
2. Degree of pollution: PD2.
3. Altitude: below 2,000m.a.s.l; derating is required when the altitude is above 2,000m.a.s.l.
4. AC input distribution system: TN or TT system.
5. System exhausted-air volume requirements:
The amount of exhaust air required by the system should be calculated according to the formula of the thermal design.
According to the formula: Q=CMΔT (ΔT is the temperature difference between the inlet and outlet of the system, the outdoor
cabinet generally chooses 10 degrees. If the air duct is not good, this value should be reduced again. And the indoor cabinet can
increase the temperature difference properly), The total loss Q of the system is obtained by the efficiency of the system (the Q
value of the strong sunshine area also needs to be added with solar radiation): M (air mass required for heat dissipation) = Q / C /
ΔT (C is the specific heat capacity of the air), V = M / ρ (mass / density) to obtain the air volume (m ^ 3/s), in this way, the air
volume of the system can be obtained, but this air volume is the actual air volume required by the system. Corresponding to the selection
of the fan, the fan should be selected according to the actual air volume of 2 times (the maximum air volume of the air volume is
actually unachievable). The actual work efficiency point is about 0.5 times the maximum air volume).
Simplified design, according to the air volume of a single module fan is 405 CFM, the total airflow of the system should be
not less than N*405CFM, N is the number of modules.
BEG1K075G
BEG1K075G
BEG1K075G
Fig. 2-2 Example of power wiring and communication lines of the cabinet
1 DC_CAN+
2 DC_CAN
3 AC_CAN+
4 AC_CAN-
5 Carrier_Sync/Estop
6 50Hz_Sync
7 OffGridbus
8 OutputRsvd
9 VCOMPort_GND
Fig. 2-5 The communication signal definition
Fig. 2-6 Input and output cable terminal mounting screws (supplied with cable terminals)
Fan blocking Remove the object blocking the operation of the fan
The module is Obstructed air duct: Remove the obstacle at the air inlet
subjected to Too high
Module
over-temperature environmental Lower the environmental temperature
protection
protection. Main temperature
causes include: Not insert the
bidirectional module Re-insert the bidirectional module
fully in place
Protection
Check whether there is normal communication for the
indicator light
bidirectional module and whether the communication line is
(yellow) on Unbalanced The average current of the module is more
connected normally. If there is normal communication but there is
module current than 3A.
still abnormity in the system, the bidirectional module shall be
replaced.
Change the position of the abnormal bidirectional module and the
Module normal bidirectional module. If the abnormal bidirectional
AC side overvoltage protection
protection module still fails to work, the bidirectional module shall be
replaced.
Module AC/DC side voltage beyond the normal
Ensure that the AC/DC side voltage is within the normal range.
protection range
Protection
Module
indicator light
communication Module communication interruption Check the connection of the communication line
(yellow)
interruption
flashing
Fault indicator Pull out the bidirectional module and restart it. In case of fault
Module fault Module overvoltage or output short circuit
light (red) on protection again, the bidirectional module shall be replaced.
Fault indicator
light (red) Fan fault Fan fault Replace the fan
flashing
Note: In July 2018, the formal reports which meeting the ROHS ten requirements will be provided.
Toxic and harmful substances or elements
component
Pb Hg Cd Cr6+ PBB PBDE
Fan X O O O O O
Manufactured panel X O O O O O
Hardware X O O O O O
○:Indicates that the content of this toxic or hazardous substance in all homogeneous materials of this part is
below the limit requirement specified in SJ/T-11363-2006
×:Indicates that the toxic or hazardous substance contained in at least one of the homogeneous materials of
the part exceeds the limit requirement specified in SJ/T11363-2006
The following components and applications contain toxic and hazardous substances that are limited to the
current state of the art and cannot be reliably replaced or have no mature technical solutions:
1. Solder containing plumbum
2. Plumbum in copper
3. High temperature solder containing plumbum
Description of the period of environmental protection use: The environmental protection use period of this
product (identified on the product body) means that the product contains toxic and harmful products from the
date of production under normal conditions of use and safety precautions for compliance with this product. The
period in which a substance or element does not seriously affect the environment, person or property
Scope of application:BEG1K075G AC/DC Bidirectional Module