You are on page 1of 2

CENTRAL RAILWAY

PANVEL-VASAI SECTION

Name of the Traction Sub-Station : KHARBAO TSS


Report No. : 6
Sheet No. : 2 of 2
Date. : 11.02.2021

25KV VACUUM CIRCUIT BREAKER

i) Identification No. : BX-CB-501


ii) Make : ALIND
iii) Makers Serial No : SO-00923/520EB/3285/1
iv) External condition (check porcelain carefully) : OK
v) Insulation resistance (with 5kv Insulation Tester)
a) Between Top Terminal & Earth with breaker open : 48.00GΩ
b) Between Bottom Terminal & Earth with breaker open : 33.20GΩ
c) Between Top Terminal & BottomTerminal with breaker open : 57.00GΩ
d) Between Top Terminal & Earth with breaker Close : 43.60GΩ
vi) Insulation resistance of operating mechanism By 500 V Megger.
a) Spring charging motor with earth : 20.4Ω / 300MΩ

b) Closing coil with earth / Spring Charged (K 32/K 31) & Ohmic Value : 83.2Ω / 175MΩ

c) Trip coil with earth / C.B. Closed (K 2/K 1) & Ohmic Value : 86.9Ω / 190MΩ
vii) Contact resistance (at100A) (not more than 50µΩ) : 211.27A 27.95µΩ
: 210.89A 28.04µΩ
: 210.97A 28.05µΩ
viii) Breaker operating time
a) Closing (not more than 150ms) : 88ms, 88ms, 87ms
b) Opening (not more than 65ms) : 46ms, 46ms, 45ms
ix) Local/Remote operation : OK
x) Duplicate earth and earth continuity : OK
xi) Terminal connection (check for tightness & general condition ) : OK
xii) Check for Mechanical tripping & closing : OK
xiii) Heater circuit : OK
xiv) DC fall test (condensor tripping) : OK
xv) Operation Counter : OK (291/294)
xvi) Check Silica gel Breather condition : Replaced
xvii) Wipe : Open Close
: W1/120mm W2/112mm
: T1/50mm T2/27mm