You are on page 1of 1

Common technical data:

Rated voltage (highest system voltage):.......... 72.5kV(rms)


SCHEMATIC DIAGRAM FOR 220KV/27KV GIS TSS OF KHARBAO Service voltage (working value):...................... 66kV(rms)
Rated current :................................................. 2000 A
Rated frequency:.............................................. 50 Hz
Rated insulation levels:
Lightning impulse withstand voltage to earth:. 325 kVp
Lightning impulse withstand voltage
across the isolating distance:..................... 375 kVp
Power frequency withstand voltage to earth:. 140 kV(rms)
Power frequency withstand voltage
across the isolating distance:.................... 160 kV (rms)
Rated short-time withstand current:................. 31.5 kA
Rated duration of short circuit:......................... 3 s
Rated peak withstand current:......................... 80kAp
Related standards:........................................... IEC
GIS type :......................................................... GAI-3s

B/C
BUSBAR-2 BUSBAR-1

INCOMER INCOMER
BAY-1
BAY-2