You are on page 1of 1

CENTRAL RAILWAY

PANVEL-VASAI SECTION
Name of the Traction Sub-Station : KHARBAO TSS

Report No. : 9

Sheet No. : 1 of 2

Date :

25KV DOUBLE POLE ISOLATOR

Sr. No Activity I

1 Identification No. : BXCB DPI-507

2 Make : TRANSELECTRICALS

3 Maker SR.No : TE/07/250/19

4 Insulator( Check Condition) : OK

5 Terminal connection (Check for tightness & condition ) : OK

6 Contacts ( Check for alignment and condition) : OK

7 Opearation:( Manual )

a) Open : OK

b) Close : OK

8 Opearating Mechanism (Check for alignment & smooth operation ) : OK

locks (Check wheather bolt,locks and pad lock fit conveniently when
9 : OK
isolator is in open & close position)

10 Duplicate earth and earth continuity

a) Fixed contact to earth : OK

b) Moving contacts to earth : OK

11 Clearance between male & female contact ( in open condition ) : 510 mm

12 Insulation Resistance : 10000MΩ

13 Earth jumper for Operating handle Provided or not : Provided

14 Inter-locking provided or not : Provided

15 Pad lock Provided or not : Provided

M/S L.E.M. PVT LTD SSE/PSI/C/DR SSE/TD/PSI/PNVL