CENTRAL RAILWAY

PANVEL-VASAI SECTION

Name of the Traction sub-station : KHARBAO TSS


Report No. : 1
Sheet No. : 1 of 1
Date : 25.02.2021

LAYOUT & CLEARANCE


1 Height of live conductor above Datum (Ground) level
( i ) 220KV (Min 7.0 m) : 7.665 Mtrs
( ii) 25kV (Min 3.8 m ) : 3.90 Mtrs

Height of Bottem most portions of Any Insulator or Bushing From


2
Graund Level
( i ) 220KV (Min 2.5m) : 4.64 Mtrs
( ii) 25kV (Min 2.5 m ) : 3.48 Mtrs

3 Clearance between two live phase


( i ) 220KV (Min 2.1 m) : 3.108 Mtrs
( ii) 25kV (Min 0.45 m ) : 0.800 Mtrs

4 Electrical clearance between live and earthed parts:


( i ) 220KV (Min 1.8 m) : 2.20 Mtrs
( ii) 25kV (Min 0.4 m ) : 0.50 Mtrs

5 Compliance with Indian Electrcity rules : Complied

6 Fire buckets, fire extinguishers first aid box, Resusciationcharts etc. : Provided

7 Danger and caution board : Provided


8 Visual inspection of insulators : OK
9 Number plates : Provided
10 Fencing earthing : OK
11 Schematic diagram : Displayed
12 Doctor's address : Displayed

M/S L.E.M. PVT LTD SSE/PSI/C/DR SSE/TD/PSI/PNVL

DEE/TD/PL DEE/C/DR