You are on page 1of 1

1MVA (Galaxy 7000-2x500kVA) UPS Load

Connected FLC, Running LC, Demand LC,


NO UPS (1MVA/900KW ) Load Chart Load %
Load (KW) Amp Amp Amp

1 K-601 A/B with Auxiliary 339.77 92% 609 560 567

2 K-601 C with Auxiliary 377.95 77% 702 542 560


3 K-602 15 0% 30.6 0 18
4 PLP 15 63% 30 19 21
5 Boiler (NEW) 15.2 83% 25 20.8 22
6 AC load 34.5 33% 66 22 44
Total Load (Considering A or B) 797.42 1462.6 1163.8 1232
1 MVA UPS Load % 97.5% 77.6% 82.1%
1.2MVA (Galaxy 7000-4x300kVA) UPS load
Connected Running Load FLC, Running LC, Demand LC,
No UPS (1.2MVA/1.08MW) Load Chart
Load (KW) % Amp Amp Amp
1 K-401 A/B with Auxiliary 180.85 71% 349 248 270
2 K-401 C with Auxiliary 256.95 61% 512 312 318
3 P-5001 A/B 35.5 87% 63 55 58
4 P-5002 15 0% 26.5 0 23
5 P-5003 A/B 7.5 50% 13.97 7 7.9
6 EA-5001 A 11 83% 20 16.5 17
7 EA-5001 B 11 83% 20 16.5 17
Final Plan

8 P-301 A/B 55 92% 96 88 90


9 P-401 A/B 45 66% 68 45 47
10 P-601 A/B 11 67% 21 14 16
11 P-403 A/B 2.2 59% 4.8 2.82 3.24
12 P-006 A/B 90 64% 163 104 108
13 P-502 A/B 55 57% 96 55 64
14 Boiler (OLD) 11 57% 21 12 14
15 H-301 Blower 30 56% 54 30 31
16 Zehua exchanger EA-001 A1 11 60% 21.5 13 14
17 Zehua exchanger EA-001 A2 11 60% 21.5 13 14
18 1.2 MVA UPS room AC Load 45 25% 88 22 44
19 P-881 A/B 7.5 86% 13.96 12 13
20 P-882 A/B 15 82% 26.94 22 24
21 P-883 A/B 11 89% 20.18 18 20
22 P-891 A/B 18.5 94% 33.01 31 32
23 P-892 A/B 18.5 94% 33.01 31 32
24 EA-881 A+B 6 58% 13.68 8 12
25 EA-891 A+B 6 58% 13.68 8 12
26 SWS Plant 30 75% 60 45 50
27 BTX plant lighting loads (1&2) 20 100% 36 36 36
28 Hexane plant 74 48% 136 65 82

29 Cooling tower load (2201- A) (400 Rm Cable) 110 79% 173 137 146

30 Cooling tower load (2201- B) (300 Rm Cable) 110 79% 173 137 146

Total Load (Considering A or B) 1310.5 2391.73 1603.82 1761.14


1.2 MVA UPS Load % 120% 80% 88%