1MVA (Galaxy VL-2x500kVA) UPS Load

Connected Running Load FLC, Running LC, Demand LC,


No UPS (1MVA/900KW ) Load Chart
Load (KW) % Amp Amp Amp
1 P-2201 C 110 79% 173 137 146
2 P-2202 A 90 89% 142 126 132
3 P-2202 B 90 89% 142 126 132
4 P-2202 C 90 89% 142 126 132
5 P-2202 D 90 0% 142 0 132
6 P-810A/B 22 82% 39.08 32 35
7 P-811A/B 11 89% 20.18 18 20
8 P-821A/B 18.5 91% 33.01 30 33
9 P-822A/B 22 90% 39.08 35 38
10 P-823A/B 0.37 91% 1.1 1 1.1
11 P-831A/B 55 94% 95.71 90 92
12 P-832A/B 18.5 91% 33.01 30 33
Final Plan

13 P-833A/B 15 74% 26.94 20 25


14 P-841A/B 15 74% 26.94 20 25
15 P-851A/B 7.5 86% 13.96 12 13.5
16 EA-811 A+B 6 66% 13.68 9 12
17 EA-821 A+B 6 66% 13.68 9 12
18 EA-831 A+B 22 74% 40.8 30 36
19 EA-831C 11 74% 20.4 15 18
20 Vacuum Pump-A/B 18.5 83% 36 30 35
21 1 MVA (GVL) new UPS room AC 33 33% 66 22 44

Hexane hot oil heater ( Hot oil pump 4001


22 A/B: 55 KW + Burner Blower : 7.5 KW + 63.6 51% 108 55 62
Burner Oil pump: 1.1 KW )

BTX Hot Oil Heater ( Hot oil pump A/B: 75


23 KW + Burner Blower : 45 KW + Diesel pump: 125 53% 362.9 193 193
5.5 KW )

Total Load (Considering A or B) 939.97 1731.47 1166 1401.6


1 MVA UPS Load % 123.7% 83.3% 100.1%