STANDARD OPERATING PROCEDURES


Form No. EHSMSM/446/4013 Form Rev. No. : 01 Effective date: 13.8.2022
SOP No . FME/EDEV/SOP/22 Effective Date 10-01-2022 REVISION No 00
SOP DESC: Monitoring of Crane DSL temperature of HI bay At LD#3 Section Electronic Development
DEPARTMENT: FM Electrical Page 01 Of 03
Associated
Step Responsibility
Activity (What) Requirements/ Hazards/ Process/Tools/PPEs/ (How) Remarks
No. (Who)
Impacts

1. On the desktop, open Google Chrome


Opening Dashboard of
1
Crane DSL monitoring. 2. In the address bar, type
http:/143.0.16.167:9010/HIBay.html and press ENTER
Requirements:
1. Any PC in tata 1. Check for temperature of DSL bus bar and power
Steel Domain collector which are indicated by Cam Area 1 and
PPEs: Area 2 respectively.
2
Monitoring temperature 1. Use PPEs as per 2. Also check for temperature vs distance plot to find
Refer to
location and the location of Hotspots (if any)
Member of Annexure 1 for
requirement.
EDEV Step-wise
Hazards
visuals
1. Exposure to STF
hazard
2. Hazard identification 1. Any temperature above 110⁰C should be closely
as per location. monitored
2. If temperature is consistent at 110⁰C, it should be
Reporting or Actionable
3 reported and corrective actions to be taken.
Points
3. If temperature is below 10⁰C system should be
diagnosed for any abnormalities and faults.
2

1. Check if the internal temperature of camera is rising


Camera Protection for Member of and exceeds 44⁰C. See if camera turns off
4
heat EDEV automatically after 44⁰C. If not, inform MED
Electronics at 40255

Member of
5 Unable to view data If data is not available at dashboard, contact EDEV at 40255.
EDEV

Annexure-I

Step1: Open Google Chrome from the Desktop

Step2: In the address bar, enter the given


address and press ENTER
3

Step3: Check for temperature of DSL and Power


collector in area 1 and area 2 respectively.

Step4:
 Monitor any temperature above 110⁰C.
 Any consistent temperature above 110⁰C at a specific
location in the Distance/Temperature plot should be
reported and checked for abnormalities

Step5: Inform EDEV at 40255 if internal temperature of


camera rises above 44⁰C and is it doesn’t turn OFF.
4

PREPARED BY APPROVED BY
Name and Designation: AYUSHI / MA- II Name and Designation: Ravinder Singh

Sign with Date: Sign with Date: