You are on page 1of 1

N

NOTE:
ELV RISER 1
THIS IS A GENERIC SCHEMATIC FOR AN
ROOF OVERVIEW OF THE LIGHTING MANAGEMENT
CONTROL "BUSINESS HOURS "AFTER HOURS
TYPE
AREA LIGHTING CONTROL DESCRIPTION
(7AM TO 7PM)" (7PM TO 7AM)" SYSTEM FOR THE DEVELOPMENT CONTRACTOR
DALI DEVICES
ELECTRICAL ROOMS
MMR ROOMS
CAT 6A
CABLE
KNX
CABLE (128 DEVICES PER DALI GATEWAY) SHALL DESIGN AND SUBMIT THE EXACT LIGHTING
MANAGEMENT SYSTEM FOR
E E E
NIR/NER ROOMS REFER TO
FIRE ROOMS LIGHTING CONTROLLED BY ON/OFF SWITCHES ONLY. SWITCHES / LAYOUT FOR
LIGHTS TURN ON WHEN
APPROVAL
DATA KNX IP KNX
1 PRAYER ROOM NO SENSORS PROVIDED. AS PER BUSINESS HOURS. SWITCH GATEWAY PANEL
CONTROLLERS ACTUAL
ACTIVATED WITH LIGHT SWITCH.
ABLUTION AREA NO DIMMING PROVIDED. QUANTITIES
SECURITY ROOM FROM LEVEL 1
FIRE CONTROL CENTRE CORE SWITCH
BIN CENTRE ALL SENSORS
COOL SPINE LEVEL 7
LOADING BAY UNINTERRUPTED POWER SUPPLY
ROOF TO BACKUP MAIN EQUIPMENTS
DALI DEVICES (FLOOR-STAND)
CAT 6A KNX
OCCUPANCY SENSORS ARE ACTIVATED. CABLE CABLE (128 DEVICES PER DALI GATEWAY)
LOBBY LIGHTS ARE DIMMED TO 20%. E E E
LIGHTING IS ALWAYS ON (24 HOURS). LIGHTING REFER TO U.P.S
FF LOBBY LIGHT BRIGHTNESS IS AUTOMATICALLY SET TO
CONTROLLED BY OCCUPANY SENSORS. LIGHTING IS ALWAYS ON. LAYOUT FOR (30MINS.)
2 LOADING DOCK AREA 100% UPON MOVEMENT DETECTION. DATA KNX IP KNX SWITCHES / E
LIGHTING CONNECTED TO DALI DRIVER. BYPASS OCCUPANCY SENSORS ARE DEACTIVATED. ACTUAL
CORRIDORS LIGHTS ARE AUTOMATICALLY DIMMED TO 20% SWITCH GATEWAY PANEL
CONTROLLERS
SWITCHING CONTROL LOCATED IN SECURITY ROOM. QUANTITIES
COLOCATION CORRIDORS AFTER 30 MINUTES WHEN NO MOVEMENT IS FROM LEVEL 1
DETECTED. RELAY CONTROLLER RELAY CONTROLLER
CORE SWITCH
CORE TO EVERY LEVEL
ALL SENSORS
LEVEL 6 SWITCH DATA SWITCHES.
MULTI-USE RESTROOMS
LIGHTING CONTROLLED BY OCCUPANCY SENSORS. LIGHTS ACTIVATED UPON MOVEMENT DETECTION.
STAIRCASES
3 NO ON/OFF SWITCHES PROVIDED. LIGHTS TURN OFF AFTER 30 MINS WHEN NO AS PER BUSINESS HOURS.
MANTRAPS
LIGHTING CONNECTED TO DALI DRIVER. MOVEMENT IS DETECTED. DALI DEVICES
CUSTOMER LOUNGE CAT 6A KNX
CABLE CABLE (128 DEVICES PER DALI GATEWAY)
CPU
E E CAT 6A
E
REFER TO CABLE
LAYOUT FOR LIGHTING MANAGEMENT SYSTEM
SINGLE OCCUPANCY RESTROOMS DATA KNX IP KNX SWITCHES / TO BMS
LIGHTING CONTROLLED BY OCCUPANY SENSORS. ACTUAL WORKSTATION WITH KNX OPC
SHOWER ROOM LIGHTS ACTIVATED UPON MOVEMENT DETECTION. SWITCH GATEWAY PANEL
CONTROLLERS
OCCUPANCY SENSORS CAN BE OVERRIDE BY ON/OFF QUANTITIES SERVER E
4 FLEX OFFICE LIGHTS TURN OFF AFTER 30 MINS WHEN NO AS PER BUSINESS HOURS. FROM LEVEL 1
SWITCHES (FOR MAINTENANCE PURPOSES).
FACILITY MOVEMENT IS DETECTED. CORE SWITCH
LIGHTING CONNECTED TO DALI DRIVER.
OPERATIONS OFFICE
ALL SENSORS
OPERATIONS BREAK ROOM LEVEL 5
LOCATED AT 1ST STOREY SECURITY CONTROL ROOM
LIGHTING CONTROLLED BY ON/OFF SWITCHES WITH LIGHTS TURN ON WHEN ACTIVATED WITH LIGHT
DIMMING CONTROL (WITHIN THE ROOM - MANUALLY SWITCH.
SMALL CONFERENCE ROOMS DALI DEVICES
5 CONTROLLED BY USER). AS PER BUSINESS HOURS. CAT 6A KNX
MEDIUM CONFERENCE ROOMS CABLE CABLE (128 DEVICES PER DALI GATEWAY)
NO SENSORS PROVIDED. E
E E
LIGHTING CONNECTED TO DALI DRIVER. REFER TO
LIGHTS ARE DIMMABLE. LAYOUT FOR
DATA KNX IP KNX SWITCHES /
SWITCH GATEWAY PANEL
CONTROLLERS ACTUAL
COMPOUND LIGHTING LIGHTING CONTROLLED BY TIMER VIA LIGHTING LIGHTS ARE TURNED OFF BASED ON LIGHTS ARE TURNED ON BASED ON QUANTITIES
6 CONTROL SYSTEM. TIMER ACTIVATION. TIMER ACTIVATION. FROM LEVEL 1
CORE SWITCH
ALL SENSORS
LIGHTS ACTIVATED UPON MOVEMENT DETECTION. LEVEL 4
7 COLOCATION - COLD AISLE LIGHTING CONTROLLED BY OCCUPANY SENSORS. LIGHTS TURN OFF AFTER 30 MINS WHEN NO AS PER BUSINESS HOURS.
MOVEMENT IS DETECTED.
CAT 6A KNX DALI DEVICES
CABLE CABLE (128 DEVICES PER DALI GATEWAY)
LIGHTING CONTROLLED BY OCCUPANY SENSORS. LIGHTS ACTIVATED UPON MOVEMENT DETECTION. E E
E
8 COLOCATION - HOT AISLE OCCUPANCY SENSORS CAN BE OVERRIDE BY ON/OFF LIGHTS TURN OFF AFTER 30 MINS WHEN NO AS PER BUSINESS HOURS. REFER TO
SWITCHES (FOR MAINTENANCE PURPOSES). MOVEMENT IS DETECTED. KNX SWITCHES / LAYOUT FOR
DATA KNX IP
SWITCH GATEWAY PANEL
CONTROLLERS ACTUAL
QUANTITIES
FROM LEVEL 1
RELAY CONTROLLER RELAY CONTROLLER
CORE SWITCH
LIGHTING CONTROL TABLE LEVEL 3 ALL SENSORS

NTS
CAT 6A KNX DALI DEVICES
CABLE CABLE (128 DEVICES PER DALI GATEWAY)
E E E
REFER TO
KNX SWITCHES / LAYOUT FOR
DATA KNX IP
SWITCH GATEWAY PANEL
CONTROLLERS ACTUAL
QUANTITIES
FROM LEVEL 1
CORE SWITCH
ALL SENSORS
LEVEL 2

CAT 6A KNX DALI DEVICES


CABLE CABLE (128 DEVICES PER DALI GATEWAY)
E E E
REFER TO
KNX SWITCHES / LAYOUT FOR
DATA KNX IP
SWITCH GATEWAY PANEL
CONTROLLERS ACTUAL
QUANTITIES
FROM LEVEL 1
CORE SWITCH
ALL SENSORS
LEVEL 1M

CLIENT

CAT 6A KNX DALI DEVICES


CABLE CABLE (128 DEVICES PER DALI GATEWAY)
E E E
REFER TO
SWITCHES / LAYOUT FOR
DATA KNX IP KNX
SWITCH GATEWAY PANEL CONTROLLERS ACTUAL
QUANTITIES
FROM LEVEL 1
CORE SWITCH
ALL SENSORS REV DATE REVISION DETAILS APPROVED
LEVEL 1 C 12.08.22 RIBA 4 ADDENDUM 2 K. CHEN
B 10.05.22 RIBA 4 SUBMISSION K. CHEN
A 14.01.22 RIBA 3 DRAFT SUBMISSION K. CHEN

LIGHTING MANAGEMENT SYSTEM SCHEMATIC DIAGRAM


Filename: Autodesk Docs://520939 - Equinix JK2-1 Data Centre/JK2-M3-E-0001-ZZ-ZZ-ZZZZ-AUR.rvt

NTS
SCALE
As indicated
SIZE
A0
RIBA 4
NOT FOR CONSTRUCTION
DRAWN APPROVED
J.MAZLAN DATE
DESIGNED 12.08.2022
K.CHANDRA K.CHEN
CHECKED
K.TIANG K.CHEN
PROJECT
Equinix JK02-1 Data Centre

TITLE
ELECTRICAL SERVICES
Office: AUR

LIGHTING MANAGEMENT SYSTEM


SCHEMATIC DIAGRAM
Plot Date: 12/8/2022 2:53:59 pm

PRINT IN COLOUR DRAWING NUMBER


Equinix Client Number REV

E 628- XX C
Aurecon Document Number: JK02-1- JK2-DR-E-628-XX-ZZ-POWR-AUR-SC

You might also like