You are on page 1of 2

Sept.

4, 2022

Project: FARIDAH COMM. BLDG.

Subject : Electrical Load .‫ األحمال الكهربائية‬: ‫الموضوع‬

This is reference to the above project/subject regarding for the final electrical load
calculation of the above project. The required transformer are 2 x 1000 Kva, 380/230
Volt, 60Hz. ‫ كيلو فولت أمبير‬1000 ‫المطلوب عدد محولين بسعة‬

The following kilowatt meter hour are:

Transformer # 01, 1000 Kva 1 ‫حسابات المحول رقم‬

Ground floor: ‫العدادات المطلوبة للدور االرضي‬

1- Shop # 01------ Demand Load = 65.71 Kva, MCB/KWHM - 125 Amps


2- Shop # 02 ----- Demand Load = 62.65 Kva, MCB/KWHM - 125 Amps
3- Shop # 03 ----- Demand Load = 78.96 Kva, MCB/KWHM - 150 Amps
4- Shop # 04 ----- Demand Load = 70.43 Kva, MCB/KWHM - 150 Amps
5- Shop # 05 ----- Demand Load = 85.80 Kva, MCB/KWHM - 175 Amps
6- Shop # 06 ----- Demand Load = 33.40 Kva, MCB/KWHM - 70 Apms

First floor: ‫العدادات المطلوبة للدور األول‬

1- Office # 01 ----- Demand Load = 30.18 Kva, MCB/KWHM - 70 Amps


2- Office # 02 ----- Demand Load = 62.68 Kva, MCB/KWHM -125 Amps
3- Office # 03 ----- Demand Load = 31.09 Kva, MCB/KWHM - 70 Amps
4- Office # 04 ----- Demand Load = 30.43 Kva, MCB/KWHM - 70 Amps
5- Office # 05 ----- Demand Load = 30.95 Kva, MCB/KWHM - 70 Amps
6- Office # 06 ----- Demand Load = 30.85 Kva, MCB/KWHM - 70 Amps
7- Office # 07 ----- Demand Load = 31.65 Kva, MCB/KWHM - 70 Amps
8- Office # 08 ----- Demand Load = 30.85 Kva, MCB/KWHM - 70 Amps
9- Office # 09 ---- Demand Load = 30.85 Kva, MCB/KWHM - 70 Amps
10-Office # 10 ----- Demand Load = 30.85 Kva, MCB/KWHM - 70 Amps
11-Office # 11 ----- Demand Load = 30.85 Kva, MCB/KWHM - 70 Amps

The total Demand Load of the above items are : 768.18 Kva.
Transformer # 02, 1000 Kva 2 ‫حسابات المحول رقم‬

Annex floor and services Area: ‫العدادات المطلوب لدور الملحق وباإلضافة لعداد الخدمات‬

1- Office # 12 ------ Demand Load = 42.04 Kva, MCB/KWHM - 70 Amps


2- Office # 13 ------ Demand Load = 30.98 Kva, MCB/KWHM - 70 Amps
3- Office # 14 ------ Demand Load = 30.98 Kva, MCB/KWHM - 70 Amps
4- Office # 15 ------ Demand Load = 30.88 Kva, MCB/KWHM - 70 Amps
5- Office # 16 ------ Demand Load = 30.98 Kva, MCB/KWHM - 70 Amps
6- Service Area --- Demand Load = 425.155 kva, MCB/kwhm - 200 Amps.

The total Demand Load : 591.015 Kva.

The above items refer on the Power single line Diagram # 01 and # 02 for your
reference.

Thanks