You are on page 1of 13

Project Name :- QUOTATION 127-01

Project Summary :-

Fan Tag Model Quan Airflow Static Total Rotation Shaft Motor Power Supply
tity Pressure Pressure Speed Power Power
EF-01 DV-225-2E 1 400 cfm 250 Pa 262 Pa 2693 rpm 0.21 kW 0.21 kW 230V/1/60Hz
Specification DV/W : ROOF EXHAUST FAN, UP BLAST, DIRECT DRIVE
Accessories
EF-02 DV-355-0.25-B 2 420 cfm 250 Pa 251 Pa 1232 rpm 0.14 kW 0.25 kW 380V/3/60Hz
Specification ROOF EXHAUST FAN, UP BLAST, BELT DRIVEN
Accessories
EF-03 DV-355-4E 1 830 cfm 250 Pa 254 Pa 1506 rpm 0.34 kW 0.34 kW 230V/1/60Hz
Specification DV/W : ROOF EXHAUST FAN, UP BLAST, DIRECT DRIVE
Accessories
EF-04 HRE-315-RD-90 2 760 cfm 400 Pa 414 Pa 1677 rpm 0.3 kW 0.55 kW 380V/3/60Hz
Specification SWSI, CENTRIFUGAL BACKWARD CURVE FAN, BELT DRIVEN
Accessories Variable Frequency Drive (VFD)
EF-05 HRE-560-RD-90 2 5625 cfm 600 Pa 675 Pa 1410 rpm 3.58 kW 5.5 kW 380V/3/60Hz
Specification SWSI, CENTRIFUGAL BACKWARD CURVE FAN, BELT DRIVEN
Accessories Variable Frequency Drive (VFD)
EF-06 HRE-630-RD-90 2 6685 cfm 600 Pa 662 Pa 1256 rpm 3.91 kW 5.5 kW 380V/3/60Hz
Specification SWSI, CENTRIFUGAL BACKWARD CURVE FAN, BELT DRIVEN
Accessories Variable Frequency Drive (VFD)
Project Name: QUOTATION 127-01
Unit Tag: EF-01
Date: Sep 11,2022

‡DV/W : ROOF EXHAUST FAN, UP BLAST, DIRECT DRIVE

Brief Description FAN Technical Data


Base frame with bolts for tightening of inlet accessories and rectangular inlet cone made from Model Name DV-225-2E
galvanized steel; from size 560 -710 additionally plastic coated. Rain hood up to size 500 made Air Volume (cfm) 400
from seawater resistant aluminium, from size 560 from galvanized steel. Motor supporting plate
with integrated protection guard made from plastic coated round bar steel. Fans are equipped Static/Total Pressure (Pa) 250/262
with backward curved high efficiency aluminium impellers, mounted onto the rotor of a speed Dynamic Pressure (Pa) 12
controllable external rotor motor. Balanced on two levels according to quality level G 2.5
DIN/ISO1940. Motor closed protection class F with protection against humidity and thermal Outlet Velocity (m/s) 4.75
contacts wired in windings from size 355. Maintenance free ball bearings, closed on both sides, Static/Total Efficiency 23/24
sealed for life. Easy access to the terminal box (not connected) under rain hood.
Fan Speed (rpm) 2693
Fan Absorbed Power (kW) 0.21
Voltage (V) 215

Accessories Motor Technical Data


Pmax (kW) 0.21

Imax (A) 0.7

IP 44

Class F

Roof Opening (mm) 220X220

Actual Power (kW) 0.21

Motor Speed (rpm) 2693

Power Supply 230V/1/60Hz

Sound Data
Hz 63 125 250 500 1000 2000 4000 8000 Total

LwA (dBA) 44 55 63 68 71 68 59 51 74
-By theoritical Calculation

Fan Performance Curve

2
Project Name: QUOTATION 127-01
Unit Tag: EF-01
Date: Sep 11,2022

Fan Drawing & Dimensions


Dimension in mm

3
Project Name: QUOTATION 127-01
Unit Tag: EF-02
Date: Sep 11,2022

‡ROOF EXHAUST FAN, UP BLAST, BELT DRIVEN

Brief Description FAN Technical Data


Base frame with bolts for tightening of inlet accessories and rectangular inlet cone made from Model Name DV-355-0.25-B
galvanized steel. Rain hood up to size 500 made from seawater resistant aluminium. Motor Air Volume (cfm) 420
supporting plate with integrated protection guard made from plastic coated round bar steel.
Roof exhaust fans shall be up blast centrifugal belt driven type. The fan impeller is centrifugal Static/Total Pressure (Pa) 250/251
backward, made of aluminium Balanced on two levels according to quality level G 2.5 Dynamic Pressure (Pa) 1
DIN/ISO1940 Motors shall be heavy duty ball bearing type, Motors and drives are mounted out
of the air stream according to DIN 18869-1:2003-10. Fresh air for motor cooling is drawn into Outlet Velocity (m/s) 2
the motor compartment from a ventilation tube. Motors are mounted under removable weather Static/Total Efficiency 37/37
hood.
Fan Speed (rpm) 1232
Fan Absorbed Power (kW) 0.14

Accessories Motor Technical Data


Motor Power (kW) 0.25

Motor Speed (rpm) 1725

Power Supply 380V/3/60Hz

Sound Data
Hz 63 125 250 500 1000 2000 4000 8000 Total

LwA (dBA) 58 65 74 80 82 80 75 71 86
-By theoritical Calculation

Fan Performance Curve

4
Project Name: QUOTATION 127-01
Unit Tag: EF-02
Date: Sep 11,2022

Fan Drawing & Dimensions


Dimension in mm

5
Project Name: QUOTATION 127-01
Unit Tag: EF-03
Date: Sep 11,2022

‡DV/W : ROOF EXHAUST FAN, UP BLAST, DIRECT DRIVE

Brief Description FAN Technical Data


Base frame with bolts for tightening of inlet accessories and rectangular inlet cone made from Model Name DV-355-4E
galvanized steel; from size 560 -710 additionally plastic coated. Rain hood up to size 500 made Air Volume (cfm) 830
from seawater resistant aluminium, from size 560 from galvanized steel. Motor supporting plate
with integrated protection guard made from plastic coated round bar steel. Fans are equipped Static/Total Pressure (Pa) 250/254
with backward curved high efficiency aluminium impellers, mounted onto the rotor of a speed Dynamic Pressure (Pa) 4
controllable external rotor motor. Balanced on two levels according to quality level G 2.5
DIN/ISO1940. Motor closed protection class F with protection against humidity and thermal Outlet Velocity (m/s) 3.96
contacts wired in windings from size 355. Maintenance free ball bearings, closed on both sides, Static/Total Efficiency 29/29
sealed for life. Easy access to the terminal box (not connected) under rain hood.
Fan Speed (rpm) 1506
Fan Absorbed Power (kW) 0.34
Voltage (V) 200

Accessories Motor Technical Data


Pmax (kW) 0.43

Imax (A) 2

IP 54

Class F

Roof Opening (mm) 443X443

Actual Power (kW) 0.34

Motor Speed (rpm) 1506

Power Supply 230V/1/60Hz

Sound Data
Hz 63 125 250 500 1000 2000 4000 8000 Total

LwA (dBA) 45 56 66 68 71 69 63 55 75
-By theoritical Calculation

Fan Performance Curve

6
Project Name: QUOTATION 127-01
Unit Tag: EF-03
Date: Sep 11,2022

Fan Drawing & Dimensions


Dimension in mm

7
Project Name: QUOTATION 127-01
Unit Tag: EF-04
Date: Sep 11,2022

‡SWSI, CENTRIFUGAL BACKWARD CURVE FAN, BELT DRIVEN

Brief Description FAN Technical Data


The whole spiral casings are made of black sheet steel. The side plates with holes for fixing the Model Name HRE-315-RD-90
stand fastened to the scroll by lock seam and are spot welded construction. The stands and the Air Volume (cfm) 760
inlet cones are attached to the casing by screw nuts which are mounted on the side plates.
Generally our impellers with built-in shafts are statically and dynamically balanced on precision Static/Total Pressure (Pa) 400/414
machines according to quality standard Q2, 5 or 6, 3 of DIN/ISO 1940. The quality standard Dynamic Pressure (Pa) 14
depends on the size of the impeller. The impeller of fan series HRE is manufactured out of
aluminium. The construction of spark resistance fan will be according to AMCA type C, This Outlet Velocity (m/s) 4.6
construction offers good level of spark resistance by using of an aluminium impeller, inlet cone Static/Total Efficiency 48/50
and rub rings.
Fan Speed (rpm) 1677
Fan Absorbed Power (kW) 0.3

Accessories Motor Technical Data


Variable Frequency Drive (VFD) Motor Power (kW) 0.55

Motor Speed (rpm) 1725

Power Supply 380V/3/60Hz

Sound Data
Hz 63 125 250 500 1000 2000 4000 8000 Total

LwA (dBA) 55 66 76 69 68 68 64 56 79
-By theoritical Calculation

Fan Performance Curve

8
Project Name: QUOTATION 127-01
Unit Tag: EF-04
Date: Sep 11,2022

Fan Drawing & Dimensions


Dimension in mm

9
Project Name: QUOTATION 127-01
Unit Tag: EF-05
Date: Sep 11,2022

‡SWSI, CENTRIFUGAL BACKWARD CURVE FAN, BELT DRIVEN

Brief Description FAN Technical Data


The whole spiral casings are made of black sheet steel. The side plates with holes for fixing the Model Name HRE-560-RD-90
stand fastened to the scroll by lock seam and are spot welded construction. The stands and the Air Volume (cfm) 5625
inlet cones are attached to the casing by screw nuts which are mounted on the side plates.
Generally our impellers with built-in shafts are statically and dynamically balanced on precision Static/Total Pressure (Pa) 600/675
machines according to quality standard Q2, 5 or 6, 3 of DIN/ISO 1940. The quality standard Dynamic Pressure (Pa) 75
depends on the size of the impeller. The impeller of fan series HRE is manufactured out of
aluminium. The construction of spark resistance fan will be according to AMCA type C, This Outlet Velocity (m/s) 10.78
construction offers good level of spark resistance by using of an aluminium impeller, inlet cone Static/Total Efficiency 44/50
and rub rings.
Fan Speed (rpm) 1410
Fan Absorbed Power (kW) 3.58

Accessories Motor Technical Data


Variable Frequency Drive (VFD) Motor Power (kW) 5.5

Motor Speed (rpm) 1725

Power Supply 380V/3/60Hz

Sound Data
Hz 63 125 250 500 1000 2000 4000 8000 Total

LwA (dBA) 77 78 84 80 79 73 70 66 88
-By theoritical Calculation

Fan Performance Curve

10
Project Name: QUOTATION 127-01
Unit Tag: EF-05
Date: Sep 11,2022

Fan Drawing & Dimensions


Dimension in mm

11
Project Name: QUOTATION 127-01
Unit Tag: EF-06
Date: Sep 11,2022

‡SWSI, CENTRIFUGAL BACKWARD CURVE FAN, BELT DRIVEN

Brief Description FAN Technical Data


The whole spiral casings are made of black sheet steel. The side plates with holes for fixing the Model Name HRE-630-RD-90
stand fastened to the scroll by lock seam and are spot welded construction. The stands and the Air Volume (cfm) 6685
inlet cones are attached to the casing by screw nuts which are mounted on the side plates.
Generally our impellers with built-in shafts are statically and dynamically balanced on precision Static/Total Pressure (Pa) 600/662
machines according to quality standard Q2, 5 or 6, 3 of DIN/ISO 1940. The quality standard Dynamic Pressure (Pa) 62
depends on the size of the impeller. The impeller of fan series HRE is manufactured out of
aluminium. The construction of spark resistance fan will be according to AMCA type C, This Outlet Velocity (m/s) 10.12
construction offers good level of spark resistance by using of an aluminium impeller, inlet cone Static/Total Efficiency 48/53
and rub rings.
Fan Speed (rpm) 1256
Fan Absorbed Power (kW) 3.91

Accessories Motor Technical Data


Variable Frequency Drive (VFD) Motor Power (kW) 5.5

Motor Speed (rpm) 1725

Power Supply 380V/3/60Hz

Sound Data
Hz 63 125 250 500 1000 2000 4000 8000 Total

LwA (dBA) 80 80 86 82 81 76 72 65 90
-By theoritical Calculation

Fan Performance Curve

12
Project Name: QUOTATION 127-01
Unit Tag: EF-06
Date: Sep 11,2022

Fan Drawing & Dimensions


Dimension in mm

13

You might also like