You are on page 1of 3

STRONG ROOM & Safes

The reason for the Construction of Strong While a modular prefabricated strong room
Room is to have a very high secured place has thin walls not exceeding 150mm, with
in order to protect high volume of cash the same or even higher burglary protection
money, precious stones, jewelers and other grade. Such weight and disassembled walls
valuables like art collection items. permit the set-up of these modular strong
rooms in the upper floors of new buildings,
Building a fixed strong room requires its components are welded together making
a place with very high structural load a very clean and compact construction site.
bearing capacity, normally it should be in There are also additional advantages,
the underground floor of the bank, due to such as the possibility of disassembling the
the thick armored walls that usually vary strong room and transporting it to another
between 30 to 60 cm, relative to the level location, it can also be expanded or reduced
of protection needed, which makes strong in volume, expected load not exceeding
room a very heavy load. 300 kg/m2 inner and wall covering can be
added to match the general design of the
premises.

1.Floor and Ceilings Components 5.Ventilation System


2.Construction of Components 6.Vault Door
3.Inner Covering 7.Airing
4.Cables 8.Outer Coverings

ssspl directory
Vault doors follow the level of security people inside, as is found in some rubbery
selected for the modular panels from cases. Also, the installation of an anti-
0 to 9. Also, they may have two to four intrusion alarm system should be taken into
different combinations & locks, preferably: consideration while preparing cabling.
one high security double bit lock, and the In the end, not all engineers and architects
other a keyless mechanical or electronic are capable of designing a perfect strong
programmable combination. Moreover, a room, therefore it is advised to coordinate
daily grill gate should be installed inside, either with experts or your future safe
behind the vault doors, and kept close while equipment provider.
working in the strong room to keep out
unauthorized employees or visitors.
The Design Plan related to ventilation is a
very important survival factor in case the
vault door closes for any reason, trapping

Double bits
Mechanical
Lock

Mechanical
Combination
Electrical Combination Lock Lock

Vault Doors

ssspl directory
VAULT ROOM CONSTRUCTION
MINIMUM BANK VAULT ROOM; FLOOR AND CEILING REQUIREMENTS

TYPICAL WALL AND FLOOR


REINFORCEMENT ARRANGEMENT (SIDE &
TOP VIEW)

Vaults require at least 30cms thickness walls, centers and weighting at least 30kgs/m2
floor and ceiling of reinforced concrete. The each direction. Number of grids required
vault door should be manufactured from for reinforced walls, floor, and ceiling of
steel with 9cms minimum in thickness, or bank vaults is as follows: 30cms thickness
other drill and torch resistant material and requires 3 grids; 45cms thickness requires
equipped with a dial combination lock (a time 4 grids; 68cms thickness or greater requires
lock is optional) in additional to a Security 5 grids.
key lock and a substantial grill gate. The front elevation of steel reinforcing grids
should show maximum space requirements
Concrete: of 16mm deformed steel reinforcing bars.
The adequate concrete used in walls, floor Grids for all (RC) Reinforced concrete walls
and ceiling for bank vaults will develop an are to be located not less than 10cms apart
ultimate compressive strength of at least and staggered equally.
212 kg/cm2 (the (RC) would then weigh Finally, the weights of reinforced concrete
2300KGkni2 on 30 cm thickness basis - ) (RC) per square meter of wall, floor and
in accordance with the American Concrete ceiling area are as follows: 30cms with
institute standards (ACI). SR=763.3Kgs. 35cms with SR=1175.0Kgs.
68cms with SR=1721.6Kgs.
Steel Reinforcing (SR):
Deformed steel of 16mm diameter reinforcing
bars (SR) should be located in vertical and Systems and Equipment cannot be
horizontal rows in each direction to form a reliable unless properly maintained by
grid with not more than 10cms space in the professionals on a yearly basis