You are on page 1of 2

Technical Specification Sheet

Document No. A6V11270833


August 1, 2018

Remote IO modules IO-R-16/34


IO-R-16

8 Universal inputs Type 3 (10k) thermistors


0-100kΩ
0-10VDC
0-20mA with external resistor

4 Relay outputs Form A contacts 24VAC @ 0.5A


rated

Description
4 Analog outputs 0-10VDC

Communication RS-485
The IO-R is part of the Niagara portfolio of hardware,
software and tools designed for remote monitoring Power Supply 15VDC
and control applications that enables end-to-end Can be powered from an IO-R-34
automation and device-to-enterprise integration. IO-R
allows the TNM® 8000 to interface directly with IO-R-34
simple non-intelligent inputs and outputs remotely
located up to 4,000 feet from the TNM. The 16 Universal inputs Type 3 (10k) thermistors
connection is established via an industry-standard RS
0-100kΩ
485 multi-drop communications bus. Multiple IO-R
devices can be utilized, providing 250+ IO points on a 0-10VDC
single TNM. 0-20mA with external resistor

Features 10 Relay outputs Form A contacts 24VAC @ 0.5A


rated
● Operates with Niagara 4.3 the latest version of the
Niagara Framework® 8 Analog outputs 0-10VDC

● Remote (up to 4000ft) IO module for distributed


IO on RS-485
Power Supply 24 VAC/DC
● Allows the TNM-8000 to interface with inputs and Can provide power to up to 4
outputs.
attached IO-R-16 modules
● Multiple IO modules can be utilized on a single
TNM Communication RS-485

Specifications
Agency Listings
Operating System
UL Listings UL 916, C-UL
Niagara 4 Requires Niagara 4.3 or later
CE EN 61326-1:2013,
Niagara AX Requires Niagara 3.8u3 or later
FCC Compliance FCC Part 15, Class B

Siemens Industry, Inc. Page 1 of 2


Agency Listings IO-R-16
RoHS RoHS2
82.5mm (w) x 116mm (h) x 61mm (d) (3.25 in x 4.5
China ROHS
in x 2.4 in)
Other RCM; REACH; WEEE; Open
Energy Management Class 2

Ambient Conditions

Operating Temperature -20°C to 60°C

Storage Temperature -40°C to 85°C

Relative Humidity Range 5% to 95% — Non condensing

Shipping and vibration: ASTM D4169, Assurance Level II

MTTF 10 years+

Expandability
IO-R-34
Licensing
162mm (w) x 116mm (h) x 61mm (d) (6.8 in x 4.5 in
Included with the TNM-8000 is 16 IO device count.
- 1 IO-R-16 = device count 1 x 2.4 in)
- 1 IO-R-16 = device count 2
Therefore, the maximum Expansion is
- 8 IO-R-34 (8* device count 2)
or
- 16 IO-R-16 (16* device count 1)
or a combination
- E.g. 4 IO-R-34 and 8 IO-R-16 (4* device
count 2 + 8* device count 1 = device count
16)

Mounting and Dimensions


The I/O-R I/O modules support mounting on EN50022
standard 7.5mm * 35mm DIN rail or panel mounting. Product Ordering Information
Description Part Number

16 Point IO Module. Connected to the IO-R-16


TNM-8000 over RS-485

34 Point IO Module. Connected to the IO-R-34


TNM-8000 over RS-485

Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design
improvements are introduced. TALON is a registered trademark of Siemens Industry, Inc. Facility Go is a trademark of Siemens Industry, Inc. Product or
company names mentioned herein may be the trademarks of their respective owners. ©2018 Siemens Industry, Inc.

Siemens Industry, Inc. Your feedback is important to us. If you have Document No. A6V11270833
Building Technologies Division comments about this document, please send them to Printed in the USA
1000 Deerfield Parkway SBT_technical.editor.us.sbt@siemens.com Page 2 of 2
Buffalo Grove, IL 60089-4513
USA
Tel. 1 + 847-215-1000