UL-EU CERTIFICATE

Certificate No. UL-EU-01125-CPR


Page 1/17
Date of Issue 2019-12-18

Certificate Holder Sika Services AG


Tueffenwies 16
8048 Zurich
Switzerland

Manufacturer Manufacturer site code E046

Certified Product Type Fire Stopping and Sealing Product, Linear Joint and Gap
Seal
Product Trade Name Sikasil®-670 Fire
Trademark N/A
Rating/Classification See Appendix

Harmonised Technical Specifications EAD 350141-00-1106; EN 13501-2


Supporting Documentation ETA 14/0474, EC - CERTIFICATE OF CONSTANCY OF
PERFORMANCE – 1121-CPR-JA5054
Additional information
Expiry date 2029-12-17

This is to certify that representative samples of the Certified Product listed above have been investigated by Underwriters
Laboratories to the Standard(s) indicated on this Certificate, in accordance with the UL Global Services Agreement and the UL-EU
Mark Service Terms and Conditions (“Agreement”). The Certificate Holder is entitled to use the UL-EU Mark for the Certified Product
Head of Notified Body listed on the certificate and manufactured at the production site(s) listed, in accordance with the terms of the Agreement. Only
those products bearing the UL-EU Mark for Europe should be considered as being covered by UL’s UL-EU Mark Service. This
Chris Miles Certificate shall remain valid through the Expiration date, unless a Standard identified on this Certificate is amended or withdrawn
prior to that date or there is a non-compliance with the Agreement.

www.ul.com 27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 2/17
Date of Issue 2019-12-18

This certificate relates to the use of Sikasil®-670 Fire Sealant for fire stopping where there are joints in or between walls & floors.
The detailed scope is given in pages 3 to 16 of this Certificate. This shows the thickness and acceptable dimensions, substrates and
orientations required to provide fire resistance periods of up to 240 minutes for differing seal configurations and wall/floor
constructions.

The product is certificated on the basis of:

i) ETA 14/0474
ii) EC - CERTIFICATE OF CONSTANCY OF PERFORMANCE – 1121-CPR-JA5054
iii) Inspection and surveillance of factory production control by UL
iv) Fire resistance test data in accordance with EN 1366-4: 2006 and EN 1366-4: 2006+A1:2010
v) Classification in accordance with EN 13501-2
vi) Durability and Serviceability as defined in EAD 350141-00-1106

The durability class of Sikasil®-670 Fire is X - intended for use in conditions exposed to weathering.

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 3/17
Date of Issue 2019-12-18

Product-type: Fire Stopping and Sealing Product Intended use: Linear Joint and Gap Seal
Basic requirement for Basic requirement for
Basic Requirement
construction work construction work
BWR 1 Mechanical resistance and stability
- None -
BWR 2 Safety in case of fire
EN 13501-1 Reaction to fire Class E
EN 13501-2 Resistance to fire See page 4-16
BWR 3 Hygiene, health and environment
EN 1026:2000 Air permeability (material property) No performance determined
EAD 3504101-00-1106 Water permeability (material property) No performance determined
Declaration of manufacturer Release of dangerous substances Declaration of manufacturer
BWR 4 Safety in use
EOTA TR 001:2003 Mechanical resistance and stability No performance determined
EOTA TR 001:2003 Resistance to impact/movement No performance determined
EOTA TR 001:2003 Adhesion No performance determined
BWR 5 Protection against noise
EN 10140-2/ EN ISO 717-1 Airborne sound insulation Rw (C;Ctr)= 38(-2;-9)
BWR 6 Energy economy and heat retention
EN 12664, EN 12667 or EN
Thermal properties No performance determined
12939
EN ISO 12572
Water vapour permeability No performance determined
EN 12086
General aspects relating to fitness for use
EOTA TR 024:2009 Durability and serviceability X
BWR 7 Sustainable use of natural resources
- - No performance determined

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 4/17
Date of Issue 2019-12-18

1. Wall assembly – Min. 150 mm of aerated autoclaved concrete, normal weight concrete or brickwork
(Density ≥ 760 kg/m3)

2. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from each surface of wall as required to accommodate the required thickness of fill material.

3. Sealant – Sikasil®-670 Fire applied within the joint, flush with each surface of wall.

Sikasil®-670 Fire
Configuration - Wall to Wall Joint (rigid wall)
Minimum Minimum
Fire resistance classification
wall Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
EI240 - V - 25 - F - W 12-50
Concrete/ PE Backing EI240 - V - X - F - W 12-50
150 Both sides 0.5 x width
Concrete Rod E240 EI180 - T - 25 - F - W 12-50
EI240 - T - X - F - W 12-50

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 5/17
Date of Issue 2019-12-18

1. Wall assembly – Min. 150 mm of aerated autoclaved concrete, normal weight concrete or brickwork
(Density ≥ 760 kg/m3)

2. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from unexposed surface of wall as required to accommodate the required thickness of fill material.

3. Sealant – Sikasil®-670 Fire applied within the joint, flush with unexposed surface of wall.

Sikasil®-670 Fire
Configuration - Wall to Wall Joint (rigid wall)
Minimum Minimum
Fire resistance classification
wall Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
15 E180 EI45 - V - 25 - F - W 10-30
E240 EI30 - V - 25 - F - W 12-50
Concrete/ Unexposed PE Backing E120 EI60 - V - X - F - W 12-50
150
Concrete side 0.5 x width Rod
E120 EI60 - T - 25 - F - W 12-50
E240 EI60 - T - X - F - W 12-50

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 6/17
Date of Issue 2019-12-18

1. Wall assembly – Min. 150 mm of aerated autoclaved concrete, normal weight concrete or brickwork
(Density ≥ 760 kg/m3)

2. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from exposed surface of wall as required to accommodate the required thickness of fill material.

3. Sealant – Sikasil®-670 Fire applied within the joint, flush with exposed surface of wall.

Sikasil®-670 Fire
Configuration - Wall to Wall Joint (rigid wall)
Minimum Minimum
wall seal Fire resistance classification
Seal Backing
Substrate thickness depth according to
position material
EN 13501-2
[mm] [mm]
15 E60 EI45 - V - 25 - F - W 10-30
0.5 x width E60 EI45 - V - 25 - F - W 30-50
15 E60 EI45 - V - X - F - W 10-30
Concrete/ Exposed 0.5 x width PE Backing E60 EI45 - V - X - F - W 30-50
150
Concrete side 15 Rod E60 EI45 - T - 25 - F - W 10-30
0.5 x width E60 EI45 - T - 25 - F - W 30-50
15 E180 EI60 - T - X - F - W 10-30
0.5 x width E90 EI60 - T - X - F - W 30-50
27-CP-F0855 Issue: 3.1
Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 7/17
Date of Issue 2019-12-18

1. Wall assembly – Min. 150 mm of aerated autoclaved concrete, normal weight concrete or brickwork
(Density ≥ 760 kg/m3).

2. Insert – Gap facing made of steel.

3. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from each surface of wall as required to accommodate the required thickness of fill material.

4. Sealant – Sikasil®-670 Fire applied within the joint, flush with each surface of wall.

Sikasil®-670 Fire
Configuration - Wall to Wall Joint (rigid wall)
Minimum Minimum
Fire resistance classification
wall Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
Concrete/ Both PE Backing E240 EI60 - V - X - F - W 12-30
150 0.5 x width
Steel sides Rod E240 EI90 - V - X - F - W 30-50

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 8/17
Date of Issue 2019-12-18

1. Wall assembly – Min. 150 mm of aerated autoclaved concrete, normal weight concrete or brickwork
(Density ≥ 760 kg/m3).

2. Insert – Gap facing made of steel.

3. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from unexposed surface of wall as required to accommodate the required thickness of fill material.

4. Sealant – Sikasil®-670 Fire applied within the joint, flush with unexposed surface of wall.

Sikasil®-670 Fire
Configuration - Wall to Wall Joint (rigid wall)
Minimum Minimum
Fire resistance classification
wall Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
Concrete/ Unexposed PE Backing
150 0.5 x width E180 EI20 - V - X - F - W 12-50
Steel side Rod

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 9/17
Date of Issue 2019-12-18

1. Wall assembly – Min. 150 mm of aerated autoclaved concrete, normal weight concrete or brickwork
(Density ≥ 760 kg/m3).

2. Insert – Gap facing made of timber.

3. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from each surface of wall as required to accommodate the required thickness of fill material.

4. Sealant – Sikasil®-670 Fire applied within the joint, flush with each surface of wall.

Sikasil®-670 Fire
Configuration - Wall to Wall Joint (rigid wall)
Minimum Minimum
Fire resistance classification
wall Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
Concrete/
EI120 - V - X - F - W 12-50
Softwood
150 Both sides 0.5 x width PE Backing Rod
Concrete/ EI180 - V - X - F - W 12-30
Hardwood EI240 - V - X - F - W 30-50

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 10/17
Date of Issue 2019-12-18

1. Wall assembly – Min. 150 mm of aerated autoclaved concrete, normal weight concrete or brickwork
(Density ≥ 760 kg/m3).

2. Insert – Gap facing made of timber.

3. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from unexposed surface of wall as required to accommodate the required thickness of fill material.

4. Sealant – Sikasil®-670 Fire applied within the joint, flush with unexposed surface of wall.

Sikasil®-670 Fire
Configuration - Wall to Wall Joint (rigid wall)
Minimum Minimum
Fire resistance classification
wall Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
Concrete/ Unexposed PE Backing
150 0.5 x width EI90 - V - X - F - W 12-50
Softwood side Rod

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 11/17
Date of Issue 2019-12-18

1. Floor assembly – Min. 150 mm of reinforced aerated autoclaved concrete, reinforced lightweight concrete or reinforced
normal weight concrete (Density ≥ 670 kg/m3).

2. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from each surface of floor as required to accommodate the required thickness of fill material.

3. Sealant – Sikasil®-670 Fire applied within the joint, flush with each surface of floor.

Sikasil®-670 Fire
Configuration - Floor to Floor Joint (rigid floor)
Minimum Minimum
Fire resistance classification
floor Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
Concrete/ Both PE Backing E240 EI180 - H - 25 - F - W 12-50
150 0.8 x width
Concrete sides Rod EI240 - H - X - F - W 12-50

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 12/17
Date of Issue 2019-12-18

1. Floor assembly – Min. 150 mm of reinforced aerated autoclaved concrete, reinforced lightweight concrete or reinforced
normal weight concrete (Density ≥ 670 kg/m3).

2. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from unexposed surface of floor as required to accommodate the required thickness of fill material.

3. Sealant – Sikasil®-670 Fire applied within the joint, flush with unexposed surface of floor.

Sikasil®-670 Fire
Configuration - Floor to Floor Joint (rigid floor)
Minimum Minimum
Fire resistance classification
floor Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
0.8 x width PE E180 EI60 - H - 25 - F - W 12-50
Concrete/ Unexposed
150 Backing E240 EI120 - H - X - F - W 12-30
Concrete side 0.5 x width
Rod E240 EI60 - H - X - F - W 30-50

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 13/17
Date of Issue 2019-12-18

1. Floor assembly – Min. 150 mm of reinforced aerated autoclaved concrete, reinforced lightweight concrete or reinforced
normal weight concrete (Density ≥ 670 kg/m3).

2. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from exposed surface of floor as required to accommodate the required thickness of fill material.

3. Sealant – Sikasil®-670 Fire applied within the joint, flush with exposed surface of floor.

Sikasil®-670 Fire
Configuration - Floor to Floor Joint (rigid floor)
Minimum Minimum
floor seal Fire resistance classification
Seal Backing
Substrate thickness depth according to
position material
EN 13501-2
[mm] [mm]
Concrete/ Exposed PE Backing E90 EI60 - H - 25 - F - W 12-50
150 0.8 x width
Concrete side Rod EI60 - H - X - F - W 30-50

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 14/17
Date of Issue 2019-12-18

1. Floor assembly – Min. 150 mm of reinforced aerated autoclaved concrete, reinforced lightweight concrete or reinforced
normal weight concrete (Density ≥ 670 kg/m3).

2. Insert – Gap facing made of steel.

3. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from each surface of floor as required to accommodate the required thickness of fill material.

4. Sealant – Sikasil®-670 Fire applied within the joint, flush with each surface of floor.

Sikasil®-670 Fire
Configuration - Floor to Floor Joint (rigid floor)
Minimum Minimum
floor seal Fire resistance classification
Seal Backing
Substrate thickness depth according to
position material
EN 13501-2
[mm] [mm]
Concrete/ PE Backing
150 Both sides 0.8 x width E240 EI60 - H - X - F - W 12-50
Steel Rod

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 15/17
Date of Issue 2019-12-18

1. Floor assembly – Min. 150 mm of reinforced aerated autoclaved concrete, reinforced lightweight concrete or reinforced
normal weight concrete (Density ≥ 670 kg/m3).

2. Insert – Gap facing made of steel.

3. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from unexposed surface of floor as required to accommodate the required thickness of fill material.

4. Sealant – Sikasil®-670 Fire applied within the joint, flush with unexposed surface of floor.

Sikasil®-670 Fire
Configuration - Floor to Floor Joint (rigid floor)
Minimum Minimum
Fire resistance classification
floor Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
Concrete/ Unexposed 0.5 x width PE Backing E240 EI30 - H - X - F - W 12-30
150
Steel side 0.8 x width Rod E120 EI15 - H - X - F - W 30-50

27-CP-F0855 Issue: 3.1


Appendix UL-EU CERTIFICATE
Certificate No. UL-EU-01125-CPR
Page 16/17
Date of Issue 2019-12-18

1. Floor assembly – Min. 150 mm of reinforced aerated autoclaved concrete, reinforced lightweight concrete or reinforced
normal weight concrete (Density ≥ 670 kg/m3).

2. Insert – Gap facing made of steel.

3. Packing material – PE backer rod firmly packed into opening as a permanent form. Packing material
to be recessed from exposed surface of floor as required to accommodate the required thickness of fill material.

4. Sealant – Sikasil®-670 Fire applied within the joint, flush with exposed surface of floor.

Sikasil®-670 Fire
Configuration - Floor to Floor Joint (rigid floor)
Minimum Minimum
Fire resistance classification
floor Seal seal Backing
Substrate according to
thickness position depth material
EN 13501-2
[mm] [mm]
Concrete/ Exposed PE Backing
150 0.8 x width E90 EI60 - H - X - F - W 12-50
Steel side Rod

27-CP-F0855 Issue: 3.1


Appendix UL-EU Certificate
Certification Mark UL-EU mark
Certificate No. UL-EU-01125-CPR
Page 17/17
Date of Issue 2019-12-18
The UL-EU Mark, as displayed below, shall appear on certified products only. Minimum size is not
specified, as long as the Mark is legible. The following is suggested.

The minimum height of the registered trademark symbol ® shall be 1 mm. When the overall diameter of
the UL-EU Mark is less than 9.5 mm, the trademark symbol may be omitted if it is not legible to the naked
eye.

The UL-EU Mark may appear on a label, nameplate, or may be cast, stamped or molded into the product.
When appearing on a label or nameplate, the Manufacturer’s name or trademark along with a model
number are also required on that same label or nameplate. If cast, stamped or molded, the Manufacturer’s
name or trademark and model number shall also appear elsewhere on the product.

All content shall be in accordance with the details provided on this UL-EU Certificate.

PROCUREMENT

The Production site may reproduce the Mark or obtain it from a UL authorized supplier. The list of UL
authorized suppliers can be found on UL’s online directory at www.ul.com.

27-CP-F0855 Issue: 3.1