Electrical Wiring ESM-4410 (48 x 48 1/4 DIN) A BC D E / FG HI / U V W Z Never attempt to disassemble, modify or repair this unit.

Tampering with the unit may results in malfunction, electric shock


ON / OFF TEMPERATURE CONTROL UNITS ESM 4410 with Relay Output: ESM-7710 (72 x 72 1/4 DIN) or fire.
c Y CAT II
0 1 / 00 / 2 0 0
ESM-XX10 ESM-9910 (96 x 96 1/4 DIN) Do not use the unit in combustible or explosive gaseous
ESM-4410 A Supply Voltage atmospheres.
PTC, NTC
PT100 OUTPUT
7A@250VV
2 24 V W ( - %15, + %10 ) 50/60 Hz During the equipment is putted in hole on the metal panel while
PT1000 mechanical installation some metal burrs can cause injury on
3 24 V V ( ± %15 ) 50/60 Hz hands, you must be careful.
C NO Supply
115 V V ( ± %15 ) 50/60 Hz
TC
1 2 3 4 5 6 7 Voltage 4 Montage of the product on a system must be done with it’s own
Switch
Temperature
Sensor Input
L N 230VV 5 230 V V ( ± %15 ) 50/60 Hz fixing clamps. Do not do the montage of the device with
115VV
(TC, PTC, NTC Output inappropriate fixing clamp. Be sure that device will not fall while
PT100 or PT1000)
24VV
24 V W
9 Customer doing the montage.
1AVT Fuse
BC Input Type Scale(°C) It is your responsibility if this equipment is used in a manner not
ESM-9910 ESM-7710 ESM-4410 ESM 4410 with SSR Output:
ESM-4410, ESM-7710, ESM-9910 05 J ,Fe CuNi IEC584.1(ITS90) 0°C 800°C specified in this instruction manual.
Digital, ON/OFF Temperature Controller Unit cY CAT II

- 3 Digits display ESM-4410 10 K ,NiCr Ni IEC584.1(ITS90) 0°C 999°C


DIMENSIONS
- NTC Input or, PTC, NTC
OUTPUT
09 PT 100 , IEC751(ITS90) -19.9°C 99.9°C
PTC Input or, PT100 Maximum 5mm / 0.2 inch
PT1000 SSR Driver Out 03 PT 100 , IEC751(ITS90) 0°C 400°C
Max.
J type thermocouple or, 10mA@5V Z ESM-4410
K type thermocouple or, TC Supply
Voltage
12 PTC (Note-1) -50°C 150°C ESM-4410
PT-100, PT1000, 2-wire or 3-wire temperature input 1 2 3 4 5 6 7
Switch
( It must be determined in order ) 15 PTC (Note-1) -19.9°C 99.9°C

48 mm/ 1.89 inch


Temperature L N 230VV
- ON/OFF control form Sensor Input 115VV
(TC, PTC, NTC Output 24VV 14 PT 1000, IEC751(ITS90) -50°C 400°C
- Selectable heating and cooling function PT100 or PT1000) 24 V W
1AVT Fuse 13 PT 1000, IEC751(ITS90) -19.9°C 99.9°C
- Operating type selection with hysteresis OUT PROG

- Adjustment of temperature offset value 18 NTC (Note-1) -50°C 100°C SET


ESM 7710 with Relay Outputs:
- Minimum pulling time adjustment for control outputs
c Y CAT II 19 NTC (Note-1) -19.9°C 99.9°C SET
- Set value low limit and set value high limit boundaries P

- Password protection for programming mode ESM-7710 Note-1: If input type is selected PTC or NTC (BC = 12, 15, 18, 19 ),
ESM series temperature controllers are designed for measuring and Temperature sensor is given with the device. For this reason,
PTC, NTC
controlling temperature. They can be used in many applications with On/Off If input type is selected as PTC, sensor type (V = 0, 1 or 2) or 48 mm/ 1.89 inch
OUTPUT-2 OUTPUT-1 11 ± 1 mm /0.43 inch 84 mm / 3.31 inch
control form and heating and cooling selection. PT100 7A@250VV 7A@250VV If input type is selected as NTC, sensor type (V = 0, 3 or 4) must be
PT1000
They are mainly used in glass, plastic, petro-chemistry, textile, automotive and Maximum 15mm / 0.59 inch
declared in ordering information.
machine production industries. TC C NO C NO NC Supply ESM-7710
1 2 3 4 5 6 7 8 9 10
Voltage E Output-1 ESM-7710
SPECIFICATIONS Switch
INPUT Temperature L N 230VV 1 Relay Output(7A@250VVat resistive load,1NO+1NC)

72mm / 2.83 inch


115VV
NTC: NTC (10kW @ 25°C) Sensor Input 24VV
2 SSR Driver Output (Maximum 10 mA@ 5 V Z)
(TC, PTC, NTC Output-2 Output-1 24 V W
PTC: PTC (1000W @ 25°C) PT100 or PT1000) Note-1 1AVT Fuse OUT PROG

Thermocouple(TC): J, K (IEC 584.1) (ITS90) FG Output-2 SET

Thermoresistance(RTD): 2 or 3-wire PT100, PT1000 (IEC 751) (ITS90) ESM 7710 with SSR Outputs:
Measurement Range: It is in ordering information 00 None SET

c Y CAT II
P

Accuracy: ± 1% of full scale For ESM9910; Relay Output(7A@250VVat resistive load,1NO+1NC)


Cold Junction Compensation: Automatically ±0.1°C/1°C ESM-7710 01
For ESM7710; Relay Output(7A@250VVat resistive load,1NO)
Sensor Break Protection:Upscale
Sampling Cycle: 3 samples per second
PTC, NTC
OUTPUT-2 OUTPUT-1
02 SSR Driver Output (Maximum 10 mA@ 5 V Z)
PT100
CONTROL PT1000 SSR Driver Out SSR Driver Out 72mm / 2.83 inch 11.5 ± 1 mm /0.45 inch 84 mm / 3.31 inch
Max.
10mA@5V Z 10mA@5V Z
Max. V Temp.Sensor which is given with ESM-xx10
Control Form: ON/OFF Supply
ON/OFF hysteresis: It can be configured for two control outputs
1 2
TC
3 4 5 6 7 8 9 10
Voltage 0 None Maximum 15mm / 0.59 inch
Switch
OUTPUT L N 230VV 1 PTC-M6L40.K1.5(PTC Air probe with 1.5 m silicon cable) ESM-9910
Temperature
115VV
Output-1 : Relay (7A@250VV at resistive load ) or Sensor Input
(TC, PTC, NTC Output-2 Output-1
24VV 2 PTCS-M6L30.K1.5.1/8”(PTC Liquid probe with 1.5 m silicon cable)
SSR Driver Output (Maximum 10 mA@ 5 V Z) 24 V W

96mm / 3.78 inch


PT100 or PT1000) Note-1 1AVT Fuse
Output-2 : Relay (7A@250VV at resistive load ) or 3 NTC-M5L20.K1.5 (NTC Probe, thermoplastic moulded with
ESM 9910 with Relay Outputs: 1.5 m cable for cooling application)
SSR Driver Output (Maximum 10 mA@ 5 V Z)
Outputs that are on the device can be used as process or alarm output. c Y CAT II 4 NTC-M6L50.K1.5 (NTC Probe, stainless steel housing with
1.5 m cable for cooling application)
DISPLAY ESM-9910 9 Customer
Process Display :
PTC, NTC
ESM-4410 : 10 mm Red 3 digits LED Display Installation
OUTPUT-2 OUTPUT-1

c
ESM-7710 : 14 mm Red 3 digits LED Display PT100 7A@250VV 7A@250VV Before beginning installation of this product, please read
PT1000
ESM-9910 : 20 mm Red 3 digits LED Display
Supply
the instruction manual and warnings below carefully. 96mm / 3.78 inch
LED Display : TC C NO NC C NO NC 12 ± 1 mm / 0.47 inch 84 mm / 3.31 inch
Voltage
Device with 1 Output : SET(Green), OUT(Red), PROG(Red) 1 2 3 4 5 6 7 8 9 10 11 Switch
In package ,
Device with 2 Outputs : SET1(Green), SET2(Green), OUT1(Red), Temperature L N 230VV - One piece unit 2
115VV
OUT2(Red), PROG(Red) Sensor Input
24VV - Two pieces mounting clamps PANEL MOUNTING 1
(TC, PTC, NTC Output-2 Output-1 24 V W
POWER SUPPLY PT100 or PT1000) 1AVT Fuse
- One piece instruction manual
Note-1
230 V V ( ±15% ) 50/60 Hz - 3 VA ESM 9910 with SSR Outputs: A visual inspection of this product for possible damage occured during
115 V V ( ±15% ) 50/60 Hz - 3 VA shipment is recommended before installation. It is your responsibility to 1-Insert the unit in the panel
24 V V ( ±15% ) 50/60 Hz - 3 VA c Y CAT II ensure that qualified mechanical and electrical technicians install this cut-out from the front side.
24 V W ( - %15, + %10 ) 50/60 Hz - 3 VA ESM-9910 product. 2- Insert the mounting clamps
(Supply voltage must be determined in order) If there is danger of serious accident resulting from a failure or defect in to the holes that located top
PTC, NTC
ENVIRONMENTAL RATINGS and PHYSICAL SPECIFICATIONS this unit, power off the system and separate the electrical connection of and bottom sides of device and
OUTPUT-2 OUTPUT-1
Operating Temperature : 0...50°C PT100
the device from the system. screw up the fixing screws until
PT1000 SSR Driver Out SSR Driver Out
Humidity : 0-90%RH (none condensing) Max.
10mA@5V Z
Max.
10mA@5V Z
the unit completely immobile
Protection Class : IP65 at front, IP20 at rear Supply The unit is normally supplied without a power switch or a fuse. Use within the panel
TC Voltage
1 2 3 4 5 6 7 8 9 10 11 Switch
power switch and fuse as required.
DEVICE WEIGHT DIMENSION PANEL CUT-OUT Temperature L N 230VV
115VV
Be sure to use the rated power supply voltage to protect the unit against
ESM-4410 160 gr 48x48 mm, Depth:95 mm 46 x 46 mm Sensor Input
24VV damage and to prevent failure.
(TC, PTC, NTC Output-2 Output-1 24 V W
ESM-7710 210 gr 72x72 mm, Depth:95.5 mm 69 x 69 mm PT100 or PT1000) Note-1 1AVT Fuse Keep the power off until all of the wiring is completed so that electric
ESM-9910 280 gr 96x96 mm, Depth:96 mm 92 x 92 mm Note-1:Output-2 exists in only ESM-7710 and ESM-9910 Devices shock and trouble with the unit can be prevented. Introduction Brochure. ENG ESM-xx10 01 V03 10/11
Front Panel ESM-xx10 with Two Relays Entering to Programming Mode, Changing and Saving Parameters Hysteresis Parameter For Output-2
Main Operation 1 to 100 °C for TC Type Devices,
Temperature Display Adjustment of SET1 Value Screen 1 to 100 °C for PT100 (0°C , 400°C),PT1000 (-50°C , 400°C),
ESM-7710 Hysteresis for
When SET1 button is pressed
P
1.0 to 10.0 °C for PT100, Pt1000 (-19.9°C, 99.9°C),
Led indication of OUTPUT-1 is active, Main for 10 seconds PROG led Output-2
Programming mode is active, Operation starts to blink. If 1 to 100 °C for PTC (-50°C, 150°C),
°C
OUTPUT-2 is active Screen °C
programming mode entering 1.0 to 10.0 °C for PTC and NTC(-19.9°C, 99.9°C),
°C OUT1 PROG OUT2
password is different from 0 1 to 20 °C for NTC(-50°C, 100°C)
°C
OUT1 PROG OUT2 Led indication of SET1/2 value OUT1 PROG OUT2
SET1 SET2
programming mode
SET1 SET2
changing mode SET1 SET2 SET1 SET2 entering screen OUT1 PROG OUT2 Operation type selection parameter of output-1
P SET1 SET2
SET1 SET2 Press SET1
P button will be observed.
SET1
P
SET2
P SET1 SET2 Operation Type of Output-1 relay can be adjusted
P

Programming Mode
as “HEATING”. Normally energised.
Temperature Controller Entering Screen Operation Type of Output-1 relay can be adjusted
Operation Form Selection as “COOLING”. Normally de-energised.
SET1 value °C for Output-1
OUT1 PROG OUT2 Operation type selection parameter of output-2
SET1 LED lights SET1 SET2
Press button This parameter is not active in devices with one relay.
°C on SET1 SET2 for accessing to the
OUT1 PROG OUT2 P
password entering screen °C Operation Type of Output-2 relay can be adjusted
It is used for entering to SET1 value changing mode
SET1
P
SET1 SET2 OUT1 PROG OUT2 as “HEATING”. Normally energised.
and programming mode Change SET1 SET1 SET2
SET1
P
SET2
value with Password Entering Operation Type of Output-2 relay can be adjusted
SET1 SET2
Screen as “COOLING”. Normally de-energised.
SET2 It is used for entering to SET2 value changing mode and buttons P

and confirm a parameter in programming mode °C Process Offset Parameter


OUT1 PROG OUT2
Enter the programming Operation Form Selection -10 to 10 °C for TC Type Devices,
SET1 SET2
It is used to increase the value mode accessing for Output-2 -10 to 10 °C for PT100(0°C , 400°C), PT1000(-50°C , 400°C),
SET1 SET2
°C P password with -10.0 to 10.0 °C for PT100, PT1000(-19.9°C, 99.9°C),
OUT1 PROG OUT2
and buttons -10 to 10 °C for PTC(-50°C, 150°C),
It is used to decrease the value SET1 SET2 °C -10.0 to 10.0 °C for PTC and NTC(-19.9°C, 99.9°C),
Save SET1 value Password Entering
SET1 SET2 Screen OUT1 PROG OUT2 -10 to 10 °C for NTC(-50°C, 100°C)
P with button
SET2
SET1 SET2

°C
Minimum Pulling Time Parameter for Output-1
SET1 SET2
P When Output-1 is inactive this time must be expired for
Main OUT1 PROG OUT2

Operation SET1 SET2


Press SET2 button for Output-1 to become active again. It can be adjusted from 0 to
Screen SET1 SET2 accessing to the 100 seconds
P Process Offset
Adjustment of Set Values °C parameters Parameter Programming Mode Accessing Password
OUT1 PROG OUT2 It is used for accessing to the programming mode. It can be
ESM-xx10 with One Relay SET1 SET2
Minimum Set adjusted from 0 to 999. If it is selected 0, password is not
SET1 SET2 Value Parameter °C entered for accessing to the parameters.
P
OUT1 PROG OUT2
°C
SET1 SET2
Failure Message
OUT1 PROG OUT2
Main SET1 SET2
SET1 SET2
ESM-7710 Sensor failure in analogue inputs. It
Operation Adjustment of SET2 Value P
SET1 SET2 means sensor connection is wrong or
°C Screen P
there is no sensor.
Main
OUT PROG Operation Minimum Pulling Time
for Output-1 °C
SET
Screen
°C Maximum Set OUT1 PROG OUT2
SET Press SET
P button Value Parameter
P OUT1 PROG OUT2
SET1 SET2

SET1 SET2 °C °C
SET1 SET2
SET1 SET2 OUT1 PROG OUT2 P
P
Press SET2
button OUT1 PROG OUT2
SET1 SET2
SET1 SET2
SET value
SET1 SET2 SET1 SET2 Temperature Controller
P P
SET LED lights on
°C Warranty
SET2 value
OUT PROG Hysteresis for Programming Mode EMKO Elektronik warrants that the equipment delivered is free from
SET Output-1 Accessing Password
Change SET
SET2 LED lights on defects in material and workmanship. This warranty is provided for a
°C
SET
P value with °C period of two years. The warranty period starts from the delivery date.
OUT1 PROG OUT2
and buttons SET1 SET2
OUT1 PROG OUT2 This warranty is in force if duty and responsibilities which are determined
Change SET2 °C
SET1 SET2
in warranty document and instruction manual performs by the customer
SET1 SET2 value with OUT1 PROG OUT2
P
SET1
P
SET2
SET1 SET2
completely.
and buttons
SET1
P
SET2 Maintenance
°C
If Repairs should only be performed by trained and specialized personnel.
button is pressed again, device
SET2

OUT PROG
turns to parameter beginning of
Cut power to the device before accessing internal parts.
SET
the programming mode.
Do not clean the case with hydrocarbon-based solvents (Petrol,
SET
Save SET value °C
P with button Parameters Trichlorethylene etc.). Use of these solvents can reduce the mechanical
OUT1 PROG OUT2
SET1 SET2 Minimum Set Value Parameter reliability of the device. Use a cloth dampened in ethyl alcohol or water to
Save SET2 value
Main SET1 SET2
with button
SET2
Set value can not be lower than this value. This parameter clean the external plastic case.
P
Operation value can be adjusted from minimum value of devices scale Other Information
Screen to maximum set value parameter
°C Main Producer Firm Information:
OUT PROG Operation Maximum Set Value Parameter Emko Elektronik Sanayi ve Ticaret A.Þ.
SET Screen Set value can not be greater than this value. This parameter Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA
SET
°C value can be adjusted from minimum set value to Tel : (224) 261 1900
P OUT1 PROG OUT2
maximum value of device scale Fax : (224) 261 1912
SET1 SET2

SET1 SET2
Hysteresis Parameter For Output-1
P 1 to 100 °C for TC Type Devices, Repair and maintenance service Firm information:
1 to 100 °C for PT100 (0°C , 400°C),PT1000 (-50°C , 400°C), Emko Elektronik Sanayi ve Ticaret A.Þ.
1.0 to 10.0 °C for PT100, Pt1000 (-19.9°C, 99.9°C), Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA
If no operation is done in programming or Set value mode for If no operation is done in programming or Set value mode for
i i
1 to 100 °C for PTC (-50°C, 150°C),
20 seconds, device turns to main operation screen 20 seconds, device turns to main operation screen Tel : (224) 261 1900
1.0 to 10.0 °C for PTC and NTC(-19.9°C, 99.9°C),
automatically. automatically. Fax : (224) 261 1912
1 to 20 °C for NTC(-50°C, 100°C)