CONSTRUCTION OF KHAZAEN FRUIT & VEGETABLE
Vegetable CENTRAL MARKET
Central Market KHAZAEN ECONOMIC CITY MIDDLE EAST
SAOC BARKA, SULTANATE OF OMAN

Rigid Non-flame Propagating Conduits of


BS6099
Insulating Materials
Fire Tests on Building Materials and
BS476
Structures
BS4678
Trunking made of Insulating Material
Part 4
I.E.E.E. Wiring Regulations
All related Test reports for loading on Ducting, Service, Junction outlet boxes from a
recognized testing institution should be made available for final approval of materials.
Submittals
a) Manufacturers data and installation instructions.
b) Schedule of materials to be used.
c) Shop drawings showing all layout, connections wall and floor boxes fixing methods
and the like.
d) Trunking sizing calculation shall be submitted for the various areas along with shop
drawing.
2.6.3 Conduits/Trunking And Fittings
Materials
a) Surface conduits shall be heavy gauge hot dipped galvanized after fabrication rigid Noted &
steel Class 4 manufactured in accordance with BS 4568 Part Complies
b) Conduits run in or under floor slabs, or in poured concrete walls shall be high Noted &
impact PVC type, minimum 1.7 mm wall thickness manufactured in accordance with BS Complies
4607 and BS 6099. with current
standard
c) Use liquid tight (LFMC) flexible steel conduit with ground conductor for final BS EN
connections to motors. Lengths shall not exceed 500 mm. 61386-21.
d) All metal cable trunking shall be manufactured from sheet steel in accordance with
BS 4678. �
e) Gauges shall be 1.6 mm thickness up to 100 mm x 100 mm or equivalent cro--��-�-
sectional area, and 2 mm thickness for sizes over 100 mm x 100 mm. /41/;';'�:v;;;,��\
f) Protectio� against co�ros!on shall be_ _ hot dip zinc c?�ting after fabrication. (•-Posi:�f�f:;�;•:i��'·"•\\
g) All conduit and trunking In uncond1t1oned and unfinished areas eg. plant r�rrr§!..: ;::;�i�i tY
electrical rooms, etc. shall be painted with one coat of metal primer after installatio'':..,.:: PtAs"f\cx'?v
�--
2.6.4 Cable Tray and Fittings
Materials
a) The cable tray system shall be complete with all necessary trays, risers, elbows,
supports, end plates, drop outs and fittings required for the installation.

0070_Xtr_003 Electrical Systems - Technical Specifications Booklet 82/148