STANDARD ELVP BATTERY MONITOR SETTINGS - 602S

NAME DESCRIPTION OUR SETTING RANGE DEFAULT UNIT


Cb Set to EMER. AH 20-9999 200 Ah Cb VALUE 4 ELVP 600 Ah
Vc Charged Voltage 27.4 0-90 13.2 V 6 ELVP 800 Ah
It Tail Current Default .5-10 4 % 8 ELVP 1000 Ah
Tcd Charged Detection Time Default Jan-50 3 Min.
CEF Charge Efficiency Factor Default 50-100 95* %
PC Peukert Exponent Default 1-1.5 1.25
Ith Current Threshold Default 0-2 .1** A
Tdt Average Time to Go 12 0-12 3 Min.
Df Discharge Floor Default 0-99 50 %
CIS Clear SOC Relay (State of Charge) Default 0-99 90 %
RME Relay Minimum Enable Time Default 0-500 0 Min.
RDD Relay Disable Delay Default 0-500 0 Min.
AI Alarm Low Voltage 23.5 0-95 0 V
Aic Clear Low Voltage Alarm 24.5 0-95 0 V
Ah Alarm High Voltage Default 0-95 0 V
Ahc Clear High Voltage Alarm Default 0-95 0 V
AIS Alarm Low Starter Battery Voltage 23.5 0-95 0 V
AISC Clear Low Starter Battery Voltage Alarm 24.5 0-95 0 V
AhS Alarm High Starter Battery Voltage Default 0-95 0 V
AhSc Clear High Starter Battery Voltage Alarm Default 0-95 0 V
As Alarm Low SOC (State of Charge) Default 0-99 0 %
Asc Clear Low SOC Alarm (State of Charge) Default 0-99 0 %
A BUZ When set the Buzzer will sound on Alarm Default YES
RI Relay Low Voltage 24.5 0-95 0 V
Rlc Clear Relay Low Voltage 25 0-95 0 V
Rh Relay High Voltage Default 0-95 0 V
Rhc Clear Relay High Voltage Default 0-95 0 V
RIS Relay Low Starter Battery Voltage 23.5 0-95 0 V
RISc Clear Relay Low Starter Battery Voltage 25 0-95 0 V
RhS Relay High Starter Battery Voltage Default 0-95 0 V
RhSc Clear Relay High Starter Battery Voltage Default 0-95 0 V
SA Maximum Rated Shunt Current Default 0-9999 500 A
SVThe Shunt Output Voltage at the Maximum Rated Current Default 0.001-.1 0.05 V
BL I Intensity Backlight Default 0-9 5
BL ON Backlight Always on Default NO
DV Battery Voltage Display Default YES
D VS Starter Battery Voltage Display Default YES
DI Current Display Default YES
D CE Consumed Energy Display Default YES
D SOC State of Charge Display NO YES
D TTG Time to Go Display NO YES
ZERO Zero Current Calibration Hold Select for 3 Seconds
SYNC Manual Synchronization Hold (+) & (-) for 3 Seconds
R DEF Reset to Factory Defaults Hold Select for 3 Seconds
CI HIS Clear History Data Hold Select for 5 Seconds
Lock Set up Lock YES NO
SW Firmware Version Default NOT ALTERED
STANDARD ELVP BATTERY MONITOR SETTINGS VICTRON BMV - 702
Description Our Setting Range Default Unit
01. Battery Capacity Set to EMER. AH 20-9999 200 Ah
02.Charged Voltage 27.4 0-90 13.2 V
03.Tail Current Default .5-10 4 %
04.Charged Detection Time Default Jan-50 3 Min.
05. Peukert Exponent Default 50-100 1.25 %
06. Charge Efficiency Factor Default 1-1.5 95%
07. Current Threshold Default 0-2 .1** A
08. Average Time to Go 12 0-12 3 Min.
09. Zero Current Calibration
10. Synchronise
11. Relay Mode Default
12. Invert Relay Default ON/OFF OFF
13. Relay State (Read Only)
14. Relay minimum closed time Default 0-500 0 Min.
15. Relay minimum open time Default 0-500 0 Min.
16. SOC relay (discharge floor) 0 0-99 50 %
17. Clear SOC relay 0 0-99 99 %
18. Low Voltage Relay 24.5 0-95 0 V
19. Clear low voltage Relay 25 0-95 0 V
20.High Voltage Relay Default 0-95 0 V
21. Clear high voltage relay Default 0-99 0 V
22. Low Starter voltage relay 23.5 0-99 0 V
23. Clear low starter voltage relay 25 0-99 0 V
24. High starter voltage relay Default 0-95 0 V
25. Clear high starter voltage relay Default 0-95 0 V
26. High temperature relay Default 0-99 0 °C
27. Clear high temperature relay Default 0-99 0 °C
28. Low temperature relay Default 0-99 0 °C
29. Clear low temperature relay Default 0-99 0 °C
30. Mid voltage relay Default 0-99 0 %
31. Clear mid voltage relay Default 0-95 0 %
32. Alarm Buzzer Default ON/OFF ON
33. Low SOC Alarm Default 0-99 0 %
34. Clear Low SOC alarm Default 0-99 0 %
35. Low voltage alarm 23.5 0-99 0 V
36. Clear low voltage alarm 24.5 0-99 0 V
37. High Voltage Alarm Default 0-99 0 V
38. Clear High Voltage Alarm Default 0-99 0 V
39. Low Starter voltage alarm 23.5 0-99 0 V
40. Clear low voltage starter alarm 24.5 0-99 0 V
41. High starter voltage alarm Default 0-99 0 V
42. Clear High Voltage starter alarm Default 0-99 0 V
43. High Temperature alarm Default 0-99 0 °C
44. Clear High Temperature alarm Default 0-99 0 °C
45. Low temperature alarm Default 0-99 0 °C
46. Clear low temperature alarm Default 0-99 0 °C
47. Mid voltage alarm 0 0-99 2 %
48. Clear low voltage alarm 0 0-99 1.5 °C
49. Backlight intensity Default 0-9 5
50. Backlight always on Default ON/OFF OFF
51. Scroll speed Default 1-May 2
52. Main Voltage Display Default ON/OFF ON
53. Current Display Default ON/OFF ON
54. Power Display Default ON/OFF ON
55. Consumed Ah display OFF ON/OFF ON
56. State of charge display OFF ON/OFF ON
57. Time to go display OFF ON/OFF ON
58. Starter voltage display Default ON/OFF ON
59. Temperature Display OFF ON/OFF ON
60. Mid-voltage display OFF ON/OFF ON
61. Software version Read Only
62. Restore Defaults
63. Clear History
64. Lock Setup ON ON/OFF OFF
65. Shunt Current Default 1-9999A 500 A
66. Shunt Voltage Default 1-100 50 mV
67. Temperature Unit Default CELC/FAHR CELC
68. Temperature Coefficient Default
69. Aux Input START S/M/T

Main Battery Bank (EMERGENCY) must be connected to "B1" terminal on Shunt.

If changing menu options, ensure select button is pressed until a beep is heard, before exiting back out to menu.
ELVP CHARGING

For the NEW type of ELVP, where the switch has only two positions, standby, and
emergency, use the following procedure:

1. Connect mains power to refuge chamber


2. Turn on main supply breaker located on back wall of the refuge chamber
3. Ensure the Battery Control Switch, located on rear wall is in the Standby position.
4. Switch the Charger / Inverter to the ON position using the switch located on the
front of the scrubber.
5. Red strobe will turn off automatically.
6. e banks are charged.
7. The refuge chamber is now recharged and ready for standalone use.

For the OLD type of ELVP, where the switch has three positions, standby, emergency,
and charge, use the following procedure:

1. Connect mains power to refuge chamber


2. Turn on main supply breaker located on back wall of the refuge chamber
3. Switch the Charger / Inverter to the ON position using the switch located on the
front of the scrubber.
4. Red strobe will turn off automatically.
5. Ensure the Battery Control Switch, located on rear wall stays in the Standby
position for 4 hours. This will allow that bank to accept a charge before linking it
to the main bank in the next step.
6. After a minimum of 4 hours switch the battery selector switch to the charge
position.
7. LED indicators on the controller will show state of charge.
8.
9. The refuge chamber can stay in this position indefinitely while connected to
mains
10. If disconnecting from mains rotate Battery Control Switch back to standby
11. Switch the Charger / Inverter switch to the OFF position.
12. The refuge chamber is now recharged and ready for standalone use.
240volt 50hz 16 amp Inverter/Charger remote
supply panel

A 16 Amp Mains 15 SCRUBBER


Battery monitor internal UNIT
Breaker alarm relay
DIGITAL VICTRON BMV-
N 600 BATTERY MONITOR EXTERNAL STROBE
Data cable INDICATING BATTERY
CHARGE REQUIRED
E SCRUBBER FRONT

RCD / CB 10 amp fusing


VICTRON A Blower
X1 INV/CHARGER
N AIRCON UNIT
24/3000/70 Blower run indicator
E AIRCON ISOLATOR
240VOLT AC OUTPUT 5 amp fusing light
Interior light
BATTERY BANK
SELECTOR SWITCH Interior light
Indicator light
CHARGING BOTH 5 amp fusing
Internal link Green strobe light
DATA CABLE FROM DC
SHUNT MAIN BATTERY BANK
Green strobe light
2 5 amp fusing on indicator light

0.5amp COMMON Siren


1
STAND BY BATTERY BANK
BATTERY SHUNT Siren on indicator
OFF 10 amp fusing light
24 VOLT +VE SUPPLY

12Volt auxiliary
output
12 VOLT DC OUTPUT
-VE 12VOLT +VE -VE 12VOLT +VE
Auxiliary output on
5 amp fusing Indicator light

-VE 12VOLT +VE -VE 12VOLT +VE 24,volt aux output


BATTERY DGM
TEMPERATURE PROBE
DGM Output
-VE 12VOLT +VE -VE 12VOLT +VE Indicactor light

MineARC Systems Australia


-VE 12VOLT +VE -VE 12VOLT +VE
6 MAN 24V ELVP Control System
Drawing By: TC
Drawing Date: 1/31/2012
-VE 12VOLT +VE -VE 12VOLT +VE
Modified By: KD
Date Modified: 8/4/2012
240 Volt 50/60hz 16A supply
Inverter/Charger remote panel

16A Mains Breaker


15
Battery monitor internal alarm EXTERNAL STROBE
N
relay INDICATING BATTERY CHARGE
DIGITAL VICTRON BMV-602S REQUIRED
BATTERY MONITOR

E
Data cable

SCRUBBER FRONT

10A Fuse
Blower
VICTRON AC OUT 1
A
INV/CHARGER N
A AC OUT 2 AIRCON UNIT
24/3000/70 Blower on indicator
E light
240 VOLT AC OUTPUT 5A Fuse
Interior light

Interior light on
Indicator light
BATTERY SELECTOR SWITCH
5A Fuse
Green strobe light
DATA CABLE FROM DC SHUNT
EMERGENCY
BATTERY
BANK Green strobe on
2 indicator light
COMMON 5A Fuse
STANDBY
BATTERY Siren
BANK
1
Siren on indicator
BATTERY SHUNT light
OFF

24 VOLT +VE SUPPLY 1A Fuse 10A Fuse


12 Volt Radio Supply

1A Fuse
125A 24/12 VOLT CONVERTER
150WATT
Fuse 12 VOLT DC OUTPUT
-VE 12 VOLT +VE -VE 12 VOLT +VE Radio Supply on
indicator light
Paralleled
#10 Cables 5A Fuse
BATTERY TEMPERATURE
DGM/Aux. Supply
PROBE 100A
Fuse
Paralleled SCRUBBER UNIT DGM/Aux. Supply on
#10 Cables indicator light

-VE 12 VOLT +VE -VE 12 VOLT +VE

80Amp Fusing MineARC Systems America

-VE 12 VOLT +VE -VE 12 VOLT +VE 24V ELVP Control System

Drawing By: TC

Drawing Date: 1/31/2012

-VE 12 VOLT +VE -VE 12 VOLT +VE Modified By: TC

Date Modified: 22/3/2013