You are on page 1of 7

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/344049996

Design and Building a High Voltage Switchgear Safety System

Conference Paper · July 2020


DOI: 10.1109/ICCSP48568.2020.9182459

CITATIONS READS
0 563

7 authors, including:

Prashobh Karunakaran Mohammad Shahril Osman


University College of Technology Sarawak University of Technology Sarawak
36 PUBLICATIONS   44 CITATIONS    37 PUBLICATIONS   299 CITATIONS   

SEE PROFILE SEE PROFILE

Sung Chee Cheng Man Djun Lee


UCTS Curtin University Sarawak
7 PUBLICATIONS   3 CITATIONS    39 PUBLICATIONS   82 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Men and Women; an analysis of the difference status of Men and Women especially in the Asian Regions View project

Politics and technology View project

All content following this page was uploaded by Prashobh Karunakaran on 06 January 2021.

The user has requested enhancement of the downloaded file.


Design and Building A High Voltage
Switchgear Safety System
Prashobh Karunakaran, Member IEEE, Mohammad Shahril Osman, V. Karuppanna, Sung Chee
Cheng, Lee Man Djun, Alexon John and Ting Kwong Hieng

basically a computer which should be treated the same. Also,


Abstract—High Voltage (HV) switching is dangerous and there in rural locations where many substations are located, there is
have been many fatalities among switching personnel. It is inaccessibility of spare parts to repair a VFD or electronic
therefore imperative that HV switching be performed from a safe based system. A system using a motor without VFD was tried
distance away from the switchgear. Motors with lead screws
seem to be the standard solution for actuation today but after
by the local electric authority (LEA) and it did not have
much deliberation of the practicality, the solution formulated is enough force to perform the switching [1]. If a more powerful
an electro-pneumatic one. The high voltage Switchgear Safety motor is used, it might break the switchgear handle.
System developed in this research is focused on the Lucy brand Therefore, an expensive VFD is necessary to precisely control
of 11kV switchgears which is the most common in Sarawak, the force exerted by an induction motor. Comparatively a
Malaysia but can easily be modified to operate other brands of simple tuning screw shown in “Fig. 1” can vary the air
switchgears. This is because the basic idea is to have a high force
actuation happening at a safe distance away. User-friendliness of
pressure going into a pneumatic cylinder and therefore the
operation, maintenance as well as weight considerations were the force exerted by it.
prime criteria used in the design. The system was successfully Switching of HV switchgears have caused many fatalities
tested on a high voltage switchgear. or serious injuries. IGBT (insulated gate bipolar transistors)
switchgears have been recently developed and will potentially
Index Terms— accidents, arc-quenching, electro-pneumatic, solve the HV switching hazards of the future [1], but in the
high-voltage, remotely control, switchgear safety switching, meantime, a system must be designed to enable switching
substations
personnel (SP) to be far away from HV switchgears when
switching it. The HV switching system designed in this
I. INTRODUCTION
research will eliminate the chances of injury to SP because
D ESPITE most actuation moving towards motor control
with lead screws today, after much research and study, it
was determined that electro-pneumatics is the best option to
they can be up to 25m away, in their car while triggering the
HV Switchgear Safety System.
33kV and above switchgears or circuit breakers (CB) are
build this high voltage (HV) Switchgear Safety System. This typically switched remotely from a control center (dispatch
is especially so upon making the main criteria user- center), but 11kV switchgears are normally manually
friendliness and ease of maintenance. Many high voltage switched. Investigations into the root causes of HV
(HV) switching are done in rural settings where transportation switchgear accidents have indicated that most are due to SP
of the switching system over long distances in a car can result not following the operation checklist diligently but there are
in exposure to heat and vibrations on bad roads which can cases where totally abnormal or unpredictable events have
damage a VFD (variable frequency drive) controlled motor to caused the accidents [2]. So, it is imperative that the SP be
pull or push the switchgear lever. It must be noted that just as away from the switchgear as it is being switched.
a laptop cannot withstand heat, vibration and dust, a VFD is Among the accident cases, four SPs in Kuala Lumpur (KL),
Malaysia were switching a 11kV switchgear and all died when
the switchgear exploded upon switching. Investigations
showed that the previous SP jumped the fuse for the
switchgear. [2].
Prashobh Karunakaran is a Senior Lecture in electrical engineering at Another accident was a SP observing that the oil level in an
University College of Technology (UCTS), Sibu, Sarawak, Malaysia (Phone: oil circuit breaker (OCB) was low but assumed it was
60128879578, e-mail: prashobh.karunakaran@gmail.com).
sufficient, he switched the breaker off and it exploded causing
Mohammad Shahril Osman is a Professor of mechanical engineering
UCTS (drshahril@ucts.edu.my). the SP to receive second degree burns [2]. This accident
V. Karuppanna is a PhD student at UCTS (vayaloorank@gmail.com). occurred because the length of the arc between the HV
Sung Chee Cheng is a Masters student at UCTS (davidsung@klt.edu.my). contacts was shorter and thicker than the it should be. So, it is
Lee Man Djun is a lecture in mechanical engineering lecturer at UCTS
(man.djun@ucts.edu.my critical that the arc be exactly the right length and thinness.
Alexon John is a degree student at UCTS (benlex12@gmail.com). A third accident was a SP who tried to observe the SF6 level
Ting Kwong Hieng is a degree student at UCTS (jacktinghieng@outlook.com in a 11kV breaker but the glass covering the gauge was
blurred so he switched it anyway resulting in an explosion but
luckily, he was not injured [2]. It was discovered that the SF6 It is due to such problems of OCBs that the electric industry
leaked out. This SF6 breaker is made by Siemens which is a has moved to SF6 breakers because it is very hard to separate
172-year-old electric company with the second largest revenue the F from the S in SF6 compared to insulating oil. SF6 is not
among electrical component making companies. If a SF6 can harmful to humans since it is a stable compound which is hard
leak from switchgear from such a company, it is a reasonable to ionize. Ions are dangerous for humans as well as electrical
assumption that it will leak from any brand of SF6 systems because they form conductive paths. But because of
switchgears. Keeping SF6 in a leak proof tank is possible but these strong bonds, it is 22,800 times more dangerous than
there is always an actuation shaft which moves through an O- CO2 as a global warming gas, having an atmospheric lifetime
ring to enable the electrical breaking. It is through this O-ring of 800-3200 years compared to 20-200 years for CO2 [6].
that SF6 leaks out as the O-ring becomes defective [3,4]. Another difference between HV CB and the home MCB is
The fourth accident can be found as the words, “Switchgear that they have an extra arching contacts made of tungsten.
explosion - YouTube” is typed in Google. This Youtube Tungsten has the highest melting point among all elements
video is shown by most electrical engineering lecturers to their discovered so far, at 3422 °C. The tungsten arching contacts
students. It is a security camera footage of two SPs raking in a are made sharper and are closer to each other than the main
HV VCB (vacuum circuit breaker). The three L1, L2, L3 contacts which are made of copper plated with silver. Electric
VCBs are in a metal compartment with four wheels below it. current will always choose a sharper contact to travel through
As this unit is racked in, three VCBs are placed in between which is why electrical personnel should never wear metals on
three HV live contacts (L1, L2, L3) at the bottom to the three their bodies; sharp points of gold rings have been known to
HV load contacts at the top. But if the wheels of this take off electric personnel’s fingers. This author was working
compartment are not properly sitting on rails below it, a phase in the local electric utility (LEA) and was tasked to investigate
to phase short can occur which is what happened in this the case of a 11-year old boy who climbed up a 11kV tower.
footage, killing one of the SP. He took three days to die. Upon visiting him at the hospital,
It should be mentioned here that all ions are conductors of every sharp point of his body was missing or burnt off (finger,
electricity and the standard electrical breaking system from a toes, nose ears and genital). He could talk and was
good quality MCB (miniature circuit breaker) in homes all the continuously calling out for his mom, who apparently ran
way the largest electrical breaker, is that some insulator away from home; he probably committed suicide. So, all
material is blown in between the contacts such that the arc arcing passes through the arcing contacts and only then the
formed upon breaking the contacts is as long and thin as main contacts touch each other. All main contacts from good
possible. Short and thin arcs can be powerful and can cause quality MCBs of homes or factories to the largest HV CBs
explosions as second case study above showed. On the other have the main contacts made of copper plated with silver.
side of the contacts where the arcs are blown into are many
parallel plate structures with edges facing the arc. These II. LITERATURE REVIEW
edges split the arc and prevent it from being continuous and It should be noted that breaking a HV switchgear is about
dangerous; these are called arc splitters. The problem with oil 2.5 times more dangerous than closing it. Table 1. depicts the
circuit breakers (OCB) which used to be the main HV typical ratings of a 11kV switchgear. The rated interrupting
switchgears previously, is that oil can be ionized and all ions current is 26.5-43kA while the rated making or closing current
or plasma of metals elements or compounds all the way to is 69kA.
insulator are conductors. The standard way to convert an atom
or neutral compound to an ion is by passing them through a
powerful arc. This is exactly what occurs in switchgears as
they are switched on or off. The reverse process of changing Therefore, breaking is 2.5 times more dangerous than closing
ions back to atoms is by cooling which happens as the fast this HV CB. The earliest HV switchgear were knife switches
mounted on asbestos frames but as voltages increased these
flow of the oil or gas is blown over the arc. Therefore, in an
became too dangerous. Today HV CBs needs complicated
OCB as the insulating oil is blown across the arc, it will
mechanical engineering designs and material technology
eventually become ions and therefore a conductor. If these knowledge and are therefore quite highly priced [7]. The cost
conductive ions are blown in between the contacts, an of HV CBs increases as the voltage increases due to the
explosion will result, probably injuring the SP [5]. To increasing quality of materials and mechanical engineering
overcome this, the procedure followed by electric utilities is to needed to quench bigger arcs [8]. Another problem in HV CB
open a nut at the bottom of the OCB and drain a little of the are tiny leaks of rain water or moisture into the insulating oil
insulating oil and test its dielectric strength. The previous SP tanks which reduces its dielectric strength.
not performing this activity is one of the causes of OCB
explosion despite following all the check-list procedures. The latest development in HV CB was done by a consortium
at N.C. State University. This can potentially eliminate HV
Many electric utilities follow a span of time like six months
CB accidents and fatalities because the HV switching is done
before testing the insulating oil. But the proper procedure
with IGBT or silicon carbide SiC MOSFET based switchgears
should be the number of times the OCB is switched since the
[9]. These HV transistors switch in 1070ns compared to 0.1s
ionization of the oil is directly proportional to the number of for OCB.
times the switchgear is switched.
Therefore, these solid-state switchgears can switch 100,000
times faster than an OCB. At such high speed of switching,
all the mostly mechanical engineering arc-quenching
mechanisms need not be used. Once this becomes
commonplace, switching accidents and fatalities will be a Fig. 1: Tuning screw to vary force of the pneumatic cylinder.
thing of the past. The design at N.C. State University includes
a small transformer following the logic of SMPS (switch mode So, a ratchet rope will be swung round HV switchgear’s
power supply). body to hold down the wooden base of the pneumatic cylinder.
Initially a light load capacity ratchet rope was purchased but it
broke while pulling the 11kV Lucy CB at the LEA. This
Table 1: Typical specification of a HV switchgear indicates the high force to pull CB handle. Then the highest
Table 1: Typical specification of a HV switchgear
Type 11kV Indoor VCB
strength ratchet rope was purchased.
The full circuit designed to get this system to work is shown
Isolation Type Vertical/ Horizontal in “Fig. 2”. Initially as the Start button is pressed, an AC
Rated Voltage 3.7 - 12.3kV
240V will provide energy to magnetize the solenoid in the
contactor which will pull down the contacts to close the 24V
Continuous Current 400 - 1595A
circuit via the NO contact sending 24V DC from the power
Rated interrupting current 26.5-43 kA supply to the electro-pneumatic valve, specifically the
solenoid in this valve. This will magnetize it, pulling the shaft
Rated Making Current ≤ 69 kA depicted in “Fig. 3” to the other end. As the shaft is at the left,
Rated Short Time Current ≤ 27 kA for 4 s 60psi of pumped air is allowed to move into an entrance hole
and exit other holes. As the shaft moves to the right, the
Busbar Current Rating ≤ 2300A entrance hole previously opened is blocked and exit holes
previously blocked is now open. A solenoid moves the shaft
A SMPS rectifies the incoming 50-60 Hz AC waves into DC to the right and it returns to the left via a spring when the
then creates AC of more than 100kHz; as the frequency solenoid is deenergized. In both actuation of extending and
increases, the transformer decreases in size plus ensures a retracting the pneumatic cylinder shaft, the compressed air at
flatter DC. This DC is then inverted back to 50/60 Hz AC. the other side of the piston is released via an exhaust hole of
With such a system, today’s 1 MVA transformer which the electro-pneumatic valve.
weights seven tons and has dimensions of about 9’ X 9’ X 7’
is reduced in size to a 2’ X 1’ X 1.3’ frame. Note 2’ is less
than a stretched-out arm length, so the requirement for a land
area for a switchyard will also disappear, and the whole HV
incoming Ring Main Unit (RMU) can be placed on a pole [9].

III. DESIGN AND TESTING


The HV Switchgear Safety System designed and built in Fig. 2: Electro-pneumatic circuit diagram.
this research focuses on the Lucy Electric brand 11kV
switchgear which is a U.K. brand commonly used in Sarawak,
Malaysia. But the final system developed can be easily
modified to be used for other brands of switchgears, including
raking in of 33kV HV VCB units. Fig. 3: Typical shaft inside the electrop-neumatic valve.
After a long deliberation and experimentations, the design
was to use an electro-pneumatic system. It must be noted that The next thing needed is a base to hold the pneumatic
the Lucy brand 11kV switchgear requires a strong person’s cylinder and the solution to this shown in “Fig. 4”. The base
force to switch it. must be built such that the pneumatic cylinder has a maximum
An electro-pneumatic circuit was designed and built degree of freedom to allow for human variation in exactly
consisting of a contactor, an electro-pneumatic valve, Start & where the wooden base is fastened onto the bottom of the HV
Stop switches, a pneumatic pump, a 24V power supply and a CB with a ratchet strap. The ratchet strap will be used to hold
screw tunable air pressure controller. The initial thinking was down the wooden portion below the pneumatic cylinder to the
to use a heavy base to hold down the pneumatic cylinder but body of the HV CB. The wooden base is made of five layers
this option was foregone because a SP will not be willing to of plywood. It is not smoothened because friction is needed
carry such a heavy thing to the switchyard. for it to hang onto the HV CB’s body while the ratchet strap
holds it down and actuation of the pneumatic cylinder
happens. And the pneumatic cylinder will be actuated from
the SP’s car. Two pumps are used in this design, the 2.5HP
one is the yellow one in “Fig. 6” bottom and the smaller tap of 220V was made because Malaysia is close to China and
0.25HP one is shown in “Fig. 8”, right middle is 0.25HP. has lots of Chinese machines and therefore the need for a
In “Fig. 8”, the left-most socket point will switch on the Chinese voltage supply.
small 0.25 HP pump and if this does not have enough force to After noticing that the 2.5HP pump can only be run slowly
pull the switchgear lever, the 2.5HP pump plug will need to be with the inverter, a 2kW (PF=1.0, 240V) genset was
inserted to the top most socket point. Then the pressurized air purchased to provide the required 240V. This genset is shown
fitting (quick-connect fitting) will also need to be swapped to in “Fig. 6” below the wooden box. With this genset, the
enable using the bigger pump. The 2.5 HP pump can generate whole system and the pump ran continuously with full power.
7 atm of air pressure while the 0.25 HP pump can generate In “Fig. 7”, left, all the socket points are joined in parallel
2.05 atm. therefore plugging a plug from the genset to any of the four
After successfully pulling the HV CB as shown in an initial socket points will energize all the socket points and therefore
test at the LEA, the next step was to build an easily carried the whole system. The finalized system is shown in “Fig. 6”.
wooden box to carry the whole system in the back seat of a It takes two trolleys to move the whole system to a SP’s car
car. A 3000-watt inverter was purchased to run the system which is normally a pickup truck. “Fig. 7” and “Fig. 8” are
from within a car. The next step was to build an extra-long the components in the top and lower components of the
jumper cable. The ones sold in the market cannot be used wooden box respectively. The wooden box must be placed in
because they are too short. The jumper cable in this design the back seat of a car and the yellow 2.5HP air pump can be
must be connected to the car battery terminals, located in the placed between the front seat and the back seat. That is the
front of the car and the system in the wooden box located in most appropriate place for it to prevent it from tipping it over.
the back seat of the car. But upon powering up, the 3000-watt If this pump is tipped over, lubricating oil will leak out.
inverter could not power up the 1865 watts (2.5HP) pump. Because the genset is outgassing and will even have residual
The sound made by the pump indicated it was trying to turn smell after operation, the best vehicle is a pickup or double
but did not have sufficient power. After going through much cab truck (basically a small truck where four people can sit).
literature, it was discovered that for non-surging devices like a This is optimum because there is a separation between the
laptop, the inverter should be specified to have a rating of 50% humans and the cargo bed.
above the marked rating meaning a 100W laptop should be “Fig. 9” is the final testing done at the university HV lab
powered by a 200W inverter. But for surging equipment like with a 11kV Lucy brand switchgear donated by the LEA. As
motors where currents can shoot up during starting, it is shown in the picture, the yellow ratchet rope needs to be at
recommended to use an inverter of 200 to 300% of the motor different positions to achieve switching on and switching off.
rating [10]. Therefore, to run a 1865 (2.5 HP) pneumatic During the initial test, the link between the pneumatic cylinder
pump, the rating must be 5595 watts. and the switchgear handle was a 4mm2 electric cable which
Therefore, to run larger loads the only way was to purchase eventually came loose despite a double knot tie. Therefore,
a larger inverter. The larger inverter shown in “Fig. 5” (black this was replaced with a multi-strand flexible steel rope shown
box on the road) was purchased. This inverter was made by in “Fig. 4” bottom. This multi-strand flexible steel rope is tied
Wagan and is rated at 10,000W with surge capability of in between the blue Al cylinder (which came with the
20,000W. This inverter must be connected to the car battery pneumatic cylinder) and the washer and nut below it. A
with a jumper cable. But upon connecting the pump to the ratchet socket wrench of size #13 (the typical type used by
inverter, it ran continually and but not continuously. It is mechanics) is determined to be the best wrench to lock the
however enough to build up pressure in the pump as long as wire rope fastener (shown in “Fig. 4” bottom) at the site; this
an air-off valve of “Fig. 5” bottom right is installed at the is activity takes the longest time in the process of performing
outgoing pipe of the pump. But it was not a total the switching operation. A big combination plier to hold the
disappointment because the inverter can run the 0.25HP pump wire nut fastener to make the final tight spanner turn of the nut
and therefore the whole system as long as this amount of force will be helpful. At least 1” length of rope must be provided
is sufficient to pull the switchgear handle. This experiment between the blue cylinder and the hole in the switchgear
proved that inverters do not perform as advertised. This handle, to increase the degree of freedom for this actuation.
inverter was purchased from the USA therefore its output is
120V. In “Fig 5” top right is an autotransformer used to step
up the voltage from 120V to 240V to power the 2.5HP pump.
The autotran was designed and contracted out to be fabricated
by a transformer factory for MYR380≈USD92. It can convert
voltages to or from 120V, 240V or 220V and has a current
carrying capacity of 20A. Though autotrans are well known
in industry, there are apparently many who do not know their
advantages especially cost-wise. There was a big American
factory in Kuching, Malaysia named Sanmina which ran all
their American voltage (120V) requiring machines with
standard, two coil 240V:120V step down transformers costing
USD3,600 each. Those transformers had dimensions of 2’ X
1’ X 1’ and weighted close to 50kg. But none of those factory Fig.4: The SP will carry the above pneumatic cylinder
together with a ratchet strap to the HV switchgear
machines needed more than 15A of current to run. An extra
Fig. 8: The finalized circuitry located in the bottom
compartment of the wooden box.

Fig 5: On left is the testing of the 2.5HP pump powered by the


10,000W inverter. On the right top is a 20A capacity autotran.

Fig. 9: The final successful test on the 11kV switchgear.

REFERENCES
[1] Karunakaran, Prashobh., Osman, M. S., Boniface, I. R. A., & Shah, A.
N. (2018). Development of a system to improve safety in switching of
high voltage circuit breakers, IEEE Explore, pp. 7-12. IEEE.
[2] Karunakaran, P. (2018). Electrical Power Simplified. AuthorHouse.
[3] Wilson, H., Dufournet, D., Mercure, H., & Yeckley, R. (2019). History
of Circuit Breakers. Switching Equipment, 157-198.
[4] Koch, D. (2003). SF6 properties, and use in MV and HV switchgear.
Fig. 6: The final system in an easily carried wooden box. Two Cahier technique, 188.
trolleys must be used to move the whole system to a car. On [5] Karunakaran, Prashobh., Osman, M. S., Boniface, I. R. A., & Shah, A.
one trolley is the wooden box with the electro-pneumatic N. (2018). Development of a system to improve safety in switching of
system and the genset below it. The other trolley is to carry high voltage circuit breakers, IEEE Explore, pp. 7-12. IEEE.
the pneumatic pump plus the inverter. [6] Knobloch, H. (1998). The comparison of arc-extinguishing capability of
sulfur hexafluoride (SF6) with alternative gases in high-voltage circuit-
breakers. In Gaseous Dielectrics VIII (pp. 565-571). Springer, Boston,
MA..]
[7] Balcombe, H. G. (1997). The assessment and management of aged oil-
filled switchgear.
[8] Wilson, H., Dufournet, D., Mercure, H., & Yeckley, R. (2019). History
of Circuit Breakers. Switching Equipment, 157-198.S. Hirayama, T.
Fujino, M. Ishikawa, T. Mori, H Kawano, "Numerical study of arc in
SF6 gas circuit breaker with externally applied magnetic field.", IEEJ
Transactions on Electrical and Electronic Engineering 2016.
[9] Bhattacharya, Subhashish. High MegaWatt MV Drives, Dept. of ECE,
FREEDM Systems Center, NC State University
[10] Jou, H. L., Wu, J. C., Wu, K. D., & Shen, H. R. (2018). New three-port
DC-AC inverter outputting a single-phase and a set of three-phase AC
voltages. International Journal of Electronics, 105(11), 1962-1975.
Fig. 7: The non-circuitry parts are placed in the top
compartment of the wooden box.
View publication stats

You might also like