Professional Documents
Culture Documents
VOL-3: K 1
FREEQUENCY RESPONSE ANALYSIS:
1. INTRODUCTION
2. FREQUENCY RESPONSE FROM TRANSFORE FUNCTION
3. CO-RELATION BETWEEN TIME AND FREQUENCY RESPONSE
VOL-3: K2
GRAPHICAL PLOTS:
1. POLAR PLOT (E.g. 1 & E.g. 2)
2. BODE PLOT (E. g 1, E. g. 2 & E. g. 3)
3. G.M & P.M
4. NYQUIST PLOT (EXAMPLE – 1 & 2)
VOL-3: K3
CLOSE LOOP FREQUENCY RESPONSE
1. CONSTANT M-CIRCLES
2. CONSTANT N-CIRCLES
3. USE OF NICHOL’S CHART
2
INTRODUCTION:
The sinusoidal input signal when applied to a linear system results in an output signal which is
sinusoidal in steady state and offers same frequency as that of input sinusoid, however in nonlinear
system the output with sinusoidal input contains higher and sub-harmonics of the input frequency.
Definition:
The magnitude and phase relationship between the sinusoidal input and the steady – state output
of a system is termed as the Frequency Response.
Advantages of Frequency Response Method:
(1) As the frequency response method and the pole zero method are two different ways of applying
the same principles of analysis and design, hence one method may be used to check the accuracy of
other.
(2) Experimental data for control system are often presented in terms of frequency response
measurement can be made with any degree of accuracy and convenience as compared to other methods.
(3) The design specification for control systems are generally given in terms of system frequency
response characteristics. This is particularly true when the input signals are random functions of time
having only statistical properties.
(4) In control system having multiple loops the frequency response method gives the design and
analysis specifications more quickly than are obtained by pole – zero method.
(5) Some of the procedure used for analysis of non – linear systems are based on the frequency
response method hence it is preferred as compared to other methods.
Disadvantages:
Frequency response method for analysis and design of control system is the indirect link
between the frequency and time domain. Direct correlations between the frequency response and
corresponding transient response are tenuous and in practice the frequency response characteristic of
the system is adjusted by using various design criteria which results in the satisfactory system transient
response.
1. Frequency Response from Transfer Function.
The function G(j ω) representing the sinusoidal steady state behaviour of the system is a function of
complex variable j ω having magnitude and phase angle and is known as Frequency Function of the
System.
is .................... (1)
if ..................... (2)
When a sinusoidal signal is applied at the input terminals of the system at t = O +:
x i ( t )=E sinωt
X;(t) Xo(t)
Eω Linear System
x i ( s) = 2 2 ⋯ ⋯ (3)
(s +ω ) (Input) (Output)
Where E = Peak Amplitude of the sinusoidal input signal ω = frequency of oscillation of the sinusoidal
signal.
3
EωK ( S + Z1 ) ( S+ Z 2 )
From 2 & 3, x o ( s )= ......................... (4)
( S 2 +ω2 ) ( S+ P1 ) ( S+ P2 )
¿
Ko Ko K1 K2
¿ + + + ................................ (5)
( s− jω ) ( s+ jω ) ( s+ p1 ) ( s+ p 2 )
From (5) it is clear that, all the terms for poles except, first two will decay with time as these poles lie in
the lift half of s-plane. Hence these decaying terms will be represented by decaying transients in the
system output. Thus the steady state value of the system output from (5) is,
¿
Ko Ko
X o (s )/¿ ss = + ¿ .............. (6)
( s− jω) ( s+ jω )
Where X o (s )/¿ ss ¿ the Laplace Transform of the stead state system output,
s [ K o + K ¿o ] jω [ K o−K ¿o ]
Or x o (s)/¿ss = 2 2 + ¿ ⋯ ⋯(7)
(s +ω ) ( s 2+ ω2 )
And K o =Eωk [ ] πz (s)
πp( s)
/s= jω ..................... [form (4)]
Or K o = 2 jω [
Eωk ( jω+ z 1 ) ( jω+ z 2 )
( jω+ P1 ) ( jω+ P2 ) ]
/s= jω ⋯ ⋯(8)
¿− j
[
E K ( jω+ z 1) ( jω+ z 2)
2 ( jω+ P 1) ( jω+ P 2 ) ]
E
¿− j
2
[ G ( jω ) ]=a+ jb .............. (9)
¿
And hence K 0= a – j b................. (10)
Substituting (9) and (10) i (7) we get
¿ ¿
s [K o + K o ] jω[ K o−K o ]
X o (s )/¿ ss = + ¿
( s2 +ω 2 ) ( s 2 +ω2 )
s [ a+ jb +a− jb ] + jω[a+ jb−a+ jb]
¿
( s 2+ ω2 )
s [ a+ jb +a− jb ] + jω[a+ jb−a+ jb] 2 as 2ωb
¿ 2 2 − 2 2 ............................... (11)
(s +ω )
2 2
s +ω s +ω
Taking Laplace Inverse of Eqn. (11)
X o (t)/¿ss = ( 2a cosωt−2 b sinωt )=2 √ a +b sin[ωt + ∅(ω)]¿ ................ (12) #
2 2
(ii)
The closed loop transfer function of a control system is G ( s )=10 ¿ ¿ Determine the closed
loop steady state response of this system when a sinusoidal input xi(t)=5 sin(ω t+ θ) is
applied.
x o (s) 10 (s +2)
G ( s )= =
x i(s) ( s+1 ) ( s+ 5 )
10(2+ jω) 10 (2+ jω)
Hence G ( jω )= ( 1+ jω ) ( 5+ jω ) = =¿
[ ( 5−ω2 ) +6 jω ]
10 √ 4+ ω2 −1 ω −1 2
And M ( ω )= ; ∅ ( ω )=tan −tan 6 ω /(5−ω )
√ ( 15−ω ) +36 ω
2 2 2
Substituting E=5 and ω t = (ω t + θ) for the system input x; (t):
The steady state frequency response of the system:
(From Eqn. 20)
5
[ 50 √ 4+ ω
[ ]]
2
−1 ω −1 6 ω
x o (t) ss =5 M ( ω ) sin ωt +θ+ ∅ ( ω )= sin ωt+θ +tan −tan
2 2
( 5+ω ) + 36 ω 2 2 5−ω
2
- -
≡
Fig. A: Second order system.
For the system the closed loop transfer function
2
ωn
2
c (s ) ωn (s ¿ ¿ 2+2 ωn s)
¿ M ( s )= = 2 = ¿
R ( s ) s +2 δωsn+ ω2n 1+ ω2n /(s ¿ ¿ 2+ 2ω n s)¿
Hence the frequency function = the sinusoidal transfer function
2
C ωn 1
¿ Mc ( jω )= ( jω )= 2
= ⋯ ⋯ ⋯ (1)
R ( jω ) +2 δ ω n jω+ ωn ( 1−u ) + j2 δu
2 2
ω
Where u= is the normalized driving signal frequency (i.e. ω is the driving signal frequency and
ωn
ω n is the system natural frequency).
1
From (1) ∣ M ( ω ) ∣=M = ................ (2)
√( 1−u ) +(2δu)
2 2 2
U = 0, M = 1 and φ 0
1
U = 1, M=
and φ = - ∧/2
2δ
U → ∞ M 0 and φ - ∧
1.4 M(δ=δ1<0.707)
Magnitude M 1.0
Mr
0.6
M(δ=0.707)
0.2
6
0 ω/ωn=u
Fig: (a) Frequency Response
Ur=ωr/ωn
Magnitude Characteristics:
Fig: (b) Frequency Response Phase Characteristic.
The frequency where M has peak value is known as the resonant frequency (ω r) and M = Mr and
u = u r = u r/ω n = Normalized resonant frequency. All this frequency, the slope of the magnitude
curve is zero. From Eqn. (2),
[
−1 −4 ( 1−ur ) ur +8 ur ]
2
2 δ
dM
/¿ u=ur = =0 ¿ Which gives, 4 u3r −4 ur +8 δ 2 ur =0 or ur= √1−2 δ 2 ------- (4)
du [ ]
2 ( 1−u2 )2 + ( 2 δur )2 3/2
r
Phase φ 0 (δ=δ1)
-90°
-180 ω
=u
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 ωn
Fig: (b) Frequency Response Phase Characteristic (δ=δ1)
The frequency where M has peak value is known as the resonant frequency (ωr) and M = Mr and u
= u r = ω r/ω n = Normalized resonant frequency. At this frequency, the slope of the magnitude
curve is zero.
At resonant frequency ω r:
1
From eqn. 2 the maximum value of M (M Resonant Peak = Mr) i.e. M r= ⋯ ⋯(5);
2 δ √ 1−δ 2
∅ r (From (3))¿−tan −1 [ √ 1−2 δ 2 /δ ] from eqns. 4 & 5, it is seen that as δ0, ω r ω η and Mr ∞.
1
For0<δ < (0.707), the resonant frequency has a value less than ω η and the resonant peak has a
√2
1
value greater than 1. for< , it is seen from eqn. 4 that d M/du, the
√2
Slope of the magnitude curve does not become zero for any real value of ω. For this range of δ,
the magnitude M decreases monotonically from M = 1 at u=0 with increasing u, as shown in fig:
1
(a). It therefore follows that forδ < , there is no resonant peak as such and the greatest value of
√2
M equal 1.
Thus for a second order system, its resonant peak M r of its frequency response is indicative of its
1
damping factor δ for 0 δ ≤ (i.e. 0.707) and the resonant frequency ωr of the frequency
√2
response is indicative of its natural frequency for a given δ and hence indicative of its speed of
response (as t s = 4/δ ω n) M r and ω r of the frequency response could thus be used as
performance indices for second order system.
Considering only the exponentially decaying envelope for a tolerance band of 2% the settling time
e−δωnts
is given by =0.02∨e−δωnts ≈ 0.02 (for low value of δ) orts ≈ 4 =4 T ; similarly for 5%
√( 1−δ ) 2 δωn
3
tolerance band, ts ≈
δωn
7
Mr
1
M r=
2 δ √ 1−δ
2
1
−πδ
0.707 Band Width √ 1−δ 2
Whereas , M p=1+e
ω
ωr ωc
Fig: (c) Typical magnification curve of a Feedback control system.
In the Fig: (c) we notice that for ω>ω r, M decreases monotonically. The frequency at which M
has a value of (i.e. 0.707) is of special significance and is called the cut off frequency ω e. The signal at
frequencies above cut off is greatly attenuated in passing through a system. For feedback systems, the
range of frequencies over which M is equal to or greater than (i.e. 0.707) is defined as Bandwidth
ω b. Control systems being low pass filters (at zero frequency, M = 1) the bandwidth is equal to cut off
frequency i.e.
.
The bandwidth of control system indicates the noise – filtering characteristics of the system. Also
bandwidth gives a measure of the transient response properties as observed below:
ωb 1 1
The normalized bandwidth ub = of the second order M = = ; where
ωn
2
√
(1−u 2b ) + ( 2 δ ub ) 2 √ 2
ωb
ub = or ub4−2 ( 1−2 δ 2 ) u2b−1=0
ωn
[ ]
1
Or u = 1−2 δ 2+ √ ( 2−4 δ 2 +4 δ 4 ) 2 ........................ (6)
b
(As the bandwidth must be a positive real quantity, the negative sign in the quadratic solution and the
negative sign in taking the square root have been discarded)
1.6
1.4
1.2
Normalized 1.0
Bandwidth 0.8
0.6
0.4
0.2
0.2 0.4 0.6 0.8 1.0 1.4 1.6 1.8
Fig: (d)
[ ]
1
The den moralised bandwidth from eqn. (6) ¿ ωn 1−2δ 2 + ( 2−4 δ 2+ 4 δ 4 ) 4 ............ (7)
For step response: with 0 ≤ δ ≤ 1 are,
ω d = damped frequency of oscillation ¿ ω n √ ( 1−δ 2 ) .................... (8)
[ ]
δ
−∧
Mp = Peak overshoot ¿ e=
( 1−δ2 )
Compare eqn. (4) and (8) records that there exists a definite correlation between the resonant frequency
ω r of the frequency response and damped frequency of oscillations of the step response.
8
ωr
√
2
1−2 δ
The ratio of these two frequencies is: = which is a function of δ and is plotted in fig (f).
ωd 1−δ 2
1.4
1.2
1.0
0.8
0.6
0.8
VOL-3: K2
GRAPHICAL PLOTS:
1. Polar plot:
In practice the frequency function of the system are so complex and long that the characteristic of
the system cannot be determined at the desired frequency only by inspection of the system frequency
function (i.e. from the mathematical expression). Therefore the frequency functions of systems are
plotted in graphical forms which indicate the system characteristics. Any curve giving information
regarding the gain or phase shift of the frequency function is known as the frequency response curve of
the system. In polar plots the amplitude of G (j ω) is plotted as the distance from the origin while phase
angle is plotted as angular displacement from the right hand horizontal axis on the polar graph as shown
in fig. below.
Advantage: Polar plots are preferred as compared to rectangular plots because polar plot contains the
ready information of both the parameters, amplitude and phase angle.
Limitations:
(1) Addition of poles zeros to an existing system requires the complete recalculation of frequency
response.
(2) The calculation of frequency response in this manner is tedious and does not give the effect of
individual poles and zeros.
Lt
4. Calculate the phase angle of G (j ω) at ω 0 and ω = ∞ by having ω → 0 and
.
5. Rationalise the complex frequency function G (j ω) and separate the real and imaginary parts.
6. Determine the frequencies at which the plot intersects the real axis by equating the imaginary parts
of G (j ω) equal to zero i.e. I m [G (j ω)] = 0. Hence calculate the value of G (j ω) at the intersection point
by substituting the determined value of G (j ω)at the intersection point by substituting the determined
value of frequency in the rationalised expression.
7. Determine the frequencies at which the curve intersects the imaginary axis by equating the real
parts of G (j ω) equal to zero Re [G (j ω)] = 0. Hence calculate the value of G (j ω) at the intersection point
by substituting the determined value of ω in the rationalised expression of G (j ω).
8. Sketch the complete polar of the system which satisfies the above specifications.
E.g. 1 Sketch the polar plots for the following transfer functions for + v e frequencies
K K K ( 1+ s T 1 ) K ( 1+ s T 2 )
( a ) G ( s )= ; ( b ) G ( s )= ; ( b) G ( s) = ; ( c ) G ( s )= ;
1+ sT 1+ sT 1+ sT a ( 1+ s T b )
10
( d ) G ( s) =
s(1+ 0.1 s)
K K
(a) G ( jω )= 1+ jωT = −1
−tan ωT
√ 1+ω T2 2
Lt K
|G( jω)|= Lt =K ;
ω→0 ω → 0 √ 1+ ω2 T 2
Lt K
|G ( jω)|= L t =0 ;
ω→∞ ω →∞ √ 1+ω 2 T 2
K (1− jωT ) K ωK
G ( jω )= 2 2
= 2 2
−j 2 2
=Re G ( jω ) + I m G ( jω)
1+ ω T 1+ ω T 1+ ω T
−ωK
I m G ( jω ) =0 → =0 → ω=0∧ω=∞
1+ ω2 T 2
Hence + v e values of ω, the polar plot will intersect the real axis at ω = 0 and ω = ∞ for which
G ( jω )=K 0 , G ( jω )=0 90 0 respectively. The coordinates of the intersection on points A and 0 are K 90
and .
K
Re G ( jω )=0 =0 → ω=∞
1+ ω2 T 2
For positive value of frequencies the polar plot intersects the Imaginary axis at ω=∞ for which
. The coordinates of the intersection point is i.e. point 0(origin). Thus at origin the
polar plot, real axis and imaginary axis intersect each other.
G(jω) - plane
Aω=0
O K
Increasing
10
(b) G ( jω )=K ¿ ¿
√
2 2
L t G( jω) = Lt K 1+ ω T 1 =K ; L t G ( jω )=L t tan−1 ω T −tan −1 ω T =0 0
ω→0
| |
ω→0 2 2
[ 1 a]
1+ ω T a
ω→∞
Lt
|G( jω) |=
Lt
ω →∞
K
√ 1+ω 2 T 21 K T 1
=
1+ω2 T 2a T a
; T 1 >T a ;
I m G (j ω)
√ ω 2 T 1 T 21 ω
K 1+
1+ω 2 T 2a Increasing
Re G (j ω)
O K ∠0
0 KT1
∠ 00
T
A ta ω = ∞
At ω=O
;
t t
G ( j ) tan 1 tan 1 180
2
For positive values of frequencies the polar plot intersects the real axis at ω = 0
For positive values of frequencies the polar plot intersects the real axis at = for which
respectively
For positive values of frequencies the intersection points with imaginary axis at and for which
and
I m G (j ω)
G(jω)
O A
O O R e G (j ω)
at ω √ 2
(b)
12
For positive values of frequencies the intersection points on the real axis at and for which
-2
ω
(c)
Re
Hence the plots intersects the real axis at ω=∞ for which G (j ω) = 0
Re
For positive frequencies the plot intersects the imaginary axis at and ω=∞ for which
(Refer Table 8.1 Page 253 Nagrath & Gopal for shapes of Polar Plots of different functions)
14
E. g:
Y= 20log
Y=m x (a s t. Line):
Y = magnitude of (j ω) N in db
m = slope of the s t line = d y /d x
x = log ω
Hence
i. e. Number of octave =
80
60
40
20
00
M↑
¿ db
0.10.1 0.11.0 0.110 0.1100 0.11000 0.110,0000
-20
-40
-60
1 1
1 -40db/decade: -20db/decade:
-60db/decade: ( jω )2 ( jω)
( jω )3
20 log using asymptotic approximation i.e. making ω T<1 and ω T>1 (i.e. at ω = 0
and ω = ∞) respectively the magnitudes at these limiting frequencies are:
i. e.
ωT >1 ; ∓20 log √1+ω T =¿ ∓ 20 log( ωT )¿
2 2
17
Thus it is clear that for lower frequencies the magnitude plot is straight line of zero slope at zero db ordinate but at
higher frequencies the plot is straight line of 20db /decade slope. These two straight lines intersect at which:
−20 log √ 1+ ω T
2 2
Or a Pole Factor
−20 log √ 1+ ω2 T 2 In db
1
ωT = 1 or ω = = ω b or ω c
T
Similarly for conjugate zero a reverse curve will be the Bode Plot.
Similarly for zero on real axis all- v e values will be + v e values. From this table, the last column the error in
magnitude of is plotted as a function of frequency as shown in the fig. drawn in next page. This curve is
used to obtain the accurate magnitude bode plots from the appropriate plots which are shown in the Fig. drawn in
next page. This curve is used to obtain the accurate magnitude bode plots from the approximate plots which are
1
shown in the fig. The error curve is symmetrical w. r. t corner or Break frequency, is ω b= and have the following
T
properties:
(i) The error is -3db at break frequency (ω b)
(ii) The error is -1 db one octave above and below the break frequency i.e. at 2ωb and ωb/2
(iii) The error is -0.4 db one decade above and below the break frequency i.e. at 10ωb and ωb/10.
[ ( )]
2 −1
j2 δω jω
Ex. Considering the pole: 1+ +
ωn ωn
Where δ and ωn are the damping ration and natural frequency of oscillations of the system. The magnitude in
|[ ( )] | |( ) | √( )( )
2 −1
j 2 δω jω ω2 j 2 δω ω2 2 δω 2
db, = 1+ + =20 log 1− 2 + =−20 log 1− 2 +
ωn ωn ωn ωn ωn ωn
ω ω
Using asymptotic approximations, i.e. assuming <1 and >1; -20log i.e. for ω=0 and ω=∞ respectively, the
ωn ωn
ω
magnitude at these limiting frequencies are: for ωn <1; -20 log =0
18
√( )( ) ( )
2 2 2 2 2
ω ω 2 δω ω ω
For >1;−20 log 1− 2
+ =−40 log db ; 2 i . e .4th power of ω
ωn ωn ωn ωn ωn
It is clear that at lower frequency the magnitude plot is a straight line of zero slope at zero db ordinate while at
higher frequency the plot is also straight line of -40 db /decade slope. These straight lines interest at the point
[ ( )]
( )
2 −1
j2 δω jω 2 δω
∅= 1+ + =−tan −1
ωn ωn ω
2
1− 2
ωn
ω
The asymptotic magnitude vs. plot is sketched below: in Fig. 4
ωn
60
50
40
30
20
10
0
-10
-20
-30
-40 ω /ω n
0.1 1.0 10 100
i. e.
40
20
19
1 10 = ω b
100
(
ω i. e .
ω ω
=
ω n 10 )
(A) Procedure for magnitude vs. Frequency plot.
(1) Determine the transfer function of the system.
(2) Substitute s=j ω in the transfer function of the system and obtain the frequency function of the
system and then factorize the numerator and the denominator.
(3) Plot for the constant gain for K.
(4) For poles /zeros at origin sketch the plots.
(5) For poles/zeros on the real axis, obtain the break frequencies and sketch the approximate
asymptotic plot. Using the error curve make the necessary correction to have
(6) For complete conjugate poles /zeros obtain the break frequency (i.e. ω = ω c = ω b) sketch the
approximate plots and using the error curves get the accurate plot.
(7) Obtain the complete magnitude plot for the system by adding graphically all the plots for
magnitude sketched above.
(B) Procedure for phase angle v s frequency plot:
(1) Sketch separately for k, (j ω)±N, (1+jωT)±1
(2) For each pole zero on the real axis plot the following points on the semi log graph paper Ø (ω) v s ω
plot is obtained by joining all the points with a smooth curve.
(i) Point for the phase angle of 0° at zero frequency.
(ii) Point for the phase angle of -45° (pole) at the break frequency +45° (zero)
(iii) Point for the phase angle of -26.6° (pole) / +26.6° (zero) at the frequency one octave below the
break frequency i.e. at ω b/2.
(iv) Point for the phase angle of -5.7° (pole) /5.7° (zero) at the frequency on decade below the
corner frequency i.e. at ω b/10.
(v) Point for the phase angle of -63.4° (pole) /+63.4° (zero) at the frequency one octave above the
break frequency i.e. at 2ωb.
(vi) Point for the phase angle of -84.3° (pole) /+84.3° (zero) at the frequency one decade above the
break frequency i.e. at 10ωb.
(vii) Point for the phase angle of -90° (pole) /+90° (zero) at infinite frequency.
(3) For each complex conjugate pole/zero, Calculate and plot the phase angle at various frequencies
and join these points by smooth curve to obtain the phase angle bode plot.
(4) However Ø (ω) v s ω plot to be accurate plot but not approximate plot. At different frequencies
angles of all factors are added algebraically and total angle point to be determined and finally these
points to be joined to gate Ø (ω) plot.
20
Example 1:
( 1+100 s ) (1+ s)
G ( s )=
( 1+ 10 s )(1+ 0.1 s)
Get the Magnitude Bade Plot
Factors
(1)
(2)
(3)
(4)
21
32(1+0.5 s)
E. g: 2 G ( s ) H (s)=
s ( 1+0.1 s ) (1+ 0.2 s)
32(1+0.5 jω)
G ( jω ) H ( jω )= ;ω =1, 2, 5, 10 & k = 32, 20log 32
jω ( 1+0.1 jω ) (1+0.2 jω) c
22
23
C. Relative Stability:
Quantitatively, the distance between the GH – plot and the (-1, j0) point gives measure of the relative
stability of the closed loop system. More specifically, the Gain Margin and the Phase Margin have been
generally used to specify the degree of relative stability of a control system.
Gain Margin and Phase Margin:
J v = Im GH ( jω)
α
0
−180
(−1+ jo) o
φ U = Re GH ( jω)
Definition: Gain Margin is the factor by which the system gain can be increased to drive it to the verge of
instability. In Fig. 1 it is seen that at ω = ω2 the phase angle is 180° and the Magnitude
And hence the GH (j ω) plot will pass through the critical point (-1 + j0), driving the system to
the verge of instability. Therefore, the gain margin, GM may be defined as the reciprocal of the gain at the
frequency at which the phase angle becomes 180°. The frequency at which the phase angle is 180° is called
gain cross over frequency, the will become - 180°, while the magnitude remains unity. The GH (jω)
plot will then pass through the critical point driving the system to the verge of instability. This additional
phase leg Ø is known as the phase Margin (P.M). The Phase Margin is thus defined as the amount of
additional phase leg at the gain cross over frequency required to bring the system’ to the verge (or point)
of instability. In Fig. 1, it is shown that the P.M is measured positive in counter clock wise direction from the
–v e real axis. The P.M like G.M is always positive for stable feedback systems.
P. M i.e. ∅=GH ( jω ) +180 - Formula for P.M.
For any stable system P.M should be positive. A large G. M or large P.M indicates a very stable feedback
system but usually a very sluggish one. Usually a G. M of about 6db or a P.M of about 30° results in a
reasonably good degree of relative stability. It may however be observed that occasionally a good G. M
may not imply a good P.M and vice versa.
In Fig. 1(a), the critical point (-1 + j0) is encircled if when °, and . In terms of Bode
Plot curves, this means that the critical point (-1 +j0) is encircled if when
;
| |
Gain Crossover
GH ( jω) ↑ 0 Log ω.
¿ db
| |
Log ω.
GH ( jω) 0
↑
¿ db
The G. M. i. e
(GHjω)<0
Log ω.
-180
|
GH ( jω) ↑
¿ db | -Ve P.M.
-Ve P.M. |
GH ( jω)
¿ db |
-180
↑
Log ω.
Phase Crossover
+Ve P.M.
Phase Crossover
In Fig. 2(a), encirclement is likewise implied by < - 180° when . This corresponds to
( - 180° and GH(j)ω on the Bode plot. The result will be an unstable system i.e. P.M is –ve.
Now let us consider a case where the frequency response GH (jω) does not encircle the (-1 + j0)
point in the GH (jω) – plane. This happens when , and also when
Gain Parameter adjustment: Log magnitude and phase shift curves are first plotted for k = 1. Then for any
other value of K(+ve), the phase plot is unaltered and only the magnitude curve has to be shifted upward or
down –wards by 20log K db.
(1) Phase Margin: This is equal to Ø m = 180° + angle of GH (j ω) at the gain crossover frequency point. It is
designated as the angle Ø m = 180° + Ø.
(2) Gain Margin: This is the additional gain A that just makes the system unstable, expressed in terms of
the transfer function at the frequency (ω c) is ⎸GH (j ω c) ⎸α = 1 i.e. for stale system the G. M. will come
below the zero db line.
(3) Gain Crossover: This is the point on the plot of the G H (j ω) at which the magnitude is ⎸GH (j ω )⎸
= 0 db. The frequency at gain crossover is called the gain crossover frequency ω c
(4) Phase Crossover: This is the point on the plot of the G H (j ω) at which the phase angle is -180°. The
frequency at which phase crossover occurs is called the phase crossover frequency ω c
Illustrative Example (2): Adjustment of G. M. and P. M. (Plots shown below)
Example 3: Determine the Gain Margin of Unity feedback system having an open loop frequency
function
10
G ( jω )= Using Bade Plots.
jω ( 0.1 jω+1 ) (0.05 jω+1)
Also find the open loop gain for (i) a G. M. of 20db and (ii) a P. M. of 30°
Solution: Bode Plot shown in page 25.
26
27
Introduction: This relates the location of the roots of the Ch. Eqn. to the open – loop frequency response of the
system.
Unlike the root locus technique, computation of closed loop poles is not required but the stability study can be
carried out graphically from the open-loop frequency response. Hence experimentally / graphically determined open-
loop frequency response can be used direct by for the study of stability when the feedback is closed.
(1) It provides the same amount of information on the absolute stability of a feedback system as the Routh Hurwitz
criterion.
(2) It also indicates the degree of stability of a stable system and gives information on how the system stability
may be improved, if necessary
(3) The Nyquist locus gives information concerning the frequency response of the system.
The Nyquist stability criterion is based on a theorem of complex variable due Cauchy,
commonly known as “Principle of Argument”.
Introduction:
H (s)
Note:- The poles of F (s) are the same as these of G (s) H (s). If one of the poles of G (s) H (s) lies in the right half of
the s-plane, the open-loop system is unstable; however, the closed-loop system can still be stable if all the zeros of
F(s) are found in the left half of s-plane.
That is why, to reduce the steady state error of the systems high forward gain is provided but there
by inner loop system becomes unstable – But by providing proper design the entire closed loop sytem is
made stable.
Identification of Poles and Zeros:
(a) The loop gain (i. e. G (s) H(s)) zeros = the zeros of G (s) H (s)
(b) The poles of G (s) H (s) = the poles of F (s) (i. e. 1+ G (s) H (s)
(c) (
The closed-loop i . e .
C (s )
R (s) )
Poles = the zeros of F(s) (i. e. 1+ G (s) H (s) i.e. the denominator of
C(s)
R(s)
28
s3
F (s3)
s
Fig: (a). Arbitrary chosen s-plane locus Fig: (b). Corresponding F(s) locos
(It is a continuous closed path (It is also continuous closed path)
It corresponding to the points, in the s-plane, a point F(s) located in the F-plane, as the locus, the
corresponding Plane, as the locus in traced starting from the point s 1 in clockwise direction (arbitrarily
chosen) and then returning to s 1 after going through all the points on the locus, the corresponding
locus will start from the point F (s 1) and go through the points F(s2), F(s3) . . . . . and back to the starting
point F(s1). The direction of traverse of may be either clockwise or counter clockwise depending on the
particular function.
29
30
31
32
33
Example 1: Draw the Nyquist plot and assess the stability of the closed-loop system whose open-loop
s+ 4
transfer function is G ( s ) H ( s )=
( s+1 ) ( s−1 )
We observe that there is one open-loop pole i.e. s=1 in the right half of s-plane implies open loop
→
lim ∣GH ∣ 0
=−0 ; j0=+90
ω →− j ∞
Section – IV
lim ∣GH ∣ =−0 ; j0=+90 0
S= -j∞ to j∞
ω →− j ∞
lim ∣GH ∣ 0
=−0 ;− j 0=−90
ω →− j ∞
− jω ¿−4=−4
Inter section of with Real axis: =0 → ω=0=¿ . Part =0 , ω Real Part /
1+ ω2
ω=0
−4 − jω
Inter section with in 2
=0 → ω=∞=Real Part=0 ,∈ part ω=∞= 2
=0
1+ ω 1+ω
34
Im. GH Plane
−¿¿
ω=0 4 +90 ω=−∞
-4+j0 0 −0+ j
90 Re.
0 0
ω=−∞ 90 90 ω=+∞
35
−0+ j −0+ j
N = √ GH (i.e. the Nyquist Plot) encircles (-1 +j0) point once = in the clockwise direction which is taken to
be -1
P = Z – P P is in anticlockwise direction so P = +1
-1 = Z – (+1) ∴ Z = 1 – 1 = 0
36
37
38
39
40
41
42
43
44
VOL-3: K3
Close loop frequency response:
The M and N circles of G (j ω) in the gain – phase plane are transformed into M and N contours in
rectangular coordinates. A point on the constant M Locus in G (j ω) – plane is transferred to the gain-phase
plane by drawing the vector directed from the origin of G (j ω) plane to the particular point on the M circle
and then measuring the length, angle in db and degrees respectively. These values of length and angles are
the coordinates of the corresponding point in the gain-phase plane as shown in Fig (b). The critical point in
G (j ω) plane corresponds to the point of zero db and -188 in the gain phase plane. Plots of M and N circles
in gain-phase plane are known as Nichol’s Chart Fig. (b).
Constant M and N circles in the Nichol’s chart are deformed into squashed circles. The complete
Nichol’s chart extends for the phase angle of G (j ω) from 0 to -368 but the region of 𝜱 (ω) generally used
for analysis of system is between – 900 and -2700. These curves repeat after every 1800 internal.
C( jω)
E g: Using Nichol’s chart obtain the gain-phase plot for the closed loop frequency function of
R ( jω )
20
the unity feedback system having open loop transfer function G(s)=
s ( s+ 2 ) (s +5)
2
S l n. G ( jω )= =M (ω) 𝜱(ω)
jω ( 1+ 0.2 jω )( 1+0.5 jω )
2
Where M ( ω )=
ω √( 1+0.04 ω2 ) ¿ ¿ ¿
I m. (jω )
G (jω )
M=1.5 M In db
G3
M=3
M2 G2
G4 o 𝜱
indegree
𝜱1
𝜱3 Re. G (jω ) 𝜱2
𝜱4
𝜱2
Critical Point 𝜱3 𝜱4
(-1, 0)Critical point
Fig (a) (Polar-coordinates) -2700-9- (-1, 0)Critical point 900
(Polar-Plot)
Fig (b) (Rectangular coordinates)
-1800
Example 1 (7.26) Using Nicholas chart obtain the gain phase plot for the closed loop
C( jω)
frequency function R( jω) of the unity feedback system having open loop transfer function
2u
G ( s )=
s ( s+ 2 )(s +5)
Solution For the given system
20 2
G ( s )= = .. (7.233)
s ( s+ 2 )( s +5) s ( 1+ 0.5 s ) (1+0.2 s)
Substituting s = jω in Eq. (7.233)
2
G ( jω )= =M (ω)/φ(ω) .... (7.234)
( jω ) ( 1+ 0.5 jω ) (1+ 0.2 jω)
52
Where
M (ω)=M=
2
ω √( 1+ 0.25 ω ) (1+04 ¿ ω )¿
2 2
2 −1
φ ( ω )=φ=−90−tan 0.5 ω−tan 0.2 ω
} ....
(7.235)
From Eq.(7.235) the values of M and 𝜱 from for various frequencies are tabulated in
Table 7.15. From these values the gain phase plot of the open frequency function G (jω) is
sketched in the Nicholas chart of Fig. 7.68.
A table is prepared for magnitude is db angle in degrees for the G (j ω).
(Open loop data) Table 7.15 (of verma page 467)
From than table 7.15, the gain phase plot of the open loop frequency function G (j ω) is sketched in the
Nichol’s chart (Fig. 7.68 (of verma Page 467)) as shown in the next page 7.
53
M in dp 𝜱 in degree
0.25 -15.0
0.50 -18.0
9.70 -27.0
1.0 -30.0
1.4 -41.0
2.0 -50.0
2.3 -60.0
3.0 -68.0
2.0 -128.0
0.0 -150.0
-2.0 -159.0
-8.0 -180.0
-12.0 -190.0
55
MAGNITUDE IN db