Professional Documents
Culture Documents
15 Nov 17 1.10 Hyunjin Kim Modify the indoor unit “02” installation option SEG 4 setting
Modify the indoor unit “02” installation option SEG 4, SEG 8 setting
23 May 18 1.11 Hyunjin Kim
Modify “Preparation of installation”
15 Feb 19 1.13 Junho Lim Modified the indoor unit “02” installation option SEG 11, SEG22
24 May 19 1.14 Junho Lim Add the design guide for renewal
31 July 19 1.16 Junho Lim Update the Pipe limitation - Between outdoor unit (Reflect the installation manual information)
25 Mar 20 1.20 Junho Lim Modified the indoor unit “02” installation option SEG22
• Operates entirely in either cooling or heating mode, mixed operation is not allowed
HP : 2 pipes(Gas, Liquid)
MCU
IDU
MCU
Heat recovery
AM 220 K X V J N H / EU
(1) (2) (3) (4) (5) (6) (7) (8) (Buyer)
AM 045 K N 4 D E H / EU
(1) (2) (3) (4) (5) (6) (7) (8) (Buyer)
Capacity[HP]
DVM S
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 ~
DVM S Eco
DVM S Water
Old communication(DVM+4)
F1F2
DVM+4 DVM+4
DVM S
Outdoor unit Indoor unit
Indoor unit
F1F2
DVM S DVM+4
DVM S
Indoor unit Indoor unit
Outdoor unit
Unit
Unit
Wooden pallet
Wooden pallet
Main RMC
No. Model code S/N sticker Location
Address Address
Office 01
1 AM012FNNDCH 01 1A
1st floor
4
S-net pro 2 software
Manifold Set (dedicated for R410A) Flaring Tool (45º Flare) Vacuum pump & Pressure gauge
Hands tools
Nitro
gen
gas
Torch Set & brazing rod Nitrogen and flow gauge Scale & leakage detector
Brazing
Copper pipe Y-joint Socket
Socket
Indoor unit
Y-joint
Outdoor unit Socket
Socket
Y-joint
or
Header only
3 pipes
or
MCU only
2 pipes
200m(656’)
ODU to IDU
Equivalent 220m(722’)
40m(131’)
H2 H1
H3 ODU is higher *110m(361’) under special
H1 then IDU ODU-IDU
ODU is lower conditions (*Note2)
then IDU
Level H2 50m(164’) PDM kit
difference ODU-IDU *110m(361’) with PDM kit (*Note3)
First Y-joint
HP : 50m(164’)
H3
* 15m if EEV RAC is installed
IDU-IDU
HR : 15m(MCU-IDU 15m)
Main pipe : ODU - First Y-joint
* PDM kit model name : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
1) Condition required : The pipe size(Liquid & Low pressure gas) shall be increased by one grade over 45 m(see the next page)
2) PDM kit may be required over 50m.
3) Pipe size up is required according to condition(Refer to installation part)
Main pipe
Classification Condition
First Y-joint ~ The farthest IDU 45m ≤ b+c+g ≤ 90m: Y-joints (b, c) size must be increased by 1 grade
If the size of pipe main pipe(a) is not increased by 1 grade (OUD-IDU ≤ 90m)
a+(b+c)×2+d+e+f+g ≤ 1000 m
Total length of extended pipe
If the size of pipe main pipe(a) is increased by 1 grade (OUD-IDU > 90m)
(a+b+c)×2+d+e+f+g ≤ 1000 m
IDU to nearest Y-joint d, e, f, g ≤ 45 m
Distance difference Difference between the distance of the outdoor unit to the farthest indoor unit and
between IDUs nearest indoor unit ≤ 45m, (a+b+c+g)-(a+d) ≤ 45m
Size up
g
b c
e f
a d
Classification Condition
First branch joint ~ Farthest 45m ≤ e+g ≤ 90m
Indoor unit : Size of the branch liquid and low pressure gas pipes (e) must be increased by 1 grade
Total length of extended pipe If the size of pipe main pipe(between the first branch joint and the outdoor unit)
is not increased by 1 grade a+b+(e)×2+c+d+f+g ≤ 1000 m
If the size of pipe main pipe(between the first branch joint and the outdoor unit)
is increased by 1 grade (a+e)×2+b+c+d+f+g ≤ 1000 m
Each MCU ~ Each indoor unit c, d, f, g ≤ 45 m
Difference between the distance of the outdoor unit to the farthest indoor unit and nearest indoor unit ≤ 45m,
(a+e+g)-(a+b+c) ≤ 45m
Size up
a e
g
b d f
c
Height (m)
2. Liquid pipe size up for 1 grade
Continuous
Between the outdoor unit and the Y-joint right before Cooling Operation
Range
the corresponding indoor unit to minimize pressure drop
from pipe
+1 a
<Example 4> h1 > 40m & h2 > 40m & IDU-ODU(a+b+c) ≥ 90m
c
& farthest indoor unit from the first Y-joint (b+c) > 45m,
→ Size up the liquid line of (a) & (b) & (d) by one grade
→ Size up the liquid & gas of (a) by one grade additionally +2 d
b +1
(main pipe size up condition : OUD - IDU > 90m) +1 h1 h2
→ Size up the liquid & gas of (b) by one grade additionally
(*note1 condition : 1st y-joint to IDU > 45m)
+2
a
+1
Category Length
MXD-E24K132A 2 indoor
Apply to products
Indoor unit MXD-E24K200A
which do not have a EEV
to MXD-E32K200A
20m(66') or less (Wall mount & ceiling)
EEV Kit MXD-E24K232A 3 indoor
(communication)
MXD-E24K300A (AM***FNTDEH,
MXD-E32K224A AM***JNADKH,
MXD-E32K300A AM***FNCDEH)
Maximum 2m
Outdoor unit
10m
ODU to ODU No level different
Equivalent 13m(43’)
x
y
x, y, z ≤ 10m
Bad distribution
IDUs
IDUs
IDUs IDUs
Slightly Upward
Horizontal
37/367 This Document can not be used without Samsung's authorization
General guide of pipe drawing
■ Pipe limitation - Between outdoor unit
If the pipe length is over 2m between outdoor units, make traps.
Otherwise oil stagnation may occur when outdoor unit at the end of module stops
while other outdoor units are still in operation
* Vertical trap
Gas pipe : Mandatory Oil stagnation
High P. gas : Mandatory
Liquid pipe : optional
1M
1.5M (3.28’)
(5’) 1.8M
‘a’ Branch joint (6’) Branch joint
1.5M
(5’)
‘b’
1.5M 1.5M
(5’) (5’)
Sub 2 Sub 1
Main
0.3M 0.3M
‘c’ (1’) (1’)
1.2M
(4’)
Sub 2
To calculate equivalent pipe length add below constant to real pipe length.
Elbow
No. Pipe size(mm) Equivalent length (m) * Equivalent pipe length
1 Φ 9.52 0.18 Y joint : 0.5 m (1.64')
2 Φ 12.70 0.20 Header : 1 m (3.28')
3 Φ 15.88 0.25 MCU : 1 m (3.28')
4 Φ 19.05 0.35
5 Φ 22.23 0.40
6 Φ 25.40 0.45
7 Φ 28.58 0.50
8 Φ 31.75 0.55
9 Φ 38.10 0.60
10 Φ 41.30 0.70
11 Φ 44.45 0.75
12 Φ 50.80 0.80
C E IDUs 80kw
5
(5)
Follow the spec of indoor unit
14kw
73.6kW
2
3
135.2kW
1. For HP model, When the pipe length between an outdoor unit and the farthest indoor unit exceeds 90m
you must increase the size of the main pipe by one grade.(Both gas & liquid).
2. For HR model, When the pipe length between an outdoor unit and the farthest indoor unit exceeds 90m
you must increase the size of the liquid pipe by one grade among the main pipe.
135.2kW
135.2kW
If the size of the pipe between branch joints (4) is bigger than the size of the pipe connected to the
outdoor unit (3), apply the pipe size (3).
80kW 4
63.6
63.6
E
155kW
Video play
Brazing
Taping
Cap
- Failure to use nitrogen while brazing will cause accumulation of oxides at the compressor, various strainers,
and expansion valves impacting performance and causing premature failure
open
- Make sure that there are no foreign materials and impurities inside the pipe.
- Use socket when need brazing for connecting pipes.
■ Vertical Piping
Fix the vertical pipe properly
- Vertical pipe can be warped or sagging of the pipe by its weight.
How to do
1. Fix the vertical pipe with U shape bolt or circular band for each floor or every 5m Pipe sagged
below 15m Fix a pipe every 5m(16.5ft) If there is a pit, fix a pipe at each floor
* How to install the down stopper * If you don’t have down stopper
Vertical
Brazing
Pipe
torch
Down
Stopper
Prepare the Down Stopper Braze Down Stopper
15m 15m
Supporter
Supporter
Completion Assemble the clamp
Gas
Liquid
Vertical
500mm(20”) Minimum
Horizontal
ODU
ODU
300mm(12”) Minimum
Horizontal
< For MCU > < For Heat recovery outdoor unit >
MCU
Outdoor unit
Outdoor unit
MCU
Pressure gauge
Connect
Liquid pipe
Nitrogen gas
Gas pipe
Brazing Brazing
Nitrogen pressurization
Maintain a pressure of 4.1MPa Mark on the gage(wait for 24hours) Maintain a pressure of 1.0MPa
<EPDM SPEC>
Insulator(Cooling, Heating)
Item Unit Standard
High Humidity
Pipe Pipe Size(mm) Standard Remark Density g/cm3 0.048~0.096
[30℃,over
[30℃,85%]
85%] Dimension change route by
% Below -5
EPDM heat
Case 1
Case 2
Use the original uncut Only in special case is the Apply bond both sides of Dry it until it becomes thick
insulation material. vertical cutting of the the surface of EPDM and and sticky.
insulation allowed. press them together for
long lasting bonding.
Case 3
Bring face to face the each Make fitting cover to fit the Bond the both cutting sides
end of EPDM on fitting EPDM insulation. Fitting of fitting cover.
connection part. cover should be overlapped
with insulation min
1inch(2.5m).
70/367 This Document can not be used without Samsung's authorization
Insulation
■ Insulation of indoor unit’s pipe
- Refrigerant pipe before EEV kit or without EEV kit
You can contact the gas side and liquid side pipes
The pipes should not be pressed.
When contacting the gas side and gas side pipe
Use 1 grade thicker insulator.
Insulator
71/367 This Document can not be used without Samsung's authorization
Insulation
■ Insulation of outdoor unit’s pipe
- With a pipe insulator, insulate the pipe up to whole service valve located inside of the outdoor unit
- If the knock-out hole is open unnecessarily, it must be closed..
- Bind the refrigerant pipe with insulation tape if it is exposed to outside sunlight.
(When binding the tape, be careful not to reduce the thickness of the insulation.)
H/P
H/R
Brazing
Cap
Messed up
Bad Sealing
Taping
Foreign material in pipe
EEV Orifice
damaged
Butt brazing
Wrong size
Recommendation
1. Insulation thickness is 5mm or more
2. Select the desirable insulation thickness according to the humidity/temperature of the ceiling.
20mm or more
Left or right
- Install main air-vent at the front of the farthest indoor unit from the main drain
when installed units are more than 3.
- Install an individual air-vent at the top to prevent water flow back to the indoor unit.
* Air-vent should be T or 7 shape to prevent entry of dust or foreign substances.
* You may not need to install air-vent if there were proper slope in the horizontal(sub) drainpipe.
- Do not connect Horizontal drainpipe to Vertical drainpipe at a right angle to prevent back flow.
Hanger
H : 50mm or more
H
1/2H
Single Installation
Multiple Installation
100mm or more
Ceiling Horizontal drainpipe(1/100 or more slope)
Air vent
Coupler type
Push
Pour Water into Drain pipe Pour Water into Drain pipe Pour Water into Drain pipe
Check if the height of water is changed Wait for 24hours Mark the height of water
2. When the drain pump is installed, operate the unit as cooling mode and
4Way
check a drain pump pumping.
3. Confirm that the water flows / pumps out through the drain hose.
Water level of drain pan will be decreased.
Stain
Vertical pipe
Connecting a wire
Selection of wire and circuit breaker
■ Wire pipe (tube)
Install the pipe (tube) for power and communication wires separately.
* Piping work can be different in compliance with the regulation in local area
Example)
Name Temper grade Applicable conditions
Power terminal
Example 1) Install a separate circuit breaker and wire for each unit.
Select the corresponding MFA & MCA value for each unit(same with single unit).
Screw M6
R S T N
Screw M8
Interface
module
F1, F2
Sub 2 Sub 1 Main
Power(L,N)
Communication(F1,F2)
N L
Comm. terminal
F1 F2 V1 V2 F3 F4
Power PBA
POWER PBA
F1,F2 DC
12V AC
POWER
Other units
ELCB or
Another distributor kit
(Indoor unit)
ELCB(Power supply)
ELCB
2 system in
one ELCB
NEW
AM***KN4DEH
vs
• Minimize dead zone by 360 ° airflow
• Remove displeasure by horizontal airflow Cooling area44% Cooling area83%
Stylish Design
• Removable circular panel Conventional 360 CST
• Wind Display
Dead
• Panel for exposed installation 360° Airflow
Zone
2.7~3.5m
Cassette Type
<Panel height>
- 1Way
- 2Way 30mm
- 4Way
- 4Way Interior(600X600)
Duct Type
- Slim duct
- MSP duct 20mm or more
- HSP duct
Duct unit 500mm (pipe side)
20mm or more
450mm
Inspection
450mm
Cassette type Hole
Pipe
b. Duct type
- Height is more than 0.5m : Only “B” [Inspection for PBA] is applied.
- Height is less than 0.5m : Both “A” & ”B” are applied.
Duct unit
Duct type
Pipe
Height : 0.5m
Pattern sheet
<Cassette Type> <Duct Type> Laser marking tool
Note
Since the diagram is made of paper, it may shrink or stretch slightly due to
temperature or humidity. For this reason, before drilling the holes maintain
the correct dimensions between the markings
Note
• Ensure the ceiling is strong enough to support the weight of the indoor unit.
• If the length of bolt is more than 1.5m, it’s required to prevent vibration.
4. Hang the indoor unit to the suspension bolts between two nuts.
- Rubber(grommet) should be inserted to prevent up/down vibration
* 4Way Cassette Type doesn't need rubber because of different rotation direction of fan
Fan
Fan
Vibration Vibration
<4Way Cassette Type> <Other Type>
- Up to 48units(1port 8 units)
MCU-S6NEK2N
4MCUTV6A548B1A - Below 16 kW: Port 1EA
(NEW)
- Max capacity: 61.6 kW
- Up to 32units(1port 8 units)
MCU-S4NEK3N
4MCUTV4A548B1A - Below 16 kW: Port 1EA
(NEW)
- Max capacity: 61.6 kW
- Up to 16units(1port 8 units)
MCU-S2NEK2N
4MCUTV2A548B1A - Below 16 kW: Port 1EA
(NEW)
- Max capacity: 32 kW
- Up to 8units
MCU-S1NEK1N
4MCUTV1A548B1A - Below 16 kW: Port 1EA
(NEW)
- Max capacity: 16 kW
MCU address
Indoor unit
MAIN address Port enable
No use
auto
ⓐⓑⓒⓓⓔⓕ
0 1 2 3 4 5 0 1 2 3 4 5
MCU address
Same as Indoor unit
MAIN address Port enable
ⓐⓑⓒⓓⓔⓕ
On
Off
① Make an installation memo sheet ② Set an port address of MCU through rotary switch
No. Model code S/N sticker Main Address RMC Address Location 00 7.1kW
1 AM071**** Y7************* 00 1A Room #1, 1st floor MCU 01 9.0kW
2 AM090**** Y7************* 01 1A Room #2, 1st floor #1 02
14.0kW
02
3 AM140**** Y7************* 02 1A Room #1, 2nd floor
4 AM036**** Y7************* 03 1A Room #1, 3rd floor
5 AM071**** Y7************* 04 1A Room #2, 3rd floor 03 3.6kW
04 7.1kW
6 AM071**** Y7************* 05 1A Room #3, 3rd floor MCU 05
7.1kW
7 AM071**** Y7************* 06 1A Room #4, 3rd floor #2 06
7.1kW
07 14.0kW
8 AM140**** Y7************* 07 1A Room #1, 1st floor 07
④. Check the address and pipe connection through ③. Assign the address into each indoor unit through S-net pro 2
Pipe check mode trial operation. * If you cannot use s-net pro2, then you can give the address
through wired or wireless remote controller.
MCU address
Dip switch
S/W Option
Dip switch
Dip switch : Set the MCU ports to use S/W Option Dip switch : Set the MCU ports to use Y-joint
ABC D E F
:
▷ Method 1. Use auto pipe pairing - K2 13times
* If any of below model is connected to the system auto pipe pairing is not available(Use manual setting)
OAP duct, Hydro unit, AHU using fresh air, ERV + model -> manual setting required
① Set the MCU address, the MCU ports to use. ② Make an installation memo sheet
Indoor Unit MCU RMC
D 00 7.1kW No. Model code S/N sticker Location
Address Address-Port Address
MCU C 01 9.0kW 1 AM071**** Y7************* 00 1-D 1A Room #1, 1st floor
#1 B
02 14.0kW 2 AM090**** Y7************* 01 1-C 1A Room #2, 1st floor
A
3 AM140**** Y7************* 02 1-A (&B) 1A Room #1, 2nd floor
4 AM036**** Y7************* 03 2-F 1A Room #1, 3rd floor
F 03 3.6kW
E 04 7.1kW 5 AM071**** Y7************* 04 2-E 1A Room #2, 3rd floor
MCU D
05 7.1kW 6 AM071**** Y7************* 05 2-D 1A Room #3, 3rd floor
#2 C 06 7.1kW
B 7 AM071**** Y7************* 06 2-C 1A Room #4, 3rd floor
07 14.0kW
A
8 AM140**** Y7************* 07 2-A (&B) 1A Room #1, 1st floor
④. Check the address and pipe connection through ③. Assign the address into each indoor unit through S-net pro 2
trial operation. * If you cannot use s-net pro2, then you can give the address
through wired or wireless remote controller.
3 7
300mm
Room B Room A
Inspection Hole
Duct type
Pipe
Height
5m
Anchor bolt is too long Anti vibration required Indoor unit is installed too high.
Cooling & heating capacity shortage
890 ~ 900 mm
950 ~ 960 mm
Ceiling
cutting
size
735 mm
646 mm
Hanger
Bolt
position
735 mm 646 mm
735 mm × 735 mm 646 mm × 646 mm
149/367 This Document can not be used without Samsung's authorization
Installation of 360 cassette
■ Panel
4Way Cassette 360 Cassette
Φ 1050 mm
1000 mm
950 mm
950 mm 1000 mm
Panel
• Model : PC4NUSK1N • Model : PC4NUDK1N (Square panel) • Model : PC4NUNK1N (Circular panel)
• Dimension : 950 mm × 950 mm • Dimension : 1000 mm × 1000 mm • Dimension : Φ 1050 mm
※ Circular panel is for exposed
installation. If you install circular panel to
ceiling, please install 2 inspection hall for
installation & service.
Gauge
Gauge
• Indoor unit is higher than the ceiling board • Indoor unit is lower than ceiling board
Insulation
Indoor unit type Dimension
(A x Height)
360 CST
<Large chassis>
947x947x365
2,610x215 mm
<Large+ chassis>
947x947x365
360 Cassette
Hook
• Connect 4 sub hook in each center to the indoor unit then fix with 4 screw
360 Cassette
※ Hook the 2 clip wires of the grille inlet to the indoor unit • Hold the Grill inlet with fingers
Install
- There will be a gap between cover and circular - Check if the COVER PANEL is connected well.
panels if the cover panel is not connected well
or indoor unit is hung higher than guide. → You can get down or up by rotating the bolt.
Script
■ 360 CST does not require any wire connection between indoor unit and signal receiver
Fresh air
intake
Install
Sub Duct
Sub Duct connector
• No Sub Duct
To do Detail
Use pattern
sheet to cut
the ceiling
board
Use gauge
board for
leveling
HANGER
DOUBLE M-BAR
CARRYING CHANNEL
900 ~ 1200 mm
300 mm ×600 mm × 9.5mm or 12 mm
textile
900 ~ 1200 mm
19 mm
38 mm
159/367 This Document can not be used without Samsung's authorization
Installation of 360 cassette
■ Comparison with 4Way CST & 360CST
- Incase of 300x600textile 360CST more textile & M-bard required to be cut or remove.
→ We need to reinforce M-Bar to prevent textile sagging _ M-bar joint & Clip can be purchase from market
• Textile : remove 3 / Cut 3 • Textile : remove 3 / Cut 3 • Textile : remove 3 / Cut 9 • Textile : remove 3 / Cut 10
• M-BAR : cut 2 • M-BAR : cut 2 • M-BAR : cut 4 • M-BAR : cut 4
■ Textile remove / ■ textile cut / ■ M-BAR cut / ※ After cut the M-BAR, we need to reinforce M-bar to prevent textile sagging
160/367 This Document can not be used without Samsung's authorization
Installation of 360 cassette
■ If it’s required to reinforce the M bar please follow below guide
- This is common method regardless of product type in the field.
- Lay down 2 M-BAR to each side - Connect using M-BAR JOINT - Connect the M-BAR to CARRYING
(green color) CHANNEL using M-BAR CILP, then fix
* You can use the M-BAR cut for installation the textile to the M-BAR with screw.
Carrying
channel
M-BAR
JOINT M-bar clip
Shape
surface erosion
Black
- Test result Lacquer 2
After
Black
Sample Temperature Surface Result Lacquer 1
test
surface erosion
Paint for resin OK OK OK
Diluent OK OK OK Black
Lacquer 2
Normal Lacquer Discoloration Erosion NG
surface erosion
Black
- Conclusion Lacquer 1
surface erosion
: Use only paint for resin(ABS, HIPS) & diluent
for 360 panel Black
Lacquer 2
discoloration surface erosion
washer
Pad
- Discharge Duct
Install an discharge duct when space between
the air-outlet and obstacle is less then 2m(6.56ft) Less then 2m
Opening rate
- Opening rate : 80% and more
Outdoor
45℃
Outdoor
IPM 45℃
31℃
High pressure
35kg/cm2
5mins 6mins
- Open the manifold gauge valve connected to the liquid side service valve and add the liquid refrigerant.
- If you cannot add the whole quantity of the refrigerant while the outdoor unit is stopped, open the gas side and close
liquid side service valve. Then, add remaining refrigerant by refrigerant charging operation.
(Cooling : Push K2 tact switch 1 time, Heating : Push K1 tact switch 1 time)
* For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless of the pipe size.
[Unit : kg]
• If AHU kit is included among the indoor units, you must add 0.063kg of refrigerant for every 1kW of the AHU capacity
• If capacity sum of the Hydro HT exceeds 50% among the total indoor unit, ⓑ = 0kg
Wrong Foundation
Wooden pallet
20mm or more
Outdoor unit is not fixed
200mm
100mm or more
No gap between units
DVM S outdoor unit option setting method was changed from April 2016
Picture
4 5 2 3
Setting
F1, F2
Sub 3 Sub 2 Sub 1 Main
Setting
◎ Purpose : To prevent an excessive increasing of compressor performance compared to the capacity of indoor units.
◎ How to work
- The maximum cooling capacity is restricted, taking into account the capacity of indoor units, fan speed, outdoor temperature
and indoor temperature in cooling mode
- In case of overcharged or high heat load condition, target low pressure control will cause excessive cooling capacity compare
to the rated and efficiency decreasing. By this option each units can make proper cooling capacity with better efficiency.
- This function will not work if the outdoor temperature is low and it is difficult to secure low pressure and high pressure.
◎ Application
- Set “Disabled” when customer complain for cooling capacity shortage
& Current evaporator temperature [℃] > Target evaporator temperature[℃] & comp hz < 60hz .
* If this option is enabled indoor unit’s discharge control will not work.
186/367 This Document can not be used without Samsung's authorization
Outdoor Option Setting (with dip & rotary switch)
■ 2. Quantity of indoor unit
◎ Purpose : To set the quantity of connected indoor unit(Main outdoor unit only)
- If the quantity of IDU which is communicating with outdoor unit is different with option setting there will be a E201 error
2 3
10-digit 1-digit 0 6 2 6
■ 3. Quantity of MCU
◎ Purpose : To set the quantity of connected MCU(Main outdoor unit only)
- If the quantity of MCU which is communicating with outdoor unit is different with option setting there will be a E214 error
MCU Quantity
1~F
“ Normal” “ Outdoor
option setting is
needed”
(When entering the setting mode, letters are displayed as the left : “od 00”)
Sub 2 F1 / F2
Sub 1
Main
K1 K2
All the segments will blink to indicate the option has been saved
( Press K1 for 2 seconds to exit without save )
◎ Purpose : To exclude the faulty compressor from the system.(emergent use only)
Notice
If all compressor in a unit is set to emergence operation, E560 error happens.
In this case, close the service valve and disconnect communication wiring
from the module system.
NG NG
We strongly recommend the failure compressor should be replaced within 24
hours, to protect the second compressor.
#1 #1 #2
#2
As a remote controller sends “on” signal to the system, comp. emergency operation
starts with displaying the error code on outdoor unit.
After 12 hours operation, the system stops with displaying the error on indoor unit and
outdoor unit at the same time.
H/X
Out
Out
10℃
Air
Air
Air
Air
In
In
10CMM 7℃ 10CMM
Low pressure
198/367 This Document can not be used without Samsung's authorization
Outdoor Option Explanation
■ 02.Capacity correction for heating
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
0 0 3.0 (Factory default)
0 1 2.5
0 2 2.6
Capacity 0 3 2.7
Targeted high pressure
correction for Main 0 2 0 4 2.8
[MPa].
heating 0 5 2.9
0 6 3.1
0 7 3.2
0 8 3.3
H/X
Out
Out
Air
Air
Air
Air
In
In
10CMM
10CMM
80%
- If this option is set for service purpose it is supposed to be set as factory default after finishing the correct jobs of abnormal
oil return.
Oil Recovery
operation
+℃
Heating Option Default
0℃ +℃
Outdoor temp
Defrost
◎ Purpose : To increase maximum fan rpm range to secure enough airflow when discharge guide duct for outdoor
unit is used
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
0 0 Disable (Factory default)
0 1 LEVEL 1 / Auto
0 2 LEVEL 2 / Auto Enables the silent mode
Silent mode for night-time (It operates
Main 0 7 0 3 LEVEL 3 / Auto
for night-time automatically depending
0 4 LEVEL 1 / External contact on the temperature.)
0 5 LEVEL 2 / External contact
0 6 LEVEL 3 / External contact
◎ Purpose : Limit Maximum fan rpm & compressor frequency to reduce noise during the night time
- Auto : The silent mode will be switched automatically by time (normal in day, quiet mode at night - Only for cooling & Main cooling)
- Externa contact : External contact is on, the mode will be switched as silent mode in cooling and heating mode
Auto External contact
MIM-B14 required
Timer / Switch
◎ Purpose : To optimize the refrigerant control of the system according to the installation condition.
- EEV & other control will be quickly adjusted to compensate refrigerant pressure loss.
High pressure decrease
Refrigerant
Refrigerant
head loss
head loss
HP : 30 + α = 32kg/cm2, LP : 8 ΔP = 24kg/cm2 (EEV↓)
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Energy control option of
0 0 Basic (Factory default) designated operation
sequence
Energy
0 1 Energy saving
Control Main 1 0 ※ Operating in energy
Operation saving mode, capacity
might decrease
0 2 Power compared to normal
operation mode
◎ Purpose : To save energy and customize the operation load in accordance with indoor and outdoor temperature
- Room temperature is close to set temperature change the target temperature and pressure
capacity requirement is decreasing Energy Saving
Temperature
Set temperature
Set temperature +3℃
Set temperature-2℃
Set temperature
Current indoor temperature
Evap temp. Target evaporation temperature
(when the outdoor temperature is low) Target high pressure
Pressure
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Energy control option of
0 0 Basic (Factory default) designated operation
sequence
Energy
0 1 Energy saving
Control Main 1 0 ※ Operating in energy
Operation saving mode, capacity
might decrease
0 2 Power compared to normal
operation mode
◎ Purpose : To get a quick cooled air in indoor unit in the initial stage of unit starting
- When setting value is “2”, the initial target low pressure is lowered(8kg/㎠ → 6.5kg/㎠ to increase the cooling speed)
(Target evaporator temperature is still fixed as “01 option : Capacity correction for cooling” )
Default
7.5kg/㎠
7.0kg/㎠
6.5kg/㎠ Target low pressure (6.5kg/㎠ if power mode is enabled)
◎ Purpose : Continuous heating operation during defrost in module installation (HR model only)
During the R-defrost Heating Indoor unit’s airflow will be set as low.
* R-defrost → Heating → R-defrost → Heating → R-defrost → Heating → All defrost → Heating → R-defrost → Heating…
◎ Purpose : To expand cooling operation range up to -15℃ (HR model only, Default : -5℃)
IDU #1 IDU #2
(Heating) (Cooling)
Ex) OD -10℃, operation mode : main heating, If the evaporating temperature is lower than -14℃.
▷ Option setting : MCU makes low pressure difference between ODU & IDU
by controlling sol valve & EEV.
IDU #2 Evap temp = 10℃ Stable cooling
High pressure
◎ Purpose : To prevent snow is accumulating on the outdoor unit fan discharge guide.
- If a snow sensor is not installed, the outdoor fan operates for one minute every 30 minutes when the outdoor temperature
is below 5℃ .
- This feature may cause the outdoor fan to turn on during servicing. Caution is required.
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Enabling this setting
will command the air
0 0 Disabled (Factory default) conditioner to cool/heat
faster at initial start-up.
Speed
Main 1 7 However, this function
operation
will not work when
High-head condition
0 1 Enabled setting or Long piping
condition setting is
enabled.
- While safety start of the system compressor frequency can be higher then “disabled” condition.
- Noise can be increase.
Disabled Enable
Shorten safety start
Quick Hz increasing for initial 10mins
Normal operation
Safety start
Safety start Normal operation
◎ Purpose : To prevent an excessive increasing of compressor performance compared to the capacity of indoor units.
◎ How to work
- The maximum cooling capacity is restricted, taking into account the capacity of indoor units, fan speed, outdoor temperature
and indoor temperature in cooling mode (ex. 2kW IDU on comp max capacity 6kW)
- In case of overcharged or high heat load condition, target low pressure control will cause excessive cooling capacity compare
to the rated and efficiency decreasing. By this option each units can make proper cooling capacity with better efficiency.
- This function will not work if the outdoor temperature is low and it is difficult to secure low pressure and high pressure.
◎ Application
- Set “Disabled” when customer complain for cooling capacity shortage
& Current evaporator temperature [℃] > Target evaporator temperature[℃] & comp hz < 60hz .
* If this option is disabled indoor unit’s discharge control will not work.
◎ Purpose : To secure the safety in the room & to minimize refrigerant leak amount.
◎ How to work : If gas leak detected, system will start pump down operation automatically.
Process
Gas sensor Gas leak detect
DDC Signal output(Dry contact) Liquid valve close Gas valve close
Outdoor unit External contact input → Pump down start → Output signal1 → Stop※ → Output signal2 → E503 display
(Dry contact) (Dry contact) (Dry contact)
※ Stop condition : Discharge temp 100℃↑ or low pressure 1kg/㎠↓ for 10seconds or 16mins operation
If system was operating system will stop and then start to pump down
◎ Application
- Preparation : External contact board(new), DDC, Motorized 2Way Ball Valve, All unit with new PCB
- Press K3 to release E503 & output signal from the outdoor unit.
* See the next page for wiring diagram
Valve control
Valve control
Main PCB(New from 16’)
Leak detect sensor
s
Liquid pipe
s
Gas pipe
Motorized 2way ball valve
During emergency operation, there is a risk of water leakage because refrigerant flows to the failed indoor unit.
Please be careful when using it.
218/367 This Document can not be used without Samsung's authorization
Outdoor Option Explanation
■ Practical test
CASE 1 CASE 2
Topping
Adjust
E.S.P
External
control
Pizza is made in according to a kind of topping Indoor unit also same!
How?
In case of old PBA
- Option can be set by handle the rotary & dip switch in PBA
* Some of CAC and FJM, still use old PBA
<Old PBA>
Page
Option type
Value
226/100 This Document can not be used without Samsung's authorization
Indoor unit option code
■ What is option code
EEPROM is analyze received option code and define indoor unit’s characteristic
- Option code is topping or switch that can turn on the function of user wants.
EX) AM160KNMDEH***
02xxxx-1xxxxx-2xxx1x-3xxxxx
0 1
0 1 2 63 0 1 2 63
0 1 2 3
4 5 6 7
8 9 A B
C D E F
Address switch
to match indoor unit's RMC(1) (0~F)
RMC(1) : 0 RMC(1) : 0
RMC(2) : 0 RMC(2) : 3
1
RMC(1) : 1 RMC(1) : 1
RMC(2) : 5 RMC(2) : D
MCU port
ABC DE F
234/100 This Document can not be used without Samsung's authorization
Indoor unit option code
■ What is option type
Address setting - MCU address & port (Only heat recovery)
- MCU address & port setting is needed for use MCU Kit with heat recovery.
- MCU address is a dedicated address of each MCU Kit.
* MCU Kit also has to set address in it’s PBA
- Indoor unit has to set port location same with indoor unit installed in MCU port. (A ~ F)
F1/F2
10
MCU address : 10
ABC DE F MCU port : F
11
MCU address : 11
MCU port : A ABC DE F
S-Converter
AC facility
Outdoor unit
Comm. PBA
F1
F2
1 Configuration
2 Serial Port
3 Connected
4
4
5
5
6 6
Press “ESC + Set” keys together for 3 seconds. Press “Delete + Set” keys together for 3 seconds.
MWR-WE10N MWR-WE11N
* If you want about other wired R/C(MWR-SH00N, MWR-SH10N, etc.), please refer to installation manual.
246/100 This Document can not be used without Samsung's authorization
How to set indoor unit option code
■ Setting by Wired R/C (MWR-WE10N)
Option setting and address in service mode table
Address setting(Main/RMC)
Main menu
Sub menu
RMC address
(hexadecimal number)
Data bit
Initial display
* down : 1 digit
up : 10 digit
- Press the ‘Mode’ button to move to the next two bits
- Press the ‘On/Off’ button two times to set the option setting
* Clockwise : 1 digit
Counterclockwise : 10 digit
- Press the ‘Mode’ button to move to the next two bits
- Press the ‘On/Off’ button two times to set the option setting
Press Press
Evaporator drying
Value Details
0
Disuse
(Default)
3 5 minutes
If IDU turn off in cooling,
↓ 5 10 minutes
Still heat exchanger is cold 7 30 minutes
↓
Dew is occurred on the surface of heat exchanger
↓
It can cause to decay and smell
Minimizing fan
External
Value Operation when Fan in Cooling
room s/s Fan in Heating thermo off
thermo off thermo off
0 Eva in temp ≥ 20℃ : Low Low
Disuse Disuse On
(Default) Eva in temp < 20℃ : Off
1 Use Disuse On Off
Eva in temp ≥ 20℃
2 Disuse Use-Heating On : Low Low for 20sec every 5min.
Eva in temp < 20℃ : Off
3 Use Use-Heating On Off
Eva in temp ≥ 20℃ : Low Low
4 Disuse Use-Cooling Off
Eva in temp < 20℃ : Off
5 Use Use-Cooling Off Off
Eva in temp ≥ 20℃
6 Disuse Use-Both Off : Low Low for 20sec every 5min.
Eva in temp < 20℃ : Off
7 Use Use-Both Off Off
261/100 This Document can not be used without Samsung's authorization
Explanation of installation option code “02”
■ SEG 4 : External room temp. s/s / Minimizing fan operation when thermo off
Cooling when thermo off
- Fan is not relevant whether using external room sensor or not.
→ For air circulation
- But, if set minimizing fan operation as ‘Use-Cooling’ or ‘Use-Both’ when thermo off, fan is off (Value 4, 5, 6, 7)
→ Energy saving
Minimizing fan Fan mode
External In cooling
Value Operation when
room s/s
thermo off Tnermo off
0 Disuse Disuse On
1 Use Disuse On
To use a high level controller (ex. DMS2.5) SEG 5 should be set 1 Value Details
(If SEG 5 set 0, central controller can not detect the unit) 0 Disuse
1
Use
(Default)
CEO : Value 0
Robby : Value 1
Option setting
Value Details
0
Disuse
(Default)
1 Use (AUX heater on → Fan on)
Fan on
Radiator
Fan off
Hot gas
EEV EEV
120step Closely
0step
ON OFF OFF ON
Condensed liquid
269/100 This Document can not be used without Samsung's authorization
Explanation of installation option code “02”
■ SEG 11 : EEV step when heating operation is stopped
To reduce refrigerant flow rate which can be a cause of noise and slight heating
to the room while the unit is stopped.
Indication 0 1 2 3 4 5 6 7 8 9 A B
(Type1) (Type2) (Type3) (Type4) (Type5) (Type6) (Type7) (Type8) (Type9) (Type10)
*Wall mounted with EEV 0 90 100 110 120 130 160 200 250 300 400
Stopped Unit’s Default
EEV step Other indoor units except for (100~125)
0 No function
wall mounted with EEV
* Wall mounted type : EEV step is repeated the table value and 160 step periodically.
Value Details
Ext. Contact Input signal
0
Disuse
(Default)
Ext. Contact Output signal
1 On/Off control
(DC 12V)
2 Off control
3 Window On/Off control
MIM-B14
Window Control(Value : 3)
No Error
OK
Error
NG
Error Relay On Contact open Lamp Off Outdoor unit On Relay On Contact closed
Electric louver open
※ Error signal : It will be triggered in case of the error codes which cause to stop indoor unit or outdoor unit
276/100 This Document can not be used without Samsung's authorization
Explanation of installation option code “02”
■ SEG 15 : External control output & External AUX heater On/Off signal
Free cooling * Need to update indoor unit’s SW as 162222 or later
Comp
ON
100% fresh air system
B
Free cooling Comp
zone OFF Free cooling
- Sequence Economizer
MIM-B14 Free cooling
Enthalpy
When cooling thermo on → Free cooling zone → Input from Economizer sensor
→ IDU thermo off(comp stop & Fan running) → Free cooling Ambient
sensor
* Economizer, MIM-B14 are required to detect free cooling availability
Duct △ Duct S
MSD-EAN1
ERV Plus O -
* Console & AR5000 model include an ionizer (MSD-CAN1)
278/100 This Document can not be used without Samsung's authorization
Explanation of installation option code “02”
■ SEG 17 : Use of Buzzer
Buzzer sound use or not
Buzzer control
Value Details
0
Use
(Default)
1 Disuse
Number of hours
using filter
Value Details
0(Default) 1000 Hour
2 1000 Hour
6 2000 Hour
1 2 3 4
Drain pan
283/100 This Document can not be used without Samsung's authorization
Explanation of installation option code “02”
■ SEG 22 : EEV step of stopped unit during oil return / defrost operation
To reduce noise through adjusting EEV step during oil return or defrost operation
- During oil return operation or defrost operation
: EEV open → Refrigerant circulation → refrigerant flow noise may occur
→ reducing EEV step → Refrigerant flow ↓ → Noise ↓
0
300 *1)(440) 300 (440) 400 (440)
(Default)
1 *2)Right before step
150 (150) 300 (150)
(Type1) (Same)
Power Input
Power Input
Time Time
Time Time
0 min. 30 min. 50 min. 120 min. 0 min. 15 min. 30 min. 50 min. 120 min.
287/100 This Document can not be used without Samsung's authorization
Explanation of installation option code “02”
■ SEG 23 : New Motion detection sensor (Only wind free 4way cassette with 600x600)
Energy saving On/Off function
- When there is no person repetitively, this function will start in accordance with absent pattern.
→ Energy Saving comparing with full running model.
Absence
Power
* In order to use new MDS function,
input
must be set installation option.
(“02” installation option SEG 23)
People sensing O → avoid direct air flow People sensing X → direct air flow
Energy
Energy
This option determine the cycle time of swing mode Value Pulse width per Swing 1
- 1 Cycle : Vertical → Middle → Horizontal → Middle → Vertical
0(Default) 34sec
- Swing speed is fast for pulse width is narrower
1 30sec
2 38sec
Spot Mid
Wide
Control variables
2 - - - -
when use AUX heater
If Tr ≥ Ts - 1℃ If Tr < Ts – 1℃
Auto Cooling Auto Heating
- Thermo on/off condition is same as cooling & heating mode * Tr : Room temperature
* Ts : Set temperature
* Ts_new : Changed indoor unit set temp.
* △T : Heating compensation temp.
2. Mode change
* Tr : Room temperature
Cooling → Heating Heating→ Cooling
* Ts : Set temperature
Thermo off for T & Tr < Ts - D Thermo off for T & Tr ≥ Ts + C
Value Details
40m
pressure
2 Use
Multi tenant
Off
ELCB ELCB ELCB ELCB ELCB ELCB
AC 380V AC 220V AC 220V AC 220V AC 220V AC 220V
AC 24V
Transformer
…
Comm.
Room #1 Room #2 Room #3 Room #N
2 Use
Key tag
Comm.
…
Room #1 Room #2 Room #3 Room #N
Set temp.
Thermo On
Thermo Off
AUX heater On
AUX heater Off
1℃
Set temp. + f – 1 ℃
Set temp. + f – 1.5 ℃
Set temp.
Thermo On
Thermo Off
Big temperature
difference
Unit no. Water tank sensor SEG24 Unit no. Water tank sensor SEG24
1 Connected 0 1 Connected 0
2 Connected 0 2 Not connected 1
3 Connected 0 3 Not connected 1
Installation check
Auto trial operation
Trial operation
Reference
Trial Operation Introduction
■ What is the trial operation of the system
- Trial operation (Commissioning)
- Check the system is ready to use for customer
- Release UP mode
Completed
DVM product Installation
product
But there could be product defect or installation mistake and these must be fixed while trial operation.
Meanwhile to prevent skipping the trial operation DVM has UP mode.
* UP mode : System did not do a trial operation, operation is prohibited
Completion
Trial operation
Reference
Auto Trial Operation
■ Flow chart of running auto trial operation
Turn on the power Use S-NET pro or S-checker to check & record operation status
No
Finish
● Starting Tracking
- “Ad00” means starting tracking
2
● UP display
- After tracking complete, “UP” is shown on display at initial installation.
4 - “UP” means Un Prepared : Not ready to operation
- Proceed auto trial operation to release “UP”
* If “UP” is not released normal operation will be prohibited.
● UP display
Cooling Cooling
Heating Heating
- In auto trial operation, product will automatically select either cooling or heating mode.
- In the temperature is in the slashed range, there might be a system protection control during operation.
(If the system protection control is enabled, it can be hard to get the precise judgment after the auto trial operation.)
- When temperature is out of range, accuracy of judgment will be decreased in the boarder line.
2. When error occurs during auto trial operation, check the error code and take appropriate measures
- Refer to installation manual or service manual to trouble shoot.
3. When auto trial operation ends, issue a result report using S-NET pro2 or S-CHECKER
- Refer to service manual to troubleshoot if any item have “NG" or “Undetermined” result in the report.
- After trouble shoot, run the auto trial operation again.
* Auto trial operation result will be saved in the eeprom so you can make a report whenever you want.
* “Undetermined” does not mean NG but the auto trial operation can’t recognize it’s condition now.
Reference data
Trial Operation
■ Flow chart of running trial operation
Turn on the power Use S-NET pro or S-checker to check & record operation status
Trial operation No
Finish
- Operation sequence
ODU IDU for checking Other IDUs Check point
Cooling Normal operation Fan on / EEV open Fan on / EEV close Evap in temp - lowest
Heating Normal operation Fan on / EEV close Fan on / EEV open Evap out temp - lowest
- Display
1. Starting P i P E C o o L or P i P E H E A T
2. Operating A B C D E F G H A, B : Checking IDU address
C, D : IDU which evap in temp changed, “--” means none
E, F : no display
G, H : IDU which evap out temp changed, “--” means none
3. Finishing H O L D
4. Result - Normal communicating or E r r P
* When we have E r r P press K2 to see more information
Error code(E190) → MCU address & port(C00A) → IDU address checked & IDU address temp changed(00--)
Indoor 20~32℃
Outdoor 5~43℃
7-seg Display
ㅏ900 : Start
ㅏ901 : Feedback control
ㅏ902 : Judgment of stability
ㅏ903 : Judgment of refrigerant amount
ㅏ9Ed : Judgment completed
ㅏ9ng : Judgment not available
Discharge 60 ~ 105℃
7 Sub cool 5~20℃ 6
The figures presented in the graph are not absolute standards to judge the system.
If the surround conditions are out of the typical condition, the figures may be changed.
(outdoor temperature 25 ~ 40 ℃, room temperature 22 ~ 28 ℃)
EVA IN Temp. 7~14℃ ▷ Check target Eva in temperature of option setting(cooling capacity correction)
The default : EVA IN 7 ~ 9 ℃, Super heat = EVA OUT - EVA IN = 1 ~ 4 ℃ (Normal)
EVA OUT Temp. 7~14℃ ▷ Refrigerant shortage check
With all IDU operation, If more than 50% of the indoor unit’s SH is over 6 ℃ &
EEV step of those unit is over 900 step. (In case of EEV RAC : 1300 step)
▷ Refrigerant over charged check
EEV Step of
250 ~ 900 With all IDU operation, as the room temp. is over 25 ℃, If the majority of IDU of SH is 0 ~ 1 ℃ &
Indoor Unit
these EEV step is less then 200step. (In case of EEV RAC : 300 step)
▷ If only few indoor unit’s EEV step is the Max. step, check the pipe length from the first Y-joint
to indoor unit (limited 45m) also ensure that if there is any kind of flow resistance
Low Pressure ▷ The low pressure varies from 6.0 to 9.0 according to the piping length & target low pressure.
6.0 ~ 9.5
[kgf/cm2] When the ambient temperature is high or the indoor load is big, the low pressure may be higher.
High Pressure ▷ High pressure will rise when the ambient temperature rises (Max. 36kgf/cm2)
25 ~ 33
[kgf/cm2] When the ambient temperature decreases, high pressure may be decreased as well
Compressor ▷ High pressure is over 25kgf/cm2 but discharge temp. is less than 60℃ (DSH less than 20℃)
60 ~ 105℃
Discharge Temp. Please check the EVI EEV, PHE leakage, indoor EEV opening error, Indoor fan operating error.
Condensing Temp. 35 ~ 55℃ ▷ Condensing temperature will be changed according to the high pressure
Liquid Tube Temp. 25~ 50℃ ▷ Condensing temp. – liquid tube temp.= Sub-cooling (5 ~ 20℃)
328/367 This Document can not be used without Samsung's authorization
Reference data
■ Check point of cooling trial operation ※ The data is not absolute one, only can be used to check the abnormal status
Super heat(SH) : T_eva out - T_eva in = 1 ~ 4℃(Normal) Low pressure (Normal cooling load condition 6~9kgf/cm2)
- EEV step : 200 ~ 600step (EEV RAC 300~900) - When the ambient temperature is high or the indoor load is big,
- SH is less than 2 ℃ EEV step hold or decrease Check liquid back operation (DSH<10 ℃)
(Refrigerant leakage in PHE, EVI EEV, IDU EEV)
- DSH : High pressure saturated temp. – liquid pipe temp.
냉방 사이클 점검
- Avg.(H.P saturated temp – Liquid tube temp) = 10~25℃
Compressor current will be changed in accordance with
* Sometime liquid temp may higher than condenser temp. Hz & Running condition ( ambient temp, Pressure, Etc)
25
20 21℃
15 Liquid tube
10
5 Sub cooling
0
-30 -20 -10 0 10 20 30 40 50
Temperature(℃)
Overcharged
Standard
Shortage
Liquid Sub cooling is decreasing 332/367 25~ 50℃ This Document Sub cooling
can not be used is increasing
without Samsung's authorization
Reference data
■ Cooling cycle data in accordance with the refrigerant charging amount
Figures presented in the graph is not absolute standards to judge abnormal of valves, sensors and refrigerant.
If the ambient temperature is outside of typical healing conditions (outdoor temperature -5 ~ 10 ℃, room temperature 18 ~ 25 ℃)
the values can be changed.
EVA in Temp. 33 ~ 50℃ - 13℃ higher than room temp (8℃ for duct model)
- not less than 17℃ from high pressure saturated temp (22℃ for duct model)
Initial 960
▷ If all ‘Evap In temp’ is lower than normal(above) or the high pressure is lower than 25kgf/cm2 ,
(RAC 1440)
EEV Step of Higher floor ↓ - Check whether the ambient temp is lower than -5℃ / Load calculation for heating.
Indoor Unit Lower floor ↑ - It can be caused by ‘Refrigerant overcharged’ or ‘Wrong load design’.
ODU closer ↓ ▷ If only few indoor unit’s Evap In temp. is lower than normal, check the pipe length from the first
ODU farther↑
Y-joint to the indoor unit (limited 45m) also ensure that if there is any kind of flow resistance.
High Pressure
25 ~ 32 ▷ High pressure can be lower than normal in below case
[kgf/cm2]
1. Ambient temp 0℃↓ , 2. heating capacity shortage by wrong design, 3. Indoor temp 20℃↓
Low Pressure
5.0 ~ 7.5 ▷ Low pressure will be a reference value because can be changed easily by ambient temperature
[kgf/cm2]
▷ If all indoor units are operating and both 1 and 2 is satisfied, it may be normal operation.
1. Highest DSH(discharge temp - high pressure saturated temp) ≥ 20℃
Compressor
65 ~ 105℃ 2. Max. discharge temp ≤ 105℃
Discharge Temp.
* Highest DSH<20℃ : Ref. overcharged, EEV or liquid bypass valve or EVI EEV check
* Max. dis temp>105℃ : Ref. shortage, EEV malfunction, Liquid service valve close
Suction super heat 1~7 ℃ ▷ Check EEV working if suction super heat is not satisfied.
Main EEV step 300~1400 - If main eev step is max. & super heat is high, then we can suspect refrigerant shortage
336/367 This Document can not be used without Samsung's authorization
Reference data
■ Check point of heating trial operation
※ The data is not absolute one, only can be used to check the abnormal status
25
20 6℃
15 -2℃
Low.P +1
10
5 Super heat
0
-30 -20 -10 0 10 20 30 40 50
Temperature(℃)
30
Pressure(kg/cm2G)
Standard
25
20
15
10
Low
5 ambient Main Cycle
Injection Cycle
Isentropic Line
0
150 200 250 300 350 400 450 500 550
Enthalpy(kJ/kg)
Controller
Need
Replacement
② Piping cleansing
- Remove the old outdoor units - Check the service valve close status
- Vacuum the system using vacuum pump - Check the vacuum status of system
③ Trial operation
- Check the operation status using S-net pro 2 - Check the operation status
- In case existing system is with DVM or DVM plus series before DVM S, they are not compatible with DVM S as NASA
has been adapted since DVM S. If partial replacement is inevitable, you should evaluate the extra cost and labor by checking
the SVC instruction.
- Needed to consider connection policy. Combination Ratio that is less than 130% and Make sure that the maximum number
of indoor units per outdoor unit is not exceeded.
- Pumping down or flushing is required prior to removing the existing equipment depending on pipe length to flush out old oil
or foreign substances that are distributed throughout the existing refrigerant piping system.
- Basically the existing piping system can be reused, as seen below table.
- Leak test under pressure 4.1MPa should be performed after installing IDUs.
- T-Joint (Y-Joint between outdoors) should be replaced for oil balancing.
Specification
Classification Model Name
MBH KW
MXJ-TA3819M 461 and below 135 and below
Y-Joint - Outdoor unit
MXJ-TA4422M 478 and over 140 and over
Y-Joint (Only H/R) - Outdoor MXJ-TA3100M 461 and below 135 and below
unit MXJ-TA3800M 478 and over 140 and over
- Filter dryer should be installed on the liquid pipe line of each outdoor unit.
It can be provided by Samsung or supplied from the local market.
Filter Dyer Liquid pipe size DRIER FILTER code BALL VALVE code
- Y-joint for R22 cannot be reused as its design-pressure is about 3.3MPa which is lower than 4.1MPa for R410A (DVM, DVM plus).
Outer diameter Minimum thickness (DVM R410A) Minimum thickness (DVM R22)
mm inch mm inch Temper grade mm inch Temper grade
6.35 1/4 0.70 0.028 0.8 0.031
Annealed Annealed
~9.52 3/8 0.70 0.028 0.8 0.031
12.70 1/2 0.80 0.031 0.8 0.031
(C1220T-O) (C1220T-O)
15.88 5/8 1.00 0.039 1.0 0.039
19.05 3/4 0.90 0.035 1.0 0.039
22.22 7/8 0.90 0.035 1.0 0.039
25.40 1 1.00 0.039 1.2 0.048
28.58 1 1/8 1.10 0.043 1.2 0.048
Drawn Drawn
31.75 1 1/4 1.10 0.043 1.3 0.043
34.92 1 3/8 1.20 0.048
(C1220T-1/2H or (C1220T-1/2H or C1220T-
38.10 1 1/2 1.35 0.053 C1220T-H) 1.4 0.056
H)
41.28 1 5/8 1.43 0.056
44.45 1 3/4 1.60 0.063 1.7 0.067
50.80 2 2.00 0.079
53.98 2 1/8 2.10 0.083
- For pipes larger than Ø 3/4" (Ø 19.05mm), drawn type copper pipe must be used.
If a annealed type is used, pipe may break due to its low pressure resistance.
- If the existing system is for the R22 model, the pipe diameter would be larger than that of R410A.
In this case, the existing pipes can be reused. The amount of additional refrigerant can be charged according to the pipe size.
- It is possible to reuse if there were no overflow of indoor unit and no leakage in the piping system in history.
- Reusability of existing power cables and circuit breakers also should be determined by an electrical designer
considering not only capacity & size but abrasion & protective tube status as it could result in a safety hazard.
- Refer to the below figure for cable connection for indoor units.
Since DVM S requires 2wire for the connection between indoor unit and wired remote controller,
it is recommended to use communication wires, F3/F4 in case existing cable is 4wired type.
building loads should be considered for the weight of the outdoor unit.
The weight of DVM S outdoor unit is lighter than conventional DVM series as well as competitor’s outdoor unit
and it is advantageous.
However, it is necessary to confirm that load per unit area may increase depending on the combination
[ Depth ]
a
DVM S = DVM plus 2, 3, 4
b
[Weight ]
DVM S < DVM plus 2, 3,4
765mm(30.1”)
A. The combination ratio is restricted, taking into account the reliability and effective performance of the device.
For the Heat Pump model, the condensers and evaporators swap roles according to the operating condition.
Appropriate amount of refrigerant should be determined taking into account the conditions of both devices.
If there is an abnormally large difference between the condensers and evaporators, there may be an excess
or insufficient amount of refrigerant, depending on the operating condition.
For this reason, we restrict the indoor unit combination ratio to 50-130%. If the ratio is outside the range,
reliability and effective performance of the device cannot be guaranteed due to imbalanced volume between
condensers and evaporators.
A. We only provide warranty coverage when outdoor unit Y-joints are laid in parallel with the outdoor units,
as shown in the first figure.
Facing the outdoor unit Y-joints toward the outdoor units or using indoor unit Y-joints instead, as
shown in the second and third figures, is prohibited.
(1) Classification (2) Product 1 (3) Product 2 (4) Model code (or Skip)
TM Training manual VRF DVM S Standard / High ambient / ETC MWR-WE10N
Single DVM S Indoor unit Indoor unit / Hydro / ETC MR-KH00E
FJM Inverter - MRW-TA
Water Non Inverter - MIM-D01AN
SOL General Standard MIM-F00N
Accessory EHS - MCM-A300N
DVM Water -
DVM Chiller -
DMS 2.5 Controller name
Accessory product -
(5) Category (6) Region (7) Language (8) Year (9) Version
Integration GL Global EN English 2016 Ver1.00 Minor : 0.01 increment
Product EU Europe ES Spanish 2017 Ver1.01 Major : 1.00 increment
Installation NA North America ZH Chinese 2018 Ver1.02
Troubleshooting LA Latin America FR French 2019 Ver1.10 ※ If change the year, initialization
Control logic EA S.E Asia DE German 2020 Ver2.00 (Ver1.00)
WA S.W Asia KR Korea
ME MENA
CN China
AF Africa
KR Korea
This Training Manual is a property of Samsung Electronics Co.,Ltd.
Any unauthorized use of Manual can be punished under applicable International and/or domestic law. [TM] VRF_DVM S_Installation_GL_EN_2016_Ver1.0