low-voltage DC applications
up to 100 A
Stäubli Description Report
MC4 MC4-Evo 2
Summary:
■■ The connectors are suitable for use with other cable types in
lieu of PV cables
■■ For the use in systems outside of photovoltaics, no
PV-specific certification is applicable
■■ In this case connectors perform according to IEC 61984:2008
(Connectors - Safety requirements and tests).
MC4 MC4-Evo 2
Cables in the range of 2.5 mm²-10 mm² (12 AWG-8 AWG) can
be applied for such application. Cable stranding must be Class 5
according to IEC 60228.
Tinned copper strands can be connected with all metal parts. To ensure long-term stable crimping, please submit the cable
specification to the Stäubli Electrical Connectors Engineering
Untinned copper strands: team for evaluation. We offer support in qualifying cable for
For untinned copper strands of 10 mm² / 8 AWG, the round crimp customer applications.
MC4 PV-KXT4/8II-UR shall be used (cables of other diameters
need to have tinned copper strands in order to be connected to
the respective metal parts).
MC4 MC4-Evo 2
4.1 MC4
A: ø range of the
Conductor cross section
cable [mm]
b
A A
A
4-6
~5 PV-K…T4-EVO 2/6I PV-K…T4-EVO 2/6II
12 / 10
8
~ 7.2 PV-K…T4-EVO 2/10II
10
DI DII
Maroon Grey
Usable seals
PV-KBT4/8II-UR PV-KST4/8II-UR
2.5 / 4 / 6 mm² (10-14 AWG) rubber cable (usual upper limiting earthing safe wiring up to 1000 V according to VDE 0100 T520
temperature: 90 °C) can be connected to MC4 or MC4-Evo 2. and VDE 0298 T 3) or H07RNF according to DIN EN 50525-2-
e. g. NSGAFÖU cable according to VDE 0250 T 602 with 21 / VDE 0285-525-2-21:2012-01).
nominal voltage of at least U0 / U: 1.8 / 3 kV (short circuit safe and
PV-KBT4-EVO2/… PV-KST4-EVO2/…
or
PV-KBT4/2,5…/PV-KBT4/6… PV-KST4/2,5…/PV-KST4/6…
Derating
Deratingdiagrams
diagramsMC4
MC4and
andMC4-Evo
MC4-EVO2 from
from2.5
2.5mm
mm²toto
2
1010
mm 2
mm²
120
100
80 MC4 / MC4-EVO
MC4/MC4-Evo 2: 2.52mm
/ 2.5
2
mm²
MC4 / MC4-EVO
MC4/MC4-Evo 2 / 24 mm²
2: 4 mm
Titelin A
MC4 / MC4-EVO
MC4/MC4-Evo 2 / 26 mm²
2: 6 mm
60
Current
PV-KXT4/8 and1010
PV-KXT4: 8 and mmmm²
2
PV-KXT4-EVO 2/10
PV-KXT4-Evo 2: 10 andand 102 mm²
10 mm
40
20
0
20 40 60 80 100 120
Titel
Ambient temperature in °C
The derating diagram is valid for attached cables with 90 °C Possible examples of cables:
admissible temperature or higher. If cables with a temperature ■■ PVC cable: H07V-K 10 mm²: 70 °C
rating < 90 °C is used, the derating of the cable has to be ■■ Rubber cable: NSGAFÖU 1.8 / 3 kV 10 mm²: 90 °C
considered. ■■ PV cable: FLEX-SOL-EVO-DX 10 mm²: 120 °C
Maximum admissible current in Ampere for TAMB = 30 °C for 2.5 mm² to 10 mm²
* 8II-UR version for 10 mm² / 8 AWG: measured derating, smaller diameters calculated according to IEC 60364-5-52:2009
MC4
Maximum admissible current in Ampere for
PV-KXT4/8
Touchable surface
Ambient temperature 70 °C cable 90 °C cable or higher
< 65 °C
30 °C 80 85 104
40 °C 65 74 95
50 °C 41 58 88
60 °C 14 30 81
65 °C 0 15 77
70 °C 0 72
80 °C 61
90 °C 41
Touchable surface
Ambient temperature 70 °C cable 90 °C Cable 120 °C cable or higher
< 65 °C
30 °C 86 80 90 90
40 °C 72 68 83 83
50 °C 53 58 76 77
60 °C 18 30 67 70
65 °C 0 15 63 67
70 °C 0 59 63
80 °C 47 51
90 °C 27 31
8. Technical characteristics
MC4 (PV-KBT4/… and PV-ADBP4-S2/…)