KEY FEATURES
AREVA T&D
APPLICATION Type MVAJ 102 and 202 relays have been specifically
designed for applications requiring a tripping relay
Self reset relays reset when the initiating signal is which is self-resetting after a nominal delay of 2.5
removed, making them suitable for use as trip relays in seconds.
auto-reclose schemes and also for general flagging This relay may be used, for example, for inter-tripping
purposes. Hand reset relays require manual resetting between higher voltage and low voltage circuit breakers
making them effective lockout relays, which are of a large three phase power transformer. This may
commonly used to trip circuit breakers associated with become necessary when the high voltage circuit
transformers. Electrical reset relays require a voltage breaker is tripped after a heavy internal fault, by
to be applied to the unit to reset the contacts. These protection which cannot conveniently provide an
relays may be used in auto-reclose scheme, or where auxiliary contact with a dwell time long enough to
remote resetting of the relay is required. ensure correct tripping of the low voltage circuit
breaker.
When configured for high burden applications the > Low burden application
burden is either cut off or is economized to a low figure
after a 40-60ms time delay. These relays are suitable for general applications
Due to the greater minimum operating current, the high where the initiating contact is located close to the relay.
burden also permits the use of supervision relays such When configured for low burden applications, by
as type MVAX 11, where the wiring is at risk. The 40- removing the external link from terminals 22 and 24,
60ms time delay ensures reliable operation of series the burden is either cut off during operation or is
elements such as type MCAA repeat relays. economized to a low figure instantaneously.
2>3
> Control relay When the break contact cuts-off, the high burden is
held until the time delay circuit switches it out.
This time delay allows any flagging or auxiliary element
Control relay variants of the standard trip relay are
in series with the tripping relay to operate before full
suitable for applications where the operating time of the
cut-off.
unit is not critical but where the condition of the
The relay is reset by means of a push-button located
armature should be clear from the position of the
on the front cover. For type MVAJ 20 relays, each
following flag.
element is reset separately.
> Configuration
> Electrical, hand/electrical reset relays
type MVAJ 054, 055, 104, 105, 204, 205
All trip relays are supplied as high burden. With the
exception of MVAJ 102 and 202, they may be
These relays operate similarly to the hand reset relays.
converted to low burden by removing the link between
The internal break contact in series with the operate
case terminals 22 and 24.
coil breaks the coil circuit and reduces the burden to
A second link connected between case terminals 21
zero for all relays in the low burden configuration and
and 23 enables a reset inhibitor feature to be
for the MVAJ 054 and 055 relays in high burden
introduced into the circuit of 10 and 20 contact
configuration. For type MVAJ 104, 105 and 205 relays
electrical reset relays ensuring that the reset circuit is
configured for high burden operation, as supplied, the
disabled when the operate circuit is energized.
burden is reduced to approximately 100W for 40-60ms
On relay types 104, 105, 204 and 205 this link may be
before being cut off to either zero or an economized
removed if this feature is not required.
level.
This link must remain fitted to MVAJ 101 and 201
For a hand/electrically reset relay, once the main
relays to enable the economizing circuit.
attracted armature unit is latched in the operated state,
Tables 2 and 3 describe the user selectable features
an internal contact closes, thus enabling the reset
which are available by external link connection.
circuit. The relay may then be reset by energizing the
reset coil by means of closing the reset contact.
If required, the rest inhibitor may be activated by linking
> Hand reset relays types MVAJ 053, 103, 203
case terminals 21 and 23. This circuit ensures that
while PR is closed contact RL2-1 is open, stopping the
These relays incorporate an internal break contact in reset circuit from being simultaneously energized and
series with the operate coil of the attracted armature thus protecting the circuit.
unit. This contacts breaks the coil circuit and reduces If the reset contact is closed while the protective
the burden to zero for all relays in the low burden contact PR is also closed, the relay will oscillate
configuration and for the MVAJ 053 relay in high between operate and reset states.
burden configuration.
For type MVAJ 103 and 203 relays configured for high
burden operation, as supplied, the burden is reduced to
approximately 100W for 40-60ms before being cut off
to zero.
Self reset relays operate in the same manner as the > Standard flag
hand and electrical models but have a residual gap in
the magnetic path to ensure that they reset. All MVAJ trip relays are fitted with a standard hand
For a self-reset relay, when the attracted armature unit reset flag which drops upon the operation of the relay.
is energized by the protection contact PR a resistance When the relay is reset the flag stays in the operated
is switched in series which reduces the burden state indicating that a fault has occurred. The flag(s)
sufficient to hold the unit in the operated condition. On may be reset by means of a lever on the cover.
the opening of PR this economized burden is removed
and the relay resets.
For all relays in the low burden configuration and for > Following flag
the MVAJ 051 relay in high burden configuration the
burden is economized instantaneously. For type MVAJ Following flags are generally fitted to relays required
101 and 201 relays configured for high burden for control functions. Upon the operation or reset of
operation the burden is reduced to approximately 100W the relay the flag follows the armature to indicate the
for 40-60ms before being cut off to an economized current condition of the relay.
level. The external link between case terminals 21 and Where the following flag is fitted, the operation of the
23 must remain fitted on these relays. relay is increased to approximately 15ms which is
generally unsuitable for trip relay applications.
> Burdens
Burden at higher rated voltage (W) Minimum operating current (mA)
To operate * Operated To reset Up to 125V * 220/250v *
MVAJ 05 80/150 ≤5 <40 >25/50 >10/20
MVAJ 10 50/150 ≤4 <40 >25/50 >10/20
MVAJ 20 50/150 ≤4 <80 >25/50 >10/20
* low/high burden configuration
Make Break MVAJ 051 MVAJ 101 MVAJ 103 MVAJ 201 MVAJ 203 CC*
MVAJ 053 MVAJ 102 MVAJ 104 MVAJ 202 MVAJ 204
MAVJ 054 MVAJ 105 MVAJ 205
MVAJ 055
5 0 • 00
4 1 • 01
3 2 • 02
2 3 • 03
10 0 • • 00
8 2 • • 02
6 4 • • 04
4 6 • • 06
2 8 • 08
20 0 • • 00
18 2 • • 02
16 4 • • 04
14 6 • • 06
12 8 • • 08
10 10 • • 10
8 12 • • 12
6 14 • 14
4 16 • 16
* Contact combination required when ordering
CASE
MVAJ 05 and MVAJ 10 relays are housed in size 2 Midos cases as shown in Figure 1.
MVAJ 20 relays are housed in size 4 Midos cases as shown in Figure 2.
13
4 holes 4.4ø 24
45
168 159
Push button 48
projection 10 max
Panel cut-out:
Flush mounting fixing details
32 212 25 min.
Reset
51 Flush mounting
All dimensions in mm
52
97 4 holes Ø 4.4
23.5
Push button
projection 10 max. 99
Panel cut-out:
Flush mounting fixing details.
32 212
25 min.
103 11
Flush mounting.
Proven protection
as safe, simple and versatile
6>7
as your application needs.
INFORMATION REQUIRED WITH ORDER
Number of contacts:
5 contact 05
10 contact 10
20 contact 20
Contact mechanism:
Self reset 1
2.5s delayed self reset
(not available with 5 contacts) 2
Hand reset 3
Electrical reset 4
Hand/electrical reset 5
Case size:
5/10 contacts - size 2 case R
20 contacts - size 4 case T
Flag:
Standard hand reset flag (trip relay) A
Following (self reset) flag (control relay) B
Voltage rating:
24/27 V 0 0
30/34 V 0 2
48/54 V 0 5
110/125 V 0 8
220/250 V 1 0
Design Suffix
AREVA TRACK RECORD -
TRIPPING AND CONTROL RELAYS
>> MVAJ: Range launched 1984.
Over 16,000 relays delivered
>> MVAJ 05, 10, 20 Range launched in 1999.
Over 10,000 relays delivered
>> Simple, reliable, secure
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-MVAJ05/20-BR-11.07-1754-GB - ©2007 AREVA - AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
AREVA T&D Worldwide Contact Centre: Our policy is one of continuous development. Accordingly the
http://www.areva-td.com/contactcentre/ design of our products may change at any time. Whilst every
effort is made to produce up to date literature, this brochure
Tel.: +44 (0) 1785 250 070 should only be regarded as a guide and is intended for
information purposes only. Its contents do not constitute an offer
for sale or advise on the application of any product referred to in
it. We cannot be held responsible for any reliance on any
www.areva-td.com decisions taken on its contents without specific advice.
www.areva-td.com/protectionrelays