This function must be carried out with a high degree of safety and
reliability.
Switching Functions
In an MV power system, apart from the normal ON/OFF operations,
the switching operations can be divided into the following:
1.
1. Short-circuit interruptions
2. Switching of capacitive currents
3. Switching of inductive currents
1. Very low inductive currents
2. Low inductive currents
4. Special applications
1. Arc Furnace
2. Traction system
3. Use on ships
1. Short-circuit interruptions
All circuit breakers are designed to interrupt rated short-circuit
currents. The number of short-circuit interruptions seen in the life of a
circuit breaker depends on its location in the system, quality of the
system design, environmental conditions, etc.
The VCBs are ideally suited for auto-reclosing duties because they act
fast and can be reclosed with a minimum time interval between two
closings as cooling of the dielectric is not involved.
Most of the substations in rural areas are outdoor and situated in far-
off places. This necessitates the setting up of outdoor
maintenance-free circuit breakers.
Go back to contents ↑
After this, as shown in b), the moving contact connects the diodes and
the bank is naturally supplied at voltage zero.
Lastly, as shown in c), after a quarter of a cycle, the moving contact
closes the switch and allows current to flow without losses.
Go back to contents ↑
Figure 2 –
Current chopping phenomenon
Go back to contents ↑
Observation #1
High voltage motors may be safely operated under start-stop
conditions by vacuum circuit breakers where surge suppressors are
provided to limit associated switching over-voltages.
Observation #2
The front time of the switching impulses is determined by the system
configurations mainly by the surge impedance of busbars and cables,
and current transformer inductances.
Observation #3
Switching off of motors having starting currents of more than 600 A
during starting generates low switching over-voltages and the motors
do not require protection by surge suppressors even in 11 kV cable
systems.
It has also been observed that when other types of breakers are used
to handle such switching operations, high overvoltages may occur
due to multiple re-ignition.
Moreover, it has now been found that when motors are switched ‘ON’,
high overvoltage surges can occur which are independent of the arc-
quenching medium including in SF6 circuit breakers.
Go back to contents ↑
4. Special applications
Special applications like arc furnaces involve a large number of
operations per day. Track-side sub-stations require the switchgear to
operate in varying set of conditions from switching the charging current
of catenary systems to transformer magnetising currents to a whole
range of load currents and fault currents varying from 2 kA to 12 kA.
Go back to contents ↑
Go back to contents ↑
Since VCBs have short contact travel and shorter arcing times, the
total break time is quite less and thus meets the special requirements
of short breaking times easily.
Go back to contents ↑
Go back to contents ↑
References //
1. Switchgears book by BHEL – Bharat Heavy Electricals Limited
2. SWITCHING OF SMALL INDUCTIVE CURRENTS USING
VACUUM CIRCUITBREAKERS by Pavel NOVAK, Mario HAIM,
Peter BEER, Uwe KALTENBORN and Stephane MELQUIOND
(Schneider Electric)
3. IEC: 62271-100, “High Voltage Alternating Current Circuit Breakers”
4. IEC: 62271-200, “Metal Enclosed Smitchgear and Control Gear for
Rated Voltage upto and including 38kV”
5. Medium voltage switching devices: technologies and applications
by ABB
Related EEP's content with sponsored
links
Premium Membership
Premium membership gives you an access to specialized technical
articles and extra premium content (electrical guides and software).
GET PREMIUM NOW ⚡
Edvard Csanyi
Electrical engineer, programmer and founder of EEP. Highly
specialized for design of LV/MV switchgears and LV high power
busbar trunking (<6300A) in power substations, commercial buildings
and industry facilities. Professional in AutoCAD programming.
3 Comments
1.
Tapan Kumar Das
SE P 0 3 , 2 0 1 9
Very nice information and very useful for users of this type of MV
switchgear
(reply)
2.
Swanand Desai
OCT 18, 2018
Very good Valuable Topic!!
(reply)
3.
Hassan Al-Amin
OCT 17, 2018
Hello,
I would like to thank you for yo