1 Circuit breaker nameplates

1 Protection and control devices

Moulded-case circuit-breaker: Tmax T

CIRCUIT-BREAKER TYPE
Series Size Rated ultimate short-circuit Rated
T 1 breaking capacity at 415 Vac uninterrupted
2 B = 16 kA current
3 C = 25 kA 160 A
4 N = 36 kA 250 A
5 S = 50 kA 320 A
H = 70 kA 400 A
6
L = 85 kA (for T2) 630 A
7 L = 120 kA (for T4-T5-T7) 800 A
L = 100 kA (for T6) 1000 A
V = 150 kA (for T7) 1250 A
V = 200 kA 1600 A

Rated insulation
Rated uninterrupted voltage Ui; i.e. the
current Iu maximum r.m.s. value
of voltage which the
circuit-breaker is
Rated operational capable of
voltage Ue withstanding at the
supply frequency
under specified test
conditions.

Rated impulse
withstand voltage
Uimp; i.e. the peak
Tmax T2L160 Iu=160A Ue=690V Ui=800V Uimp=8kV IEC 60947-2 value of impulse
Ue (V) 230 400/415 440 500 690 250 500
voltage which the
Made in Italy
circuit-breaker can
Icu (kA) 150 85 75 50 10 85 85 by ABB SACE
withstand under
Ics (% Icu) 75 75 75 75 75 75 75 specified test
Cat A 50-60Hz 2P 3P conditions.
in series

Rated ultimate short- According to the CE marking affixed on Compliance with the
circuit breaking capacity international Standard ABB circuit-breakers to international
(Icu) and rated service IEC 60947-2, the circuit indicate compliance Standard
short-circuit breaking breakers can be divided with the following CE IEC 60947-2:
capacity (Ics) at into Category A, i.e. directives: “Low-Voltage
different voltage values. without a specified “Low Voltage Directive” switchgear and
short-time withstand (LVD) no. 2006/95/CE controlgear-Circuit-
ASDC008046F0201

current rating, or “Electromagnetic breakers”.


Category B, i.e. with a Compatibility Directive”
specified short-time (EMC) no. 89/336 EEC.
withstand current rating.

ABB | Protection and control devices 29