Calculate Size of Inveter & Battery Bank

Electrical Load Details


Sr.No Equiment Name No Watt P.F Total Watt Total VA
1 2 60 0.8 120 150
1 200 0.8 200 250
2 30 0.8 60 75
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0 :Size of Inve
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
380 475
Total Load 380 Watt
Total Load 475 VA
& Battery Bank Jignesh.Parmar www.electricalnotes.wordpress.com

Battery Bank's Voltage 24 Volts DC


Reaserve Hour: (How many Hour Do you want to get Power
2 Hour
from battery Banks)
Loose Connection/Wire Loss Factor: 20 % 0.2
Battery Efficiency 90 % 0.9
Battery Aging: 20 % 0.2
Depth of Discharge:(DOD) 50 % 0.5
Battery Operating Temp: 46 C°
The Battery Bank Required: 101.3 Amp.Hr

If You are Selecting Battery 60 Amp.Hr @ 12 volts


Batteries connection for Battery Bank Series-Parral

:Battery Bank Detail :


Type of Connection For Batteries Series-Parral Connection
Selection of Batteries Connection: O.K
Selection of Each Battery Voltage O.K
Number of String for Battry Bank 2 Nos
Total Amp.Hr of Each String 60 Amp.Hr
Total No of Battery in Each String 2 Nos

Total Battery Bank Amp.Hr 120 Amp.Hr


Total Nos of Batteries in Battery Bank 4 Nos

:Size of Invertor:
Calculate Additional Future Load 20 %
Effieciency of Invertor 80 %
Size of Invertor 570 Watt or 712.5

CALCULATIONS:
Total Watt 380.0 Watt
Total Watt.Hr 760.0 Watt.Hr
Total Storage Required ( Amp.Hr) 31.7 Amp.Hr
Average Load 42.2 Amp.Hr

Battery Aging 50.7 Amp.Hr


Including Operating Temp 50.7 Amp.Hr
Depth of Discharge 101.3 Amp.Hr