&DOFXODWH6L]HRI7UDQVIRUPHU)XVH&LUFXLW%UHDNHU
Calculation Size of Circuit Breaker & Fuse are as per NEC 450.3
Transformer Details
Total D.F Load 5327.6505 Kva
Primary Side Voltage (L-L): 13800 Volt
Secondary Side Voltage (L-L): 480 Volt
Transformer Impedance: 5%
Transformer Connection ∆-Y
Size of Transformer: 7500 Kva OR Kva 7500
Efficency of Transformer at Full Load 98.40% 0.984
Efficency of Transformer at 1/4 Load 97.50% 0.975
Location of Transformer Supervised Not Supervised
Pri.Side & Sec.Side
:Results:
Transformer Voltage / Current
Primary Line Voltage (L-L) 13800 Volt
Primary Phase Voltage (L-P) 13800 Volt
Primary Line Current(L-L): 314 Amp
Primary Phase Current(L-P): 181 Amp
Secondary Line Voltage (L-L) 480 Volt
Secondary Phase Voltage (L-P) 277 Volt
Secondary Phase Current(L-P): 9021.4 Amp
Secondary Line Current(L-L): 9021.4 Amp
Size of Circuit Breaker / Fuse (As per NEC 450.3)
Size of Circuit Breaker on Primary Side: 1600 Amp
Size of Fuse on Primary Side: 800 Amp
Size of Circuit Breaker on Secondary Side: 6000 Amp
Size of Fuse on Secondary Side: 6000 Amp
Transformer Losses
Total Losses@ Full Load 121951 Watt
Total Losses@ 1/4 Load 48077 Watt
Full Load Copper Loss 78799 Watt
Core Loss 43152 Watt