Professional Documents
Culture Documents
Sprinkler Systems
Planning and Installation
August 2013
VdS Schadenverhütung GmbH - Fire Protection Association - 2014-08-19
Insurance Europe Standard
CEA 4001
Sprinkler Systems
Planning and Installation
August 2013
The technical work has been carried out by the Expert Group 4.
The editorial work has been carried out by CNPP ENTREPRISE, on behalf of the other prevention bodies.
The copyright of the non-binding standards is shared by the Consortium of prevention bodies:
This non-binding standard contains updated specifications and more details compared with the previous edition
(February 2009) and also by comparison with the European Standard EN 12845.
CONTENTS
Foreword ................................................................................................................................. 13
1 General............................................................................................................................. 13
1.1 Scope ....................................................................................................................... 13
1.2 Aims ......................................................................................................................... 13
1.3 Description .............................................................................................................. 14
1.4 Approvals................................................................................................................. 14
2 Definitions ....................................................................................................................... 16
3 Contract planning and documentation.................................................................. 20
3.1 General .................................................................................................................... 20
3.2 Initial Considerations............................................................................................... 20
3.3 Preliminary or estimating stage ............................................................................... 20
3.4 Design stage............................................................................................................. 21
3.5 Commencement of installation works ................................................................... 24
4 Extent of sprinkler protection .................................................................................. 25
4.1 Buildings and areas to be protected ....................................................................... 25
4.2 Compartmentation and separation ........................................................................ 25
5 Classification of occupancies and fire hazards..................................................... 26
5.1 General .................................................................................................................... 26
5.2 Hazard classes ......................................................................................................... 26
5.3 Storage ..................................................................................................................... 27
5.4 Protection of concealed spaces .............................................................................. 29
6 Hydraulic design criteria ............................................................................................ 29
6.1 General .................................................................................................................... 29
6.2 High Hazard Storage - HHS.................................................................................... 30
6.3 Pressure and flow requirements for precalculated systems.................................. 32
6.4 Pipe sizing and layout .............................................................................................. 34
18 Maintenance ................................................................................................................... 85
18.1 General .................................................................................................................... 85
18.2 Action following sprinkler operation ...................................................................... 86
18.3 User’s programme of inspection and checking ...................................................... 87
18.4 Service and maintenance schedule ......................................................................... 88
Annex A ................................................................................................................................... 91
Annex B.................................................................................................................................... 94
B.1 General .................................................................................................................... 94
B.2 Material factor ......................................................................................................... 94
B.3 Effect of stored materials configuration ................................................................. 95
Annex C ................................................................................................................................... 97
Annex D ................................................................................................................................... 100
D.1 Scope ....................................................................................................................... 100
D.2 Zoning of installations ............................................................................................. 100
D.3 Requirements for zoned installations ..................................................................... 100
D.4 Block Plan ................................................................................................................ 101
Annex E .................................................................................................................................... 102
E.1 Scope ....................................................................................................................... 102
E.2 Design criteria ......................................................................................................... 102
E.3 Water supplies ........................................................................................................ 102
Annex F .................................................................................................................................... 106
F.1 Subdivision into zones ............................................................................................. 106
F.2 Wet Pipe Installations ............................................................................................. 106
F.3 Sprinkler type and sensitivity .................................................................................. 106
F.4 Installation Main Control Valve Set ........................................................................ 106
F.5 Water Supplies ........................................................................................................ 106
F.6 Theatres ................................................................................................................... 106
F.7 Additional precautions for maintenance ................................................................ 106
Annex G ................................................................................................................................... 108
G.1 Calculation of pressure losses in pipework............................................................ 108
G.2 Pre-calculated systems ............................................................................................ 109
G.3 Fully calculated systems........................................................................................... 115
Annex H (Informative) ....................................................................................................... 118
Annex I (Informative) .......................................................................................................... 127
Annex J (Informative) .......................................................................................................... 128
Annex K.................................................................................................................................... 129
K.1 Aerosols................................................................................................................... 129
Table T 12.2.1a: Sprinkler types and K factors for various hazard classes ........................ 72
Table 12.2.6a: Minimum recommended lengths between dry sprinkler fitting
and the outside surface of cold room ..................................................... 74
Table T 12.5.1a: Sprinkler sensitivity ratings ....................................................................... 74
Table T 13.4a: Minimum size of drain valves ................................................................... 77
Table T 15.2a: Design parameters for pipe supports ..................................................... 82
Table T 15.2b: Minimum dimension of flat iron rods and clips ....................................... 82
Table T Aa: Light Hazard occupancies ........................................................................ 91
Table T Ab: Ordinary Hazard occupancies (A.2) ....................................................... 91
Table T Ac: High Hazard Process occupancies .......................................................... 93
Table T B.3a: Categories as a function of stored materials configuration .................... 95
Table T Ca: Stored products and categories .............................................................. 97
Table T G.1.1a: C values for various types of pipe ........................................................... 108
Table T G.1.4a: Equivalent length of fittings and valves .................................................... 109
Table T G.1.5a: Accuracy of hydraulic calculations ........................................................... 109
Table T G.2.2.3a: Location of design points – TG.2.2.3a .................................................... 110
Table T G.2.2.3b: Location of design points – OH, HHP and HHS .................................... 110
Table T G.2.3.1a: Range pipe diameters for LH installations .............................................. 111
Table T G.2.3.2a: Maximum friction loss between control valve set and any
design point – LH ..................................................................................... 111
Table T G.2.3.3a: Pressure loss for design flow rates in LH installations ............................ 111
Table T G.2.4.1a: Range pipe diameters for OH installations ............................................. 112
Table T G.2.4.1b: Distribution pipe diameters in OH installations ..................................... 112
Table T G.2.5a: Range pipe diameters for HH installations with pressure and flow
characteristics as given in Table T 6.3.2a (first or second part) ............ 114
Table T G.2.5b: Distribution pipe diameters downstream for the design point
in HH installations with pressure and flow characteristics as given
in Table T 6.3.2a (first part) .................................................................... 114
Table T G.2.5c: Distribution pipe diameters downstream for the design point
in HH installations with pressure and flow characteristics as given
in Table T 6.3.2a (second, third and forth part) ..................................... 115
Table T G.2.5d: Range pipe diameters for HH installations with pressure and flow
characteristics as given in Table T 6.3.2a (third or forth part) .............. 115
Table T G.3.4a: Minimum sprinkler discharge pressure and minimum sprinkler K factor 117
Table T K.1a: Protection criteria for aerosol storage ................................................... 129
Table T K.3a: Flammable liquids in metal drums (ST1) with a capacity > 20 l
and ≤ 208 l ............................................................................................... 131
Table T K.3b: Flammable liquids in metal drums (ST4) with a capacity >20 l
and ≤208 l ................................................................................................ 131
Table T K.3c: Flammable liquids in metal drums (STl,ST5,ST6) with a capacity
of maximum 20 l ...................................................................................... 131
Table T K.4a: Protection of solid piled or palletized pallets .......................................... 132
Table T K.4b: Protection of rack storage of pallets (ST4) ............................................. 132
Table T K.6.1a: Non-woven synthetic fabric: design criteria with roof or ceiling
protection only ......................................................................................... 133
Table T K.8a: Density for mobile shelving – in room less than 150 m2 ........................ 134
Table T K.10.2a: Maximum bulk and bale storage heights ................................................. 135
Table T K.10.2b: Design data for sprinkler systems for bulk and bale storage ................. 135
Table T K.11.2.2a: Design data for on-side, on-tread and laced storage ............................. 138
Table T K.11.3a: Design data with ESFR Sprinklers for ST2 and ST3 configuration ......... 138
Table T L.1.4.3a: Sprinklers design and maximum height ................................................... 141
Table T L.2.2.5a: Sprinklers design beneath obstruction .................................................... 143
Table T L.2.3.1a: Distance between sprinklers ................................................................... 143
Table T Na: Minimum water supply for all hazard classes shall be superior .............. 147
These Rules specify requirements and give An automatic sprinkler system is designed to
recommendations for the design, installation detect a fire and extinguish it with water in its
and maintenance of fixed fire sprinkler systems early stages or hold the fire in check so that
in buildings and industrial plants, and particular extinguishment can be completed by other
requirements or sprinkler systems which means.
require high level of reliability. The sprinkler system is intended to extend
The requirements and recommendations of throughout the premises with only limited
these Rules are also applicable to any addition, exceptions.
extension, repair or other modification to a It should not be assumed that the provision of a
sprinkler system. sprinkler system entirely obviates the need for
It covers the classification of hazards, other means of fighting fires and it is important
provision of water supplies, components to to consider the fire precautions in the premises
be used, installation and testing of the system, as a whole.
maintenance, and the extension of existing Structural fire resistance, escape routes, fire
systems, and identifies construction details of alarm systems, particular hazards needing
buildings which are necessary for satisfactory other fire protection methods, provision of
performance of sprinkler systems complying extinguishing means, safe working and goods
with these Rules. handling methods, management supervision
The requirements concerning water supplies and good housekeeping all need consideration.
may be applicable as guidance, to be used It is essential that sprinkler systems should be
with experienced judgement for other fixed properly maintained to ensure operation when
fire fighting systems where no other CEA non- required. This routine is liable to be overlooked
binding standards exist. or given insufficient attention by supervisors.
These Rules do not deal with water spray It is, however, neglected at peril to the lives
deluge systems. of occupants of the premises and at the risk
The requirements are not valid for automatic of crippling financial loss. The importance of
sprinkler systems on ships, in aircraft, on proper maintenance cannot be too highly
vehicles and mobile fire appliances or for below emphasized.
ground systems in the mining industry. When sprinkler systems are out of service extra
These Rules are intended for use by those attention should be paid to fire precautions and
concerned with purchasing, designing, installing, the appropriate authorities informed.
sprinkler head
range pipes
riser
arm pipe
drop
riser
main distribution pipe
During the inspection, the shut down period A number of sprinklers shall be removed and
inspected. Table T 1.4.3.2.2a specifies the scope
shall be in accordance with 18.1.3.
of sampling as a function of the total number of
sprinklers installed in the premises.
1.4.3.1 Annual Inspection
The sprinkler system shall be periodically
Table T 1.4.3.2.2a: Minimum number of
inspected at least once a year by the approved sprinklers per type to be inspected
inspectors.
Total number Minimum number
The inspection report shall confirm that the of sprinklers installed of sprinklers
system is in accordance with the rules, well (n) to be inspected
maintained and in full working order. Any faults (batch)
d) a statement that the installation will comply 3.4.3 Installation layout drawings
fully with these rules or giving details of any
deviations from their requirements and the 3.4.3.1 General
reasons therefore. The scale shall be not less than 1:200. Layout
drawings shall include the following information:
3.4 Design stage a) north point indication;
3.4.1 General b) the class or classes of installation according
to hazard class including storage category
The information provided shall include a and design storage height;
summary schedule (see 3.4.2), complete
c) constructional details of floors, ceilings,
working drawings of the sprinkler installation(s) roofs, exterior walls and walls separating
(see 3.4.3) and details of the water supplies (see sprinklered and non-sprinklered areas;
3.4.4).
d) sectional elevations of each floor of each
building showing the distance of sprinklers
3.4.2 Summary schedule
from ceilings, structural features, etc. which
The summary schedule shall give the following affect the sprinkler layout or the water
information: distribution from the sprinklers;
p) the location and details of any fire department pf is the frictional pressure loss in the
inlet connections; distribution pipework between the
q) a key to the symbols used. design point and the control valve ‘C’
gauge, in bar;
NOTE: details of other services should not appear on
sprinkler drawings except insofar as they are necessary ph is the static pressure between the level
for the correct installation of the sprinkler system. of the highest design point on the floor
concerned and the level of the highest
3.4.3.2 Pre-calculated pipework design point in the top storey, in bar;
ps, is the static head loss owing to the
(Limited scope see 6.4.1)
height of the highest sprinkler in the array
For pre-calculated pipework the following concerned above the control valve ‘C’
details shall be given on, or with, the drawings: gauge, in bar.
a) identification of the design point of each
array on the layout drawing (for example, as 3.4.3.3 Fully calculated pipework
in Figure F H.d); For fully calculated pipework, the following shall
b) a summary of the pressure losses between be given, with detailed calculations, either on
the control valve set and the design points at purpose designed work sheets or as a computer
the following design rates of flow: print-out:
1) in an LH installation 2251/min; a) the program name and version number, if
2) in an OH installation 10001/min; applicable;
– the position of the hydraulically most reducing valve, water meter, water lock and any
unfavourable area of operation; connection supplying water for other services,
shall be indicated.
– the position of the hydraulically most
favourable area of operation;
3.4.4.2 Hydraulic calculation
– the four sprinklers upon which the design
density is based; Hydraulic calculation (with relevant flow tests)
shall show that each trunk main together with
– the height above datum of each point of any branch main, from each water supply to a
identified pressure value; main installation control valve set water supply
e) for each operating sprinkler: test and drain valve and control valve ‘C’ gauge
(i.e. including the installation control valves) is
1) the sprinkler node or reference number;
capable of providing the required pressure and
2) the nominal K factor; flow at the installation control valve test and
3) the flow through the sprinkler in litres per drain valve.
minute;
3.4.4.3 Town main
4) the inlet pressure to the sprinkler or
sprinkler assembly in bar; Where a town main forms one or both of the
supplies or provides infill to a reduced capacity
f) for each hydraulically significant pipe: storage tank, the following details shall be given:
1) pipe node or other reference; a) the nominal diameter of the main;
2) nominal bore in millimetres; b) whether the main is double-end fed or dead-
3) the pipe constant for type and condition end; if dead-end, the location of the nearest
(see G1.1.) (e.g. Hazen Williams constant); double- end fed main connected to it;
4) flow in litres per minute; c) the pressure/flow characteristic graph of the
town main determined by a test at a period
5) velocity in metres per second; of peak demand. At least three test points
6) length in metres; shall be shown. The graph shall be corrected
for friction losses and static head difference
7) numbers, types and equivalent lengths of
between the test location and either the
fittings;
control valve ‘C’ gauge or the suction tank
8) static head change in metres; infill valve, as appropriate;
9) pressures at inlet and outlet in bar; d) the date and time of the town main test;
10) friction loss in bar; e) the location of the town main test point
11) indication of flow direction. relative to the installation control valve; and
where the pipework is fully calculated the
3.4.4 Water supply following additional details shall be given
f) a pressure/flow characteristic graph indicating
3.4.4.1 Water supply drawings the available pressure at any flow up to the
The drawings shall show water supplies and maximum flow demand;
pipework there from up to the installation g) the demand pressure/flow characteristic
control valves. The drawings shall be on an graph for each installation for the hydraulically
indicated scale of not less than 1: 100. A key to most unfavourable (and if required the most
the symbols shall be included. The position and favourable) area of operation with pressure
type of stop and check valves and any pressure taken as at the control valve ‘C’ pressure gauge.
a) a pump characteristic curve for low water c) the volume of stored water;
level ‘X’ (see Figures F 8.3.5a and F 8.4.1b), d) the air pressure;
showing the estimated performance of the e) the height of the highest sprinkler above the
pump or pumps under installed conditions bottom of the tank;
at the control valve ‘C’ gauge;
f) details of the means of replenishment.
b) the pump manufacturer’s data sheet showing
the following: 3.4.4.6 Water storage tank
1) the generated head graph; The following details shall be provided:
2) the power absorption graph; a) the location;
3) the net positive suction head (NPSH) b) the total volume;
graph;
c) the volume and duration of stored water;
4) a statement of the power output of each
d) inflow for reduced capacity tanks;
prime mover;
e) vertical distance between the pump centre
c) the installer’s data sheet showing the pump
line and the tank low water level ‘X’
set installed performance pressure/flow
(see Figures F 8.3.5a and F 8.4.1b);
characteristics, at the control valve ‘C’ gauge
for normal water level and for low water f) structural details of the tank and roof;
level ‘X’ (see Figures F 8.3.5a and F 8.4.1b), g) anticipated frequency of schedule repairs
and at the pump outlet pressure gauge for requiring emptying of the tank.
normal water level;
d) the height difference between the control 3.4.5 Electrical installation for
valve ‘C’ gauge and the pump delivery electrically driven pumps
pressure gauge; The following details shall be provided:
e) the installation number and the hazard a) protection of the cable against mechanical
classification(s); damage;
f) the available and the specified NPSH at b) protection of the cable against fire;
maximum required flow;
c) layout drawing of the electrical installation.
g) the minimum depth of water cover in the
case of submersible pumps; In addition
where the pipework is fully calculated the 3.5 Commencement of
following details shall be provided; installation works
h) the demand pressure/flow characteristic Before the commencement of any works for
for the hydraulically most unfavourable and new installations or an extension to an existing
most favourable area of operation calculated installation, the installer shall send a written
at the control valve ‘C’ gauge. notification to the authorities.
Figure F 5.3.1a: Flow chart for determining the class required for storage
post-pallet storage (ST2) post-pallet storage (ST3) solid or slatted shelves (ST5/6)
wide of the higher density extending into the product (or mix of products) and its packaging
designed area of lower density. (including the pallet) and the method and height
of storage.
6.2 High Hazard Storage - HHS Specific limitations apply to the various types of
storage methods as detailed in Clause 5.
6.2.1 General
The type of protection and determination 6.2.2 Ceiling or roof protection only
of the design density and area of operation Table T 6.2.2a specifies the appropriate design
are dependent on the combustibility of the density and area of operation according to
Table T 6.2.2a: Design criteria for HHS with roof or ceiling protection only
the category and maximum permitted storage 6.2.3.2 The design density for the roof
height for the various types of storages with roof or ceiling sprinklers shall be a minimum of
or ceiling protection only. More specifically, 7.5 mm/min over an area of operation of 260 m2.
the storage heights indicated in the table are If goods are stored above the highest level of
considered the maximum for efficient sprinkler intermediate protection, the design criteria for
protection where sprinklers are only provided the roof or ceiling sprinklers shall be taken from
at the roof or ceiling. Storage heights exceeding Table T 6.2.3.2a.
these limits require that intermediate levels
of in-rack sprinklers be provided as per 6.2.3 6.2.3.3 It shall be assumed that 3 heads are
below. The distance between the maximum operating simultaneously on each level of in-rack
permitted storage height and the roof or ceiling sprinklers, up to a maximum of three levels, at
sprinklers should not exceed 4 m. the most hydraulically remote position. Where
NOTE: storage height, building height and ceiling rack aisles are no less than 2.4 m in width only
clearance (the vertical distance between the roof one rack need be assumed to be involved.
or ceiling sprinklers and the top of the storage) Where rack aisles are less than 2.4 m but no less
are all significant variables contributing to the than 1.2 m in width, two racks shall be assumed
effectiveness and required design density of to be involved. Where rack aisles are less than
sprinkler protection. 1.2 m in width, three racks shall be assumed to
be involved.
6.2.3 Intermediate level in-rack
sprinklers In case of racks with more than 1 row of
sprinklers in each protected level, a maximum
6.2.3.1 Where more than 50 intermediate of 3 adjacent rows of sprinklers with 3 (or more
level sprinklers are installed in the racks, roof in case of obstruction – see 11.5.1) sprinklers
or ceiling sprinklers shall be installed with a per line and with a maximum of 3 levels shall be
separate set of control valves. hydraulically considered.
NOTE 1: the vertical distance from the highest level of in-rack sprinklers to the roof or ceiling sprinklers, minus1 m.
NOTE 2: dry and alternate systems should be avoided on High Hazard storages especially with the more combustible products (the higher
categories) and the higher storages. Should it nonetheless be necessary to install a dry or alternate system, the area of operation shall be
increased by 25%.
6.3 Pressure and flow 6.3.2.1 Where the area of the HHP or HHS
requirements for portion of an occupancy is less than the area of
precalculated systems operation, the flow rate in Table T 6.3.2a can
be proportionately reduced, (see 6.3.2.6), but
6.3.1 LH and OH systems the pressure at the highest sprinklers in the area
The water supply shall be capable of providing shall either be equal to that shown in the table
the flows and pressures at each installation for the appropriate flow rate or be determined
control valve set as specified in Table T 6.3.1a. by hydraulic calculation.
The pressure loss due to friction and static
between the water supply and each control 6.3.2.2 When the HHP or HHS portion of
valve set shall be calculated separately. occupancy involves less than 48 sprinklers, the
flow rate and appropriate pressure shown in
6.3.2 HHP and HHS systems without Table T 6.3.2a shall be available at the level of
in-rack sprinklers the highest sprinklers at the point of entry to
the HHP or HHS area of sprinklers.
NOTE: in-rack sprinklers must always be fully
calculated (see G.3).
6.3.2.3 Where the design area of operation
The water supply shall be capable of delivering is greater than the area of HHP or HHS
at the highest design point not less than the protection and this area is adjacent to the
appropriate flow and pressure specified in table OH protection, the total flow rate shall be
T 6.3.2a, or as modified in 6.3.2.1 to 6.3.2.4. calculated as the sum of the HHP or HHS
The total requirement for the pressure at the portion when reduced proportionately as in
control valve set shall be the sum of the pressure 6.3.2 plus the flow rate for the OH section
at the design point, the pressure equivalent of calculated on the basis of a design density of
the difference in height between the control 5 mm/min. The pressure at the level of the
valve set and the highest sprinkler downstream highest sprinklers in the HHP or HHS portion
of the design point and the pressure loss for the of the risk shall be either that shown in
flow in the piping from the control valve set to Table T 6.3.2a, or be determined by hydraulic
the design point. calculation.
Design Flow required l/min Pressure at the highest design point bar
density
Area of operation per sprinkler m2
mm/min
Wet or Dry or 6 7 8 9
pre- action alternate
With pipe diameters in accordance with Tables T G.2.5a & T G.2.5b and sprinklers having a K factor of 80
7.5 2 300 2 900 - - 1.80 2.25
10.0 3 050 3 800 1.80 2.40 3.15 3.90
With pipe diameters in accordance with Tables T G.2.5a & T G.2.5c and sprinklers having a K factor of 80
7.5 2 300 2 900 - - 1.35 1.75
10.0 3 050 3 800 1.30 1.80 2.35 3.00
With pipe diameters in accordance with Tables T G.2.5c & T G.2.5d and sprinklers having a K factor of 80
7.5 2 300 2 900 - - 0.70 0.90
10.0 3 050 3 800 0.70 0.95 1.25 1.60
With pipe diameters in accordance with Tables T G.2.5c & T G.2.5d and sprinklers having a K factor of 115
10.0 3 050 3 800 - - - 0.95
12.5 3 800 4 800 - 0.90 1.15 1.45
15.0 4 550 5 700 0.95 1.25 1.65 2.10
17.5 4 850 6 000 1.25 1.70 2.25 2.80
20.0 6 400 8 000 1.65 2.25 2.95 3.70
22.5 7 200 9 000 2.05 2.85 3.70 4.70
25.0 8 000 10 000 2.55 3.50 4.55 5.75
27.5 8 800 11 000 3.05 4.20 5.50 6.90
30.0 9 650 12 000 3.60 4.95 6.50 -
b) If the supply is capable of supplying the sum sprinkler alarm valve. In this case a stop
of simultaneous maximum calculated flows valve shall be fixed downstream as
from each system, where the systems can near as possible to the connection and
be activated by the same fire. The flows shall consideration regarding false alarm when
be corrected up to the pressure required hose reels are used for a non fire fighting
by the most demanding system. The flow purpose shall be taken into account.
and pressure required by other water e) unless the pressure tank is provided with
based automatic fire fighting systems shall automatic refilling device designed for a flow
be in accordance with the relevant design corresponding to the hose reel maximum
approved by the authority; demand (or 6 m3/h whichever is greater),
c) Connected through a stop valve fitted connection of hose reels to pressure tanks
upstream of the sprinkler alarm valve set(s), as is not permitted.
close as is practical to the point of connection NOTE: However, it needs to be considered that
to the sprinkler system supply pipe; both systems (sprinklers and hose reels) may be
d) The additive volume required by the other out of order at the same time (See 18.1.3 for
water based automatic fire fighting systems precautions and procedures when a system is not
shall be based on their relevant design fully operational).
duration, and f) Unless a single water supply is accepted by
e) The type of water supply shall be superior authority, the type of water supply shall be
single or duplicate. superior single or duplicate.
e) The type of water supply shall be superior pressure and flow for checking compliance with
single or duplicate. clauses 6.3 and 9.
NOTE: However it needs to be considered that
both systems (sprinklers and hydrants) may be
7.4.1 At control valve sets
out of order at the same time (See 18.1.3 for A flow measuring device shall be installed at
precautions and procedures when a system is not each control valve set except in the following
fully operational). cases:
7.2.4 Connection for drinking and a) where two or more control valve sets
sanitary water (non industrial use) are installed together, the device need
be installed only at the hydraulically most
If accepted by the authority, water for drinking remote set, or, when the installations belong
and sanitary purpose may be taken from the to different hazard classes, at the control
pipe connected to the town main and feeding valve set which requires the highest water
the sprinkler system only in accordance with flow;
the following: b) where the water supply is by an automatic
a) The system shall be fully calculated; pump or pumps, the flow measuring device
b) The connection for drinking and sanitary may be installed at the pumphouse.
water shall be limited to one single connection In all cases, the appropriate allowance must
and shall not be more than 25 mm when the be made for the pressure losses between the
sprinkler supply pipe is no less than 100 mm water source and the control valve set(s) using
and 40 mm when the sprinkler supply pipe is the calculation methods specified in G.1.
no less than 150 mm; Adequate facilities shall be provided for the
c) If the supply is capable of supplying the sum disposal of test water.
of simultaneous maximum calculated flows
NOTE: dry or alternate control valve sets (main
from sprinkler system and a fixed value for
or subsidiary) may have an additional flow test
drinking and sanitary water: 6 m3/h for 25 mm
valve arrangement of unspecified flow loss
connection and 12 m3/h for 40 mm connection;
characteristic fitted below the control valve set,
d) Connected through a stop valve fitted downstream of the main stop valve, to facilitate
upstream of the sprinkler alarm valve set(s), as informal supply pressure testing. Such flow test
close as is practical to the point of connection valves and pipework should have a nominal
to the sprinkler system supply pipe. diameter of 40 mm for LH installations and of
50 mm for other installations.
7.3 Housing of equipment
for water supplies 7.4.2 At water supplies
At least one suitable flow and pressure
Water supply equipment, such as pumps,
measuring arrangement shall be permanently
pressure tanks and gravity tanks, shall not be
installed and shall be capable of checking each
housed in buildings or sections of premises
water supply.
in which there are hazardous processes or
explosion hazards. The testing apparatus shall be of adequate
capacity and shall be installed in accordance with
7.4 Test facility devices the manufacturer’s instructions. Care shall be
taken with the distance from valves and fittings.
Sprinkler installations shall be permanently The apparatus shall be installed in a frost-proof
provided with suitable devices for measuring area.
For both precalculated and fully calculated Where a water contamination problem
installations, the water supply shall be tested at arises, consideration shall be given in
least at the installation maximum flow demand accordance with national regulation and/or the
(Q max). recommendations given in the document entitled
« Recommendations for the Fire Protection of
Stores Containing Hazardous Substances ».
7.6 Water supply
pressure test
8.2.2 Boosted mains water level and the lowest effective water level.
If the tank is not frost proof, the normal water
If booster pumps are used, they shall be installed level shall be increased by 1.0 m and ice venting
in accordance with the requirements of clause 9. provided. In the case of enclosed tanks, easy
NOTE: the agreement of the water authority will access shall be provided.
normally be needed before a booster pump can
be connected to a town main. The water authority 8.3.2.1 Precalculated systems
or water undertaker will normally require that the
Table T 8.3.2.1a specifies the minimum effective
pump cannot draw vacuum under any water supply
volume of water required for LH and OH
and demand condition.
precalculated systems. The quantities of water
Stop valves shall be fitted in the pump suction indicated shall be reserved solely for the use of
and delivery pipes as well as back pressure the sprinkler system.
valves in the pump delivery. Where a single
Table T 8.3.2.1b specifies the minimum quantity
pump is supplied, a by-pass connection shall
of water required for precalculated HHP or
be provided with at least the same dimension
HHS systems. The water volume indicated shall
as the water supply connection to the pump
be reserved solely for the use of the sprinkler
and be fitted with a back pressure valve and
system.
two stop valves. The pump or pumps shall be
reserved solely for fire protection.
8.3.2.2 Calculated systems
8.3 Water storage tanks The minimum water volume shall be calculated
by multiplying the flow at the most unfavourable
8.3.1 General area of the system (hydraulically calculated) by
the following:
Water storage tanks, where used, shall be one
or more of the following: – LH 30 minutes
– pump suction tank; – OH 60 minutes
– gravity tank; – HH 90 minutes
– reservoir.
8.3.3 Refill rates for full capacity tanks
8.3.2 Minimum water volume The water source shall be capable of refilling
the tank in no more than 36 hours.
For each system a minimum water volume is
specified. This shall be supplied from one of the The outlet of any feed pipe shall be situated at
following: least 2.0 m away from the pump inlet, measured
horizontally.
– a full capacity tank, with an effective capacity
at least equal to the specified minimum water
8.3.4 Reduced capacity tanks
volume. The tank may be divided into two
sections; The following conditions shall be met for
– a reduced capacity tank (see 8.3.4), where reduced capacity tanks:
the required minimum water volume is a) the inflow shall be from a town main and shall
supplied jointly by the effective capacity of be automatic, via at least two mechanical
the tank plus the automatic infill. float valves;
The effective capacity of a tank shall be calculated b) the effective capacity of the tank shall be no
by taking the difference between the normal less than that shown in Tables T 8.3.4a;
Table T 8.3.5a specifies minimum dimensions If a vortex inhibitor is installed with the minimum
for the following: dimensions specified in Table T 8.3.5a, dimension
– ‘A’ from the suction pipe to the low water ‘A’ may be reduced to 0.10 m.
level, (see Figure F 8.3.5a); A tank may be provided with a sump in order
– ‘B’ from the suction pipe to the bottom of to maximise the effective capacity (See Figure
the sump, (see Figure F 8.3.5a). F 8.3.5a). In this case the sump width shall be
A1 B1
N N
X X
A ≥ 0.03 m
D
B A
D
≥ 5D ≥ 0.3D B
≥ 5D ≥ 0.3D
A2 B2
N N
X ≥ 0.03 m X
A
D A
B D
≥ 6D B
≥ 6D
> 2.5D
effective capacity
Nominal diameter of Distance ’A’ minimum Distance ‘B’ minimum Minimum dimension
suction pipe’D’ m m of vortex inhibitor
mm m
65 0.25 0.08 0.20
80 0.31 0.08 0.20
100 0.37 0.10 0.40
150 0.50 0.10 0.60
200 0.62 0.15 0.80
250 0.75 0.15 1.00
300 0.90 0.20 1.20
400 1.05 0.20 1.20
500 1.20 0.20 1.20
not less than 6 times the nominal diameter of shall have a continuous slope towards the
the suction pipe. settling chamber or suction pit of at least 1:125.
The diameter of feed pipes or conduit shall be
8.3.6 Strainers determined by the following formula
In the case of pumps under suction lift d1 ≥ 21.68 Q0.357
conditions, a strainer shall be fitted upstream
of the back pressure valve on the pump suction where:
pipe. It shall be fitted so that it can be cleaned d1: internal diameter in mm;
without the tank having to be emptied. In
Q: flow in l/min.
the case of open tanks feeding pumps under
positive head conditions, a strainer shall be The suction chamber dimensions shall be as
fitted to the suction pipe outside the tank. A specified in 8.3.5.
stop valve shall be installed between the tank
and the strainer. In the case of flowing waters the angle between
the flow direction and the intake axis (seen in
Strainers shall have a cross-sectional area of the direction of flow) shall be less than 60°.
at least 1.5 times the nominal area of the pipe
and shall not allow objects greater than 5 mm 8.4.1.2 The inlet to pipes or conduit shall
diameter to pass. be submerged at least one diameter below
the lowest known water level. The depth d1
8.4 Inexhaustible sources of water in open channels or weirs (including
the weir between the settling chamber and
Water sources include natural and artificial
suction chamber) below the lowest known
sources such as rivers, canals and lakes which
water level of the water source shall be not
are virtually inexhaustible for reasons of capacity
less than that specified in Table T 8.4.1a for the
and climate etc.
corresponding width w and flow, where the
8.4.1 Settling chambers flow is the maximum flow demand (Qmax) The
and suction pits total depth of open channels and weirs shall
accommodate the highest known water level of
8.4.1.1 Where a suction or other pipe draws the water source.
from a settling chamber or suction pit fed
The dimension of the suction chamber and the
from an inexhaustible source, the design and
location of suction pipes from the walls of the
dimensions in Figure F 8.4.1b shall apply. Pipes,
chamber, their submergence below the lowest
conduits and the bed of open-topped channels
known water level (making any necessary
allowances for ice) and clearance from the
S bottom shall conform to 8.3.5 Figures F 8.5.3a
su ettl
ct ing and figure F 8.4.1b.
io a
n nd
The settling chamber shall have the same
width and depth as the suction chamber
In and a length of at least 10 d1 where d1 is the
ta minimum bore of the pipe or conduit, and not
ke
< 60° ax less than 1.5 m.
is
River flow direction 8.4.1.3 The chamber, including any screening
Figure F 8.4.1a: Location of settling and suction arrangement, shall be arranged to prevent
chamber: water flow direction ingress of wind borne debris and of sunlight.
lowest know
water level X
d1 d1
D
h (m)
≥ 0.3 m suction
settling chamber chamber
strainers
w shut-off unit b D
strainers
shut-off unit
lowest know
water level X
d1 d1
D
h (m)
suction
settling chambers chamber
≥ 0.3D
h = f(A.B.D) according to 8.3.5, Fig. 4, Table 13
strainers w shut-off b D
unit
suction
settling chambers chamber
strainers
shut-off unit
lowest know
water level X
≥ d1 ≥ d1 D
d1 h (m)
≥ 0.3 m suction
settling chamber chamber
strainers
d1 b D
suction
settling chambers chamber
8.4.1.4 Before entering the settling chamber obstructed and have a mesh not greater than
the water shall first pass through a removable 12.5 mm.
screen of wire mesh or perforated metal plate Two screens shall be provided, with one in
having an aggregate clear area below the water use and the other in a raised position ready for
level of 150 mm2 for each litre/min at the interchange when cleaning is necessary.
maximum flow demand (Qmax)
8.4.1.6 Where the suction inlet draws from
8.4.1.5 The inlet to the pipe or conduit a walled off area of the bed of the river, canal,
feeding the settling chamber or suction lake etc., the wall itself shall be extended above
chamber shall be provided with a strainer the water surface with an aperture screening
having an aggregate clear opening of at least arrangement. Alternatively, the space between
five times the cross sectional area of the pipe the top of the wall and the water surface shall
or conduit. The individual openings shall be be enclosed with a screen. Screens shall be as
of such a size as to restrict the passage of a specified in 8.4.1.4.
25 mm diameter sphere. Provision shall be
made for the settling chamber to be isolated 8.4.1.7 Excavation of the bed of the lake
for periodical cleaning and maintenance. etc., to create the necessary depth for a
Duplicate supplies shall be provided with pump suction inlet is not recommended, but if
separate suction and settling chambers. The unavoidable the area shall be enclosed with the
screen shall be strong enough to withstand largest screen practicable, but in any case having
the weight of water should it become sufficient clear area as specified in 8.4.1.4.
Table T 8.4.1a: Minimum width of inlet to settling chambers, suction chambers, open channels and weirs
0.25 m < d1* < 0.5 m 0.5 m ≤ d1* ≤ 1.0 m d1* ≥ 1.0 m
width maximum flow l/min width maximum flow width maximum flow
m m l/min m l/min
0.088 280 0.082 522 0.078 993
0.125 497 0.112 891 0.106 1 690
0.167 807 0.143 1 380 0.134 2 590
0.215 1 200 0.176 1 960 0.163 3 630
0.307 2 060 0.235 3 160 0.210 5 650
0.334 2 340 0.250 3 510 0.223 6 260
0.410 3 160 0.291 4 480 0.254 7 830
0.500 4 190 0.334 5 590 0.286 9 580
0.564 4 950 0.361 6 340 0.306 10 750
0.750 7 260 0.429 8 310 0.353 13 670
1.110 12 050 0.527 11 420 0.417 18 070
1.170 12 800 0.539 11 820 0.425 18 640
1.500 17 380 0.600 13 900 0.462 21 410
2.000 24 400 0.667 16 270 0.500 24 400
4.500 60 300 0.819 21 950 0.581 31 140
1.000 29 170 0.667 38 910
2.000 203 300
* Dimension d in Figure F 8.4.1b.
NOTE: for dimensions not included in this table, the conduit shall be designed such that the water velocity does not exceed 0.2 m/s.
The pressure tank shall be easily accessible The minimum quantity of water in a pressure
for external and internal inspection. It shall be tank for a single supply shall be 15 m3 for LH and
protected against corrosion both internally and 23 m3 for OH1.
externally. The minimum quantity of water in a pressure
The discharge pipe shall be situated at least tank for duplicate supplies shall be 15 m3 in LH
0.05 m above the bottom of the tank. and OH (all groups).
The air pressures and water flow rates from the 8.5.6 Control and safety equipment
tank shall be sufficient to satisfy the sprinkler
installation demand requirements, up to the The tank shall be fitted with a pressure gauge
point of exhaustion. and the correct service pressure shall be marked
on the gauge.
8.5.4.2 Calculation A gauge glass shall be fitted to indicate the water
level. Stop valves shall be fitted at each end of
The air pressure to be maintained in the tank
the gauge glass and they shall normally be kept
shall be determined from the following formula:
closed and a drain valve shall also be provided.
Vt The gauge glass shall be protected against
P = (P1 + P2 + 0.1h) – P1
Va mechanical damage and shall be marked with
the correct water level.
where:
The tank shall be fitted with suitable safety
P is the gauge pressure, in bar; devices to ensure that the highest permitted
P1 is atmospheric pressure, in bar pressure is not exceeded.
(assume P1 = 1);
P2 is the minimum pressure required at 8.6 Type of water supply
the highest sprinkler at pressure tank
An example of the choice of the water supply is
exhaustion, in bar. For precalculated
given in annex N. The authorities shall be consulted
systems this value shall be taken from
to determine the choice of water supply.
Tables T 6.3.1a and T 6.3.2a, plus any
additional pressure losses between the
8.6.1 Single water supplies
control valve set and pressure tank
(Table 6.3.1a) or between the design The water supply shall conform to the pressure,
point and pressure tank (Table T 6.3.2a), flow and duration requirements given in clauses
but ignoring static pressure; 8 and 6.
h is the height of the highest sprinkler The following constitute acceptable single water
above the bottom of the pressure tank supplies:
(i.e. negative if the highest sprinkler is
a) town main;
below the tank), in metres;
b) town with one or more booster pumps;
Vt is the total volume of the tank, in
cubic metres; Va is the volume of air in c) pressure tank (LH and OH1 only);
the tank, in cubic metres. d) gravity tank;
8.5.5 Charging with air and water e) storage tank with one or more pumps;
f) inexhaustible source with one or more
Pressure tanks used as a single supply shall
pumps.
be provided with means for automatically
maintaining the air pressure and water level. The 8.6.2 Superior single water supplies
air and water supplies shall be capable of filling
and pressurising the tank completely in no more Superior single water supplies are single water
than 8 hours. supplies which provide a higher degree of
The water supply shall be capable of topping up reliability. They include the following:
with water at the gauge pressure (P in 8.5.4) of a) town main fed from both ends, where each
the pressure tank with a flow of at least 6 m3/h. end is capable of satisfying the pressure and
flow demands of the system. The town main 8.7 Isolation of water supplies
pipe network shall be fed from two or more
water sources and shall not be dependent at The connections between the water sources
any point on a single, common trunk main; and sprinkler control valve sets shall be arranged
so as to ensure the following:
If booster pumps are required, two or more
shall be provided. a) that servicing of main components such as
strainers, pumpsets, back pressure valves
Provided that flow and pressure from one
and water meters is facilitated;
single direction are able to cover the required
demand without booster pump, only one single b) that any problem occurring to one supply
booster pump is required , if accepted by the shall not impair the operation of any other
authority. source or supply;
b) gravity tank with no booster pump, or water c) that maintenance can be carried out on one
storage tank with two or more pumps, where supply without impairing the operation of
the tank fulfils the following conditions: any other source or supply.
– The tank shall be full capacity;
– There shall be no entry for light or foreign 9 PUMPS
matter;
– Potable water shall be used; 9.1 General
– Painting or other corrosion protection, The H(Q) characteristic curve for the sprinkler
which reduces the need for emptying the pumps should be stable and flat. No instability
tank for maintenance shall be approved by may amount to more than 5% of the maximum
the authorities (see clause 18.4.6); deliver head.
c) inexhaustible source with two or more Pumps shall be driven either by electric motors
pumps. or diesel engines capable of providing at least the
power required to comply with the following:
8.6.3 Duplicate water supplies a) For pumps with non-overloading power
Duplicate water supplies consist of two characteristic curves: the maximum power
single water supplies where each supply is required at the peak of the power curve plus
independent of the other. Each of the supplies a 5% safety margin for electrical driven pump
forming part of a duplicate supply shall conform or 20% for diesel engines;
to the pressure and flow characteristics given in b) For pumps with rising power characteristic
clause 6. curves: the maximum power for any
Any combination of single supplies (including conditions of pump load, from zero flow
superior single supplies) may be used, with the to a flow corresponding to a pump NPSH
following limitations: required equal to 16 m or maximum suction
static head plus 11 m whichever is greater
a) no more than one pressure tank shall be
plus a 5% safety margin for electrical driven
used for OH systems; pump or 20% for diesel engines;
b) no more than one storage tank of the The coupling between the driver and the
reduced capacity type shall be used. pump of horizontal pumpsets shall be of a type
Two or more pumps drawing water from which ensures that either can be removed
two independent suction tanks constitute an independently and in such a way that pump
acceptable duplicate water supply. internals can be inspected or replaced without
affecting suction or discharge piping. End suction on the downstream side of the outlet non-
pumps shall be of the “back pull-out” type. return valve of the pump via a subsidiary stop
Pipework shall be supported independently of valve secured in the open position, together
the pump. with a water flow detector in accordance with
EN 12259-5, to provide visible and audible
indication of the operation of the sprinklers.
9.2 Multiple pump The alarm equipment shall be installed either at
arrangements the control valves or at a responsibly manned
Pumps shall have compatible characteristic location such as a gatehouse.
curves and be capable of operating in parallel at A 15-mm nominal diameter drain and test valve
all possible flow rates. shall be fitted downstream of the flow alarm to
Where two pumps are installed, each one permit a practical test of the alarm system.
shall be capable independently of providing the
specified flows and pressures.
9.3.3 Temperature
Where three pumps are installed, each pump The pump compartment shall be maintained at
shall be capable of providing at least 50% of the or above the following temperature:
specified flow at the specified pressure. – 4°C for electric motor driven pumps;
Where more than one pump is installed in a – 10°C for diesel engine driven pumps.
superior or duplicate water supply, no more
than one shall be driven by an electric motor. 9.3.4 Ventilation
(See clause 9.8.1.1)
Pump compartments for diesel engine driven
pumps shall be provided with adequate
9.3 Compartments for
ventilation in accordance with the supplier’s
pumpsets
recommendations.
9.3.1 General
9.4 Maximum temperature of
Pumpsets shall be housed in a compartment
of non-combustible construction having a fire
water supply
resistance of no less than 60 min, used for no The water supply temperature shall not exceed
other purpose than fire protection. It shall be 40°C. Where submersible pumps are utilised
one of the following (in order of preference): the water temperature shall not exceed 25°C,
a) A separate building; unless the suitability of the motor has been
proven for temperatures up to 40°C.
b) A building adjacent to a sprinkler-protected
building with direct access from outside;
9.5 Valves and accessories
c) A compartment within a sprinkler-protected
building with direct access from outside. A stop valve shall be fitted in the pump suction
pipe and a non-return and a stop valve shall be
9.3.2 Sprinkler protection fitted in the delivery pipe. In lift condition, when
Compartments for pumpsets shall be sprinkler- the centre line of the pump is above the maximum
protected. Where the pump compartment water level, a stop valve may be omitted.
is separate, it may be impractical to provide Any taper pipe fitted to the pump outlet shall
sprinkler protection from the control valve expand in the direction of flow at an angle not
sets in the premises. Sprinkler protection may exceeding 20°. Valves on the delivery side shall
be provided from the nearest accessible point be fitted after any taper pipe.
Means for venting all cavities of the pump casing when it is not practicable to arrange positive suction
shall be provided unless the pump is made self- head. It is critical that suction lift arrangements
venting by arrangement of its branches. should not vary from that stated in 9.6.2 and as
Arrangements shall be made to ensure a shown in figures F 9.6.2.4a.
continuous flow of water through the pump
sufficient to prevent overheating when it is 9.6.2 Suction pipe
operating against a closed valve. This flow shall 9.6.2.1 General
be taken into account in the system hydraulic
calculation and pump selection. The outlet shall The pump suction shall be connected to a
be clearly visible and where there is more than straight or taper pipe at least two diameters
one pump the outlets shall be separate. long. The taper pipe shall have horizontal
NOTE: Diesel engine cooling circuits usually use topside and a maximum included angle not
the same water. However, if additional water is exceeding 20º. Valves shall not be fitted directly
used, it shall also be taken into account. to the pump inlet.
Tapings on the pumps for inlet and outlet The suction piping, including all valves and
pressure gauges shall be easily accessible. fittings, shall be designed in such a way as to
ensure that the available NPSH at the pump
inlet exceeds the required NPSH by at least
9.6 Suction conditions
1 m with flow defined in table T9.6.2.1a and
9.6.1 General maximum water temperature.
Suction piping shall be laid either horizontal or
Wherever possible, horizontal centrifugal pumps
with a continuous slight rise towards the pump
should be used, installed with a positive suction
to avoid the possibility of air locks forming in
head. i.e. in accordance with the following:
the pipe.
– At least two thirds of the effective capacity
A foot valve shall be fitted where the centre line
of the suction tank shall be above the level of
of the pump is above the low water level (see
the pump centre line;
8.3.5).
– The pump centre line shall be no more than
2 m above the low water level of the suction 9.6.2.2 Positive head
tank (level X in 8.3.5).
The diameter of the suction pipe shall be no
NOTE 1: If this is not feasible, the pump may be less than 65 mm. Furthermore, the diameter
installed under suction lift conditions or vertical shall be such that a velocity of 1.8 m/s is not
turbine pumps may be used. exceeded when the pump is operating at flow
NOTE 2: Suction lift and submersible pump defined in table T9.6.2.1a. This velocity may
arrangements should be avoided and only used be increased to 2.5 m/s, if the pressure in the
Pipework Hazard Class Flow reference for suction pipe Pump inlet condition
Pre-calculated LH/OH Maximum demand flow from table For tanks, with water
T 6.3.1a supply at low water level
(see X in Figure F 8.3.5a).
HH 1.4 × Flow Required from table T 6.3.2a
For booster pumps, with
Fully calculated All Flow at 1.4 × Q100 minimum town main
pressure.
suction pipe is not more than 0.4 bar below The priming tank, the pump and the suction
ambient pressure, when considering water pipework shall be kept constantly full of water
supply at low water level. even where there is leakage from the foot valve
referred to in F 9.6.2.3. Should the water level
Where more than one pump is provided the
in the tank fall to two-thirds of the normal level,
suction pipes may only be inter-connected if
the pump shall start.
they are fitted with stop valves to allow each
pump to continue operating when the other If the supply to the priming tank is taken from
is removed for maintenance. The connections the town main forming a supply to the sprinkler
shall be dimensioned as appropriate for the installation, the connection shall be made
flow rate required. upstream of the non-return valve on the town
main connection.
9.6.2.3 Suction lift conditions The size of the priming tank and the pipe shall
The diameter of the suction pipe shall be no be in accordance with tablet 9.6.2.4a.
less than 80 mm. Furthermore, the diameter
shall be such that a velocity of 1.5 m/s is not Table T.9.6.2.4a: Pump priming tank capacity
exceeded when the pump is operating at flow and pipe size
defined in table T9.6.2.1a equal to 1.4 × Q100. Hazard class Minimum Minimum
This velocity may be increased to 2.5 m/s, if tank capacity diameter of
the pressure in the suction pipe is not more l priming pipe
than 0.4 bar below ambient pressure, when mm
considering water supply at low water level. LH 100 25
Where there is more than one pumpset OH, HHP and 500 50
HHS
installed, the suction pipes shall not be
interconnected.
The height from the low water level (see 8.3.5) 9.7 Performance
to the centre line of the pump shall not exceed characteristics
3.2 m.
The suction pipe shall be positioned in the 9.7.1 General
tank or reservoir in accordance with figure F The closed valve pressure shall not exceed 12
8.3.5a and table T 8.3.5a or figure F 8.4.1b and bars.
tableT8.4.1a, as appropriate. A foot valve shall
In suction lift condition, the NPSH required by
be fitted at the lowest point on the suction
the pump shall not exceed 5 m at flows up to
pipe. Each pump shall have automatic priming
that defined in table T 9.7.1a.
arrangements in accordance with 9.6.2.4.
In positive head condition, no limitation is
9.6.2.4 Pump priming for suction lift given to the NPSH required by the pump as
long as the requirement of clause 9.6.2.1 is
Each pump shall be fitted with a separate fulfilled.
automatic priming arrangement.
The arrangement shall consist of a tank situated 9.7.2 Pre-calculated systems
at a higher level than the pump and with a pipe - LH and OH
connection sloping from the tank to the delivery Where the pumps take water from a storage
side of the pump. A non-return valve shall be tank, the characteristic of pre-calculated
fitted to this connection. Figure F 9.6.2.4a LH and OH systems shall conform to table
shows two examples. T 9.7.2a.
12
5 3
4
6 7 L
2/3L
8 14 15
10
2
11
A
3
5 4
13
6 L
2/3L
1. Test and drain valve
2. Pump air bleed and min. flow line 8
3. Pump priming tank 14 15
4. Infill 2 10
5. Overflow
6. Drain valve 9
7. Low level switch for pump starting
8. Priming supply stop valve
9. Priming supply check valve
10. Pump start arrangement
11. Suction tank
12. Installation trunk main
13. Low level valve for pump starting 1
14. Pressure switches for pump starting
15. Pressure gauge B
9.7.3 Pre-calculated systems - HHP and to run until stopped manually. Where one of
HHS with no in-rack sprinklers the pumpsets is electric motor driven this shall
be the first to start.
The nominal pump flow and pressure for HHP
and HHS pre-calculated systems shall conform 9.7.6.3 Testing the pressure switches
to 6.3.2. In addition the pump shall be capable
of supplying 140% of this flow at a pressure of Means shall be provided for testing each
no less than 70%. pressure switch. If any isolating valve is installed
on the connection between the trunk main
and any pump starting pressure switch, a back
9.7.4 Calculated systems pressure valve shall be installed in parallel with
The pump shall provide a pressure at least the isolating valve so that a fall in pressure
0.5 bar higher than that required for the most on the trunk main will be transmitted to the
unfavourable area at lowest water level. (see pressure switch even when the isolating valve
annex H). is closed.
In addition the pump shall be capable of
supplying 140% of Q100 flow at a pressure of no
9.8 Electrically driven
less than 70%.
pumpsets
premises and where this is not permitted, by a 9.8.4 Installation between the main
connection from the main switch. switchboard and the pump
controller
The fuses in the pump controller shall be of high
rupturing capacity, capable of carrying the stalled 9.8.4.1 The current for calculating the correct
motor current for a period of not less than 75% dimension for the cable shall be determined by
of the time needed for the motor windings to taking the largest possible full load current and
fail and thereafter be able to carry the normal adding 50%. The cable shall furthermore be able
current plus 100% for a minimum of 5 hours. to carry the largest possible starting current for
10 seconds.
9.8.2.2 All cable shall be protected against
fire and mechanical damage. The protection
shall be accepted by the authorities. 9.8.5 Pump controller
NOTE 1: all wiring associated with the electric motor 9.8.5.1 The pump controller shall be able:
driven pump, including the monitoring circuits,
should be in accordance with the appropriate a) to start the motor automatically on receiving
regulations for electrical installations. To protect a signal from the pressure switches;
cables from direct exposure to fire they should be b) to start the motor manually;
run outside the building or through those parts of
c) to stop the motor by manual operation only.
the building where the fire risk is negligible and
The controller shall be equipped with an
which are separated from any significant fire risk
ammeter.
by walls, partitions or floors with a fire resistance
of not less than 60 min, or they should be given
9.8.5.2 Except in the case of submersible
additional direct protection.
pumps, the pump controller shall be situated
NOTE 2: it is strongly recommended that the cable in the same room (pump room) as the electric
be buried. motor and pump. In the case of submersible
pumps a duplicate plate with its characteristics
9.8.3 Switchboard shall be affixed to the pump controller.
9.8.3.1 The switchboard for the premises
shall be situated in a fire compartment used
9.8.5.3 Contacts shall comply with
for no other purpose than for electrical power
utilisation category AC-3 of 60947-1 and EN
supplies, any other location shall be approved 60947-4.
by the authorities.
The electrical connections in the main
9.8.6 Monitoring of pump operation
switchboard shall be such that the supply to the 9.8.6.1 The following conditions shall be
pump controller is not isolated when isolating monitored:
other services.
– power available to the motor on all three
9.8.3.2 Each switch on the dedicated phases;
power feed to the sprinkler pump shall be – pump on demand;
labelled:
– pump running.
SPRINKLER PUMP MOTOR SUPPLY - NOT TO
BE SWITCHED OFF IN THE EVENT OF FIRE 9.8.6.2 All monitored conditions shall be
The letters on the notice shall be at least 10 mm visually indicated individually in the pump
high and white on a red background. room.
They should also be visually and audibly indicated a pressure reducing device if necessary,
at a location normally attended by responsible in accordance with the manufacturer’s
personnel. specification. The outlet pipe shall be open
so that the discharge water is visible;
9.8.6.3 The visual fault indication shall be b) a heat exchanger, where the water is taken
yellow. The audible signals shall have signal
from the sprinkler pump via a pressure
strength of at least 75dB and shall be able to be
reducing device if necessary, in accordance
silenced.
with the manufacturer’s specification.
The outlet pipe shall be open so that the
9.8.6.4 A lamp test for checking the signal discharge water is visible. The water in
lamps shall be provided. the closed circuit shall be circulated by an
auxiliary pump driven by the engine. If the
9.9 Diesel engine driven auxiliary pump is belt driven, there shall be
pumps multiple belts such that even if half the belts
are broken, the remaining belts are able to
9.9.1 General drive the pump. The capacity of the closed
circuit shall conform to the value specified
A diesel engine shall be capable of operating
by the engine manufacturers;
continuously at full load at site elevation with
a rated output in accordance with ISO 3046- c) an air cooled radiator with a fan multiple
1:2002. belt driven from the engine. If half the belts
The pump shall be fully operational within should break, the remaining belts shall be
15 seconds of the beginning of any starting capable of driving the fan. The water in
sequence. Horizontal pumps shall have a direct the closed circuit shall be circulated by an
drive. auxiliary pump driven by the engine. If the
auxiliary pump is belt driven, there shall be
The automatic start and operation of the multiple belts such that even if half the belts
pumpset shall not depend on any energy are broken, the remaining belts are able to
sources other than the engine and its batteries. drive the pump. The capacity of the closed
circuit shall conform to the value specified
9.9.2 Engines by the engine manufacturers;
The engine shall be capable of starting at an d) direct air cooling of the engine by means
engine room temperature of 5°C. of a multiple belt driven fan. When half the
It shall be provided with a governor to belts are broken the remaining belts shall be
control the engine speed to ± 5% of its rated capable of driving the fan.
speed under normal load conditions, and be Where cooling water is taken from the pump
constructed so that any mechanical device fitted in quantities exceeding 2% of the maximum
to the engine which could prevent the engine calculated system demand rate, the flow
starting automatically, will return to the starting shall be taken into account in the system
position. calculations.
9.9.5 Exhaust system that the starter motor and batteries may be
common to the two systems.
The exhaust pipe shall be fitted with a suitable
silencer and the total back pressure shall not It shall be possible to start the diesel engine
exceed the engine-maker’s recommendation. both automatically, upon receipt of a signal
from the pressure switches, and manually
Where the exhaust pipe is higher than the engine,
by means of a push button on the pump
means shall be provided to prevent any condensate
controller. It shall be possible to shut down
flowing back to the engine. The exhaust pipe shall
the diesel engine only manually. Engine
be positioned in such a way as to prevent exhaust
monitoring devices shall not cause the engine
gases from re- entering the pump room.
to stop.
9.9.6 Fuel, fuel tank and fuel feed pipes The rated voltage of the batteries and starter
motor shall be no less than 12 V.
The quality of the diesel fuel used shall conform
to the engine-maker’s instructions. The fuel The starter motor and each battery power
tank shall contain fuel oil sufficient to enable the source shall have the design capacity to rotate
engine to run on full load for: the engine at 0°C and 760 mmHg atmospheric
– 3 hours for LH; pressure for not less than 10 cycles each of
not less than 15 s cranking and not more than
– 4 hours for OH; 10 s rest. At the end of the energised part
– 6 hours for HHP and HHS. of each cycle the engine cranking speed shall
The fuel tank shall be of welded steel. Where be not less than 120 r/min while power is
there is more than one diesel driven pumpset, applied.
there shall be a separate fuel tank and fuel feed
pipe for each engine. 9.9.7.2 Automatic starting system
The fuel tank shall be fixed at a higher level than The automatic starting sequence shall make
the motor’s fuel pump to ensure a positive head, six attempts to start the engine, each one of
but not directly above the engine. The fuel tank 5 to 10 s duration, with a maximum pause
shall have a sturdy fuel level gauge. of 10 seconds between each attempt. The
Any valves in the fuel feed pipe between the fuel starting device shall reset itself automatically.
tank and the engines shall be placed adjacent to It shall function independently of the line
the tank, have an indicator and be locked in the power supply.
open position. Pipe joints shall not be soldered. The system shall switch over automatically to the
Metallic pipes shall be used for fuel lines. other battery after each starting attempt. The
The feed pipe shall be situated at least 20 mm control voltage shall be drawn from both batteries
above the bottom of the fuel tank. A drain valve simultaneously. Facilities shall be provided to
of at least 20 mm diameter shall be fitted to the prevent one battery having an adverse effect on
base of the tank. the other.
The fuel tank vent should be terminated outside
9.9.7.3 Emergency manual starting
the building.
system
9.9.7 Starting mechanism Emergency manual start facilities, with starting
power available from both batteries, shall be
9.9.7.1 General
provided, with a breakable cover. Facilities shall
Automatic and manual starting systems shall be provided to prevent one battery having an
be provided and shall be independent except adverse effect on the other.
9.9.7.4 Test facility for manual starting mechanical speed sensor. Pressure switches,
system for example on the engine lubrication system or
water pump outlet, shall not be used as a means
A manual start test button and indicator lamp of de-energising the starter motor.
shall be provided to permit periodic testing
of the manual electric start system without Centrifugal speed switches or voltage generators
breaking the cover over the emergency manual used for sensing shall have a direct coupling to,
start facilities button. The starter panel shall be or be gear-driven by, the engine; flexible drives
marked, adjacent to the lamp, with the wording: shall not be used.
shall be suitable for local conditions (climate, at the rated flow given in Table T 9.6.2.1a. The
regular maintenance, etc.). following shall be recorded on the test certificate:
A boost charge facility shall be provided for a) the engine speed with the pump churning;
charging to a higher voltage not exceeding 1.75 V b) the engine speed with the pump delivering
per cell. The charger output shall be between water at the rated flow;
25% and 167% of the 5 h capacity of the battery.
c) the pump churning pressure;
9.9.10 Sitting of batteries and chargers d) the suction head at the pump inlet;
Batteries shall be mounted on stands or stillages. e) the pump outlet pressure at the rated flow
NOTE: the chargers may be mounted with the downstream of any outlet orifice plate;
batteries. Batteries and chargers should be located f) the ambient temperature;
in readily accessible positions where the likelihood of
g) the cooling water temperature rise at the
contamination by oil fuel, damp, pump set cooling
end of the 1.5 h run;
water, or of damage by vibration is minimal. The
battery should be as close as possible to the engine h) the cooling water flow rate;
starter motor, subject to the above constraints, in i) the lubrication oil temperature rise at the
order to minimise voltage drop between the battery end of the test run;
and starter motor terminal.
j) where the engine is fitted with a heat
9.9.11 Starter alarm indication exchanger, the initial temperature and the
temperature rise of the engine closed circuit
The following conditions shall each be indicated cooling water.
both locally and at a responsibly manned location
by both a red warning light and an audible alarm: 9.9.13.2 Site commissioning test
a) the use of any switch which prevents the When commissioning an installation the
pump starting automatically; automatic starting system of the diesel engine
b) the failure of the engine to start by the end driven pump set shall be activated with the
of the six cyclic attempts; fuel supply isolated for the six cycles each or
not less than 15 s cranking and not more than
c) pump running.
15 s or less than 10 s rest. After completion of
The warning lights shall be appropriately marked. the six starting cycles the fail to start alarm shall
operate. The fuel supply shall than be restored
9.9.12 Tools and spare parts and the pump set shall start when the manual
start test button is operated.
A standard kit of tools and spare parts as
recommended by the engine and pump
manufacturers shall be provided.
10 INSTALLATION TYPE
9.9.13 Engine tests and exercising AND SIZE
Engine tests and exercising shall be as follows: 10.1 Wet pipe installations
there is no possibility of frost damage, and where shall be electrically monitored and triggered by
the ambient temperature will not exceed 95°C. separate temperature sensors.
Only wet pipe installations shall be used for grid The trace heating system shall be monitored for
and loop systems. power supply failure and failure of the heating
elements or sensors.
Table T 10.1.1a: Maximum number of sprinklers per For subsidiary dry pipe or alternate extensions,
installation - wet pipe and pre-action installations see 10.5.
Hazard class Maximum number For antifreeze installation and extension see
of sprinklers 10.1.2.2
LH 500
OH, including any LH 1 000, except as allowed 10.1.2.2 Antifreeze installation
sprinkler in Annexes D and F
HH, including any OH 1 000 10.1.2.2.1 General
and LH sprinklers An antifreeze installation is defined as an
automatic sprinkler installation in which the
entire installation downstream the alarm valve
10.1.2 Protection against freezing is charged with an anti-freeze solution.
10.1.2.1 General In some countries authority may apply additional
restrictions for the application of antifreeze
Pipework subject to freezing shall be protected installation.
by anti-freeze liquid or electrical trace heating
or subsidiary dry pipe or alternate extensions. The anti-freeze solution, followed by water,
discharges immediately upon actuation of the
An anti-freeze solution shall be prepared with sprinkler heads.
freezing point below the expected minimum
From a hydraulic calculation point of view the
temperature for the locality (see clause 18.3.3).
anti-freeze installation is considered as a wet
In the case of a trace heating system, the system.
piping shall be provided with non-combustible
Authority may require a complementary
insulation. The piping shall be provided with
hydraulic calculation based on the Darcy-
a Euroclass A1 or A2 or equivalent in existing
Weisbach formula.
national classification systems insulation of not
less than 25 mm thick with a water resistant An anti-freeze solution shall have a freezing
covering. All ends shall be sealed to prevent point at least 5°C below the minimum expected
ingress of water. Trace heating tape shall have a temperature including the temperature of
maximum rating of 10 W/m. incoming cold air.
At least a single heating system shall be provided Attention shall be paid to the historical lowest
over the complete length of the affected temperature.
pipework when the pipe work supplies no more
than 20 sprinklers. 10.1.2.2.2 Type of Anti-Freeze solution
Duplicate heating systems shall be provided The antifreeze solutions shall be accepted by
over the complete length of the affected the authority and the following criteria’s shall be
pipework when the pipe work supplies more taken into account:
than 20 sprinklers. Even in the case of a failure t The physical characteristics of anti-
of one of the two heating systems a minimum freeze solutions depends on the additive
temperature of 4°C shall be maintained. Circuits components that are introduced by
manufacturers like anti-corrosion or anti- t The pipe work shall be arranged with
bactericide additive, so the checking and adequate slope for drainage to the
replacement of the antifreeze solution has collection reservoir.
to be made according to the manufacturer t A jockey pump connected to the anti-
requirements; freeze solution reservoir. The start
t When necessary anti-freeze solution shall pressure of the anti-freeze jockey pump
include anti-corrosion or anti-bactericide shall be at least 0.5 bar above that of the
additive; water jockey pump. This anti-freeze jockey
t Acceptable anti-freeze solutions are pure pump is aimed to maintain the pressure in
glycerine, water based solution of ethylene the pipe work and to refill the sprinkler
glycol, water based solution of propylene pipe work after mixing.
glycol;
10.1.2.2.4 Design criteria
t For ethylene glycol and propylene glycol,
the concentration of glycol shall not exceed t For HHS the design density shall be increased
30% in general rule; by 10%.
t Attention shall be paid to the local NOTE: consideration should be given to the use
environmental and health regulations; of sprinklers with a K factor of 160 in order to
accelerate the release of pure water.
t The compatibility with sprinkler system
components; 10.1.2.2.5 System design
t Galvanised surfaces are not compatible Whenever possible, upright sprinklers shall be
with propylene glycol; used. If not possible pendant sprinkler shall be
t Flammable liquids shall not be used; installed in such a way that water cannot be
trapped in the drop pipe to the sprinkler.
t The anti-freeze solution shall be suitable
under non-circulating conditions; Grid system is not allowed.
t Except in case of fire, attention shall be paid In order to limit the pressure variation in the
to environmental protection especially pipe work, relief valves according to clause 13.8
during tests; shall be provided.
This mixing device includes: When some parts of the pipe work cannot be
drained by gravity directly to the anti-freeze
t An anti-freeze collection reservoir collection reservoir, a mobile tank shall also be
constructed of material compatible with provided to collect the solution in low points.
the anti-freeze solution. This reservoir shall
at least have the capacity of the volume The antifreeze jockey pump shall be connected
of the pipe work in the largest antifreeze directly downstream the alarm check valve.
installation, plus a sufficient volume of anti- The alarm valve trim used for antifreeze
freeze solution to supply the jockey pump. installation is similar to the wet alarm valve
An alarm shall be provided when the level trim. Device or mean (eg. Non return valve and
in the reservoir is below 300 l. stop valve downstream the alarm valve) shall be
provided to ensure that the amount of water A permanent air/inert gas supply to maintain the
mixing with antifreeze solution will be limited as pressure in the pipe network shall be installed.
much as possible at weekly tests. The installation shall be pressurised to within
If the following is fulfilled, a specific alarm the pressure range recommended by the alarm
valve is not required and the pipe work under valve manufacturer.
antifreeze can be connected downstream an Dry pipe installations shall only be installed where
alarm valve as an extension. there is a possibility of frost damage or the
t The size of any one anti-freeze extension temperature exceeds 95°C, e.g. in drying ovens.
shall not exceed 20 sprinklers.
t The total number of sprinklers on anti-freeze
10.2.2 Sprinkler orientation
extensions shall not exceed 100 sprinklers All sprinklers in a dry pipe installation shall be fitted
per alarm valve. in the upright position, except where dry pendent
or horizontal sidewall sprinklers are used.
10.1.2.2.6 Control and maintenance
Once a year the pipe work shall be drain to the 10.2.3 Size of installations
collection reservoir for homogenisation.
The net volume of the pipework downstream
The control of the protection level of the solution of the control valve set shall not exceed that
against freezing shall be made at that occasion shown in Table T 10.2.3a.
by measuring anti-freeze concentration.
In addition, the maximum time between a single
The pH level and the alkaline level shall be sprinkler opening and water discharging shall
checked according to the limit given by the not exceed 60 seconds for HH, and shall not
manufacturer. When necessary, the anti-freeze exceed 90 seconds for LH and OH.
solution shall be completed or replaced.
NOTE: it is strongly recommended that dry and
alternate installations should not be used for HHS
10.1.3 Sprinkler orientation
applications, since the delay in water reaching the
Where possible the sprinklers shall be fitted first operating sprinklers could seriously impair the
in the upright position to avoid mechanical effectiveness of the system.
damage and the collection of foreign matter in
the sprinkler fittings and to make it easier to Table T 10.2.3a: Maximum size per installation -
drain the pipe network. Dry and alternate installations
Maximum
10.1.4 Size of installations volume of pipe
work (m3)
The number of sprinklers to be controlled by
a wet alarm valve, including any sprinklers in Without accelerator or exhauster 1.5
a subsidiary extension, shall not exceed that With accelerator or exhauster 4.0
shown in Table T 10.1.1a.
of the alternate or dry alarm valve is charged with response of the detectors, a pressure drop in the
air or inert gas under pressure and the remainder pipework causes the opening of the alarm valve.
of the installation upstream of the alarm valve NOTE: type B pre-action installations may be
with water under pressure. At other times of installed wherever a dry pipe system is called for
the year the installation operates as a wet pipe and the spread of fire is expected to be rapid, e.g.
installation. in high-rack storage. They may also be used instead
of ordinary dry pipe systems with or without an
10.3.2 Sprinkler orientation accelerator or exhauster.
All sprinklers in an alternate installation shall be
fitted in the upright position, except where dry 10.4.2 Sprinkler orientation
pendent or horizontal sidewall sprinklers are used.
In Type A installations sprinklers shall be installed
in the upright position or, only in a frost proof
10.3.3 Size of installations
building, in the up-right or pendent position. In
The net volume of the pipework downstream Type B installations, sprinklers shall be installed
of the control valve set shall not exceed that in the upright position.
shown in Table T 10.2.3a.
10.4.3 Automatic detection system
10.4 Pre-action installations The detection system shall be installed in all
10.4.1 General rooms and compartments protected by the
pre-action sprinkler system and shall comply
Pre-action installations are divided into two types: with the relevant parts of EN54.
11 SPACING AND LOCATION The maximum distance from walls and partitions
OF SPRINKLERS to the sprinklers shall be the smallest value
applicable from the following list:
11.1 General – 2.0 m for standard spacing;
– 2.3 m for staggered spacing;
11.1.1 All measurements of sprinkler spacing
shall be taken in the horizontal plane – 1.5 m where the ceiling or roof is open joisted
except where otherwise specified in or the rafters are exposed;
these rules. – 1.5 m from the open face of open faced buildings.
Table T 11.2a: Maximum coverage and spacing for sprinklers other than sidewall
0.5S
0.25S1
0.75S1
S
S1
S1
S
0.5S1
0.5S D1 D1 0.5D1
D D
0.5D 0.5D 0.5D1
11.4.2 Distance from ceiling The distance from girders or beams to the
sprinklers shall be at least 0.2 m, or alternatively
Sprinklers shall wherever possible be situated sprinklers may be positioned directly above
with the deflector between 0.075 m and 0.15 m a girder or beam non wider than 0.2 m at a
below the ceiling or roof except when they are vertical distance of at least 0.15 m.
fitted in underdrawn ceilings. Where this is not
practicable sprinklers may be installed at lower Where narrow bays are formed between beams
levels provided that the figures given in 11.4.6 spaced at not more than 1.5 m between centres,
are adhered to and that the height b is the one of the following solution can be used:
maximum possible. a) In non combustible construction it is
Sprinkler shall never be installed lower than 0.3 m accepted to have the heat sensitive element
below the underside of combustible ceilings or of the sprinklers at a distance from ceiling
0.45 m below non-combustible roofs or ceilings. exceeding 0.45 m, providing that beams
Where circumstances make it unavoidable to create closed spaces with a maximum length
use the maximum distances of 0.3 m and 0.45 m, of 20 m. If the distance of 20 m is exceeded,
the area involved shall be as small as possible. smoke curtains that have the same depth as
the beams shall be installed in such a way that
11.4.3 Slope of rooms these closed spaces have similar volumes
and are evenly spaced. Sprinklers shall be
Sprinklers shall be installed with their deflectors placed as close as possible to the ceiling in
parallel to the slope of the roof or ceiling. respect with figure F 11.4.6a and T 11.4.6a.
Where the slope is greater than 30° a row of
sprinklers shall be fixed at the apex or not more
than 0.75 m radially there from.
11.4.4 Canopies d
b
The distance from the edge of a canopy to the
sprinklers shall not exceed 1.5 m.
11.4.5 Skylights a
the beams and no greater than 1.5 m from 0.1 m wide. If the width is greater than 0.1 m the
walls perpendicular to the beams; minimum distance shall be 0.6 m. Alternatively
– sprinklers installed inside bays shall sprinklers may be positioned directly above a
be placed such that the deflectors are truss no wider than 0.2 m at a vertical distance
between 0.075 m and 0.15 m below the of at least 0.15 m.
underside of the ceiling.
11.4.8 Columns
11.4.7 Roof trusses
If roof or ceiling sprinklers are placed closer than
Sprinklers shall be located at least 0.3 m laterally 0.6 m to one side of a column, another sprinkler
from truss members which are no more than shall be placed within 2 m from the opposite side.
≤ 1.5 m 1
2
≤ 1.5 m
Plan view
≤S
Key
1. Ceiling
2. Wall
Minimum horizontal distance Maximum height of sprinkler deflector (d) above (+) or below (-)
from sprinkler vertical axis to bottom of beam or joist (b in figure F 11.4.6a) (m)
side of beam or joist
(a in figure F 11.4.6a)
Conventional sprinkler Spray sprinkler
M Upright Pendent Upright Pendent
0.20 -0.20 not allowed -0.02 -0.02
0.40 0.00 not allowed 0.00 0.00
0.60 0.03 not allowed 0.02 0.06
0.80 0.06 not allowed 0.03 0.12
1.00 0.10 -0.20 0.05 0.20
1.20 0.14 -0.17 0.10 0.28
1.40 0.19 -0.12 0.13 0.36
1.60 0.26 -0.03 0.16 0.47
1.80 0.39 0.17 0.18 0.67
NOTE: dimensions may be interpolated
11.4.9 Platforms, ducts etc. has been shown not to impair sprinkler
protection.
Sprinklers shall be provided under platforms,
ducts, heating panels, galleries, walkways etc. Where sprinklers are fitted below suspended
which are: ceilings, the ceiling material shall be of a type
which has been shown not to be subject to
a) rectangular, more than 0.8 m wide and less
partial collapse under incipient fire conditions.
than 0.15 m from adjacent walls or partitions;
b) rectangular and more than 1.0 m wide; 11.4.13 Suspended open ceilings
c) circular, more than 1.0 m in diameter and Suspended open ceilings, i.e. ceilings having
less than 0.15 m from adjacent walls or
a regular open cell construction recurring
partitions;
throughout their design, may be used beneath
d) circular and more than 1.2 m in diameter. LH and OH sprinkler systems not involving
storage areas where the following conditions
11.4.10 Escalators and stair wells are met:
The number of sprinklers shall be increased – the total plan open area of the suspended
around the ceiling opening formed by escalators, open ceiling, including light fittings, shall not
stairs etc. Sprinklers shall not be more than be less than 70% of the ceiling plan area;
2 m nor less than 1.5 m away from each other.
If, owing to the design of the structure, e.g. – the minimum dimension of the ceiling
girders, the minimum distance of 1.5 m cannot openings shall be no less than 0.025 m
be maintained, smaller spacing may be used or no less than the vertical thickness of
provided adjacent sprinklers are not able to wet the suspended ceilings, whichever is the
each other. greater;
The horizontal distance between the sprinklers – the structural integrity of the ceiling and any
and the opening in the ceiling shall not exceed other equipment, such as light fittings within
0.5 m. The sprinklers in the region of the the volume above the suspended ceiling, shall
opening shall be capable of providing the not be affected by operation of the sprinkler
minimum flow rate for sprinklers in the rest of system.
the ceiling protection. For hydraulic calculation
Sprinklers shall be installed as follows:
purposes, only the sprinklers on the longer side
of the opening need be considered. – sprinkler spacing above the ceiling shall not
exceed 3 m;
11.4.11 Vertical shafts and chutes – vertical separation between any conventional
At least one sprinkler shall be installed at the or spray sprinkler deflector and the top of the
top of all shafts except where the shaft is suspended ceiling shall not be less than 0.8 m.
incombustible and inaccessible and contains no This distance may be reduced to 0.3 m if flat
combustible materials except electrical cabling. spray sprinklers are used;
In shafts with combustible surfaces, sprinklers – supplementary sprinklers shall be provided
shall be installed at each alternate floor level and to discharge below light fittings or similar
at the top of any trapped section. obstructions exceeding 0.8 m in width.
Where obstructions within the ceiling void are
11.4.12 Ceiling obstructions
likely to cause significant interference of the
The use of suspended ceiling material below water discharge they shall be treated as walls
the sprinklers is not allowed unless the material for the purpose of sprinkler spacing.
Sprinkler
Sprinkler row
row
Tiers
Tiers
Aisle Aisle
Longitudinal flue Transverse flue Longitudinal flue Transverse flue
staggered with respect to the next highest row b) Single row racks more than 1.6 m wide and
(see Figure F 11.5a). The horizontal distance not more than 3.2 m wide shall be protected
between sprinklers shall not exceed 3.75 m and by a single row of sprinklers fitted in the
the product of the horizontal distance and the middle of the rack tier levels. Sprinklers shall
vertical distance between sprinklers shall not be fitted at every 2nd transverse flue space
exceed 9.8 m2. for Cat. I and II and at every transverse flue
In the case of Category III or IV goods, space for Cat. III and Cat. IV.
sprinklers shall be installed in the longitudinal The maximum vertical distance between
flue at the intersection with each transverse flue sprinklers shall be as stated in clause 11.5.2.
(see Figure F 11.5.1b). The horizontal distance
c) For single row racks of more than 3.2 m
between sprinklers shall not exceed 1.9 m and
width, authority shall be consulted.
the product of the horizontal distance and the
vertical distance between sprinklers shall not
11.5.5.2 Double row rack
exceed 4.9 m2.
a) Double row racks no more than 3.2 m wide
11.5.4 Numbers of rows of sprinklers at shall be protected by sprinklers centrally in
each level the longitudinal flue space at the tier levels
shown in Figures F 11.5.1a and F 11.5.1b;
The number of sprinkler rows per level shall be
determined by the total width. When racking The maximum vertical distance between
is placed back to back the total width shall be sprinklers shall be as stated in clause 11.5.2.
calculated by adding together the width of each The maximum horizontal distance between
rack and the distance between them. sprinklers shall be as stated in clause 11.5.3.
1 row of sprinklers per level shall be installed b) Double row racks more than 3.2 m wide, but
for every 3.2 m of rack width. They shall be not more than 6.4 m wide shall be protected
installed in the flue spaces wherever possible. by two rows of sprinklers installed centred
over the respective load. The sprinklers at a
11.5.5 HHS intermediate sprinklers in particular level in each line shall be located in
non-shelved racks the same set of transverse flue spaces. The
When required (see 6.2.2 and table T 5.3.2a), sprinklers in the transverse flue spaces shall
intermediate sprinkler (in rack) sprinklers shall be arranged so that the maximum vertical
be provided for palletised rack storage and distance between two sprinklers is 7 m for
multiple row rack storage according to the cat I and II and 3.5 m for cat III and IV.
following: The vertical distance from the floor to the
lowest intermediate level and between levels
11.5.5.1 Single row rack
shall not exceed 3.50 m or two tiers, whichever
a) Single row racks not more than 1.6 m is the lesser.
wide shall be protected by single rows of Additionally, at a maximum vertical distance
sprinklers fitted on the side of the rack not of 7 m (between intermediate levels), the
used for access or in the middle of rack at longitudinal flue shall be protected by sprinklers
the tier levels. Sprinklers shall be fitted at every 2nd transverse flue space for category I and
every 2nd transverse flue space for Cat. I and II and every transverse flue space for category
II and at every transverse flue space for Cat. III and IV. It shall be ensured that the maximum
III and Cat. IV. distance between the top longitudinal flue in
The maximum vertical distance between rack protection and the top of storage is 3.5 m
sprinklers shall be as stated in clause 11.5.2. or less according to table T 6.2.3.2a.
Every 4 levels
with maximum 7 m
3.75 m
Every second level maximum
with maximum 3.5 m
3.75 m
maximum
Figure F 11.5.5.3a: Multiple-row racks HHS 1-2 with flue space in only one direction
Every 4 levels
with maximum 7 m
1.9 m
Every second level maximum
with maximum 3.5 m
1.9 m
maximum
Figure F 11.5.5.3b: Multiple-row racks HHS 3-4 with flue space in only one direction
11.5.5.4 Multiple row racks with longitudinal c) Multiple row racks HHS 4
and transverse flue spaces Multiple row rack configuration with longitudinal
In this type of configuration, the rack structure and transverse flue spaces in HHS 4 shall be
and the organisation of the storage are made submitted to authority.
so that longitudinal and transverse flue spaces d) For multiple row racks next to a wall (less than
exist. 700 mm from the wall) authority shall be con-
In this case the flue spaces shall be at least sulted. Consideration should be given to the in-
150 mm wide. stallation of supplementary sprinklers especially
if the wall is made of combustible material.
The figures F 11.5.5.4a and F 11.5.5.4b fix
the maximum distances between in rack ST4 movable rack storage configuration shall be
sprinklers. submitted to authority but can be interpolated
from this chapter 11.5.5.
a) Multiple row racks HHS 1 – 2
b) Multiple row racks HHS 3 11.5.6 HHS intermediate sprinklers
below solid or slatted shelves in
Sprinklers are arranged so that there is an in- racks (ST5 and ST6)
rack sprinkler at each intersection between
longitudinal and transverse flue space, at least Intermediate sprinklers shall provided above
every 7 m. each shelf (including the top shelf if the roof or
Every 4 levels
with maximum 7 m
Every second flue with
3.75 m maximum
Figure F 11.5.5.4a: Multiple-row racks HHS 1 - 2 with longitudinal and transverse flue spaces
Every 4 levels
with maximum 7 m
Every second flue with
1.9 m maximum
Figure F 11.5.5.4b: Multiple-row racks HHS 3 with longitudinal and transverse flue spaces
ceiling sprinklers are more than 4 m above the each row is the same distance from the nearest
goods or water access to the goods is restricted), shelf edge.
and located as shown in Table T 11.5.6a and The distance from the end of the shelf parallel
Figure F 11.5.6a. The vertical distance between to the range pipe lines to the nearest sprinkler
rows shall not exceed 3.5 m. shall be half the sprinkler spacing along the range
Single rows of sprinklers shall be central above lines or 1.6 m, whichever is the smaller.
shelves. Double rows shall be positioned so that
Sprinkler row
≤ 2.8 m
≤3m
equally spaced
Sprinkler
row ≤ 2.8 m
equally spaced
≤ 2.8 m
≤6m
12.2.1 General
12.2.5.1 Extended coverage sidewall sprinkler
Sprinklers shall be used for the various hazard
Extended coverage sidewall sprinklers may be
classes in accordance with Table T 12.2.1a, and
used in LH and OH1 hazards. They may be
as specified in 12.2.2 to 12.2.4.
used in rooms, which have a maximum area of
12.2.2 Ceiling or flush, recessed and 126 m2, a fire resistance of the compartment
concealed sprinklers of at least 30 minutes, a smooth ceiling and
a maximum ceiling height of 4.1 m. In one
Flush, recessed and concealed sprinklers shall area only, sprinklers with identical response
not be installed in, HHP or HHS areas. sensitivity class may be used.
Flush, recessed and concealed sprinklers shall The area per sprinkler must not exceed 21 m2. In
not be installed in OH4 areas except: rooms with a maximum width of 6.5 m, only one
– Cinemas, row of extended coverage sidewall sprinklers
needs to be installed along the longitudinal wall.
– Theatres,
In rooms with a width of between 6.5 m and
– concert halls, 11 m, two rows of extended coverage sidewall
– Film (TV) studios, sprinklers must be installed along each of the
longitudinal walls. In this case, the sprinklers
– Exhibition halls,
must be installed staggered.
As long as the ceiling height doesn’t exceed 10 m.
The area of operation with extended coverage
Sprinklers without fixed deflectors, i.e. with sidewall sprinklers shall not be less than 126 m2.
retracted deflectors which drop to the operating
The minimum design pressure shall be 2.5 bar
position on actuation, shall not be fitted:
for ceiling heights up to 2.8 m and 3 bar for
a) where the ceiling is more than 45° from the ceiling heights between 2.8 m and 4.1 m.
horizontal;
The distance between two extended coverage
b) in situations where the atmosphere is sidewall sprinklers installed along the same wall
corrosive or likely to have a high dust content; shall be between 3 m and 4.5 m. Extended
c) in racks or under shelves. coverage sidewall sprinklers shall be installed
at a maximum distance of 300 mm from the
12.2.3 Sidewall pattern adjacent wall and at a distance of 100 mm to
250 mm from the ceiling. Extended coverage
Sidewall sprinklers shall not be installed in HHP
sidewall sprinklers shall be installed at a minimum
or HHS installations or above suspended ceilings.
horizontal distance of 0.5 m from corners.
They may only be installed under flat ceilings.
– The length of the dry shall be chosen according Under normal conditions in temperate climates
to the temperature in the cold room in order a rating of 68°C or 74°C is suitable.
to limit the risk of freezing due to heat transfer. In unventilated concealed spaces, under skylights
The table T12.2.6a gives the minimum lengths or glass roofs etc., it may be necessary to install
of the dry sprinklers that shall be exposed to sprinklers with a higher operating temperature,
positive temperature (outside the cold room). up to 93°C or 100°C. Special consideration shall
Table 12.2.6a: Minimum recommended lengths be given to the rating of sprinklers in the vicinity
between dry sprinkler fitting and the outside of drying ovens, heaters and other equipment
surface of cold room which gives off radiant heat.
NOTE: sprinklers are colour coded to indicate their
Cold room Minimum length
Temperature M temperature rating as follows:
0°C to – 29°C 0.3 Bulb: °C
– 30°C to – 40°C 0.45 – Orange 57 °C
– 41°C to – 51°C 0.6 – Red 68 °C
– Yellow 79 °C
– Green 93-100 °C
– Blue 121-141 °C
12.3 Flow from sprinklers – Mauve 163-182 °C
– Black 204-345 °C
The water flow from a sprinkler shall be
calculated from the following formula: Fusible link: °C
– Uncoloured 57-77 °C
Q=K P – White 80-107 °C
– Blue 121-149 °C
where: – Red 163-191 °C
Q is the flow in litres per minute; – Green 204-246 °C
– Orange 260-302 °C
K is the constant given in Table T 12.2.1.a; – Black 320-343 °C
P is the pressure in bar.
12.5 Sprinkler Thermal
12.4 Sprinkler temperature sensitivity
ratings
12.5.1 General
Sprinklers shall be chosen with a temperature
rating close to but no lower than 30°C above Sprinklers of different sensitivities shall be used
the highest anticipated ambient temperature. in accordance with T 12.5.1a.
Sensitivity rating in-rack Ceiling above in- Dry systems All others
rack sprinklers
Standard ’A’ No Yes Yes Yes
Special No Yes Yes Yes
Quick Yes Yes No Yes
NOTE 1: the sprinkler at the ceiling shall have a sensitivity equal to or of slower response than the sprinklers situated in the racks.
NOTE 2: most types of sprinklers are rated, in descending order of sensitivity, as one of the following types:
– quick response;
– special response;
– standard response ‘A’.
The sprinkler sensitivities rating are specified in EN 12259 part 1.
≥6 ≥6
0° 0°
≥6 ≥6
0° 0°
12.9 Corrosion protection of in such a way that no section shall include more
sprinklers than 4 control valve sets.
Flushing connections, with or without Pressure gauge scale divisions shall not exceed:
permanently installed valves, shall be fitted on a) 0.2 bar for a maximum scale value less than
the spur ends of the installation distribution or equal to 10 bar;
pipes. They shall:
b) 0.5 bar for a maximum scale value greater
– be at least DN50 and than 10 bar.
– in case of distribution pipes bigger than DN50 NOTE: the maximum scale value should be of the
be connected eccentrically at the bottom of order of 150% of the known maximum pressure to
the distribution pipe and be applied.
NOTE 2: When mechanical pipe joints are t The bending strength of the welded pipe
used, Minimum wall thickness shall also be joint shall be at least 80% of the pipe
in accordance with the joint manufactures’ bending strength;
recommendations. t If robot welding machines are used, the
welding operation shall be fully automatic.
15.1.3 Welding
Welders shall be approved in accordance with 15.1.4 Mechanical pipe joints
EN 287-1.
Mechanical pipe joints shall be approved.
Welded pipe and fittings less than DN 65 mm
in diameter shall be welded in the supplier 15.1.5 Flexible pipes and joints
factory.
If relative movement is likely to occur between
The company producing welding shall have a different sections of pipework within the
quality management system accepted by the sprinkler system, e.g. owing to expansion joints
authorities such as ISO 9001. or in the case of free-standing storage racking,
An accredited laboratory accepted by the a flexible section or joint shall be fitted at the
authorities shall check the following welding point of connection to the distribution main.
procedures and welding test pieces: Before installation it shall meet the following
requirements.
– Socket weld procedure: Welding of sockets
onto pipes smaller than DN 65 mm; a) it shall be capable of withstanding a test
pressure of four times the maximum
– Pipe weld procedure: Welding of pipes
working pressure or 40 bar, whichever is the
smaller than DN 65 mm including welding
greater, and shall not include parts which,
of pipes smaller than DN 65 mm onto larger
when subject to fire, might impair either the
dimensioned pipes.
integrity or the performance of the sprinkler
The quality management system shall include system;
the following main requirements:
b) Flexible pipes shall contain a continuous
t The welded joint shall be made according pressure-retaining stainless steel or non-
to EN 25817, quality class D “Arc-welded ferrous metal inner tube;
joints in steel – guidance on quality levels
c) Flexible pipes shall not be fitted in the fully
for imperfections”;
extended position.
t No debris shall be left inside the pipes
Flexible pipes and joints shall not be used to take
after the welding operation;
up misalignment between a distribution main
t The welded joint shall fully penetrate and the feed pipes to intermediate sprinklers.
the pipe wall if no evidence according to
EN 288 “specifications and approval of 15.1.6 Concealment
welding procedures for metallic materials”
is provided. The welded joint shall not Pipes shall be installed in such a way that they
intrude into the pipe more than: are easily accessible for repairs and alterations.
They shall not be embedded in concrete floors
a) 1 mm average; or ceilings.
b) 1.5 mm maximum. NOTE 1: Authorities may accept for risk no greater
t Welded connections shall not cause than OH3 category, the use of embed sprinkler
pressure losses higher than 105% of the piping in concrete, providing the system is certified
loss produced in standard fittings; for this application.
NOTE 2: wherever possible, piping should not racks or other structures. They shall not be
be installed in concealed spaces which make used to support any other installations. They
inspection, repairs and modifications difficult. shall be of the adjustable type in order to secure
an even load bearing capability. Supports shall
15.1.7 Protection against fire and completely surround the pipe and shall not be
mechanical damage welded to the pipe or fittings.
Piping shall be installed in such a way that the The part of the structure to which the supports
pipes are not exposed to mechanical damage. are secured shall be capable of supporting the
Where pipes are installed above gangways with pipework (see Table T 15.2a). Pipes greater than
low headroom, or at intermediate levels, or 50 mm diameter should not be supported from
in other similar situations, precautions shall be corrugated steel sheet or aerate concrete slabs.
taken against mechanical damage. Distribution pipes and risers shall have a
Where it is unavoidable for water supply pipework suitable number of fixed points to take account
to pass through an unsprinklered building, it shall of axial forces. No part of any support shall be
be installed at ground level and shall be enclosed made of combustible material. Nails shall not
by dwarf brick walls covered by concrete slabs. be used.
Supports for copper pipes shall be provided
15.1.8 Painting with a suitable lining with sufficient electrical
Non-galvanised ferrous pipework shall be resistance, in order to prevent contact
painted. Galvanised piping shall be painted corrosion.
wherever the coating has been damaged, e.g.
by threading. 15.2.2 Spacing and location
NOTE: extra protection may be needed for Supports shall generally be spaced no more
unusually corrosive conditions. than 4 m apart on steel pipe and 2 m apart
on copper pipe. For pipes of over 50 mm
15.1.9 Drainage diameter these distances may be increased
by 50% provided that one of the following
Mean shall be provided to enable all the pipework conditions is met:
to be drained. Where this cannot be done through
the drain valve at the control valve set, extra valves – 2 independent supports are fitted directly to
shall be fitted in accordance with 13.4. the structure;
In the case of dry, alternate and pre-action – a support is used which is capable of bearing
installations range pipes shall have a slope a load 50% greater than that called for in
towards the distribution pipe of at least 0.4% Table T 15.2a.
and distribution pipes shall have a slope towards When mechanical pipe joints are used:
the appropriate drain valve of at least 0.2%. – there shall be at least one support within lm
Range pipes shall only be connected to the side of each joint;
or top of distribution pipes. – there shall be at least one support on each
pipe section.
15.2 Pipe supports
The distance from any terminal sprinkler to a
15.2.1 General support shall not exceed:
Pipe supports shall be fixed directly to the – 0.9 m for 25 mm diameter piping;
building or, if necessary, to machines, storage – 1.2 m for piping greater than 25 mm diameter.
16.2.2 Signs for stop valves 4) the height of the highest sprinkler above
the level of the ‘C’ gauge;
A sign shall be fitted close to the main and any
5) the height difference between the ‘C’
subsidiary stop valves bearing the words:
gauge and the pump delivery pressure
‘SPRINKLER CONTROL VALVE’. gauge.
Any faults disclosed, such as permanent If it is required by the authorities. The user shall
distortion, rupture or leakage, shall be corrected have the test, service and maintenance schedule
and the test repeated. carried out under contract by the system
NOTE: if climatic conditions do not allow hydraulic installer or a similarly qualified company.
testing to be carried out immediately, it should be After an inspection, check, test service or
carried out as soon as conditions permit. maintenance procedure the system, and any
automatic pumps, pressure tanks and gravity
17.1.2 Equipment tanks shall be returned to the proper operational
condition.
The system shall be tested as specified in 18.3.2
and 18.4.2 (i.e. making the tests which will be NOTE: if appropriate, the user should notify
made on a routine weekly and quarterly basis) interested parties of the intent to carry out tests
and any faults shall be corrected. and/or of the results.
When an installation is rendered inoperative Before a system is wholly or partly shut down
the user shall implement the following every part of the premises shall be checked to
measures: ensure that there is no indication of fire.
a) the fire authorities shall be informed if the Where premises are subdivided into
alarm is connected to the fire brigade; separate occupancies constituting buildings
b) alterations and repairs to an installation or in communication or at risk, protected by
its water supply should be carried out during common sprinkler systems or installations, all
normal working hours; occupiers shall also be advised that the water is
to be turned off.
c) any hot work shall be subject to a permit
system. Smoking and naked lights shall Particular attention shall be given to
be prohibited in affected areas during the situations where installation pipework
progress of the work; passes through walls or ceilings where these
may feed sprinklers in areas needing special
d) when an installation remains inoperative consideration.
outside working hours all fire doors and fire
shutters shall remain closed; 18.1.3.3 Unplanned shut-down
e) fire extinguishing appliances shall be kept in
When an installation is rendered inoperative
readiness, with trained personnel available
as a matter of urgency or by accident, the
to handle them;
precautions in 18.1.3.1 shall be observed as far
f) as much as possible of the installation shall be as they are applicable with the least possible
retained in an operative condition by blanking delay. The authorities shall also be notified as
of pipework feeding the part or parts where soon as is possible.
work is taking place;
g) in the case of manufacturing premises, when 18.2 Action following sprinkler
the alterations or repairs are extensive, or it operation
is necessary to disconnect a pipe exceeding
40 mm nominal diameter, or to overhaul or 18.2.1 General
remove a main stop valve, alarm valve or Following shut-down after operation of an
check valve, every effort shall be made to installation, the operated sprinkler heads shall
carry out the work while the machinery is be replaced by heads of the correct type and
stopped; temperature rating, and the water supply
h) any pump which is out of commission shall restored. Unopened sprinklers around the area
be isolated by means of the valves provided. in which operation took place shall be checked
for damage by heat or other cause and replaced
NOTE: where possible parts of installations should
as necessary.
be reinstated to provide some protection overnight
by using blinders and blanks within the pipework; The water to an installation or zone of an
the blinders and blanks should be fitted with visible installation that has operated shall not be shut
indicator tags numbered and logged to aid timely off until all fire has been extinguished.
removal. The decision to shut down an installation or
zone which has operated because of fire shall
18.1.3.2 Planned shut-down be taken only by the fire service.
Only the user shall give permission for a Components removed from the system shall be
sprinkler installation or zone to be shut down retained by the user for possible examination
for any reason other than an emergency. by an authority.
18.3.2.3 Water motor alarm test 18.3.2.7 Fire brigade and remote central
station alarm connection
Each water motor alarm shall be sounded for
not less than 30 s and simultaneously the fire The equipment for automatic transmission of
brigade connection shall be checked. alarm signals from a sprinkler installation to a
18.3.2.8 Trace heating and localised heating 18.4.2.3 Sprinklers, multiple controls and
systems sprayers
Heating systems to prevent freezing in the Sprinklers, multiple controls and sprayers
sprinkler system shall be checked for correct affected by deposits (other than paint) shall be
function. carefully cleaned. Painted or distorted sprinkler
heads, multiple controls or sprayers shall be
18.3.3 Special consideration replaced.
Any petroleum jelly coatings shall be checked.
The specific gravity of the anti-freeze solution
Where necessary the existing coatings shall be
shall be verified quarterly for permanent cold
removed and the sprinklers, multiple controls or
storage and yearly, before winter for unheated
sprayers shall be coated twice with petroleum
areas.
jelly (in the case of glass bulb sprinklers to the
sprinkler body and yoke only).
18.4 Service and maintenance
schedule Particular attention shall be paid to sprinklers
in spray booths, where more frequent
18.4.1 General cleaning and/or protective measures may be
necessary.
18.4.1.1 Procedures
In addition to the schedule given in this clause
18.4.2.4 Pipework and pipe supports
any procedures recommended by component Pipework and hangers shall be checked for
manufacturers shall be carried out. corrosion and painted as necessary.
18.4.2.5 Water supplies and their alarms 18.4.3.2 Dry alarm valves
Each water supply shall be tested with each Dry alarm valves, and any accelerators and
control valve set in the system. The pump(s), exhausters, in dry pipe installations and subsidiary
if fitted, in the supply shall start automatically extensions shall be exercised in one of the
and the supply pressure at the appropriate flow following ways, as appropriate:
rate shall be not less than the appropriate value
a) the inspection cover plate shall be removed
in accordance with clause 9, recognising any
and the moving parts shall be operated
changes required by 18.4.2.2.
manually;
18.4.2.6 Electrical supplies b) if a screw-down diaphragm interlocking
key type subsidiary stop valve is fitted
The electrolyte level and density of all open downstream of the alarm valve, subsidiary
nickel-cadmium cells (including those in diesel stop valve shall be closed, the space between
engine starter batteries and those for control the dry pipe valve clack and the underside
panel power supplies) shall be checked. If the of the subsidiary valve shall be primed with
density is low the battery charger shall be water, and the installation drain valve shall
checked and if necessary repaired or replaced. be opened.
If the charger is working normally, the battery
or batteries affected shall be replaced. NOTE: alternate installations need not be tested in
this way since they are exercised twice a year as a
Any secondary electrical supplies from diesel result of the change-over from wet to dry operation
generators shall be checked for satisfactory and back.
operation.
18.4.4.5 Pump suction strainers At not more than 15 year intervals, all storage
tanks shall be drained, cleaned, examined
Pump suction strainers and settling chamber internally and the fabric attended to as
screens shall be inspected at least annually and necessary.
cleaned as necessary.
ANNEX A
Classification of typical hazards
Tables T Aa, T Ab and T Ac contain lists of also be used as guidance for occupancies not
minimum hazard classification. They shall specifically mentioned.
% by weight
30 of unexpanded plastic
15
5
material material material material
factor 1 factor 2 factor 3 factor 4
5 25 30 40
% by volume
of unexpanded plastic
Limit of application of Annex K7
Figure F B.2a: Material Factor
The following four material factors shall be used B.2.3 Material factor 3
in determining the category.
Materials which are predominantly unexpanded
B.2.1 Material Factor 1 plastic (see Figure F.B.2a) or materials of a
similar energy content.
Non combustible products in combustible
packaging and low or medium combustibility Examples:
products in combustible/non-combustible – electric cables on reels or in cartons;
packaging. Products having little plastic content
– synthetic fabrics
as defined below:
– accumulators without electrolyte;
– unexpanded plastic content less than 5% by
weight (including the pallet); – personal computers;
– expanded plastic content less than 5% – unexpanded plastic cups and cutlery.
volume. Examples:
– metal parts with /without cardboard B.2.4 Material factor 4
packaging on wood pallets; Materials which are predominantly expanded
– grain in sacks; plastic (more than 40% by volume) or materials
– canned foods; of similar energy content (see Figures F B.2a).
side of a single alarm valve with a bypass connec- any trunk main supplying the system has
tion of the same nominal bore around all three fallen to a value 0.5 bar or more below the
valves, fitted with a normally closed stop valve normal static pressure;
(see Figure F D.3.6a). Each of the three stop valves
e) by means of audible devices and red visual
shall be fitted with tamper proof devices to moni-
indicators that water is flowing into the
tor their status (i.e. fully open or not fully open).
installation;
D.3.7 Installation monitoring f) by means of audible devices and red visual
and alarms indicators that water is flowing into one or
more zones.
The monitoring devices required by D.3.4 and
D.3.6 shall be electrically connected to a control Facilities shall be provided at the indicator panel
and indicating panel, located on the premises, for silencing the audible alarms but the visual
where the following indications and warnings indicators shall continue to operate until the
shall be given: installation is restored to the normal standby
a) by means of green visual indicators that condition.
each monitored stop valve is in its correct Any change in the panel alarm or fault indication
operational position; after the audible alarm has been silenced shall
b) by means of audible devices and amber cause it to resume sounding until it is again
visual indicators that one or more control silenced or the panel reset to the normal
valve sets are not fully open; standby condition.
Test connection
Alarm devices
Downstream stop valves
Figure F D.3.6a: Control valve bypass arrangement for zoned multi-storey building installations
difference equivalent to the height of the highest E.3.4 Pump performance for pre-
sprinkler above the installation zone subsidiary calculated installations
stop valve.
Automatic pumps shall have characteristics in
E.3.3 Water supply characteristics for accordance with Table T 9.7.2a.
pre-calculated installations NOTE: pressures are taken at the pump outlet or
The water supply characteristics shall be the relevant stage of multi-stage pumps, on the
determined by a hydraulic calculation of the delivery side of any orifice plate.
pipework upstream of the zone subsidiary stop
valve outlet, at the higher and lower flow rates
specified in Table T 6.3.1a, and shall include
calculations at the water supply datum point.
1. Storage tank
2. Multistage pump
3. Flow meter
4. Water supply datum point
5. Alarm valve station
(with bypass arrangement)
6. Flow test and zone drainage
≤ 45 m
7. Zone subsidiary stop valve
8. Water flow alarm switch
9. Sprinkler head
10.Water flow alarm switch test
valve and zone drain valve
Valves in black
are normally closed
≤ 45 m
10
h
8
9
7
4
3
Figure F Ea: Typical layout of high rise system with pump supply
≤ 45 m
1
≤ 45 m
1. Storage tank
2. Multistage pump
3. Flow meter
4. Water supply datum point
10 5. Alarm valve station
(with bypass arrangement)
8 6. Flow test and zone
9
7 drainage
7. Zone subsidiary stop valve
6 8. Water flow alarm switch
9. Sprinkler head
5 10.Water flow alarm switch
test valve and zone drain
valve
4
3
6
Figure F Eb: Typical layout of high rise system with gravity tanks and booster pumps
One of the stop valves to the alarm valve to be – if water is not available, the stop valve shall be
serviced shall be closed and an alarm test (see opened immediately, and the fault rectified
18.3.2.3) carried out immediately on the other before proceeding.
alarm valve;
ANNEX G p = 0.098h
where:
Methods for sizing pipework
p is the static pressure difference, in bar;
G.1 Calculation of pressure h is the vertical distance between the
losses in pipework points, in metres.
– where the water flows join together at a increase in the direction of flow of water to any
junction, the calculation shall be balanced to sprinkler.
within 1 mbar;
– the algebraic sum of water flow at a junction G.2.1.2 Range pipe sizes and the maximum
shall equal 0 l/min +/− 0.1 l/min. number of sprinklers fed by each size of pipe in the
range shall be as specified in Tables T G.2.4.1a and
G.2 Pre-calculated systems G.2.4.1b, except in the case of Light Hazard, where
Table T G.2.31a specifies only the pipes feeding the
G.2.1 General last three or four sprinklers on each range.
G.2.1.1 Pipe sizes shall be determined partly
from the following tables and partly from G.2.1.3 The size of all pipes upstream of each
hydraulic calculations. Pipe diameters shall not design point shall be calculated as specified
Fittings and valves Equivalent length of steel straight pipe for a C value of 120°
m
Nominal diameter (mm)
20 25 32 40 50 65 80 100 125 150 200 250
90° screwed elbow 0.63 0.77 1.04 1.22 1.46 1.89 2.37 3.04 3.67 4.30 5.67 7.42
(standard)
90° welded elbow (r/d=1.5) 0.30 0.36 0.49 0.56 0.69 0.88 1.10 1.43 1.72 2.00 2.64 3.35
45° screwed elbow 0.34 0.40 0.55 0.66 0.76 1.02 1.27 1.61 1.96 2.30 3.05 3.89
(standard)
Standard screwed tee or 1.25 1.54 2.13 2.44 2.91 3.81 4.75 6.10 7.36 8.61 11.34 14.85
cross (flow through branch)
Gate valve - straight way - - - - 0.38 0.51 0.63 0.81 0.97 1.13 1.50 1.97
Alarm or back pressure valve - - - - 2.42 3.18 3.94 5.07 6.12 7.17 9.40 12.30
(swinging type)
Alarm or back pressure valve - - - - 12.08 18.91 19.71 25.46 30.67 35.88 47.27 61.85
(mushroom type)
Butterfly valve - - - - 2.19 2.86 3.55 4.56 5.47 6.38 8.62 9.90
Globe valve - - - - 16.43 21.64 26.80 34.48 41.64 48.79 64.29 84.11
These equivalent lengths can be converted as necessary for pipes with other C values by multiplying by the
following factors:
C value 100 110 120 130 140
Factor 0.714 0.850 1.000 1.160 1.330
in G.2.3.2 for Light Hazard and G.2.4.2 for G.2.2.2 In Light Hazard installations the design
Ordinary Hazard. point shall be located downstream of the
sprinkler identified in Table T G.2.2.3a column
G.2.1.4 Risers or drops, connecting 3.
distribution pipes to ranges, and pipes G.2.2.3 In Ordinary and High Hazard
connecting single sprinklers, other than arm installations the design point shall be located
pipes, shall be considered as distribution pipes downstream of the junction of distribution
and sized accordingly. pipes and range pipes in accordance with
Table T G.2.2.3b column 3.
G.2.2 Location of Design Points Where the number of sprinklers on one array
in a room, or on a single distribution pipe, is
G.2.2.1 The design point shall be located at the less than or equal to the number of sprinklers
point of connection of a horizontal distribution for which the distribution pipes are designed,
pipe to one of the following: indicated in Table T G.2.2.3b column 2, the
– a range pipe; design point shall be positioned downstream of
the point of connection to the distribution pipe
– a riser or drop connecting ranges to distribution
of the range or the array hydraulically nearest
pipes; to the control valve set.
– a pipe feeding a single sprinkler. NOTE 1: figure F Hb illustrates typical range pipe
The maximum number of sprinklers downstream arrays.
of each design point is specified in Tables T NOTE 2: examples of pie layouts with the
G.2.2.3a and T G.2.2.3b The design point is appropriate design points are given in Figure F Hc
located by counting from the hydraulically most for LH, Figure F Hd for OH and Figures F He, F Hf
remote sprinkler in the array. and F Hg for HHP and HHS.
Hazard class Number of sprinklers Location of design point downstream of nth sprinkler
on a range, in a room where n is
LH ≤3 3
≥4 4
G.2.3.2 All pipework between the main control NOTE: figure F Hc shows an example of pipe
valve set and the design point at each extremity layout in LH with design points from which the
of an array shall be sized by hydraulic calculation piping shall be fully calculated.
Table T G.2.3.2a: Maximum friction loss between control valve set and any design point – LH
All others 32 3
40 6
50 9
65 18
Between design points All To be calculated in accordance with G.2.4.2
and the control valve set
In these cases, the height difference between the G.2.5.2 For installations with water supplies
highest sprinkler level and the installation pressure with conform to the demands shown in
gauge shall be indicated on the completion Table T 6.3.2a (first part) and with sprinklers
certificate, together with the pressure required having a K factor of 80, the pipe sizes for range
at the installation pressure gauge. pipes and distribution pipes shown in Tables T
G.2.5a and T G.2.5b shall apply.
G.2.4.4 Where the same system includes
both OH3 or OH4 and HHP or HHS areas, No more than 4 sprinklers shall be installed
all connected to a common water supply, on any range pipe. No range pipe shall be
the maximum friction loss of 0.5 bar may be connected to a distribution pipe exceeding
increased by 50% of the available extra pressure, 150 mm in diameter. 100 mm diameter pipe
as indicated in the following example for OH3. may be installed between the design points and
the control valve set if calculation shows this to
Example: be possible.
– Pressure required at the control valve set NOTE: figure F He gives an example of a pipe
excluding static pressure (Table T G.3.1a for layout in accordance with Tables T G.2.5a and
OH3) 1.4 bar T G.2.5b and design points from which the pipe
– Pressure difference due to the difference in diameters shall be fully calculated.
height between the highest sprinkler and the
control valve set 1.2 bar G.2.5.3 For installations with water supplies
which conform to the requirements shown in T
– Required pressure at the control valve set 6.3.2a (second part) and with sprinklers having
2.6 bar a K factor of 80, the pipe sizes for range pipes
– Pressure available at the control valve and distribution pipes shall be determined from
set for the flow appropriate in HH e.g. Tables T G.2.5.b and T G.2.5c.
6.0 bar
No more than 4 sprinklers shall be installed
– Extra pressure which may be used: on any range pipe. No range pipe shall be
50% of (6.0 - 2.6)= 1.7 bar connected to a distribution pipe exceeding
– The pipework shall be dimensioned to allow 150 mm in diameter. No distribution pipe less
for a maximum pressure loss of: than 65 mm diameter is permitted for 4 end-
0.5+1.7 (1 000/1 350)2 = 1.43 bar side systems. 150 mm diameter pipe may be
installed between the design points and the
control valve set if calculation shows this to be
G.2.5 High hazard - HHP and HHS
possible.
(except intermediate level
sprinklers) NOTE: figure F Hf gives an example of a pipe
layout in accordance with Tables T G.2.5b and
G.2.5.1 The pipe sizing depends upon: T G.2.5c and design points from which the pipe
diameters shall be fully calculated.
– the design density;
– the spacing of the sprinklers; G.2.5.4 For installations with water supplies
– the K factor of sprinkler used; which conform to the requirements shown in
Table T 6.3.2a (third part) and with sprinklers
– the pressure/flow characteristic of water supply. having a K factor of 80, and as shown in
No pipe shall have a nominal diameter of less Table T 6.3.2a (forth part) with sprinklers
than 25 mm. having a K factor of 115, the pipe sizes for
range pipes and distribution pipes shown in G.2.5.5 The pressure loss between the
Tables T G.2.5c and T G.2.5d shall apply. design points and the control valve set shall be
determined by calculation. The pressure loss
In an end-side arrangement, no more than 6
with the flows shown in Table T 6.3.2a, plus
sprinklers shall be fitted to any range pipe. In a two
the necessary pressure at the design point
end-centre layout, no more than 4 sprinklers shall
plus the static pressure equal to the height
be fitted to any range pipe. No range pipe shall
difference between the highest sprinkler and
be connected to a distribution pipe exceeding
the control valve set shall not exceed the
150 mm in diameter. No distribution pipe less
available pressure.
than 65 mm diameter shall be used for 4 end-side
systems. 150 mm diameter pipe may be installed Where the highest sprinkler is upstream of the
between the design points and the control valve design point, the portion requiring the higher
set if calculation shows this to be possible. static head shall have its own distribution
NOTE: figure F Hg gives an example of a pipe pipe.
layout in accordance with Tables T G.2.5c and NOTE: the pressure loss in the distribution pipes
T G.2.5d and design points from which the pipe feeding each section of the risk may be balanced
diameters shall be fully calculated. by suitably sizing the distribution pipe.
Table T G.2.5a: Range pipe diameters for HH installations with pressure and flow characteristics as given
in Table T 6.3.2a(first or second part)
Table T G.2.5b: Distribution pipe diameters downstream for the design point in HH installations with
pressure and flow characteristics as given in Table T 6.3.2a (first part)
Table T G.2.5c: Distribution pipe diameters downstream for the design point in HH installations with
pressure and flow characteristics as given in Table T 6.3.2a (second, third and forth part)
Table T G.2.5d: Range pipe diameters for HH installations with pressure and flow characteristics as given
in Table T 6.3.2a (third or forth part)
Other ranges 32 1
40 2
50 4
65 6
Ranges at remote end of all 2 end-centre, last 32 1
distribution pipes 3 ranges 40 2
Other ranges 32 2
All ranges 3 and 4 end-centre 32 1
40 2
50 4
to the line joining the sprinklers and by the range, or pair of ranges where there is an end-
boundary of the area covered (see figure F Hh). centre layout. Sprinklers not constituting a full
Where in-rack sprinklers are installed, the range or pair of ranges shall be grouped as
calculation shall be carried out taking into close as possible to the distribution pipe on the
account the simultaneous flow and pressure next up-stream range row to the rectangular
requirement for roof or ceiling sprinklers and area (see figures F Hi and F Hl);
the intermediate level sprinklers. b) in the case of gridded configurations where
ranges run parallel to the ridge of a roof
G.3.2 Locations of the area of operation having a slope greater than 6°, or along bays
formed by beams greater than 1.0 m deep,
G.3.2.1 Hydraulically most unfavourable the far side of the area shall have a length L
location parallel to the ranges, such that L is greater
Variations in sprinkler spacing, layout, elevation, than or equal to two times the square root
range centres, sprinkler orifice size and Pipe sizes, of the area of operation;
as well as all possible locations, whether on the c) in the case of all other gridded configurations
distribution pipes or between distribution pipes the far side of the area shall have a length L
where these are connected by range pipes, shall parallel to the ranges, such that L is greater
be considered when determining the hydraulically than or equal to 1.2 times the square root of
most unfavourable location of the area of the area of operation;
operation (see figures F Hi, F Hk and F Hl).
The area of operation shall be as far as possible
NOTE: proof of the correct position of the symmetrical with respect to the sprinkler layout
hydraulically most unfavourable area of operation (see figure F Hk).
in the case of gridded installations entails displacing
the area of operation by one sprinkler pitch in each G.3.3.2 Hydraulically most favourable
direction along ranges, and in the case of looped location
installations by one sprinkler pitch along distribution
pipes. The area of operation shall be as near as possible
square. The following shall be considered:
G.3.2.2 Hydraulically most favourable a) in the case of terminal and looped
location configurations, the area shall where possible
Include sprinklers on one distribution pipe
All possible locations, whether on the
only. The number of sprinklers calculated
distribution pipes, or between distribution
to be operating on ranges, or pairs of
pipes where these are connected by range
ranges in end-centre installations, shall be
pipes, shall be considered when determining
located on each range or pair of ranges at
the hydraulically most favourable location of the
the hydraulically most favourable Location.
area of operation (see figures F Hj to F Hl).
Sprinklers not forming a full range or pair
of ranges shall be located on the next range
G.3.3 Shape of the area of operation
row at the hydraulically closest locations
G.3.3.1 Hydraulically most unfavourable (see figures F Hj and F Hl);
location b) in the case of gridded configurations, the area
shall be located on ranges at the hydraulically
The area of operation shall be as near as possible
most favourable location. Sprinklers not
rectangular. The following shall be considered:
forming a full range length shall be located
a) in the case of terminal and looped configurations, on the next range row at the hydraulically
the far side of the area shall be defined by the closest locations (see figure F Hk).
ANNEX H (INFORMATIVE)
Figures with examples
100%
Most Maximum demand flow
unfavourable
area
70%
Most
favourable
area
Q
100% 140%
a) Two end-side with central feed b) Three end-side with end feed
c) Three end-centre with central feed d) Two end-centre with end feed
K
— A (2 sprinkler point) = 0.7 bar
— B (3 sprinkler point) = 0.7 bar
— C, D, E, F, G, H, J and K (2 sprinkler point) = 0.9 bar
NOTE 2: dimensions shown as <25> or <32> indicate
probable pipe sizes resulting from calculation
25 20
25
25
25
25 20
<25>
J
<25>
20
20
<25>
25 20
<32>
<32>
20
20
20
G
25
25
25
20
20
D
25
20
20
25
<32>
25
20
<25>
25
25
<25>
<25>
C
25
<32>
B
A
25
<25>
<25>
20
<25>
<32>
<25>
<32>
<32>
Supply point
48 sprinkler point
Figure F He: Example of application of design points in an HH installation with pipework sized from
Tables T G.2.5a and T G.2.5b
48 sprinkler point
Figure F Hf: Example of application of design points in an HH installation with pipework sized from
Tables T G.2.5a and T G.2.5c
48 sprinkler point
Figure F Hg: Example of application of design points in an HH installation with pipework sized from
Tables T G.2.5c and T G.2.5d
Figure F Hh: Determination of area covered Figure F Hj: Most favourable areas of operation in
per sprinkler (see G.3.1) one-sided and two-sided pipe layouts (see G.3.2)
Figure F Hi: Most unfavourable areas of operation in one-sided and two-sided pipe layouts (see G.3.3.1)
Elevation Riser
Figure F Hk: Most favourable and unfavourable areas of operation in a gridded pipe layout (see G.3)
Riser
Most favourable area
Elevation
Four sprinklers under consideration
Figure F Hl: Most favourable and unfavourable areas of operation in a looped pipe layout (see G.3)
ANNEX I (INFORMATIVE)
Approved components e) water flow detectors;
Components subject to approval include, but f) pipe couplings;
are not necessarily limited to: g) pipe hangers;
a) sprinklers; h) pressure switches;
b) wet alarm valve assemblies; i) sprinkler pumpsets;
c) dry alarm valve assemblies; j) preaction alarm valve assemblies Type A;
d) alarm motors and gongs; k) preaction alarm valve assemblies Type B.
ANNEX J (INFORMATIVE)
New technology These sprinklers should only be used in
These rules cover only the types of sprinkler accordance with the results of large scale fire
specified in Table T 12.2.1a and annex L. During test data and where the design criteria are fully
the years preceding the preparation of these rules acceptable to the authorities involved.
new technologies were being developed for special It is intended that they will be included in future
applications, including in particular the following: editions of these rules.
– large drop sprinklers;
– residential sprinklers.
Table T K.3a: Flammable liquids in metal drums (ST1) with a capacity > 20 l and ≤ 208 l
Table T K.3b: Flammable liquids in metal drums (ST4) with a capacity > 20 l and ≤ 208 l
Table T K.3c: Flammable liquids in metal drums (ST1,ST5,ST6) with a capacity of maximum 20 l
Table T K.6.1a: Non-woven synthetic fabric: design criteria with roof or ceiling protection only
Maximum Density
room height (mm/min)
(m)
≥ 1.2 m
3 7.5
2.6 5 Figure F K.9.1a: Typical layout of racks
with solid shelves and gang ways
The hydraulic design of rack protection shall K.10.2 Design data of sprinkler systems
consider the following parameters: for recycling plants
– area of operation of 90 m2 for each level in A sprinkler system shall be used for:
addition to the ceiling protection
– free pile storage;
– 0.5 bar minimum pressure at sprinkler
– bale storage (compressed plastic);
K.9.2 Ceiling protection – sorting area;
The ceiling protection shall have the following The following equipment should be protected
characteristics: by an additional water extinguishing system
(sprinkler or deluge system):
– design: 10 mm/min over 260 m2
– material storage bunker;
– K-factor min. 80
– comminuting systems (e.g. shredders, mills);
– RTI-value special or quick
– drying systems;
– protection area per sprinkler max. 9 m2
– silo systems.
K.9.3 Additional measures The maximum storage heights for bulk storage
and bale storage are given in table T K.10.2a
Foam proportioning with AFFF foam for rack
and the design data in table T K.10.2b.
and ceiling protection shall be provided.
For local protection of the equipment present in
For limiting horizontal fire spread vertical non
the sorting area a density of discharge of 7.5 mm/
combustible sheet barriers shall be installed
min is required. Special or quick response
within one double rack line and at a maximum
sprinklers shall be used.
distance of every 7 m.
If dry pipe systems are required for the NOTE: Alternatively to sprinkler protection
protection of bulk and bale storage, it shall be according to section K10.2, bulk and bale storage
ensured that an opening of the test fitting at the may be protected by a deluge system with a density
end of the pipework induces the discharge of of discharge of 17.5 mm/min and a proportioning
water after 20 s at the latest. of film-forming foam, provided that the storage
heights are in accordance with table T K.10.2a.
K.10.3 Design data of deluge systems in
recycling plants K.10.4 Area of operation for deluge
systems
A deluge system shall be used for enclosed
mechanical conveyor equipment such as long The area protected by one deluge installation
belt, chain and spiral or vibratory conveyors shall be not less than 100 m2 except rooms
with a density of discharge of 7.5 mm/min. with an area of less than 200 m2. The water
7m
7m
supply shall be capable to supply the total area Dry installations are not permitted.
of operation. The total area of operation shall Only wet system without antifreeze solution is
be found by assuming a fire at the borderline permitted.
between adjacent areas protected by different
deluge installations. All areas are to be supplied Typical rubber tyre storage layouts are the
at the same time which is touched by a radius followings:
of 7 m from the most unfavourable possible
location of a fire.
Upon triggering of the deluge system,
the conveyor and screening equipment
of the appropriate area shall be disabled
automatically.
The water demand for the local protection
equipment in the operating areas shall be
hydraulically taken into account.
Table T K.11.2.2a: Design data for on-side, on-tread and laced storage
Table T K.11.3a: Design data with ESFR Sprinklers for ST2 and ST3 configuration
(1) transverse flues shall be at least 0.08 m width a) have a slope not exceeding 170 mm/m;
and shall be spaced at distances of not more b) are continuous and have no permanent
than 3.0 m (see Figure F L.1.4.2.2a); and opening;
(2) longitudinal flues shall be at least 0.15 m c) are of non-combustible construction;
width and shall be spaced at distances of
not more than 3.0 m d) withstand an upward pressure of 150 N/m2.
NOTE 1: Where the roof or ceiling slope
exceeds 170 mm/m, the roof or ceiling may be
underdrawn with a false ceiling complying with
3 m maximum (a) to (d) above, with EFSR sprinklers located
below the false ceiling.
NOTE 2: Typical ceiling materials include 10 mm
0.15 m
gypsum board, corrugated or sheet steel and
minimum
Transverse mineral tiles.
flue
NOTE 3: Concealed spaces shall comply with 5.4.
Longitudinal
flue
0.08 m
L.1.4.5 The following example of storage or
commodities are not suitable for protection by
ESFR sprinklers:
Figure F L.1.4.2.2a: Storage methods ST2, ST3 – certain storages which exhibit unusual fire
and ST4 transverse and longitudinal flues characteristics such as roll tissue;
– open-top combustible containers;
L1.4.2.3 Storage methods ST5 and ST6
– unusual commodities or storage arrangements
Single and double-row shelved racks shall which have not been proven, by either
comply with one of the following: testing or analysis, to be appropriate for ESFR
a) shelves having openings of less than 50% of sprinklers protection;
the plan area shall not exceed 2.0 m2 total – warehouses in which the commodities or the
plan area and shall be bounded on all four type of storage are unpredictable;
edges by flue spaces of not less than 0.15 m
width; – special risks which are described in Annex K
(K1 aerosols, K3 flammable liquid storages,
b) slatted shelves shall have shelf-open areas, K5 spirituous liquors and K7 storage
uniformly interspaced of at least 50% of the containers fabricated from polypropylene
shelf plan area. The distance openings shall and polyethylene);
not exceed 0.15 m; or;
– rubber tyres.
c) grated or mesh-type shelves shall have
uniform openings of at least 50% of the shelf
plan area. The horizontal distance between
L.2 Sprinkler System Design
openings shall not exceed 0.15 m. L.2.1 General
L.1.4.3 ESFR sprinklers shall be designed in L.2.1.1 Only wet-pipe systems shall be used.
accordance with Table T L.1.4.3a.
L.2.1.2 ESFR protection is based on
L.1.4.4 ESFR sprinklers shall only be installed construction without roof vents or other roof
in buildings with roofs or ceilings which: opening.
Category 1, 7.6 3.5 1.4 7.6 4.2 7.6 2.1 10.6 5.2 2.8
2, 3 & 4 (see
note 2 & 3)
Paper rolls 7.6 3.5 1.4 see see note see note see note 7 9.1 5.2 2.8
stored on end note 7 7 7
(stored
vertically)
in open or
closed arrays,
banded or
unbanded:
heavyweight
paper (see
note 4 & 5)
Paper rolls 6.1 3.5 1.4 see see see see 6.1 5.2 2.8
stored on end note 7 note 7 note 7 note 7
(stored
vertically)
in open or
closed arrays,
banded or
unbanded:
medium
weight paper
and plastic
coated
heavyweight
paper (see
note 4 & 5)
Mezzanine Pressure appropriate for stored goods and ceiling (mezzanine) height (see note 6)
height > 4.5 m.
All acceptable
stored goods
and storage
configurations
NOTE 1: The ceiling height shall be taken as the maximum vertical distance measured from the floor to the underside of the ceiling or roof deck.
NOTE 2: Authorities shall be consulted for the protection of plastic commodity.
NOTE 3: Plastic products (expanded or unexpanded) shall be contained in wooden, cardboard or non-combustible boxes. Expanded plastic
and foamed rubber shall not occupy a greater volume than 15% of the capacity of the box.
NOTE 4: Excluding lightweight paper
NOTE 5: Lightweight paper - all paper with a weight of less than 50 g/m2 and paper with absorbent features (such as toilet paper, paper
towelling, disposable absorbent paper product) regardless of weight. Medium weight paper – non-absorbent paper with a hard or smooth finish
that weighs 50 g/m2 or more but less than 100 g/m2 heavyweight paper – non-absorbent paper or cardboard that weighs 100 g/m2 or greater.
NOTE 6: The vertical distance from the floor to the sprinkler deflector minus 1 m or the value shown in the table, whichever is the lower.
NOTE 7: The values given for a maximum ceiling height of 12.2 m shall be used.
If roof vents or other roof openings are be protected by an approved fire alarm installation.
unavoidable, they shall be operated manually. The powered ventilation shall be stopped and any
Any draft curtains used in conjunction with dampers closed automatically in response to the
roof vents or other roof openings shall be fire detection system alarm of fire.
limited in depth and located with respect to
sprinklers so that distances specified in Table L.2.2 Hydraulic design
T L.2.3.1a are complied with.
Any open roof vents or other roof openings shall L.2.2.1 ESFR sprinkler installation shall be
be closed automatically preferably before, but fully hydraulically calculated in accordance with
in no case more than 30 s after, the operation annex G1 and G3.
of the first sprinkler.
L.2.2.2 The design area of operation shall
L.2.1.3 The clear space beneath the sprinkler consist of an area with a minimum of 12 ceiling
deflectors shall be no less than 1 m. sprinklers or minimum 90 m2 whichever is the
greater. This design area of operation shall be
L.2.1.4 Skylights shall be flush to the ceiling the hydraulically most unfavourable area and
or underdrawn at ceiling level. The skylights shall may include up to 6 additional sprinklers within
be capable of withstanding, without failure, a the same area (e.g. under obstructions). The
temperature of 300°C for at least 5 min. Where minimum operating pressures are stated in
powered ventilation is employed, the building shall Table T L.1.4.3a.
The water supply shall be capable of providing be taken into account when designing the water
the demand flow for at least 60 min. supplies, in accordance with table T L.2.2.5a.
L.2.2.3 For hydraulic calculation purposes, L.2.3 Spacing and location of sprinklers
4 sprinklers shall be assumed to operate on
each of 3 range pipes. When range pipes have L.2.3.1 The area of coverage of ESFR
less than four sprinklers, all the sprinklers on sprinklers shall be not less than 7.5 m2 and not
the range pipe shall be assumed to operate more than 9 m2. The distance between sprinklers
and the number of ranges involved shall be shall be in accordance with table T L.2.3.1a.
increased until a total of 12 sprinklers are
assumed operating.
Table T L.2.3.1a: Distance between sprinklers
L.2.2.4 Where ESFR sprinklers are installed Maximum Distance between
beneath mezzanines of 4.5 m height from the height ceiling sprinklers in m
floor or less, at least 6 ESFR sprinklers shall be m
Min Max
assumed to operate (three ESFR sprinklers on
9.1 2.4 3.7
each of two ranges) at an operating pressure of
12.2 2.4 3
at least 3.5 bar.
NOTE: where standard sprinkler protection is
employed beneath mezzanines of 4.5 m height L.2.3.2 The centre line of the sprinkler
or less, the area of operation and design density heat-sensitive element shall be between 0.1 to
shall comply with the appropriate requirements of 0.33 m below the roof or ceiling for an ESFR
Section 6 - Hydraulic design criteria. sprinkler with a K factor of 200.
ESFR sprinklers shall be used beneath mezzanines
The centre line of the sprinkler heat-sensitive
which are higher than 4.5 m; twelve ESFR
element shall be between 0.1 to 0.45 m below
sprinklers shall be assumed to operate (four
the roof or ceiling for an ESFR sprinkler with a
sprinklers on each of three ranges).
K factor of 360.
L.2.2.5 Sprinklers beneath walkways, Where the roofs or ceilings are constructed using
conveyors, obstructions and mezzanines shall beams and girders or profiled paneling, sprinklers
Obstructions within the design area of operation Maximum number of additional sprinklers to be added
to the ceiling sprinkler water supply requirements
Obstructions less than 3 m width 2 sprinklers operating at 3.5 bar (K = 200) at 1.4 bar
(K = 360)
Obstructions greater than 3 m width such as 4 sprinklers operating at 3.5 bar (K = 200) at 1.4 bar
walkways and conveyors (K = 360)
Mezzanines (See note 1) 6 sprinklers operating at the design pressure (see table
T L.1.4.3a).
NOTE 1: Providing:
a) open-fronted mezzanines are fitted vertically with screens which extend at least 1.2 m below the ceiling are of non-combustible
construction and fit tightly against the underside of the ceiling;
and
b) a clear aisle beneath the screen of at least 0.6 m wide each side of the screen centre-line is maintained; additional sprinklers need not be
added to the water supply requirement.
80
0 0.5 1 1.5 2
Horizontal distance (m) (a)
(a) Horizontal distance from sprinkler to side of beam or other obstruction (m)
(b) Maximum distance deflector above bottom of beam or other obstruction (cm)
0.33 m max
ceiling
b
Figure F L.2.3.2a
ESFR: Sprinkleur location inside bays
ceiling
storage
beam or
obstruction Figure F L.2.3.2e ESFR: Sprinkleur location
distance (b) relative to obstructions (more than one level)
L.2.3.5 Upright sprinklers shall be positioned L.2.4 Separation between ESFR and
so that the deflector has a minimum distance of other sprinkler installations
0.180 m above the top of the range pipe.
L.2.4.1 Vertical screens shall be installed
L.2.3.6 Roller-type conveyor and grated between areas protected by ESFR sprinklers and
walkways with 50% or more uniform openings areas protected by other type of sprinklers. This
are not considered as obstructions to ceiling applies whether the roof over the two areas is
sprinkler discharge. However, when there at the same elevation or at different elevations.
are more than one level above each other of The screens shall extend at least 1.2 m below
conveyors or walkways 50% or more open, a the ceiling, be non-combustible and fit tightly
line of ESFR sprinklers shall be installed beneath against the underside of the roof. A clear aisle,
every other level starting from the second level at least 1.5 m on each side of the centre-line
down from the ceiling. (See figure F L.2.3.2e). beneath the screen, shall be maintained.
ANNEX M (INFORMATIVE)
Commodity classification methodology M.3 Method
utilising calorimeter tests
The method used is described in the document
“NORDTEST METHOD NT FIRE 049” or
M.1 Introduction equivalent documents.
Efficient and reliable sprinkler protection of
storage risks is dependent on appropriate M.4 Evaluation of test results
commodity classifications.
A rank value is determined for each of the three
This European sprinkler installation specification test results, by means of comparing the results
subdivides commodities into four categories, with those of known commodities. The ranking
based on experience and fire test results. Full- system, by comparison, ultimately enables the
scale fire testing has been the preferred solution determination of a commodity classification for
for determining commodity classifications, but the goods under consideration.
is a costly procedure. The development of a
purpose built Fire Products Collector (FPC) by
Factory Mutual Research Corporation (FMRC) M.5 Bibliography
has made the classification of commodities a) Chicarello, P.J. and Troup, J.M; “Fire
possible using smaller amounts of materials products collector test procedure for the
than has hitherto been acceptable. determining the commodity classification
The FPC consists of a large capacity calorimeter of ordinary combustible products”, Factory
hood with a water application pipework array Mutual Research Corporation, August
located below the collector hood, beneath 1990.
which a fuel array is burnt. b) Heskestad, G. (“A fire products collector
for calorimetry in the MW range”), Factory
M.2 Test principles Mutual Research Corporation, June 1981.
Table T Na: Minimum water supply for all hazard classes shall be superior
ANNEX O (RESERVED)
Only compatible materials with the foam If the test result does not meet the requirement
concentrate or foam solution shall be installed in the pipework shall be emptied, flushed and
the system. The foam concentrate manufacturer filled with new premix. If pre-mix solution
shall publish compatible materials to be utilized continually fails, a test of the water supply or
on the system. investigation of contamination may be required.
If contamination is present, the offending
product must be replaced.
P.1 Type of installation
solution test valve. The foam solution test valve P.3 Foam injection pumps
and installation isolation valve shall be installed
in accordance with the foam injection device P.3.1 Foam injection pumps shall be
manufacturers recommendations. selected for the special working
conditions like corrosion, tightness.
The commissioning of the installation shall include
a test of the achieved foam concentration using The performance characteristics of the foam
appropriate measuring devices. In a first test injection pumps shall be selected for the
sequence water or test foam that has been designed maximum flow rate and the viscosity of the foam
to simulate the flow and shearing characteristics agent. If foam injection proportioning devices
of the foam concentrate can be injected in place are utilized in conjunction with a foam injection
of foam to avoid unnecessary use of foam. At the pump, the minimum pressure differential
initial system testing and commissioning, the foam between the water injection point and the foam
concentrate utilized for the system shall be utilized injection device shall be per the foam injection
in the system commissioning. device manufacturers requirements, but in no
For closed head sprinkler systems, tests shall case lower than 1 bar.
be carried out with an equivalent flow rate of
four sprinklers and at the design flow rate of the P.3.2 Foam injection pumps shall not work
system. The test at the design flow rate can be under suction conditions.
carried out by replacing foam by another liquid.
The injection device shall deliver foam solution P.3.3 Foam pumps shall be installed with a
within a tolerance not less than its approval to pump casing relief valve. Casing relief valve shall
1.3 times its approval. A maximum of 1% point be set to open after pump pressure is 1 bar higher
will be allowed. (Meaning 3% concentrate shall than the design limit of either the pump or the
be allowed to be proportioned between 3% system piping network, whichever is less. The
and 3.9%, 6% concentrate shall be allowed to discharge of the casing relief valve shall not be
be proportioned between 6% and 7%). piped to the suction side of the foam pump. The
discharge of the casing relief valve may be piped or
Annual testing after the first year can be
to the liquid level of the foam storage tank.
provided utilizing water or test foam using
the comparative data from the first year. If
proportioning with the required range does not P.3.4 An approved pressure sustaining
occur with water or test foam, a new test with valve shall, if required by the injection device
foam concentrate shall be made. Corrections manufacturer, be installed in the discharge side
to the proportioning system shall be made as of the foam injection pump and shall be designed
required injection device. to discharge below the liquid level of the foam
tank. The pressure sustaining valve shall be
P.2.3 If the foam injection device utilizes calibrated to open where low water flow rate
moving parts, means shall be provided to allow through the main stream of the proportioned
a test of the mechanical operating components. is present and to close where large water flow
If the foam injection device utilizes electrical rate is present during proportioning. Piping shall
devices or electrical controllers, means shall be adequately sized on the supply and discharge
be provided to test the electrical devices or of pressure sustaining valve for full flow capacity.
electrical controllers, means of monitoring
the working condition of electrical devices P.3.5 The pipes up- and downstream
shall be provided. Foam injection devices shall the foam injection pumps shall be fitted with
immediately be ready for service after testing flushing connections. No water shall flow back
and shall restore automatically. in the foam tank.
P.3.6 Foam pumps shall start by automatic The manufacturers recommendation for the
means. Foam pumps shall require weekly testing. storage of the foam agent shall be observed.
P.3.7 Suction pipes with pure foam agent P.5.2 Non pressurized foam tank
shall be designed in such a way that the NPSH The foam tank shall be adequately designed to
available is at least 1 m higher that the required allow for the thermal expansion of the foam
NPSH of the foam pump. concentrate.
The foam tank shall have a venting, a level gauge
P.4 Foam agent and means to prevent overfilling.
P.4.1 Foam agents shall be approved by the Means for servicing and inspecting the inside
authorities. of the tank shall be provided. Foam storage
tank shall be constructed of a material that is
The foam agent shall be selected appropriate compatible with the foam concentrate. Foam
to the materials to be protected and the foam concentrate manufacturer shall be consulted
injection device. for compatible materials.
P.4.2 The water shall not have any Connections for filling and draining shall be
ingredients which are not compatible fitted. The fill and suction pipes shall end above
with the foam agent. the tank bottom. The volume under the suction
pipe shall not be taken account by calculating
The quantity of the foam agent is determined at the tank volume.
design flow rate by the operation time and the
The suction pipe may end at the tank bottom of
design concentration.
tanks only if they are manufactured of reinforced
Unless specified elsewhere, the quantity of foam glass fibre, or equivalent or corrosion resistant
agent shall allow a continuous operation of the steel and if the foam agent is a sediment free
system for at least 30 min. and synthetic type.
P.4.3 The quantity of foam agent may P.5.3 Pressurized foam tank
be reduced to 50% if the premises have a
recognised fire brigade and the same quantity Pressurized foam tanks (bladder tanks) shall
of foam agent can be feed in the foam tank in a be fitted with means for filling, draining,
time not exceeding 15 min. The fulfilling of this venting, measuring of the fill level, cleaning and
requirement shall be approved by the authorities controlling of the tank inside. Pressurized foam
in the planning state of the installation. tanks shall be designed and constructed per a
recognized standard for pressure vessels.
P.4.4 Only the same type of foam agent of Pressurized foam tanks shall incorporate
the manufacturer shall be used for refilling. Mixing a concentrate control valve near the foam
of different foam concentrates is forbidden. injection device.
An operation manual shall be provided. The
P.5 Foam tank recommendation shall be followed for all works.
Pressurized foam tanks cannot be refilled
P.5.1 Foam tanks shall be approved by the
during operation of the extinguishing activity.
authorities.
Pressurized foam tanks shall be inspected and
Depending on the type and quantity of foam tested per manufacturers recommendations and
agent a security pool can be necessary. the pressure equipment directive. The integrity
of the bladder shall be tested for leaks on an P.7 Calculation of the friction
annual basis. The quantity of foam agent may be loss of foam agent pipes
stored in more than one pressurized foam tank.
If the quantity of foam agent is stored in more
P.7.1 The calculation shall be done for
than one pressurized foam tank, piping of equal
the lowest and highest viscosity (only highest
pressure loss supplying the bladder tank and
viscosity for Newtonian liquid) of the foam agent.
piping of equal pressure loss discharging from
the bladder tank to the foam injection device This calculation shall be based on the foam
shall be maintained. demand corresponding to the sprinkler design
flow.
P.6 Foam agent and water The friction loss in the foam pipes shall be
foam pipe-work calculated with the Darcy formula
L . ρ. 2
P.6.1 Components and pipes filled with Δp = λ . ν (Darcy formula)
d 2
foam concentrate at any time shall not influence
the performance characteristics of the foam With:
agent. Only materials compatible with the Δp friction loss, in N/m2
foam concentrate shall be utilized in the foam friction number
concentrate supply line to the foam injection
device or system. L pipe length, in m
d pipe diameter, in m
P.6.2 The filling of the foam pipes upstream fluid density, in kg/m3
of the foam injection device with foam agent
shall be achieved within 10 seconds or the pipes flow velocity, in m/s
shall continuously be filled with foam agent. If the The friction number shall be determined
foam agent pump and the foam injection device depending on the Reynolds number Re using
are filled at all times with foam agent they shall the following formula.
be made of corrosion resistant materials that are
Reynolds number:
compatible and suitable as pressurized piping.
v
Re = d .
P.6.3 Galvanized pipes shall not be used γ
With:
for pipe-work filled with water foam mixture
or used in foam concentrate lines unless proof Kinematic viscosity, in m2/s
of the compatibility of the foam agent with For the determining of the Reynolds number the
galvanized pipes is available. Kinematic viscosity at the lowest temperature
at the foam tank shall be used.
P.6.4 A filter or strainer shall be fitted
For Re < 2350 (laminar) is:
upstream the foam injection device. Maintenance
64
and cleaning of the filter shall not affect the λ=
operation of the extinguishing system (by pass Re
around the strainer). d
For 2 350 < Re < 65
k
Filters are not necessary if a sphere with a with:
diameter of 8 mm can pass all ways of foam
through pressurized tanks, foam injection k pipe roughness, in mm (for steel pipes:
devices. k = 0.5 mm; for stainless steel pipes: