TEST REPORT FOR MAINTENANCE TESTING OF

VACUUM CIRCUIT BREAKER & RELAY

Carried out

at

M/S E SOLLUTIONS CONSULTANCY PRIVATE LIMITED,


Site : Indusind Bank Ltd.,
No.115,116,  G.N.Chetty Road, T.Nagar,
Chennai – 600 017.

on

13th December 2020.

Job Carried out by: DURGA SWITCHGEARS


EA 2616 – A-Grade Electrical Contractors, Consultants & Testing Engineers
No. 8/5, John Vasu Street,
Madhavaram Milk Colony,
Chennai – 600 051
11KV HT VCB
DURGA SWITCHGEARS GSTIN: 33ABSPV9616N1ZM
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,Protective relays, Transformer oil filtration
and High pot Test) HYDRAULIC OIL FILTRATION BY ALFA LAVAL CENTRIFUGE
EA 2616 -----A-GRADE ELECTRICAL CONTRACTORS,CONSULTANTS & TESTING ENGINEERS Page 1a
8/5, JOHN VASU STREET, Mobile: 9884320732
MADHAVARAM MILK COLONY, Office: 82484 17515
CHENNAI – 600 051. Mail : durgaswitchgears@yahoo.co.in
DATE: 13TH
DECEMBER 2020.
TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
To
M/S E SOLLUTIONS CONSULTANCY PRIVATE LIMITED,
Breaker Sl. No. 1306
Site : Indusind Bank Ltd.,
No.115,116,  G.N.Chetty Road, T.Nagar, Breaker Make EXCEL
Chennai – 600 017. Type EPS – C – 11
Rated Current 630 AMPS
Rated Voltage 12KV
                                                                               Title Main HT Incomer

S.NO. DESCRIPTION TYPE OF CHECK CHECKED REMARKS

PHYSICAL INSPECTION VISUAL FOR DAMAGE OK


1
INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR CORRECTNESS OK
2
OPERATIONS
3 a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping
b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

c) Tripping through RELAY ELECTRICAL FOR PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR PERFORMANCE OK

e) Closing ELECTRICAL FOR PERFORMANCE OK

f) Opening ELECTRICAL FOR PERFORMANCE OK

4
CONTACT PENETRATION FOR VCB VISUAL FOR ABNORMALITY OK

5 VCB CLOSED CONDITION VCB OPEN


INSULATION RESISTANCE R-E > 5500 M Ω CONDITION
Y-E > 5500 M Ω R I/C – R O/G
B-E > 6500 M Ω 5000 M Ω
R-Y > 9500 M Ω Y I/C – Y O/
Y-B > 9500 M Ω 5000 M Ω
B-R > 8500 M Ω B I/C – B O/G
5000 M Ω
DURGA SWITCHGEARS GSTIN: 33ABSPV9616N1ZM
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers,Protective relays, Transformer oil filtration
and High pot Test) HYDRAULIC OIL FILTRATION BY ALFA LAVAL CENTRIFUGE
EA 2616 -----A-GRADE ELECTRICAL CONTRACTORS,CONSULTANTS & TESTING ENGINEERS Page 1b
8/5, JOHN VASU STREET, Mobile: 9884320732
MADHAVARAM MILK COLONY, Office: 82484 17515
CHENNAI – 600 051. Mail : durgaswitchgears@yahoo.co.in
DATE: 13TH
DECEMBER 2020.
TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
To
M/S E SOLLUTIONS CONSULTANCY PRIVATE LIMITED,
Breaker Sl. No. 1306
Site : Indusind Bank Ltd.,
No.115,116,  G.N.Chetty Road, T.Nagar, Breaker Make EXCEL
Chennai – 600 017. Type EPS – C – 11
Rated Current 630 AMPS
Rated Voltage 12KV
Title Main HT Incomer

2) Contact Resistance Test:-

Phase Ref DC Current DC Volts Across Resistance


Applied Terminal
R-Phase 100 Amps 5.5 mv 55 Micro Ohms
Y-Phase 100 Amps 5.5 mv 55 Micro Ohms
B-Phase 100 Amps 5.6 mv 56 Micro Ohms

3) Breaker Timing Test:-

Ref Closing Time in Opening Time in milli


milli secs. secs
R-Phase 64 56
Y-Phase 64 56
B-Phase 65 57

Remarks: Test Results are satisfactory.


RELAYS
Durga Switchgears -- EA 2616 A Grade Electrical Contractors, Consultants & Testing Engineers Page 2a
Client: M/S Indusind Bank Ltd., No.115,116,  G.N.Chetty Road, T.Nagar, Chennai – 600 017.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY

Date of Test : 13th December 2020. Location : HT Switchgear Room

Feeder Name : Outdoor HT VCB Incomer Relay Make : MICOM

Type / Sl. No. : P111 / 00075969 System Volts : 11KV CT Ratio : 60 / 5 Amps

SETTINGS:-
I> --- 0.5 X In t> ---- 0.100 (Normally Inverse 3 sec.)
I>> --- 4.0 X In t> ---- 0.05 (DMT)

IN_1 --- 0.2 X In t> ---- 0.100 (Normally Inverse 3 sec.)


IN_2 --- 1.0 X In t> ---- 0.05 (DMT)

SECONDARY INJECTION TEST:

Description R - Phase Y - Phase B - Phase Earth Fault


Applied Graph Actual time in seconds E/F Graph Actual
% ofset Pick-up Current in Amps
Low 2.59 2.57 2.60 1.11
current in Time in R- Y- B- Current Time in Time in
current
Closing timeAmps
in seconds seconds 15.3
Phase Phase Phase 15.9 in Amps 15.4Seconds 13.5
Seconds

High
200 %Set Pick-up
5.0Current in Amps
1.00 1.0820.01 1.09 20.05
1.06 2.00 20.04 1.00 5.05
1.08

500% 12.5 0.43 0.48 0.45 0.44 5.00 0.43 0.46

1000% 25.0 0.30 0.32 0.31 0.33 10.00 0.30 0.32

Remarks: - Test results are satisfactory.