TRANSFORMERS

GST 33ABSPV9616N1ZM DURGA SWITCHGEARS


A-Grade Electrical Contractors, Consultants & Testing Engineers --- EA 2616
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers, Protective relays, Transformer oil filtration and High pot Test)
HYDRAULIC OIL FILTRAION BY ALFA LAVAL CENTRIFUGE PAGE 1a
Mobile: 9884320732 / 8248417515
Mail : durgaswitchgears@yahoo.co.in
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Date of Test: 03rd Januay 2019.
T R A N S F O R M E R NO. 1 O I L T E S T R E P O R T
Supply to PCC-1
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.

TRANSFORMER SPECIFICATION:-
Make : RAYCHEM RPG LTD.,
Rating : 2500 KVA
Voltage HV / LV : 33000 / 433 Volts Current HV / LV: 43.7 / 3333.4 Amps
Maker’s Serial No. : J 1716002 / 002 Oil Quantity: 2800 litres

Year of Manufacture : 2009 Next Oil Filtration Due on: 03rd January 2020.

TEST KIT DETAILS:-


Make : VA Power India
Serial Number : S 200315
Input: 230 V. AC, Output: 0 – 60KV, Freq.: 50HZ Single Phase

BDV Test Results Before Filtration:-


Bottom Sample: 30 kv
Top Sample : 28 kv

BDV Test Results After Filtration: - TEST GAP BETWEEN ELECTRODES : 2.5mm

OIL SAMPLES -- BREAK DOWN VOLTAGE VALUES IN KV AC.


NO. OF TEST BOTTOM SAMPLE TOP SAMPLE
1 55 56
2 55 54
3 56 55
4 53 53
5 54 58
6 56 56
TOTAL 329 332
AVERAGE 54.8 55.3
OIL WITHSTOOD 50 KV FOR ONE MINUTE (TOP & BOTTOM SAMPLE)

ACIDITY TEST:- 0.08 MILLIGRAM OF KOH / GRAM OF OIL


FOR DURGA SWITCHGEARS,

(AUTHORISED SIGNATORY)
GST 33ABSPV9616N1ZM DURGA SWITCHGEARS
A-Grade Electrical Contractors, Consultants & Testing Engineers --- EA 2616
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers, Protective relays, Transformer oil filtration and High pot Test)
HYDRAULIC OIL FILTRAION BY ALFA LAVAL CENTRIFUGE PAGE 1b
Mobile: 9884320732 / 8248417515
Mail : durgaswitchgears@yahoo.co.in
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Date of Test: 03rd Januay 2019.
T R A N S F O R M E R NO. 1 O L T C OIL TEST REPORT
Supply to PCC-1
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.

Make : CTR Type : EN 16


Serial number : 2920499
Normal Working Current: 30 AMPS Rated Step Voltage : 413 Volts
Oil quantity : 700 Liters Year of manufacturing : 2009
Next Oil Filtration Due on: 03rd January 2020.
TEST KIT DETAILS:-
Make : VA Power India
Serial Number : S 200315
Input: 230 V. AC, Output: 0 – 60KV, Freq.: 50HZ Single Phase

BDV Test Results Before Filtration:-


Bottom Sample: 29 kv
Top Sample : 30 kv

BDV Test Results after Filtration: - TEST GAP BETWEEN ELECTRODES: 2.5mm

OIL SAMPLES -- BREAK DOWN VOLTAGE VALUES IN KV AC.


NO. OF TEST BOTTOM SAMPLE TOP SAMPLE
1 56 57
2 56 56
3 55 57
4 56 57
5 55 58
6 57 56
TOTAL 335 341
AVERAGE 55.8 56.8

OIL WITHSTOOD 50 KV FOR ONE MINUTE (TOP & BOTTOM SAMPLE)

ACIDITY TEST:- 0.08 MILLIGRAM OF KOH / GRAM OF OIL


FOR DURGA SWITCHGEARS,

(AUTHORISED SIGNATORY)
GST 33ABSPV9616N1ZM DURGA SWITCHGEARS
A-Grade Electrical Contractors, Consultants & Testing Engineers --- EA 2616
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers, Protective relays, Transformer oil filtration and High pot Test)
HYDRAULIC OIL FILTRAION BY ALFA LAVAL CENTRIFUGE PAGE 2a
Mobile: 9884320732 / 8248417515
Mail : durgaswitchgears@yahoo.co.in
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Date of Test: 03rd Januay 2019.
T R A N S F O R M E R NO. 2 O I L T E S T R E P O R T
Supply to PCC-2
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.

TRANSFORMER SPECIFICATION:-
Make : RAYCHEM RPG LTD.,
Rating : 2500 KVA
Voltage HV / LV : 33000 / 433 Volts Current HV / LV : 43.7 / 3333.4 Amps
Maker’s Serial No. : J 1716002 / 001 Oil Quantity: 2800 litres

Year of Manufacture : 2009 Next Oil Filtration Due on: 03rd January 2020.

TEST KIT DETAILS:-


Make : VA Power India
Serial Number : S 200315
Input: 230 V. AC, Output: 0 – 60KV, Freq.: 50HZ Single Phase

BDV Test Results Before Filtration:-


Bottom Sample: 27 kv
Top Sample : 28 kv

BDV Test Results After Filtration: - TEST GAP BETWEEN ELECTRODES: 2.5mm

OIL SAMPLES -- BREAK DOWN VOLTAGE VALUES IN KV AC.


NO. OF TEST BOTTOM SAMPLE TOP SAMPLE
1 55 56
2 56 55
3 56 55
4 53 54
5 55 57
6 56 57
TOTAL 331 334
AVERAGE 55.2 55.7

OIL WITHSTOOD 50 KV FOR ONE MINUTE (TOP & BOTTOM SAMPLE)

ACIDITY TEST:- 0.08 MILLIGRAM OF KOH / GRAM OF OIL


FOR DURGA SWITCHGEARS,

(AUTHORISED SIGNATORY)
GST 33ABSPV9616N1ZM DURGA SWITCHGEARS
A-Grade Electrical Contractors, Consultants & Testing Engineers --- EA 2616
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers, Protective relays, Transformer oil filtration and High pot Test)
HYDRAULIC OIL FILTRAION BY ALFA LAVAL CENTRIFUGE PAGE 2b
Mobile: 9884320732 / 8248417515
Mail : durgaswitchgears@yahoo.co.in
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Date of Test: 03rd Januay 2019.
T R A N S F O R M E R NO. 2 O L T C OIL TEST REPORT
Supply to PCC-2
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.

Make : CTR Type : EN 16


Serial number : 2920498
Normal Working Current: 30 AMPS Rated Step Voltage : 413 Volts
Oil quantity : 700 Liters Year of manufacturing : 2009
Next Oil Filtration Due on: 03rd January 2020.
TEST KIT DETAILS:-
Make : VA Power India
Serial Number : S 200315
Input: 230 V. AC, Output: 0 – 60KV, Freq.: 50HZ Single Phase

BDV Test Results Before Filtration:-


Bottom Sample: 26 kv
Top Sample : 28 kv

BDV Test Results after Filtration: - TEST GAP BETWEEN ELECTRODES: 2.5mm

OIL SAMPLES -- BREAK DOWN VOLTAGE VALUES IN KV AC.


NO. OF TEST BOTTOM SAMPLE TOP SAMPLE
1 56 57
2 55 56
3 57 58
4 56 55
5 55 58
6 56 56
TOTAL 335 340
AVERAGE 55.8 56.7

OIL WITHSTOOD 50 KV FOR ONE MINUTE (TOP & BOTTOM SAMPLE)

ACIDITY TEST:- 0.08 MILLIGRAM OF KOH / GRAM OF OIL


FOR DURGA SWITCHGEARS,

(AUTHORISED SIGNATORY)
GST 33ABSPV9616N1ZM DURGA SWITCHGEARS
A-Grade Electrical Contractors, Consultants & Testing Engineers --- EA 2616
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers, Protective relays, Transformer oil filtration and High pot Test)
HYDRAULIC OIL FILTRAION BY ALFA LAVAL CENTRIFUGE PAGE 3a
Mobile: 9884320732 / 8248417515
Mail : durgaswitchgears@yahoo.co.in
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Date of Test: 04th January 2019.
T R A N S F O R M E R NO. 3 O I L T E S T R E P O R T
Supply to PCC-3
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.

TRANSFORMER SPECIFICATION:-
Make : RAYCHEM RPG LTD.,
Rating : 500 KVA
Voltage HV / LV : 33000 / 433 Volts Current HV / LV : 8.7 / 666.7 Amps
Maker’s Serial No. : J 1709001 / 01 Oil Quantity: 1000 litres

Year of Manufacture : 2009 Next Oil Filtration Due on: 04th January 2020.
TEST KIT DETAILS:-
Make : VA Power India
Serial Number : S 200315
Input: 230 V. AC, Output: 0 – 60KV, Freq.: 50HZ Single Phase

BDV Test Results Before Filtration:-


Bottom Sample: 25 kv
Top Sample : 27 kv

BDV Test Results After Filtration :- TEST GAP BETWEEN ELECTRODES : 2.5mm

OIL SAMPLES -- BREAK DOWN VOLTAGE VALUES IN KV AC.


NO. OF TEST BOTTOM SAMPLE TOP SAMPLE
1 57 56
2 56 55
3 57 55
4 55 55
5 54 54
6 54 55
TOTAL 333 330
AVERAGE 55.5 55.0

OIL WITHSTOOD 50 KV FOR ONE MINUTE (TOP & BOTTOM SAMPLE)

ACIDITY TEST:- 0.08 MILLIGRAM OF KOH / GRAM OF OIL


FOR DURGA SWITCHGEARS,

(AUTHORISED SIGNATORY)
GST 33ABSPV9616N1ZM DURGA SWITCHGEARS
A-Grade Electrical Contractors, Consultants & Testing Engineers --- EA 2616
(Servicing, Repairing Testing of all kinds of LT/HT Circuit Breakers, Protective relays, Transformer oil filtration and High pot Test)
HYDRAULIC OIL FILTRAION BY ALFA LAVAL CENTRIFUGE PAGE 3b
Mobile: 9884320732 / 8248417515
Mail : durgaswitchgears@yahoo.co.in
HO: 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Date of Test: 04th January 2019.
T R A N S F O R M E R NO. 3 O L T C OIL TEST REPORT
Supply to PCC-3
NAME OF THE CUSTOMER : M/S LOTTE INDIA CORPORATION LTD.,
NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,
NEMAM, TIRUVALLUR – 602 107.

Make : CTR Type : EN 16


Serial number : 2920528
Normal Working Current: 6 AMPS Rated Step Voltage : 413 Volts
Oil quantity : 700 Liters Year of manufacturing : 2009
Next Oil Filtration Due on: 04th January 2020.
TEST KIT DETAILS:-
Make : VA Power India
Serial Number : S 200315
Input: 230 V. AC, Output: 0 – 60KV, Freq.: 50HZ Single Phase

Before Oil Filtration


Top sample : Oil withstood 31 KV level.
Bottom sample : Oil withstood 28 KV level.

After Oil Filtration


TESTED BDV VALUES:- TEST GAP BETWEEN ELECTRODES : 2.5mm

OIL SAMPLES -- BREAK DOWN VOLTAGE VALUES IN KV AC.


NO. OF TEST BOTTOM SAMPLE TOP SAMPLE
1 57 57
2 54 55
3 52 55
4 53 53
5 55 54
6 53 56
TOTAL 324 330
AVERAGE 54.0 55.0

OIL WITHSTOOD 50 KV FOR ONE MINUTE (TOP & BOTTOM SAMPLE)

ACIDITY TEST:- 0.08 MILLIGRAM OF KOH / GRAM OF OIL


FOR DURGA SWITCHGEARS,

(AUTHORISED SIGNATORY)
EARTH PITS
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 10a

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
EARTH RESISTANCE TEST REPORT

Date of Test : 04th January 2019.

S.NO DESCRIPTION LOCATION Individual Combined


Resistance Resistance
in Ohms in Ohms
1 MV Panel Cable Tray Body Earth – 1 Sub-station 1.90 0.50
2 MV Panel Cable Tray Body Earth – 2 Sub-station 1.80 0.50
3 Transformer – 1 Neutral Earth -1 Sub-station 2.20 0.50
4 Transformer – 1 Neutral Earth – 2 Sub-station 1.90 0.50
5 Transformer – 1 Body Earth – 1 Sub-station 2.10 0.50
6 Transformer – 1 Body Earth – 2 Sub-station 2.10 0.50
7 Transformer – 2 Neutral Earth – 1 Sub-station 2.10 0.50
8 Transformer – 2 Neutral Earth – 2 Sub-station 1.60 0.50
9 Transformer – 2 Body Earth – 1 Sub-station 1.80 0.50
10 Transformer – 2 Body Earth – 2 Sub-station 1.80 0.50
11 Transformer – 3 Neutral Earth – 1 Sub-station 2.00 0.50
12 Transformer – 3 Neutral Earth – 2 Sub-station 1.50 0.50
13 Transformer – 3 Body Earth – 1 Sub-station 2.50 0.50
14 Transformer – 3 Body Earth – 2 Sub-station 2.10 0.50
15 DG – 1 Neutral Earth – 1 Sub-station 2.40 0.50
16 DG – 1 Neutral Earth – 2 Sub-station 1.60 0.50
17 DG – 1 Body Earth – 1 Sub-station 1.90 0.50
18 DG – 1 Body Earth – 2 Sub-station 2.30 0.50
19 DG – 2 Neutral Earth – 1 Sub-station 1.90 0.50
20 DG – 2 Neutral Earth – 2 Sub-station 2.20 0.50
21 DG – 2 Body Earth – 1 Sub-station 1.90 0.50
22 DG – 2 Body Earth – 2 Sub-station 1.80 0.50
23 HV panel Body Earth – 1 Sub-station 2.20 0.50
24 HV panel Body Earth – 2 Sub-station 1.90 0.50
DG Chimney Lightning Arrestor Body Sub-station 1.70 -----
25 Earth
26 HT Structure Body Earth – 1 HT Structure 1.20 0.50
27 HT Structure Body Earth – 2 HT Structure 2.00 0.50
28 HT Structure Body Earth – 3 HT Structure 2.10 0.50
29 HT Structure Body Earth – 4 HT Structure 2.70 0.50

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 10b

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
EARTH RESISTANCE TEST REPORT

Date of Test : 04th January 201.9

S.NO DESCRIPTION LOCATION Individual Combined


Resistance Resistance
in Ohms in Ohms
30 Building Lightning Arrestor Earth 1 HT Structure 2.00 ---
31 Building Lightning Arrestor Earth 2 HT Structure 1.90 ---
32 Building Lightning Arrestor Earth 3 HT Structure 2.00 ---
33 Building Lightning Arrestor Earth 4 HT Structure 2.10 ---
34 Body Earth – 1 Main Building 2.10 0.50
35 Body Earth – 2 Main Building 1.70 0.50
36 Body Earth – 3 Main Building 1.90 0.50
37 Body Earth – 4 Main Building 2.00 0.50
38 Body Earth – 5 Main Building 1.90 0.50
39 Body Earth – 6 Main Building 1.60 0.50
40 Body Earth – 7 Main Building 1.70 0.50
41 Body Earth – 8 Main Building 1.90 0.50

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
RELAYS
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 4a

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : TFR -1 Outgoing Relay Make : AREVA

Type / Sl. No. : P127 / 31087622 CT Ratio : 50 / 1 Amp

System Voltage : 33000 Volts

SETTINGS:-
I > 0.90 Delay Type : IEC SI TMS > 1.0 Ie > 0.18 Delay Type : IEC SI TMS > 1.0
I >> 3.6 Instantaneous Ie >> 0.90 Instantaneous

SECONDARY INJECTION TEST:

Description R - Phase Y - Phase B - Phase Earth Fault

Pick-up Current in Amps 0.92 0.93 0.91 0.22


Closing time in Seconds 1.06 1.17 1.13 1.01

Instantaneous Setting in 3.60 3.60 3.60 0.90


Amps
Actual Tripping current in 3.63 3.62 3.63 0.91
Amps

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 4b

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR MASTER TRIP RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : TFR -1 Outgoing Relay Make : ABB

Type / Sl. No. : PQ8Nch2JS / V09 – 55709 V :110

SECONDARY INJECTION TEST:

REF PICK-UP VOLTS


IN DC
COIL 57

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 5a

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : TFR -2 Outgoing Relay Make : AREVA

Type / Sl. No. : P127 / 31087620 CT Ratio : 50 / 1 Amp

System Voltage : 33000 Volts

SETTINGS:-
I > 0.90 Delay Type : IEC SI TMS > 1.0 Ie > 0.18 Delay Type : IEC SI TMS > 1.0
I >> 3.6 Instantaneous Ie >> 0.90 Instantaneous

SECONDARY INJECTION TEST:

Description R - Phase Y – Phase B - Phase Earth Fault

Pick-up Current in Amps 0.93 0.92 0.92 0.19


Closing time in Seconds 1.12 1.11 1.12 1.02

Instantaneous Setting in 3.60 3.60 3.60 0.90


Amps
Actual Tripping current in 3.62 3.63 3.62 0.92
Amps

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 5b

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR MASTER TRIP RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : TFR -2 Outgoing Relay Make : ABB

Type / Sl. No. : PQ8Nch2JS / V09 – 55703 V :110

SECONDARY INJECTION TEST:

REF PICK-UP VOLTS


IN DC
COIL 57

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 6a

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : TFR -3 Outgoing Relay Make : AREVA

Type / Sl. No. : P127 / 31087621 CT Ratio : 25 / 1 Amp

System Voltage : 33000 Volts

SETTINGS:-
I > 0.35 Delay Type : IEC SI TMS > 1.0 Ie > 0.175 Delay Type : IEC SI TMS > 1.0
I >> 1.4 Instantaneous Ie >> 0.87 Instantaneous

SECONDARY INJECTION TEST:

Description R - Phase Y - Phase B - Phase Earth Fault

Pick-up Current in Amps 0.37 0.38 0.38 0.20


Closing time in Seconds 1.09 1.11 1.06 1.05

Instantaneous Setting in 1.40 1.40 1.40 0.87


Amps
Actual Tripping current in 1.42 1.43 1.43 0.88
Amps

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 6b

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR MASTER TRIP RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : TFR -3 Outgoing Relay Make : ABB

Type / Sl. No. : PQ8Nch2JS / V09 – 55707 V :110

SECONDARY INJECTION TEST:

REF PICK-UP VOLTS


IN DC
COIL 59

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 7a

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR OVER CURRENT & EARTH FAULT RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : Main Incomer Relay Make : AREVA

Type / Sl. No. : P127 / 00015369 CT Ratio : 125 / 1 Amp

System Voltage : 33000 Volts

SETTINGS:-
I > 0.80 Delay Type : IEC SI TMS > 1.0 I0 > 0.16 Delay Type : IEC SI TMS > 1.0
I >> 3.2 Instantaneous I02 >> 0.80 Instantaneous

SECONDARY INJECTION TEST:-

Description R - Phase Y - Phase B - Phase Earth Fault

Pick-up Current in Amps 0.82 0.82 0.83 0.18


Closing time in Seconds 1.09 1.11 1.05 1.04

Instantaneous Setting in 3.20 3.20 3.20 0.80


Amps
Actual Tripping current in 3.23 3.22 3.24 0.82
Amps

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 7b

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR MASTER TRIP RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : Main Incomer Relay Make : ABB

Type / Sl. No. : PQ8Nch2JS / V09 – 55707 V :110

SECONDARY INJECTION TEST:

REF PICK-UP VOLTS


IN DC
COIL 60

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 7c

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR NEUTRAL DISPLACEMENT RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : Main Incomer Relay Make : AREVA

Type / Sl. No. : VDG 14 AF 9001 ACH / 10005972 / 31029117

Aux. Volts : 24 - 250V. dc Un: PT. Voltage - 110v. ac.

The zero sequence current that flows for an earth-fault on an un-earthed network is determined by
the capacitance of the cable to earth. This flow of current leads to a rise in the voltage of the neutral point
of the incoming supply (the star-point of either the generator or transformer). It is this rise that is
detected by a neutral voltage displacement relay.

SETTING :
PLUG TIME LEVER DMT
SETTING SETTING
20 VOLTS 0.2 5.0

TEST RESULTS:-

APPLIED GRAPH TIME IN ACTUAL TIME IN


% OF PLUG VOLTAGTE SECONDS SECONDS
SETTING

200% 25.0 6.0 6.32

500% 62.5 2.50 2.61

1000% 125.0 1.0 1.13

Pick-up voltage 21.7 volts


Closing time in seconds 38.5

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 7d

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR NEGATIVE SEQUENCE VOLTAGE RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : Main Incomer Relay Make : AREVA

Type / Sl. No. : VTNM12YF1A / 31034233 VA : 110V. 50HZ

Negative Phase Sequence Relay provides protection for rotating equipment


from the damaging effects of excessive negative sequence voltage resulting from phase
failure, phase unbalance and reversed phase sequence.
SETTING : 11% of 110 volts i.e., 12.1 volts.

TEST RESULTS:-

Pick-up voltage 12.7 volts


Closing time in seconds 4.81

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 8a

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR EARTH FAULT RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : DG Set – 1 Incoming Relay Make : AREVA

Type / Sl. No. AF 014SACH / 13167591092003 CT Sec. : 5 Amps


An "Over current Relay" is a type of protective relay which operates when the load current exceeds a
preset value. The ANSI Device Designation Number is 50 for an Instantaneous Over Current (IOC), 51 for a
Time Over Current (TOC).

SECONDARY INJECTION TEST:-

OPERATING
CURRENT SETTING CURRENT IN
AMPS
0.50 0.52

0.75 0.77

1.00 0.99

1.25 1.24

1.50 1.54

1.75 1.75

2.00 2.02

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 8b

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR INSTANT DIFFERENTIAL RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : DG Set – 1 Incoming Relay Make : AREVA

Type / Sl. No. 34AF71A / 131511780842001 CT Sec. : 1 Amp


An "Over current Relay" is a type of protective relay which operates when the load current exceeds a
preset value. The ANSI Device Designation Number is 50 for an Instantaneous Over Current (IOC), 51 for a
Time Over Current (TOC).

SECONDARY INJECTION TEST:-

CURRENT OPERATING CURRENT IN AMPS


SETTING
R-PHASE Y-PHASE B-PHASE
0.10 0.11 0.11 0.11

0.15 0.16 0.15 0.15

0.20 0.21 0.22 0.21

0.25 0.25 0.24 0.26

0.30 0.31 0.30 0.31

0.35 0.36 0.36 0.36

0.40 0.41 0.42 0.41

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 9a

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR EARTH FAULT RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : DG Set – 2 Incoming Relay Make : AREVA

Type / Sl. No. AF 014SACH / 13167591092002 CT Sec. : 5 Amps


An "Over current Relay" is a type of protective relay which operates when the load current exceeds a
preset value. The ANSI Device Designation Number is 50 for an Instantaneous Over Current (IOC), 51 for a
Time Over Current (TOC).

SECONDARY INJECTION TEST:-

OPERATING
CURRENT SETTING CURRENT IN
AMPS
0.50 0.51

0.75 0.76

1.00 0.99

1.25 1.26

1.50 1.51

1.75 1.76

2.00 2.02

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Durga Switchgears (A-Grade Electrical Contractors,Consultants & Testing Engineers – EA 2616) Page 9b

Site: M/S LOTTE INDIA CORPORATION LTD., NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD, NEMAM, TIRUVALLUR – 602 107.
TEST REPORT FOR INSTANT DIFFERENTIAL RELAY

Date of Test : 04th January 2019 Location : MV Panel Room

Feeder Name : DG Set – 2 Incoming Relay Make : AREVA

Type / Sl. No. 34AF71A / 131511780842007 CT Sec. : 1 Amp


An "Over current Relay" is a type of protective relay which operates when the load current exceeds a
preset value. The ANSI Device Designation Number is 50 for an Instantaneous Over Current (IOC), 51 for a
Time Over Current (TOC).

SECONDARY INJECTION TEST:-

CURRENT OPERATING CURRENT IN AMPS


SETTING
R-PHASE Y-PHASE B-PHASE
0.10 0.11 0.11 0.11

0.15 0.16 0.16 0.16

0.20 0.21 0.21 0.20

0.25 0.26 0.26 0.26

0.30 0.31 0.31 0.31

0.35 0.36 0.35 0.36

0.40 0.42 0.41 0.41

Remarks: - Test results are satisfactory.

PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
TEST REPORT FOR

TRANSFORMER OIL FILTRATION

MAINTENANCE TESTING OF RELAYS

&

EARTH PITS

AT

M/S LOTTE INDIA CORPORATION LTD.,

NO. 26, POONAMALLE TIRUVALLUR HIGH ROAD,

NEMAM,

TIRUVALLUR – 602 107.

0N

03rd & 04th January 2019

Job carried out by : DURGA SWITCHGEARS


EA 2616 -- A Grade Electrical Contractors,Consultants & Testing Engineers
No. 8/5, John Vasu Street,
Madhavaram Milk Colony,
Chennai – 600 051
Cell: 98843 20732