TRANSFORMER

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 1


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : durgaswitchgears@yahoo.co.in

DATE OF TEST: 29TH SEP. 2013


TRANSFORMER NO. 1 --- OIL TEST REPORT
NAME OF THE CONSUMER : M/S. ESI HOSPITAL,
K.K.NAGAR, CHENNAI – 600 078.

Make : Electric Transformer & Equipment Co. Ltd.,


Rating : 500 KVA
Phase : 3 Phases
Serial number : 8119
Voltage Primary voltage : 11000 VOLTS
Seconday Voltage : 433 VOLTS
Current HV current : 26.23 AMPS
LV current : 666.7 AMPS
Oil quantity : 600 Liters
Year of manufacturing : 1976
BREAK DOWN VOLTAGE TEST RESULT (TEST GAP 2.5 MM)
Before Oil Filtration
Top sample : Oil withstood 30 KV level.
Bottom sample : Oil withstood 29 KV level.

After Oil Filtration


Top sample : Oil withstood 40 KV for One Minute
Oil Flashed at 55KV.
Bottom sample : Oil withstood 40 KV for One Minute.
Oil Flashed at 56KV
Oil filtration carried out on &
Break down voltage tested on : 29.09.2013

Oil filtration Due & Break


Down voltage test due on : 29.09.2014

Acidity test result : 0.19 mg OF KOH PER GRAM

Tested as per For Durga Switchgears

        IS: 335: 1972 Authorized signatory


TIN 33251085384 DURGA SWITCHGEARS
CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 2


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : durgaswitchgears@yahoo.co.in

DATE OF TEST: 29TH SEP. 2013


TRANSFORMER NO. 2 --- OIL TEST REPORT
NAME OF THE CONSUMER : M/S. ESI HOSPITAL,
K.K.NAGAR, CHENNAI – 600 078.

Make : Electric Transformer & Equipment Co. Ltd.,


Rating : 500 KVA
Phase : 3 Phases
Serial number : 8118
Voltage Primary voltage : 11000 VOLTS
Seconday Voltage : 433 VOLTS
Current HV current : 26.23 AMPS
LV current : 666.7 AMPS
Oil quantity : 600 Liters
Year of manufacturing : 1976
BREAK DOWN VOLTAGE TEST RESULT (TEST GAP 2.5 MM)
Before Oil Filtration
Top sample : Oil withstood 30 KV level.
Bottom sample : Oil withstood 27 KV level.

After Oil Filtration


Top sample : Oil withstood 40 KV for One Minute
Oil Flashed at 56 KV.
Bottom sample : Oil withstood 40 KV for One Minute.
Oil Flashed at 56 KV
Oil filtration carried out on &
Break down voltage tested on : 29.09.2013

Oil filtration Due & Break


Down voltage test due on : 29.09.2014

Acidity test result : 0.18 mg OF KOH PER GRAM

Tested as per For Durga Switchgears


        IS: 335: 1972 Authorized signatory
HT VACUUM CIRCUIT BREAKER

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 3a


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : durgaswitchgears@yahoo.co.in

DATE OF TEST: 29TH SEP. 2013


TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
TO
M/S. ESI HOSPITAL, Breaker Sl. No. 03922112009
K.K.NAGAR, CHENNAI – 600 078.
Breaker Make System Control
Type Sysvac /1280025
Rating 630 Amps
Uv 11KV
Title Transformer No. 1
S.NO. DESCRIPTION TYPE OF CHECK CHECKED REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Opening ELECTRICAL FOR


PERFORMANCE OK

4 CONTACT PENETRATION FOR VISUAL (Moving contact FOR ABNORMALITY OK


VCB mechanism only)

VCB CLOSED VCB OPEN


5 INSULATION RESISTANCE CONDITION CONDITION
R-E > 200 M Ω R I/C – R O/G
Y-E > 200 M Ω > 200 M Ω
B-E > 200 M Ω Y I/C – Y O/
R-Y > 200 M Ω > 200 M Ω
Y-B > 200 M Ω B I/C – B O/G
B-R > 200 M Ω > 200 M Ω

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS
8/5, JOHN VASU STREET, Mobile : 9884320732 Page 3b
MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : durgaswitchgears@yahoo.co.in

DATE OF TEST: 29TH SEP. 2013


TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
TO
M/S. ESI HOSPITAL, Breaker Sl. No. 03922112009
K.K.NAGAR, CHENNAI – 600 078.
Breaker Make System Control
Type Sysvac /1280025
Rating 630 Amps
Uv 11KV
Title Transformer No. 1

2) Contact Resistance Test:-

Phase Ref DC Current DC Volts Across Resistance


Applied Terminal
R-Phase 100 Amps 4.60mv 46 Micro Ohms
Y-Phase 100 Amps 4.40 mv 44 Micro Ohms
B-Phase 100 Amps 4.50 mv 45 Micro Ohms

3) Breaker Timing Test:-

Ref Closing Time in Opening Time in


milli secs. milli secs
R-Phase 132 80
Y-Phase 133 79
B-Phase 135 81

Test kit Details: Relay Test Kit IR Value Tester (1000V) Tong Tester
MAKE : ANANDHA JOTHI MAKE : CIE MAKE : VARTECH
Serial No: 01410 Serial No. :36308-6/11/PD Serial No.: 09060043630

Timer Kit
Make : ANANDHA JOTHI
SerialNo. : 11005

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 4a


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : durgaswitchgears@yahoo.co.in
DATE OF TEST: 29TH SEP. 2013
TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
TO
M/S. ESI HOSPITAL, Breaker Sl. No. 03923112009
K.K.NAGAR, CHENNAI – 600 078.
Breaker Make System Control
Type Sysvac /1280025
Rating 630 Amps
Uv 11KV
Title Transformer No. 2
S.NO. DESCRIPTION TYPE OF CHECK CHECKED REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Opening ELECTRICAL FOR


PERFORMANCE OK

4 CONTACT PENETRATION FOR VISUAL (Moving contact FOR ABNORMALITY OK


VCB mechanism only)

VCB CLOSED VCB OPEN


5 INSULATION RESISTANCE CONDITION CONDITION
R-E > 200 M Ω R I/C – R O/G
Y-E > 200 M Ω > 200 M Ω
B-E > 200 M Ω Y I/C – Y O/
R-Y > 200 M Ω > 200 M Ω
Y-B > 200 M Ω B I/C – B O/G
B-R > 200 M Ω > 200 M Ω

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 4b


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : durgaswitchgears@yahoo.co.in

DATE OF TEST: 29TH SEP. 2013


TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
TO
M/S. ESI HOSPITAL, Breaker Sl. No. 03923112009
K.K.NAGAR, CHENNAI – 600 078.
Breaker Make System Control
Type Sysvac /1280025
Rating 630 Amps
Uv 11KV
2) Contact Resistance Test:- Title Transformer No. 2

Phase Ref DC Current DC Volts Across Resistance


Applied Terminal
R-Phase 100 Amps 4.30 mv 43 Micro Ohms
Y-Phase 100 Amps 4.40mv 44 Micro Ohms
B-Phase 100 Amps 4.50 mv 45 Micro Ohms

3) Breaker Timing Test:-

Ref Closing Time in Opening Time in


milli secs. milli secs
R-Phase 125 79
Y-Phase 127 78
B-Phase 126 79

Test kit Details: Relay Test Kit IR Value Tester (1000V) Tong Tester
MAKE : ANANDHA JOTHI MAKE : CIE MAKE : VARTECH
Serial No: 01410 Serial No. :36308-6/11/PD Serial No.: 09060043630

Timer Kit
Make : ANANDHA JOTHI
SerialNo. : 11005
EA 2616– Durga Switchgears Page 5
Client: M/S. ESI HOSPITAL, K.K.NAGAR, CHENNAI – 600 078
EARTH RESISTANCE TEST REPORT

Date of Test : 29th Sep. 2013

S.NO TEST REPORT


DURGA SWITCHGEARS
DESCRIPTION FOR
LOCATION
Individual Combined
Resistance
EA 2616 -- A Grade Electrical Contractors Resistance
INDEX in Ohms in Ohms
1. Transformer Neutral EarthTRANSFORMER
-1 Outdoor Area
OIL 1.98 0.40
2. Transformer Neutral Earth -2 2.04
3.
S NO
HT Panel Body Earth -1
DESCRIPTION PAGE
2.89
NO.0.40
0.40
&
1 500kva Transformer - 1 1a – 1b
2 500kva Transformer - 2 2a – 2e
HT VACUUM CIRCUIT BREAKERS
3 3a – 3e
4 4a
AT
5 5a
6 6a – 6b
7 7a – 7b
M/S ESI Hospital,

KK Nagar, Chennai – 600 078.

On

29th Sep. 2013

TESTED WITH WACO Make Digital Earth Tester


Sl. No. : 50388
Remarks: - Test results are satisfactory.
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Job carried out by : DURGA SWITCHGEARS
EA 2616 A-Grade Electrical Contractors
No. 8/5, John Vasu Street,
Madhavaram Milk Colony,
Chennai – 600 051