66 KVTransformer 2 Page
|2
Nameplate Data:
Test Results:
Test
Sr. No: Description T (C) f (Hz) U (KV) C (pF) %TanD %TanD@20C
Mode
1 UST-R 30 50 2 245.2 0.340 0.235
HV Bushing R Phase
2 UST-R 30 50 10 245.2 0.340 0.235
3 UST-R 30 50 2 241.6 0.255 0.176
HV Bushing Y Phase
4 UST-R 30 50 10 241.6 0.242 0.167
5 UST-R 30 50 2 248.2 0.382 0.264
HV Bushing B Phase
6 UST-R 30 50 10 248.2 0.308 0.213
7 UST-R 30 50 2 4448 0.434 0.299
HV to LV
8 UST-R 30 50 10 4449 0.289 0.199
9 GST-G 30 50 2 2611 0.341 0.235
HV to Ground
10 GST-G 30 50 10 2610 0.425 0.293
11 GST-G 30 50 2 7503 0.321 0.221
LV to Earth
12 GST-G 30 50 10 7493 0.417 0.288
Apply 2 - 440 volts on H.V. terminals and L.V. keep open at tap no.5
L.V Side:
Apply-1- 230 Volts on L.V. Terminals and H.V keep open at tap no.5
Page
Apply 3-ph 440 Volts on H.V. terminals and keep 1U-2U. Shorted (TAP-5) |6
Measured Voltage:
1U-1V=402
1V-1W=405
1W-1U=401
1W-2w= 346
1W-2v= 406
1V-2v=343
1V-2w= 342
1U-2n=38.5
1V-2n= 362
Conditions:
1) 1W-2w<1W-2v
346<406
2) 1V-2v=1V-2w
343342
3) 1U-2n+1V-2n=1U-1V
38.5+362=405(400.5)
LV Winding
1 Minute 10 Minute PI
HV to LV 7.92 15.8 1.99
HV to Earth 5.87 9.68 1.64
LV to Earth 6.15 12.7 2.07