1.0 NAME PLATE DETAILS :


Make VOLTAMP Vector Group YNd1
Serial No. 22505/1 % Impedance 7.648/9.56
Rating in KVA 16/20 KVA Tap Changer OLTC
Voltage Ratio 66/11 KV No. Of Taps 9
Current Ratio 139.96/839.78 MFG Date 2015
Type of Cooling ONAN/ONAN

2.0 INSULATION RESISTANCE TEST AND PI TEST : Megger Used : 5 KV


Range : > 1 T-
H. V. – L.V In 1 minute In 10 minutes
5 KV 7.561 GΩ 13.26 GΩ

L. V. – H.V&E In 1 minute In 10 minutes


L.V - E 2.4 GΩ 9.51 GΩ
H.V - E 10.99 GΩ 12.75 GΩ

3.0 VOLTAGE RATIO & TAP CONTINUITY TEST :


Measured voltage on LV Side
Tap Position RY YB BR RN YN BN ry yb br Tap continuity
1 234.9 236.3 235.5 64.4 64.7 69.5 OK.
2 235.1 236.9 235.9 66.7 66.5 66.5 OK.
3 237.3 237.6 237.0 68.8 68.4 68.3 OK.
4 235.8 236.6 235.4 69.7 69.8 69.8 OK.
5 405 405 400 235.4 236.7 235.8 71.4 71.7 71.6 OK.
6 235.6 236.6 235.6 73.4 73.5 73.6 OK.
7 235.4 236.5 235.4 75.5 75.6 75.4 OK.
8 235.1 236.5 235.3 77.5 77.8 77.5 OK.
9 235.1 236.5 235.3 79.8 80.2 77.9 OK.

4.0 MAGNETIC BALANCE TEST : at tap -2


Supply Voltage (HV Side) Voltage Measured (LV Side)
R-Y (V) Y-B (V) B-R (V) R-N (V) Y-N (V) B-N (V) r-y (V) y-b (V) b-r (V)
408 302.6 109.4 237.7 173.3 63.9 68.4 49.9 18.6
231.0 408.0 180.0 16.35 213.2 197.1 4.76 61.4 56.7
97.6 310.3 406 169.2 70.5 239.5 48.6 20.48 69.2

Witnessed/ Reviewed by NS Engineers


Signature
Name
1
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

5.0 MAGNETIZATION CURRENT TEST


HV Side
Tap
R Y B
1 6.1 mA 8.2 mA 10.8 mA
3 6.7 mA 8.1 mA 11.3 mA
9 8.6 mA 11.9 mA 15.3 mA

6.0 VECTOR GROUP TEST :


Short 1U-2U and apply Voltage Applied on HT side.
1U-2V 65.3 V 1V-2W 413 V 1W-2W 353 V

1U-1N 234.8 V 1V-2V 357 V 1W-2V 357 V

2V-1N 169.9
1U2V + 2V1N = 1U1N 1W2W < 1V2W 1W2V = 1V2V

65.3 + 168.7 = 234.8 353 < 413 357 = 357

7.0 SHORT CIRCUIT TEST :


APPLY VOLTAGE HV SIDE
R-Y PHASE R-Y PHASE R-Y PHASE
406 406 406

MEASURED CURRENT HV SIDE MEASURED CURRENT LV SIDE


TAP R Phase Y Phase B Phase LV Star Point Current
3 10.7 A 10.9 A 10.6 A 65.8 A

8.0 H.V. SIDE WINDING RESISTANCE TEST:


Tap Position R-N (mΩ) Y-N (mΩ) B-N (mΩ) Tap continuity
1 648.9 578.4 576.0 OK.
2 607.9 560.5 565.8 OK.
3 590.9 549.1 554.8 OK.
4 565.2 536.5 539.3 OK.
5 575.8 524.3 525.8 OK.
6 539.3 504.6 500.0 OK.
7 570.2 483.6 491.1 OK.
8 512.3 471.7 485.6 OK.
9 540.8 462.7 474.9 OK.

9.0 L.V. SIDE WINDING RESISTANCE TEST:


Tap Position r-y (mΩ) y-b (mΩ) b-r (mΩ) Tap continuity
3 22.7 22.8 22.8 OK

Witnessed/ Reviewed by NS Engineers


Signature
Name
2
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

10.0 CONFORMITY TESTS :


1 Visual External damage to any part of the transformer Found OK.
2 Color of silica jell / oil level in bottom seal/Leakage if any Found OK.
3 Proper Connections of body and neutral earthling Found OK.
4 Buchholz relay test for alarm/trip contact float operations Found OK.
5 Winding/oil temperature indicator alarm/trip contact operations Found OK.
6 MOG float switch contact operation Found OK.
7 Local / remote operations of OLTC Found OK.
8 Cooling System Found OK.
9 NGR Found OK.

11.0 REMARKS :
 HV NEUTRAL BUSSING OIL LEAKAGE.
 OIL LEAKAGE IN SIDE L.V TERMINAL BOX.
 TRANSFORMER BODY OIL LEAKAGE IN READIATOR SIDE.

Witnessed/ Reviewed by NS Engineers


Signature
Name
3
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF TRANSFORMER NS ENGINEERS, AHMEDABAD


Client KBC SHP 1 & 2 Tested On 07/03/2023
Plant 66KV S/S SHP – 1 Tested By RP/MM/UT
Location TRANSFORMER - 2 Comp. Code

1.0 NAME PLATE DETAILS :


Make VOLTAMP Vector Group YNd1
Serial No. 22505/2 % Impedance 7.592/9.49
Rating in KVA 16/20 KVA Tap Changer OLTC
Voltage Ratio 66/11 KV No. Of Taps 9
Current Ratio 139.96/839.78 MFG Date 2015
Type of Cooling ONAN/ONAN

2.0 INSULATION RESISTANCE TEST AND PI TEST: Megger Used : 5 KV


Range : > 1 T-
H. V. – L.V. In 1 minute In 10 minutes
5 KV 8.914 GΩ 12.36 GΩ
L. V. – H.V&E In 1 minute In 10 minutes
L.V - E 903.4 MΩ 11.64 GΩ
H.V - E 13.78 GΩ 14.43 GΩ

3.0 VOLTAGE RATIO & TAP CONTINUITY TEST :


Measured voltage on LV Side
Tap Tap
RY YB BR RN YN BN ry yb br
Position continuity
1 238.6 239.5 238.6 65.4 65.6 65.4 OK.
2 238.8 239.3 238.8 66.7 67.2 67.0 OK.
3 238.1 239.6 238.1 68.8 69 68.7 OK.
4 238.2 239.4 238.3 70.5 70.7 70.4 OK.
5 405 405 400 238.5 239.8 238.9 72.4 72.6 72.3 OK.
6 238.7 239.2 238.5 74.4 74.6 74.4 OK.
7 238.3 239.1 238.5 76.5 76.8 76.6 OK.
8 238.5 239.9 238.2 79.1 79.3 79.2 OK.
9 238.4 239.7 238.4 81.4 81.6 81.3 OK.

4.0 MAGNETIC BALANCE TEST : at tap -2


Supply Voltage (HV Side) Voltage Measured (LV Side)
R-Y (V) Y-B (V) B-R (V) R-N (V) Y-N (V) B-N (V) r-y (V) y-b (V) b-r (V)
408 302.6 109.4 237.7 208.2 28.7 66.6 58.7 7.99
231.0 408.0 180.0 124.6 237.6 113 35.13 66.8 31.9
97.6 310.3 406 32.9 204.2 236.8 9.2 57.4 66.5

Witnessed/ Reviewed by NS Engineers


Signature
Name
4
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

5.0 MAGNETIZATION CURRENT TEST


HV Side
Tap
R Y B
1 1.2 mA 2.7 mA 3.8 mA
3 4.1 mA 1.9 mA 3.7 mA
9 3.6 mA 2.0 mA 6.1 mA

6.0 VECTOR GROUP TEST :


Short 1U-2U and apply Voltage Applied on HT side.
1U-2V 66.4 V 1V-2W 415 V 1W-2W 353 V
1U-1N 236.8 V 1V-2V 356 V 1W-2V 355 V
2V-1N 169.9
1U2V + 2V1N = 1U1N 1W2W < 1V2W 1W2V = 1V2V
66.4 + 169.9 = 236.8 355 < 415 355 = 356

7.0 SHORT CIRCUIT TEST :


APPLY VOLTAGE HV SIDE
R-Y PHASE R-Y PHASE R-Y PHASE
406 406 406

MEASURED CURRENT HV SIDE MEASURED CURRENT LV SIDE


TAP R Phase Y Phase B Phase LV Star Point Current
3 10.5 A 10.3 A 10.2 A 64.6 A

8.0 H.V. SIDE WINDING RESISTANCE TEST:


Tap Position R-N (mΩ) Y-N (mΩ) B-N (mΩ) Tap continuity
1 552.4 546.9 550.1 OK.
2 536.9 533.4 536.0 OK.
3 520.9 520.4 521.5 OK.
4 513.5 506.3 509.6 OK.
5 495.5 493.2 494.9 OK.
6 481.4 479.4 481.7 OK.
7 471.0 473.0 469.8 OK.
8 459.1 452.3 454.9 OK.
9 466.0 439.1 441.6 OK.

9.0 L.V. SIDE WINDING RESISTANCE TEST:


Tap Position r-y (mΩ) y-b (mΩ) b-r (mΩ) Tap continuity
3 23.2 23.1 23.2 OK

Witnessed/ Reviewed by NS Engineers


Signature
Name
5
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

10.0 CONFORMITY TESTS :


1 Visual External damage to any part of the transformer Found OK.
2 Color of silica jell / oil level in bottom seal/Leakage if any Found OK.
3 Proper Connections of body and neutral earthling Found OK.
4 Buchholz relay test for alarm/trip contact float operations Found OK.
5 Winding/oil temperature indicator alarm/trip contact operations Found OK.
6 MOG float switch contact operation Found OK.
7 Local / remote operations of OLTC Found OK.
8 Cooling System Found OK.
9 NGR Found OK.

11.0 REMARKS : Tested and Found Healthy.

Witnessed/ Reviewed by NS Engineers


Signature
Name
6
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF HT SWITCHGEAR PANEL NS ENGINEERS


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 09/03/2023
Bay SHP-1 66KV SWITCHYARD Tested by MM/RJ/UT
Location CVT LINE-1 TC. No.

1.0 CVT SPECIFICATION AND NAME PLATE DETAILS:


Phase Make Mfg. Year Sr. No.
R MEHRU 2016/1 OCVT 6091/6/5/16
Y MEHRU 2016/1 OCVT 6091/6/3/16
B MEHRU 2016/1 OCVT 6091/6/4/16
Core CVT Ratio VA Of Core Class of core
1 66KV/√3/110V/√3 100 0.2
2 66KV/√3/110V/√3 100 3P
3 66KV/√3/110V/√3 100 0.2

1.1 INSULATION RESISTANCE TEST :


Megger Used Make Sr. No.
5KV SONAL CU1664

1.2 Primary to Earth &Primary to Secondary Applied Voltage 5KV


Phase reference
Core reference
R Y B
Primary – Earth 110.2 GΩ 377.2 GΩ 370.0 GΩ
Phase reference
Core reference
R Y B
Primary - Core – I 204.89 GΩ 29.4 GΩ 37.25 GΩ
Primary - Core – II 255 GΩ 54.50 GΩ 68.39 GΩ
Primary - Core – III 147.4 GΩ 642.44 GΩ 266.3 GΩ

1.3 Secondary to Earth Applied Voltage :500V


Phase reference
Core reference
R Y B
Core – I – Earth 10.23 GΩ 28.12 GΩ 31.30 GΩ
Core – II – Earth 44.51 GΩ 59.63 GΩ 54.45 GΩ
Core – III – Earth 84.43 GΩ 73.41 GΩ 56.09 GΩ

1.4 Secondary to Secondary Applied Voltage:500V


Phase reference
Core reference
R Y B
Core – I to Core – II 65.23 GΩ 48.33 GΩ 105.8 GΩ
Core – II to Core – III 49.99 GΩ 75.22 GΩ 85.85 GΩ
Core – III to Core – I 49.54 GΩ 50.37 GΩ 65.26 GΩ

2.0 CVT POLARITY TEST:


Witnessed/ Reviewed by NS Engineers
Signature
Name
7
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

Connect + ve at P1 and –ve at N


Phase reference
Core Ratio Terminal
R Y B
Core I 66KV/√3/110V/√3 1a-1n Forward Forward Forward
Core II 66KV/√3/110V/√3 2a-2n Forward Forward Forward
Core III 66KV/√3/110V/√3 3a-3n Forward Forward Forward

2.1 CVT. RATIO TEST:


Applied voltage- 415V
Core Ratio Terminal
R Y B
Core I 66KV/√3/110V/√3 1a-1n 0.39 0.39 0.39
Core II 66KV/√3/110V/√3 2a-2n 0.39 0.39 0.39
Core III 66KV/√3/110V/√3 3a-3n 0.39 0.39 0.39

2.2 WINDING RESISTANCE


Phase reference
Core Ratio Terminal
R Y B
Core I 66KV/√3/110V/√3 1a-1n 250 mΩ 205 mΩ 255 mΩ
Core II 66KV/√3/110V/√3 2a-2n 227 mΩ 190 mΩ 235 mΩ
Core III 66KV/√3/110V/√3 3a-3n 215 mΩ 178 mΩ 216 mΩ

3.0 REMARKS : Tested and found Healthy.

Witnessed/ Reviewed by NS Engineers


Signature
Name
8
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF HT SWITCHGEAR PANEL NS ENGINEERS


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 09/03/2023
Bay SHP-1 66KV SWITCHYARD Tested by MM/RJ/UT
Location CVT LINE-2 Sr. No.

1.0 CVT SPECIFICATION AND NAME PLATE DETAILS:


Phase Make Mfg. Year Sr. No.
R MEHRU 2016/1 OCVT 6091/6/1/16
Y MEHRU 2016/1 OCVT 6091/6/2/16
B MEHRU 2016/1 OCVT 6091/6/6/16
Core CVT Ratio VA Of Core Class of core
1 66KV/√3/110V/√3 100 0.2
2 66KV/√3/110V/√3 100 3P
3 66KV/√3/110V/√3 100 0.2

1.1 INSULATION RESISTANCE TEST :


Megger Used Make Sr. No.
5KV SONAL CU1664

1.2 Primary to Earth &Primary to Secondary Applied Voltage 5KV


Phase reference
Core reference
R Y B
Primary – Earth 32.33 GΩ 29.03 GΩ 26.66 GΩ
Phase reference
Core reference
R Y B
Primary - Core – I 140.9 GΩ 148.9 GΩ 55.87 GΩ
Primary - Core – II 163.3 GΩ 186.2 GΩ 54.87 GΩ
Primary - Core – III 77.61 GΩ 260.1 GΩ 78.92 GΩ

1.3 Secondary to Earth Applied Voltage :500V


Phase reference
Core reference
R Y B
Core – I – Earth 9.85 GΩ 26.72 GΩ 35.60 GΩ
Core – II – Earth 24.59 GΩ 49.69 GΩ 44.41 GΩ
Core – III – Earth 74.53 GΩ 63.51 GΩ 46.19 GΩ

1.4 Secondary to Secondary Applied Voltage:500V


Phase reference
Core reference
R Y B
Core – I to Core – II 35.21 GΩ 58.31 GΩ 111.6 GΩ
Core – II to Core – III 29.92 GΩ 45.22 GΩ 85.89 GΩ
Core – III to Core – I 39.54 GΩ 30.37 GΩ 75.26 GΩ

2.0 CVT POLARITY TEST: Connect + ve at P1 and –ve at N

Witnessed/ Reviewed by NS Engineers

Signature

Name
9
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

Phase reference
Core Ratio Terminal
R Y B
Core I 66KV/√3/110V/√3 1a-1n Forward Forward Forward
Core II 66KV/√3/110V/√3 2a-2n Forward Forward Forward
Core III 66KV/√3/110V/√3 3a-3n Forward Forward Forward

2.1 CVT. RATIO TEST:


Applied voltage- 415V
Core Ratio Terminal
R Y B
Core I 66KV/√3/110V/√3 1a-1n 0.39 V 0.39 V 0.39 V
Core II 66KV/√3/110V/√3 2a-2n 0.40 V 0.39 V 0.40 V
Core III 66KV/√3/110V/√3 3a-3n 0.39 V 0.40 V 0.39 V

2.2 WINDING RESISTANCE


Phase reference
Core Ratio Terminal
R Y B
Core I 66KV/√3/110V/√3 1a-1n 263 mΩ 213 mΩ 276 mΩ
Core II 66KV/√3/110V/√3 2a-2n 239 mΩ 229 mΩ 253 mΩ
Core III 66KV/√3/110V/√3 3a-3n 210 mΩ 186 mΩ 223 mΩ

3.0 REMARKS : Tested and Found Healthy.

Witnessed/ Reviewed by NS Engineers

Signature

Name
10
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF HT SWITCHGEAR PANEL NS ENGINEERS


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 06/03/2023
Bay SHP-1 11KV HT PANAL ROOM Tested by MM/RJ/UT
Location P-5, BUS PT-1 Sr. No.

1.0 P.T. SPECIFICATION AND NAME PLATE DETAILS:


Phase Make Mfg. Year Sr. No.
R INSTRANS 2016/1 Z22689
Y INSTRANS 2016/1 Z22685
B INSTRANS 2016/1 Z22687
Core P.T. Ratio VA Of Core Class of core
1 11KV/√2/110V/√3 100 3P
2 11KV/√2/110V/√3 100 0.2
3 11KV/√2/110V/√3 100 3P

1.1 INSULATION RESISTANCE TEST :


Megger Used Make Sr. No.
5KV SONAL CU1664

1.2 Primary to Earth &Primary to Secondary Applied Voltage 5KV


Core reference Phase reference
R Y B
Primary – Earth 81.00 GΩ 61.77 GΩ 66.08 GΩ
Core reference Phase reference
R Y B
Primary - Core – I 145 GΩ 218.0 GΩ 331.4 GΩ
Primary - Core – II 63.0 GΩ 120.4 GΩ 846.4 GΩ
Primary - Core – III 33.86 GΩ 397 GΩ 212.52 GΩ

1.3 Secondary to Earth Applied Voltage :500V


Core reference Phase reference
R Y B
Core – I – Earth 23.55 GΩ 14.04 GΩ 40.2 GΩ
Core – II – Earth 26.84 GΩ 7.420 GΩ 50.6 GΩ
Core – III – Earth 23.09 GΩ 21.84 GΩ 22.77 GΩ

1.4 Secondary to Secondary Applied Voltage:500V


Core reference Phase reference
R Y B
Core – I to Core – II 62.3 GΩ 65.3 GΩ 68.7 GΩ
Core – II to Core – III 52.0 GΩ 65.5 GΩ 55.2 GΩ
Core – III to Core – I 55.1 GΩ 54.1 GΩ 46.3 GΩ

2.0 P.T. POLARITY TEST:

Witnessed/ Reviewed by NS Engineers

Signature

Name
11
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

Connect + ve at P1 and –ve at N


Phase reference
Core Ratio Terminal
R Y B
Core I 11KV/√2/110V/√3 1a-1n Forward Forward Forward
Core II 11KV/√2/110V/√3 2a-2n Forward Forward Forward
Core III 11KV/√2/110V/√3 3a-3n Forward Forward Forward

2.1 P.T. RATIO TEST:


Applied voltage-500v Applied voltage-1000v
Core Ratio Terminal
R Y B R Y B
Core I 11KV/√2/110V/√3 1a-1n 5.01 5.04 5.04 10.08 10.02 10.03
Core II 11KV/√2/110V/√3 2a-2n 5.03 5.01 5.02 10.09 10.04 10.05
Core III 11KV/√2/110V/√3 3a-3n 5.01 5.03 5.03 10.05 10.09 10.07

2.2 WINDING RESISTANCE


Phase reference
Core Ratio Terminal
R Y B
Core I 11KV/√2/110V/√3 1a-1n 64.1 mΩ 57.5 mΩ 65.3 mΩ
Core II 11KV/√2/110V/√3 2a-2n 471 mΩ 470 mΩ 485 mΩ
Core III 11KV/√2/110V/√3 3a-3n 486 mΩ 490 mΩ 490 mΩ

3.0 SECONDARY INJECTION TESTING OF PROTECTIVE RELAYS CONDUCTED AND REPORTS


ENCLOSED :

4.0 REMARKS : Tested and found Healthy.

Witnessed/ Reviewed by NS Engineers

Signature

Name
12
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF HT SWITCHGEAR PANEL NS ENGINEERS


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 09/03/2023
Bay KBC SHP-1, 11KV HT PANAL ROOM Tested by MM/RJ/UJS
Location P-8, BUS PT-2 TC. No.

1.0 P.T. SPECIFICATION AND NAME PLATE DETAILS:


Phase Make Mfg. Year Sr. No.
R INSTRANS 2016/1 Z22688
Y INSTRANS 2016/1 Z22684
B INSTRANS 2016/1 Z22686
Core P.T. Ratio VA Of Core Class of core
1 11KV/√3/110V/√3 100 3P
2 11KV/√3/110V/√3 100 0.2
3 11KV/√3/110V/√3 100 3P

1.1 INSULATION RESISTANCE TEST :


Megger Used Make Sr. No.
5KV SONAL CU1664

1.2 Primary to Earth &Primary to Secondary Applied Voltage 5KV


Core reference Phase reference
R Y B
Primary – Earth 1.152 TΩ 115.4 GΩ 243.1GΩ
Core reference reference Phase
R Y B
Primary - Core – I 681.7 GΩ 313.0 GΩ 537.8 GΩ
Primary - Core – II 294.6 GΩ 392.6 GΩ 307. 1 GΩ
Primary - Core – III 250.7 GΩ 280.97 GΩ 392.6 GΩ

1.3 Secondary to Earth Applied Voltage :500V

Core reference Phase reference


R Y B
Core – I – Earth 426.7 GΩ 356.8 GΩ 412.6 GΩ
Core – II – Earth 412.2 GΩ 432.9 GΩ 465.5 GΩ
Core – III – Earth 311.1 GΩ 296.8 GΩ 302.8 GΩ

Witnessed/ Reviewed by NS Engineers

Signature

Name
13
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

1.4 Secondary to Secondary Applied Voltage:500V


Core reference Phase reference
R Y B
Core – I to Core – II 72.5 GΩ 49.6 GΩ 52.4 GΩ
Core – I to Core – III 56.3 GΩ 52.8 GΩ 55.6 GΩ
Core – III to Core – I 45.9 GΩ 65.2 GΩ 48.1 GΩ

2.0 P.T. Polarity Test: Connect + ve at P1 and –ve at N


Phase reference
Core Ratio Terminal
R Y B
Core I 11KV/110V 2a-2n Forward Forward Forward
Core II 11KV/110V 1a-1n Forward Forward Forward
Core III 11KV/110V 3a-3n Forward Forward Forward

2.1 P.T. Ratio Test:


Applied Voltage-500 Applied Voltage-1000
Core Ratio Terminal
R Y B R Y B
Core I 11KV/110V 2a-2n 5.06 5.06 5.06 10.01 10.01 10.01

Core II 11KV/110V 1a-1n 5.06 5.06 5.06 10.01 10.01 10.01

Core III 11KV/110V 3a-3n 5.06 5.06 5.06 10.01 10.01 10.01

3.0 Winding Resistance:


Phase reference
Core Ratio Terminal
R Y B
Core I 11KV/110V 2a-2n 476 mΩ 474 mΩ 472 mΩ
Core II 11KV/110V 1a-1n 59 mΩ 55 mΩ 58 mΩ
Core III 11KV/110V 3a-3n 487 mΩ 486 mΩ 487 mΩ

4.0 REMARKS : Tested and Found Healthy.

Witnessed/ Reviewed by NS Engineers

Signature

Name
14
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF CURRENT TRANSFORMER NS Engineers, Ahmedabad


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 28/02/2023
Plant KBC SHP – 1 SWITCH YARD Tested by MM/MP/RP
Location 66KV TR-1 CT TC NO.

1.0 C.T. Specification and Name Plate Details: -


Phase Make Mfg. Year Sr. No.
R MEHRU 2016 OC 6091/2/3/16
Y MEHRU 2016 OC 6091/2/4/16
B MEHRU 2016 OC 6091/2/6/16

VA Of Class of Knee Point I ext (max) at


Core C.T. Ratio Rct (Ω)
Core core Voltage VK
1 200/1 20 0.2 - - -
2 200/1 20 5P - - -
3 200/1 - PS 200V 30mA 5Ω

2.0 Insulation Resistance Test: -


Megger Used Make Sr. No.
0-5 KV, ≥ 5TΩ SONEL CU1664

2.1 Primary to Earth & Primary to Secondary: - Applied Voltage: - 5KV


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary – Earth 24.68 21.71 8.13
Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary - Core – I 46.06 41.41 34.69
Primary - Core – II 91.52 42.56 34.85

2.2 Secondary to Earth: - Applied Voltage:- 500V


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Core – I – Earth 15.78 17.74 8.35
Core – II – Earth 19.64 18.27 15.40

2.3 Secondary Winding Resistance:


Core Ratio R (Ω) Y (Ω) B (Ω)
1S1-1S2 20/1A 2.6 2.7 2.5
2S1-2S2 20/1A 1.9 1.7 1.9

3.0 C.T. Polarity Test:


Connect + ve at P1 and –ve at P2
Core Ratio Terminal Phase reference
Witnessed/ Reviewed by NS Engineers
Signature
Name
15
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

R Y B
Core I 200/1 1S1-1S3 Forward Forward Forward
Core II 200/1 2S1-2S3 Forward Forward Forward

3.1 C.T. Ratio Test:


Primary Measured Secondary Current IS
Core Ratio Terminal Applied
Current IP R (A) Y (A) B (A)

Core I 200/1 1S1-1S3 100 A 0.51 0.52 0.51


Core II 200/1 2S1-2S3 200 A 1.02 1.03 1.02

4.0 Magnetization Characteristics Test:


Reference Phase reference
Knee Point Applied Voltage Leakage Current Ma
Core
Voltage (V) R(mA) Y(mA) B(mA)
20 4.7 4.7 3.4
40 6.5 6.5 5.3
60 7.7 7.8 6.5
80 8.6 8.5 7.6
100 9.4 9.2 8.6
3S1-3S2 120 10.2 10.3 9.4
200V 140 10.8 11.6 10.3
160 11.9 12.7 11.4
180 13.1 14.3 12.4
200 14.7 16.4 13.8
220 16.4 18.8 15.6

Knee - point Voltage Kpv =200 V


Excitation - current Iex VK/2 =30 mA

4.0 REMARKS : Tested and Found Healthy.

Witnessed/ Reviewed by NS Engineers


Signature
Name
16
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF CURRENT TRANSFORMER NS ENGINEERS


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 07/03/2023
Plant KBC SHP – 1 SWITCH YARD Tested by MM/MP/RP
Location CT-20 JB 66KV LINE-2 TC. No.

1.0 C.T. Specification and Name Plate Details: -


Phase Make Mfg. Year Sr. No.
R MEHRU 2016 OC 6091/1/2/16
Y MEHRU 2016 OC 6091/1/5/16
B MEHRU 2016 OC 6091/1/1/16

VA Of Class of Knee Point I ext (max) at


Core C.T. Ratio Rct (Ω)
Core core Voltage VK
1 200/1 20 0.2 - - -
2 200/1 20 5P - - -
3 200/1 - PS 200V 30mA 5Ω

2.0 INSULATION RESISTANCE TEST: -


Megger Used Make Sr. No.
0-5 KV, ≥ 5TΩ SONEL CU1664

2.1 Primary to Earth & Primary to Secondary: - Applied Voltage: - 5KV


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary – Earth 8.809 5.377 5.833
Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary - Core – I 117.1 43.34 26.2
Primary - Core – II 28.23 38.56 28.90

2.2 Secondary to Earth: - Applied Voltage: - 500V


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Core – I – Earth 28.66 26.78 26.7
Core – II – Earth 127.9 36.84 20.90

2.3 Secondary Winding Resistance:


Core Ratio R Y B
1S1-1S2 20/1A 2.0 2.1 2.0
2S1-2S2 20/1A 1.2 1.3 1.1

3.0 C.T. Polarity Test:


Connect + ve at P1 and –ve at P2
Phase reference
Core Ratio Terminal
R Y B
Core I 200/1 1S1-1S3 Forward Forward Forward
Core II 200/1 2S1-2S3 Forward Forward Forward
Core III 200/1 3S1-3S3 Forward Forward Forward

Witnessed/ Reviewed by NS Engineers


Signature
Name
17
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

3.1 C.T. Ratio Test:


Primary Measured Secondary Current IS
Core Ratio Terminal Applied
Current IP R Y B
Core I 200/1 1S1-1S3
100 0.51 A 0.52 A 0.51 A
Core II 200/1 2S1-2S3
Core III 200/1 3S1-3S3 200 1.02 A 1.03 A 1.02 A

4.0 MAGNETIZATION CHARACTERISTICS TEST:


Reference Phase reference
Knee Point Leakage Current Ma
Core Applied Voltage V
Voltage R(mA) Y(mA) B(mA)
20 2.1 2.3 3.3
40 3.6 3.7 5.0
60 4.6 4.7 6.2
80 5.7 5.6 7.4
100 6.7 6.2 8.4
3S1-3S2 120 7.8 7.1 9.2
200V
140 9.0 7.8 10.1
160 10.2 8.7 11.2
180 11.3 10.0 12.5
200 13.1 11.3 13.4
220 14.7 13.4 15.9

Knee - point Voltage Kpv =200 V


Excitation - current Iex VK/2 =30 mA

4.0 REMARKS : Tested and Found Healthy.

Witnessed/ Reviewed by NS Engineers


Signature
Name
18
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF CURRENT TRANSFORMER NS Engineers, Ahmedabad


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 09/03/2023
Plant KBC SHP – 1 SWITCH YARD Tested by MM/MP/RP
Location CT-22 JB 66KV LINE-2 TC No.

1.0 C.T. Specification And Name Plate Details: -


Phase Make Mfg. Year Sr. No.
R MEHRU 2016 OC 6091/3/6/16
Y MEHRU 2016 OC 6091/3/1/16
B MEHRU 2016 OC 6091/3/5/16

VA Of Class of
Core C.T. Ratio
Core core
1 200/1 10 0.2
2 200/1 10 5P

2.0 Insulation Resistance Test: -

Megger Used Make Sr. No.


0-5 KV, ≥ 5TΩ SONEL CU1664

2.1 Primary to Earth & Primary to Secondary: - Applied Voltage: - 5KV


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary – Earth 78.2 89.5 68.23
Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary - Core – I 22.67 62.13 28.21
Primary - Core – II 48.12 59.67 29.92

2.2 Secondary to Earth: - Applied Voltage:- 500V


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Core – I – Earth 28.11 33.21 45.21
Core – II – Earth 32.30 38.56 29.39

2.3 Secondary Winding Resistance:


Core Ratio R Y B
1S1-1S2 20/1A 2.7 2.6 2.8
2S1-2S2 20/1A 1.9 2.1 2.1

3.0 C.T. Polarity Test: Connect + ve at P1 and –ve at P2


Phase reference
Core Ratio Terminal
R Y B
Core I 200/1 1S1-1S3 Forward Forward Forward
Core II 200/1 2S1-2S3 Forward Forward Forward

Witnessed/ Reviewed by NS Engineers


Signature
Name
19
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

3.1 C.T. Ratio Test:


Primary Measured Secondary Current IS
Core Ratio Terminal Applied
Current IP R Y B
Core I 200/1 1S1-1S2 100 A 0.49 A 0.49 A 0.48 A
Core II 200/1 2S1-2S2 200 A 1.03 A 1.02 A 1.0 A

4.0 REMARKS : Tested and Found Healthy.

Witnessed/ Reviewed by NS Engineers


Signature
Name
20
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF CURRENT TRANSFORMER NS Engineers, Ahmedabad


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 01/03/2023
Plant KBC SHP - 1 Tested by MM/MP/RP
Location CT-23 JB LINE CT TC No.

1.0 C.T. SPECIFICATION AND NAME PLATE DETAILS: -


Capacitance DissipationFactor
Phase Make Mfg. Year Sr. No.
(pF) (tanδ)% at 42 KV
R MEHRU 2016 OC 6091/2/6/16 395 0.234
Y MEHRU 2016 OC 6091/2/4/16 400 0.194
B MEHRU 2016 OC 6091/2/5/16 395 0.234

Core C.T. Ratio VA Of Core Class of core


1 200/1 10 0.2S
2 200/1 10 0.2S
3 200/1 20 5P
4 200/1 20 5P

2.0 INSULATION RESISTANCE TEST: -

Megger Used Make Sr. No.


0-5 KV, ≥ 5TΩ SONEL CU1664

2.1 Primary to Earth & Primary to Secondary: - Applied Voltage: - 5KV


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary – Earth 32.72 33.65 43.04
Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary - Core – I 39.7 65.26 17.64
Primary - Core – II 40.71 37.55 955.1
Primary - Core – lll 35.85 75.39 453.7
Primary - Core – IV 41.05 81.25 326.7

2.2 Secondary to Earth: - Applied Voltage: - 500V


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Core – I – Earth 12.62 31.68 18.31
Core – II – Earth 14.69 13.36 16.18
Core – III – Earth 9.7 23.7 15.31
Core – IV – Earth 10.91 22.80 16.40

2.3 SECONDARY WINDING RESISTANCE


Core Ratio R Y B
1S1-1S2 20/1A 2.1 Ω 1.9 Ω 2.0 Ω
2S1-2S2 20/1A 1.2 Ω 1.1 Ω 1.2 Ω

Witnessed/ Reviewed by NSENGINEERS SSNNL


Signature
Name
21
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

3.0 C.T. Polarity Test:


Connect + ve at P1 and –ve at P2
Phase reference
Core Ratio Terminal
R Y B
Core I 200/1 1S1-1S3 Forward Forward Forward
Core II 200/1 2S1-2S3 Forward Forward Forward
Core III 200/1 3S1-3S3 Forward Forward Forward
Core IV 200/1 4S1-4S3 Forward Forward Forward

4.0 C.T. Ratio Test:


Primary Measured Secondary Current IS
Core Ratio Terminal Applied
Current IP R Y B
Core I 200/1 A 1S1-1S2 100 A 0.51 A 0.52 A 0.51 A
Core II 200/1 A 2S1-2S2 200 A 1.03 A 1.04 A 1.02 A

5.0 REMARKS : Tested and Found Healthy.

Witnessed/ Reviewed by NSENGINEERS SSNNL


Signature
Name
22
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

TEST CERTIFICATE OF CURRENT TRANSFORMER NS Engineers, Ahmedabad


Client SARDAR SAROVAR NARMADA NIGAM LTD.-KBC Tested on 09/03/2023
Plant KBC SHP – 1 SWITCH YARD Tested by MM/MP/RP
Location CT-24 JB 66KV LINE-2 TC No.
1.0 C.T. SPECIFICATION AND NAME PLATE DETAILS: -
Phase Make Mfg. Year Sr. No.
R MEHRU 2016 OC 6091/2/1/16
Y MEHRU 2016 OC 6091/2/5/16
B MEHRU 2016 OC 6091/2/2/16

VA Of Class of
Core C.T. Ratio
Core core
1 200/1 10 0.2S
2 200/1 10 0.2S
3 200/1 20 5P
4 200/1 20 5P

2.0 INSULATION RESISTANCE TEST: -

Megger Used Make Sr. No.


0-5 KV, ≥ 5TΩ SONEL CU1664

2.1 Primary to Earth & Primary to Secondary: - Applied Voltage:- 5KV


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary – Earth 129.32 111.23 128.32
Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Primary - Core – I 181.21 141.23 178.24
Primary - Core – II 162.39 149.35 128.71
Primary - Core – III 159.27 162.96 183.5
Primary - Core – IV 168.92 189.68 229.8

2.2 Secondary to Earth: - Applied Voltage: - 500V


Phase Reference
Core reference
R (GΩ) Y (GΩ) B (GΩ)
Core – I – Earth 22.62 36.21 20.92
Core – II – Earth 16.72 23.19 9.91
Core – III – Earth 13.29 16.27 10.29
Core – IV – Earth 19.45 29.39 21.89

Witnessed/ Reviewed by NSENGINEERS SSNNL


Signature
Name
23
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

2.3 SECONDARY WINDING RESISTANCE


Core Ratio R(Ω) Y(Ω) B(Ω)
1S1-1S2 200/1A 1.5 1.5 1.6
2S1-2S2 200/1A 1.4 1.5 1.4
3S1-3S2 200/1A 2.7 2.6 2.6
4S1-4S2 200/1A 2.8 2.4 2.5

3.0 C.T. POLARITY TEST: Connect + ve at P1 and –ve at P2


Phase reference
Core Ratio Terminal
R Y B
Core I 200/1 1S1-1S2 Forward Forward Forward
Core II 200/1 2S1-2S2 Forward Forward Forward
Core III 200/1 3S1-3S2 Forward Forward Forward
Core IV 200/1 4S1-4S2 Forward Forward Forward

3.1 C.T. RATIO TEST:


Primary Applied Measured Secondary Current IS
Core Ratio Terminal
Current IP R Y B
100 A 0.49 A 0.48 A 0.49 A
Core I 200/1 1S1-1S2
200 A 1.03 A 1.01 A 0.99 A
100 A 0.50 A 0.49 A 0.50 A
Core II 200/1 2S1-2S2
200 A 1.02 A 1.00 A 1.02 A
100 A 0.51 A 0.49 A 0.50 A
Core III 200/1 3S1-3S2
200 A 1.01 A 1.00 A 1.01 A
100 A 0.49 A 0.50 A 0.51 A
Core IV 200/1 4S1-4S2
200 A 1.02 A 1.01 A 0.99 A

4.0 REMARKS : Tested and Found Healthy.

Witnessed/ Reviewed by NSENGINEERS SSNNL


Signature
Name
24
NS ENGINEERS
69-A, Pushpraj Complex, Jashoda Cross Road,
Vatva Road, Ahmedabad-383 445, Gujarat, INDIA

Witnessed/ Reviewed by NSENGINEERS SSNNL


Signature
Name
25