JM Switchboards May 26, 2020 4 min read

Switchboard Forms of Segregation Explained


Do you feel out of your depth when people start talking about forms of segregation, such as Form 3B or Form 4aih?

To put it simply, these are the methods for internally separating the functional units and busbars of an Assembly, as
specified by AS/NZS 61439.

The 4 main categories outlined by the standard are:


Form 1
Form 2
Form 3
Form 4

The complexity of the forms increases with the numbers.

Key definitions

Assembly
Refers to a switchboard which contains low-voltage control and switchgear.

Functional unit
Part of an Assembly comprising all the electrical and mechanical elements including switching devices that contribute
to the fulfilment of the same function e.g. a motor starter.

Busbar
Refers to a low-impedance conductor to which several electric circuits can be separately connected. The term "busbar"
does not presuppose the geometrical shape, size, or dimensions of the conductor.

Symbols Used

https://www.jmswitchboards.com.au/post/switchboard-forms-of-segregation-explained 1/6
6/18/22, 12:23 PM Switchboard Forms of Segregation Explained

Form 1
A switchboard with no internal separation. Busbars, terminals for outgoing cables and all functional units are installed
on a single central section. Form 1 segregation is suitable for smaller, lower power switchboards.

Form 2
The busbars and functional units are separated and broken down into another 2
categories – Form 2a and Form 2b
https://www.jmswitchboards.com.au/post/switchboard-forms-of-segregation-explained 2/6
6/18/22, 12:23 PM Switchboard Forms of Segregation Explained

Form 2a – External cabling terminals are not separated from the busbar.

Form 2b – External cabling terminals are separated from the busbar.

There are several advantages to segregating functional units and busbars, not least of which is safety. This model
allows circuit breakers to be reset when the switchboard is live because the operator is not exposed to a live busbar.

Form 3
Things start to get more complicated from here. As with Form 2, busbars and functional
units are segregated. Functional units are also separated from each other in cubicles, and
terminals are then separated from functional units, but they are not segregated from
other functional units’ terminals.

https://www.jmswitchboards.com.au/post/switchboard-forms-of-segregation-explained 3/6
6/18/22, 12:23 PM Switchboard Forms of Segregation Explained

This is also broken down into 2 categories:

Form 3a – External cabling terminals are not segregated from busbars.

Form 3b – External cabling terminals are separated from busbars.

Form 3b is frequently required for MCCs. It basically means that busbars and each motor starter are installed within
their own cubicles. The advantages include safety, ease of maintenance and reliability because it’s possible to isolate
and perform maintenance on each starter without having to power down the whole switchboard. Serious faults within
a starter are also more likely to be contained within a cubicle meaning adjacent starters are unaffected and can
operate normally.

All these advantages come at a cost as a Form 3 board is significantly bigger and more expensive than a Form 1 or 2
board.

https://www.jmswitchboards.com.au/post/switchboard-forms-of-segregation-explained 4/6
6/18/22, 12:23 PM Switchboard Forms of Segregation Explained

Form 3 segregation is typically used for mining projects and larger operations that have a substantial number of loads,
motors and critical processes. They are utilsed when safety, reliability and limited downtime are crucial.

Form 4
This is the highest form rating, as specified by AS/NZS 61439.1. With Form 4, busbars are
separated from functional units and external cabling terminals. Functional units are
further separated from each other, and from the external cabling terminals for each
functional unit.

As with the other forms, this is divided into 2 sub-categories:

Form 4a – External cabling terminals are within the same cubicle as the corresponding functional unit.

Form 4b – The external cabling terminals are not in the same cubicle as the corresponding functional unit,
and they are separated from the terminals of other functional units.

https://www.jmswitchboards.com.au/post/switchboard-forms-of-segregation-explained 5/6
6/18/22, 12:23 PM Switchboard Forms of Segregation Explained

The major difference between Forms 3 and 4 is the separation of the terminals of each functional unit the terminals of
other units. The main advantage of this model is the ability to safely connect and disconnect outgoing cables while the
rest of the switchboard remains in operation.

The high cost of this rating means that Form 4 is usually only used in hospitals or for critical industrial processes.

Segregating the I and H


Metallic or non-metallic barriers are typically used to segregate functional units, terminals and busbars and achieve
the form ratings outlined above. This means equipment is housed in separate cubicles within a switchboard.
Standards, however, provide for other methods to be used for segregation which are easier and cheaper, such as
utilising the integral compartments of a functional unit and insulating terminals or busbars.

Using Integral Housing


If a functional unit’s housing complies with protection standards IP2X (a finger-sized object cannot come into contact
with any live parts), it can be used to separate functional units, not including busbars. This method is used only for
segregating functional units from one another and therefore it applies only to Forms 3 and 4.

This method is identified by adding a ‘h’ to the form rating. For example, Form 3bh.

Insulating busbars or terminals


Insulation can be utilised to separate busbars from both functional units and terminals. It is also possible to shroud
terminals for segregation from the functional units of other terminals.

The use of this method of is identified through the inclusion of ‘i’ to the form rating. It is used to create 2bi, 3bi and 4bi.

Combining insulation and housing


Component housings and insulation can be used together for internal segregation. The combined use of these
methods is identified through the inclusion of ‘i’ and ‘h’ to the forms. This method is used to achieve forms 3bih, 4aih
and 4bih.

As noted, the use of “I” and “h” is a cheaper method to achieve form ratings. It should also be considered inferior to the
use of physical barriers to achieve form ratings.