CONVENTIONAL SPRINKLER =
The PROTECTOR conventional sprinkler identification
numbers (SIN) are PS009 (Standard Response) and
PS010 (Quick Response) . The design incorporate state
of the art, heat responsive, frangible glass bulb design
(standard or quick response) for prompt, precise
operation. The die cast frame is more streamlined and
altractive than traditional sand cast frames. It is cast with
a hex-shaped wrench to allow easy tightening from
different angles
This sprinkler is available in various temperature ratings
and finishes to meet many design requirements. The
recessed pendant should be utilized with a Model A
Tecessed escutcheon which provides up 3/4” of
adjustments. All protector sprinklers are manufactured
using the time proven Belleville seal used exclusively by
all major manufactures to ensure long life and safe
operation
OPERATION
i The operating mechanism is a frangible glass bulb which
Conventional contains a heat responsive liquid. During a fire, the
PS009 ambient temperature rises causing the liquid in the bulb
to expand, When the ambient temperature reaches the
rated temperature of the sprinkler, the bulb shatters, As a
result, the waterway is cleared of all sealing parts and
water is discharged towards the deflector. The deflector is
designed to distribute the water in a pattern that is most
effective in controlling the fire.
Maximum Coverage
Standard spray coverage is up to : ‘SPECIFICATIONS
Light hazard = 229 square feet (20.9 sq.m), ‘Model
ordinary hazard = 180 square feet (12.1 ose! Pso09
sq.m) per NFPA 13. Installaton direction Co
Discharge capacities 804 Jmin at 1.0 kgticm?
MATERIALS Tested pressure 5min
Frame Brass / Chrome SIN Bula Smmn Buld 3mm
Deflector Brass / Chrome style Conventional Sprinkler
Bulb-Gises Glycerin Solution Nominal KFactor 5.6inp{008.)
3mm / mm Diameter
Response Time Index(RT!) Standar Quick 30
Bushing Brass
Norminal Thread Size 412" NPT (15mm)
Seal Teflon
Max, Working Pressure 4175 PSI (1200 kPa)
Factory Hydrostatic Test 100%@500 PSI (3450 kPa)
Min, Operation Pressure 7 PSI (48 KPa)Y =
Approvals and Listings
Nominal Size
K-Factor Sprinkler ‘Approvals
Inches/ mm. Imperial s, | Response type prow
Thread Orifice UL
28 Standard tional
Standard [Recessed
Quick [Conventional
Quick Recessed
Temperature Ratings
Sprinkler Temperature Nominal Sprinkler NEPA. Maximum Ambient (Ceiling) | Glass Bulb
Classification Temp. Allowed Color
100 38°C Ora
Ordinary venge