- Cooling Only -
FTKJ-N Series
TM-FTKJ-0916-A
EDMY041447
Split Type
Air Conditioners
FTKJ-N Series
FTKJ25NVMMW RKJ25NVM
FTKJ25NVMMS RKJ35NVM
FTKJ35NVMMW RKJ50NVM
Cooling Only
FTKJ35NVMMS
FTKJ50NVMMW
FTKJ50NVMMS
1. Power Supply
Indoor Unit Outdoor Unit Power Supply
FTKJ25NVMMW
RKJ25NVM
FTKJ25NVMMS
FTKJ35NVMMW 1 phase, 220 - 230 - 240 V, 50 Hz
RKJ35NVM
FTKJ35NVMMS 1 phase, 220 - 230 V, 60 Hz
FTKJ50NVMMW
RKJ50NVM
FTKJ50NVMMS
2. Functions
FTKJ25/35/50NVMMW(S)
FTKJ25/35/50NVMMW(S)
RKJ25/35/50NVM
RKJ25/35/50NVM
Category Functions Category Functions
Basic Function Inverter (with inverter power control) z Health & Clean Air-purifying filter —
3. Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTKJ25NVMMW FTKJ25NVMMS
Model
Outdoor Unit RKJ25NVM RKJ25NVM
kW 2.5 (1.2 ~ 3.4) 2.5 (1.2 ~ 3.4)
Capacity Btu/h 8,500 (4,100 ~ 11,600) 8,500 (4,100 ~ 11,600)
Rated (Min. ~ Max.)
kcal/h 2,150 (1,030 ~ 2,920) 2,150 (1,030 ~ 2,920)
Moisture Removal L/h 1.2 1.2
Running Current (Rated) A 2.6 - 2.9 - 2.8 / 2.6 - 2.9 2.6 - 2.9 - 2.8 / 2.6 - 2.9
Power Consumption (Rated) W 520 520
Power Factor (Rated) % 90.9 - 78.0 - 77.4 / 90.9 - 78.0 90.9 - 78.0 - 77.4 / 90.9 - 78.0
COP (Rated) W/W 4.81 4.81
Liquid mm φ 6.4 φ 6.4
Piping Gas mm φ 9.5 φ 9.5
Connections
Drain mm φ 18.0 φ 18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 20 20
Max. Interunit Height Difference m 15 15
Chargeless m 10 10
Amount of Additional Charge of g/m 20 20
Refrigerant
Indoor Unit FTKJ25NVMMW FTKJ25NVMMS
Front Panel Colour White Silver
H 8.9 (313) 8.9 (313)
M m³/min 6.6 (234) 6.6 (234)
Airflow Rate (cfm)
L 4.4 (155) 4.4 (155)
SL 2.6 (91) 2.6 (91)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 29 29
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof
Running Current (Rated) A 0.12 - 0.12 - 0.12 / 0.12 - 0.12 0.12 - 0.12 - 0.12 / 0.12 - 0.12
Power Consumption (Rated) W 23 23
Power Factor (Rated) % 87.1 - 83.3 - 79.9 / 87.1 - 83.3 87.1 - 83.3 - 79.9 / 87.1 - 83.3
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 303 × 998 × 212 303 × 998 × 212
Packaged Dimensions (H × W × D) mm 322 × 1,101 × 389 322 × 1,101 × 389
Weight (Mass) kg 12 12
Gross Weight (Gross Mass) kg 16 16
Sound Pressure H / M / L / SL dB(A) 38 / 32 / 25 / 19 38 / 32 / 25 / 19
Level
Outdoor Unit RKJ25NVM RKJ25NVM
Casing Colour Ivory White Ivory White
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 1YC25DXD 1YC25DXD
Motor Output W 800 800
Type FW68DA FW68DA
Refrigerant Oil
Charge L 0.375 0.375
Type R-32 R-32
Refrigerant
Charge kg 0.9 0.9
H m³/min 31.8 (1,123) 31.8 (1,123)
Airflow Rate (cfm)
SL 28.3 (999) 28.3 (999)
Type Propeller Propeller
Fan
Motor Output W 33 33
Running Current (Rated) A 2.48 - 2.78 - 2.68 / 2.48 - 2.78 2.48 - 2.78 - 2.68 / 2.48 - 2.78
Power Consumption (Rated) W 497 497
Power Factor (Rated) % 91.1 - 77.8 - 77.3 / 91.1 - 77.8 91.1 - 77.8 - 77.3 / 91.1 - 77.8
Starting Current A 2.5 2.5
Dimensions (H × W × D) mm 550 × 765 × 285 550 × 765 × 285
Packaged Dimensions (H × W × D) mm 589 × 882 × 363 589 × 882 × 363
Weight (Mass) kg 34 34
Gross Weight (Gross Mass) kg 37 37
Sound Pressure H / SL dB(A) 46 / 43 46 / 43
Level
Drawing No. 3D090376 3D090389
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Piping Length
Indoor ; 27°CDB / 19°CWB kcal/h = kW × 860
Outdoor ; 35°CDB / 24°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Piping Length
kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB 7.5 m Btu/h = kW × 3412
Outdoor ; 35°CDB / 24°CWB cfm = m³/min × 35.3
Note: The data are based on the conditions shown in the table below.
Conversion Formulae
Cooling Piping Length
kcal/h = kW × 860
Indoor ; 27°CDB / 19°CWB 7.5 m Btu/h = kW × 3412
Outdoor ; 35°CDB / 24°CWB cfm = m³/min × 35.3
4. Dimensions
4.1 Indoor Unit
FTKJ25/35NVMMW(S)
FTKJ50NVMMW(S)
RKJ25/35NVM
150
(I.Dφ15.9 HOSE FOR CONNECTION) (M8 OR M10)
574 105.5
13 490
100
150
50 50
300
50
29.5
311
50
100
HANDLE BRAND NAME LABEL
285 8 12 765 63
OUTDOOR AIR THERMISTOR
MANUFACTURE'S
LABEL LIQUID
STOP VALVE
(φ6.4 CuT)
WIRING
INLET
550
SERVICE
PORT
165
105
196 22
IN CASE OF REMOVING
STOP VALVE COVER GAS STOP VALVE
(φ9.5 CuT)
3D073893E
RKJ50NVM
DRAIN OUTLET MINIMUM SPACE FOR AIR PASSAGE WALL HEIGHT ON AIR OUTLET SIDE
100
(I.D.φ15.9 HOSE FOR CONNECTION) =LESS THAN 1200
825 78
325
100
124 580
350
2
36
50 50
50
350
350
330
300
100
350
IN CASE OF REMOVING
STOP VALVE COVER
10
25
89 64
3D083536B
5. Wiring Diagrams
5.1 Indoor Unit
FTKJ25/35/50NVMMW(S)
RKJ25/35NVM
FIELD WIRING
INDOOR
N=2 MRM20 WHT IPM1
FU3
X1M Z3C AC1 20A L1R HR2 DB1
HR1
1 L 1 BLK L1
MRM10
BRN ~
+ +
AC2 +
2 N 2 WHT V2 HN3
S HN2 HA1 HA2 DB2 C5
3 3 RED BLU
HL3
GRY ~ - ~ + +
C119
HL2
V3 ORG +
FU1 C6
L ~ Q1
GRN/YLW
MR30 -
3.15A 1 WHT 1
N BLK V1 -
BLK PCB2 DB3 FU2
BLK 3.15A
SA1 S11 BLK
BLK
S10 ~ +
E1 BLK W V U
BLK IPM2
E2 MR30_A MR30_B 9 BLK 9 ~ - + -
GRN
MRCW
YLW
RED
BLU
Z2C S50 S100 S20 S90 S40 S70
N=2 PCB1 3 1 1 2 1 6 3 S80 1 1 6 2 1 1 4 7 10 11 12 13 X11A
GRN
OUTDOOR
WHT
BLK WHT
BRN
BRN
GRY
YLW
RED
BLU
BLK
WHT
ORG
WHT
ORG
YLW
YLW
RED
BRN
RED
BLU
BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
4 1
2 1
t˚ t˚ t˚
X12A S110 M MS Z1C
NOTE Q1L
R1T R3T 3~ N=4 V
BLK
BLK
1. REFER TO THE NAME PLATE FOR THE POWER REQUIREMENTS. SW1 Y1E W MS U
(OUTDOOR) R2T (DISCHARGE)
C5, C6, C119
DB1, DB2, DB3
: CAPACITOR
: DIODE BRIDGE PCB3 (CONDENSER) M1F 3 ~
M1C
FU1, FU2, FU3 : FUSE
IPM1, IPM2 : INTELLIGENT POWER MODULE PCB1, PCB2, PCB3 : PRINTED CIRCUIT BOARD SW1 : FORCED OPERATION SWITCH
L : LIVE S10, S11, S20, S40, S50 V1, V2, V3 : VARISTOR
L1 : COIL S70, S80, S90, S100, S110 X1M : TERMINAL STRIP
L1R : REACTOR HL3, HN3, X11A, X12A : CONNECTOR Y1E : ELECTRONIC EXPANSION VALVE COIL
M1C : COMPRESSOR MOTOR R1T, R2T, R3T : THERMISTOR Z1C, Z2C, Z3C : FERRITE CORE
M1F : FAN MOTOR SA1 : SURGE ABSORBER : PROTECTIVE EARTH
MRCW, MR30, MRM10, MRM20 : MAGNETIC RELAY
N : NEUTRAL : EARTH
Q1L : OVERLOAD PROTECTOR 3D088119A
RKJ50NVM
6. Piping Diagrams
6.1 Indoor Unit
FTKJ25/35NVMMW(S)
FTKJ50NVMMW(S)
RKJ25/35NVM
OUTDOOR UNIT
HEAT EXCHANGER
7.0 CuT OUTDOOR TEMPERATURE
THERMISTOR
7.0 CuT
7.0 CuT
HEAT EXCHANGER
MOTOR OPERATED
THERMISTOR
VALVE
6.4 CuT 6.4 CuT
9.5 CuT
4.8 CuT
MUFFLER WITH
FILTER
6.4 CuT
7.9 CuT
PROPELLER FAN
FIELD PIPING
LIQUID STOP (6.4 CuT)
DISCHARGE PIPE VALVE
THERMISTOR
COMPRESSOR FIELD PIPING
ACCUMULATOR 9.5 CuT 9.5 CuT 9.5 CuT GAS STOP (9.5 CuT)
MUFFLER
VALVE WITH
SERVICE PORT REFRIGERANT FLOW
COOLING
3D088154A
RKJ50NVM
OUTDOOR UNIT
HEAT EXCHANGER
7.0 CuT OUTDOOR TEMPERATURE
THERMISTOR
7.0 CuT
M
7.9 CuT
6.4 CuT
PROPELLER FAN
FIELD PIPING
MUFFLER (6.4 CuT)
LIQUID STOP
DISCHARGE PIPE VALVE
THERMISTOR 12.7 CuT
COMPRESSOR FIELD PIPING
ACCUMULATOR 12.7 CuT GAS STOP (12.7 CuT)
VALVE
REFRIGERANT FLOW
COOLING
3D090240
7. Capacity Tables
7.1 Cooling Only
FTKJ25NVMMW + RKJ25NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
FTKJ25NVMMS + RKJ25NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
AFR 8.9
BF 0.11
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in the
BF : Bypass factor above tables. (Figures out of the tables should not be used for calculation.)
EWB : Entering wet bulb temp. (°C) 3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
EDB : Entering dry bulb temp. (°C) Level difference : 0 m
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D090434B
FTKJ35NVMMW + RKJ35NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
FTKJ35NVMMS + RKJ35NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
AFR 10.9
BF 0.11
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in the
BF : Bypass factor above tables. (Figures out of the tables should not be used for calculation.)
EWB : Entering wet bulb temp. (°C) 3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
EDB : Entering dry bulb temp. (°C) Level difference : 0 m
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D090435B
FTKJ50NVMMW + RKJ50NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
FTKJ50NVMMS + RKJ50NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
Cooling
AFR 10.9
BF 0.18
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in the
BF : Bypass factor above tables. (Figures out of the tables should not be used for calculation.)
EWB : Entering wet bulb temp. (°C) 3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5 m
EDB : Entering dry bulb temp. (°C) Level difference : 0 m
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D090436A
90
5 10 15 20 (m)
Piping length
7.2.2 50 Class
(R-32)
(%)
100
Capacity correction factor
90
80
Range of the refrigerant additional charge
5 10 15 20 25 30 (m)
Piping length
Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.
8. Operation Limit
RKJ25/35NVM
50
46
40
Continuous operation
Pull-down period
30
20
19.4
10 14 20 23 28 30
Indoor temp. (˚CWB)
Notes:
The graph is based on
the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High
4D073983H
RKJ50NVM
50
46
40
Outdoor temp. (˚CDB)
Continuous operation
Pull-down period
30
20
19.4
10 14 20 23 28 30
Indoor temp. (˚CWB)
Notes:
The graph is based
on the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High
4D083533B
9. Sound Level
9.1 Measuring Location
1m
1m
0.8 m
MICROPHONE
MICROPHONE
FTKJ25NVMMW(S) FTKJ35NVMMW(S)
dB (0dB=0.0002µ bar)
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING NC-20
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D093568 63 125 250 500 1000 2000 4000 8000 4D093606
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
FTKJ50NVMMW(S)
60 (H) (L)
NC-60 A 46 35
20
APPROXIMATE
THRESHOLD HEARING NC-20
FOR CONTINUOUS
NOISE
63 125 250 500 1000 2000 4000 8000 4D093653A
OCTAVE BAND CENTER FREQUENCY (Hz)
RKJ25NVM RKJ35NVM
COOLING COOLING
70 OVER ALL (dB) 70 OVER ALL (dB)
NC-70 NC-70
dB (0dB=0.0002µ bar)
50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz POWER SOURCE 220-240/220-230V 50/60Hz
40 JIS STANDARD (JIS9612) 40 JIS STANDARD (JIS9612)
NC-40 Cooling NC-40 Cooling
30 30
NC-30 NC-30
20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING NC-20
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D093595 63 125 250 500 1000 2000 4000 8000 4D093602
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)
RKJ50NVM
COOLING
70 OVER ALL (dB)
NC-70
SCALE 50/60Hz
220-240/220-230V
OCTAVE BAND SOUND PRESSURE LEVEL
60
NC-60 A 50
50
NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz
40 JIS STANDARD (JIS9612)
NC-40 Cooling
30
NC-30
20
APPROXIMATE
THRESHOLD HEARING NC-20
FOR CONTINUOUS
NOISE
63 125 250 500 1000 2000 4000 8000 4D093661
OCTAVE BAND CENTER FREQUENCY (Hz)
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB
MFA : Max. fuse amps (A) Outdoor temp. 35°CDB.
RHz : Rated operating frequency (Hz) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : Rated load amps (A) 4. Instead of fuse, use circuit breaker.
OFM : Outdoor fan motor 5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
IFM : Indoor fan motor detector capable of handling high harmonics must be used in
W : Fan motor rated output (W) order to prevent malfunctioning of the earth leak detector.)
FLA : Full load amps (A)
3D090348C
3P379713-1
3P378215-1A
3P381857-1B
4P104499-1A
3P089958-2C