Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

ENGINEERING DATA
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.

Split Type Air Conditioners


If you have any enquiries, please contact your local importer, distributor and/or retailer.
Split Type Air Conditioners
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
- Cooling Only -

FTKV-N Series
FTKV-N Series

Specifications, designs and other content appearing in this brochure are current as of May 2014 but subject to change without notice.

c All rights reserved

AK
EDMT041424

Split Type
Air Conditioners
FTKV-N Series
FTKV25NVM RKV25NVM
FTKV35NVM RKV35NVM
Cooling Only
FTKV50NVM RKV50NVM
FTKV60NVM RKV60NVM
1. Power Supply ..........................................................................................2
2. Functions.................................................................................................3
3. Specifications ..........................................................................................4
4. Dimensions .............................................................................................6
4.1 Indoor Unit................................................................................................6
4.2 Outdoor Unit .............................................................................................7
5. Wiring Diagrams......................................................................................8
5.1 Indoor Unit................................................................................................8
5.2 Outdoor Unit .............................................................................................9
6. Piping Diagrams....................................................................................10
6.1 Indoor Unit..............................................................................................10
6.2 Outdoor Unit ...........................................................................................11
7. Capacity Tables ....................................................................................12
7.1 Cooling Only...........................................................................................12
7.2 Capacity Correction Factor by the Length of Refrigerant Piping
(Reference) ............................................................................................14
8. Operation Limit......................................................................................15
9. Sound Level ..........................................................................................16
9.1 Measuring Location ................................................................................16
9.2 Indoor Unit..............................................................................................16
9.3 Outdoor Unit ...........................................................................................17
10.Electric Characteristics..........................................................................18
11.Installation Manual ................................................................................19
11.1 25/35 Class ............................................................................................19
11.2 50/60 Class ............................................................................................29
12.Operation Manual..................................................................................39
13.Optional Accessories ............................................................................74
13.1 Option List ..............................................................................................74
13.2 <KPW937A4> Air Direction Adjustment Grille........................................75
13.3 <KPW945A4> Air Direction Adjustment Grille........................................76

Split Type Air Conditioners FTKV-N Series 1


Power Supply EDMT041424

1. Power Supply
Indoor Unit Outdoor Unit Power Supply
FTKV25NVM RKV25NVM
FTKV35NVM RKV35NVM 1 φ, 220 - 230 - 240 V, 50 Hz
FTKV50NVM RKV50NVM 1 φ, 220 - 230 V, 60 Hz
FTKV60NVM RKV60NVM

Note: Power Supply Intake ; Outdoor Unit

2 Split Type Air Conditioners FTKV-N Series


EDMT041424 Functions

2. Functions

FTKV25/35NVM

FTKV50/60NVM

FTKV25/35NVM

FTKV50/60NVM
RKV25/35NVM

RKV50/60NVM

RKV25/35NVM

RKV50/60NVM
Category Functions Category Functions

Basic Inverter (with inverter power control) z z Health & Air-purifying filter — —
Function Clean
Operation limit for cooling (°CDB) 19.4 19.4 Photocatalytic deodorising filter — —
~ 46 ~ 46
Air-purifying filter with photocatalytic
Operation limit for heating (°CWB) — — deodorising function — —

PAM control z z Titanium apatite photocatalytic z z


Standby electricity saving — z air-purifying filter
Compressor Oval scroll compressor — — Air filter (prefilter) z z
Swing compressor z z Wipe-clean flat panel z z
Rotary compressor — — Washable grille — —
Reluctance DC motor z z MOULD PROOF operation — —
Comfortable Power-airflow flap — — Heating dry operation — —
Airflow
Power-airflow dual flaps z z Good-sleep cooling operation — —
Power-airflow diffuser — — Timer WEEKLY TIMER operation — z
Wide-angle louvres z z 24-hour ON/OFF TIMER z z
Auto-swing (up and down) z z NIGHT SET mode z z
Auto-swing (right and left) — z Worry Free Auto-restart (after power failure) z z
(Reliability &
3-D airflow — z Durability) Self-diagnosis (digital, LED) display z z
COMFORT AIRFLOW operation — z Wiring error check function — —
Comfort Auto fan speed z z Anti-corrosion treatment of outdoor heat
Control exchanger z z
Indoor unit quiet operation z z
NIGHT QUIET mode (automatic) — — Flexibility Multi-split / split type compatible indoor — —
unit
OUTDOOR UNIT QUIET operation z z
(manual) Flexible power supply correspondence z z
INTELLIGENT EYE operation z z Chargeless 10 m 10 m
Quick warming function — — Either side drain (right or left) z z
Hot-start function — — Power selection — —
Automatic defrosting — — Remote 5-room centralised controller (option) — —
Control
Operation Automatic operation — — Remote control adaptor (normal open
pulse contact) (option) — —
Programme dry operation z z
Fan only z z Remote control adaptor — —
(normal open contact) (option)
Lifestyle New POWERFUL operation — —
Convenience (non-inverter) DIII-NET compatible (adaptor) (option) — —
Inverter POWERFUL operation z z Remote Wireless z z
Controller
Priority-room setting — — Wired — —
COOL / HEAT mode lock — —
HOME LEAVE operation — —
ECONO operation z z
Indoor unit ON/OFF button z z
Signal receiving sign z z
R/C with back light z z
Temperature display — —
Note: z : Available
— : Not available

Split Type Air Conditioners FTKV-N Series 3


Specifications EDMT041424

3. Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTKV25NVM FTKV35NVM
Model
Outdoor Unit RKV25NVM RKV35NVM
kW 2.5 (1.2 ~ 3.4) 3.5 (1.3 ~ 4.1)
Capacity Btu/h 8,500 (4,100 ~ 11,600) 11,900 (4,400 ~ 14,000)
Rated (Min. ~ Max.)
kcal/h 2,150 (1,030 ~ 2,920) 3,010 (1,120 ~ 3,530)
Moisture Removal L/h 1.2 1.9
Running Current (Rated) A 2.7 - 2.6 - 2.5 / 2.7 - 2.6 4.4 - 4.2 - 4.0 / 4.4 - 4.2
Power Consumption (Rated) W 540 910
Power Factor (Rated) % 90.9 - 90.3 - 90.0 / 90.9 - 90.3 94.0 - 94.2 - 94.8 / 94.0 - 94.2
COP (Rated) W/W 4.63 3.85
Liquid mm φ 6.4 φ 6.4
Piping φ 9.5 φ 9.5
Connections Gas mm
Drain mm φ 18.0 φ 18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 20 20
Max. Interunit Height Difference m 15 15
Chargeless m 10 10
Amount of Additional Charge of g/m 20 20
Refrigerant
Indoor Unit FTKV25NVM FTKV35NVM
Front Panel Colour Pure White Pure White
H 7.8 (275) 8.0 (282)
M m³/min 6.7 (237) 6.8 (240)
Airflow Rate (cfm)
L 5.6 (198) 5.6 (198)
SL 4.1 (145) 4.6 (162)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 40 40
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
Running Current (Rated) A 0.15 - 0.14 - 0.13 / 0.15 - 0.14 0.16 - 0.15 - 0.14 / 0.16 - 0.15
Power Consumption (Rated) W 31 33
Power Factor (Rated) % 93.9 - 96.3 - 99.4 / 93.9 - 96.3 93.8 - 95.7 - 98.2 / 93.8 - 95.7
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 283 × 800 × 195 283 × 800 × 195
Packaged Dimensions (H × W × D) mm 265 × 855 × 340 265 × 855 × 340
Weight (Mass) kg 9 9
Gross Weight (Gross Mass) kg 12 12
Sound
Pressure H / M / L / SL dB(A) 37 / 31 / 25 / 22 38 / 32 / 26 / 23
Level
Outdoor Unit RKV25NVM RKV35NVM
Casing Colour Ivory White Ivory White
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 1YC25DXD 1YC25DXD
Motor Output W 800 800
Refrigerant Type FW68DA FW68DA
Oil Charge L 0.375 0.375
Type R-32 R-32
Refrigerant
Charge kg 0.9 0.9
H m³/min 31.8 (1,123) 31.8 (1,123)
Airflow Rate (cfm)
SL 28.3 (999) 28.3 (999)
Type Propeller Propeller
Fan
Motor Output W 33 33
Running Current (Rated) A 2.55 - 2.46 - 2.37 / 2.55 - 2.46 4.24 - 4.05 - 3.86 / 4.24 - 4.05
Power Consumption (Rated) W 509 877
Power Factor (Rated) % 90.7 - 90.0 - 89.5 / 90.7 - 90.0 94.0 - 94.1 - 94.7 / 94.0 - 94.1
Starting Current A 2.5 2.5
Dimensions (H × W × D) mm 550 × 765 × 285 550 × 765 × 285
Packaged Dimensions (H × W × D) mm 589 × 882 × 363 589 × 882 × 363
Weight (Mass) kg 34 34
Gross Weight (Gross Mass) kg 36 36
Sound
Pressure H / SL dB(A) 46 / 43 47 / 44
Level
Drawing No. 3D088552 3D088553

Note: „ The data are based on the conditions shown in the table below.
Cooling Piping Length Conversion Formulae

Indoor ; 27°CDB / 19°CWB kcal/h = kW × 860


Outdoor ; 35°CDB / 24°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3

4 Split Type Air Conditioners FTKV-N Series


EDMT041424 Specifications

50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V


Indoor Unit FTKV50NVM FTKV60NVM
Model
Outdoor Unit RKV50NVM RKV60NVM
kW 5.2 (1.7 ~ 6.0) 6.0 (1.9 ~ 7.0)
Capacity Btu/h 17,700 (5,800 ~ 20,500) 20,500 (6,500 ~ 23,900)
Rated (Min. ~ Max.)
kcal/h 4,470 (1,460 ~ 5,160) 5,160 (1,630 ~ 6,020)
Moisture Removal L/h 2.9 3.9
Running Current (Rated) A 6.0 - 5.7 - 5.5 / 6.0 - 5.7 7.4 - 7.1 - 6.8 / 7.4 - 7.1
Power Consumption (Rated) W 1,300 1,580
Power Factor (Rated) % 98.5 - 99.2 - 98.5 / 98.5 - 99.2 97.1 - 96.8 - 96.8 / 97.1 - 96.8
COP (Rated) W/W 4.00 3.80
Liquid mm φ 6.4 φ 6.4
Piping φ 12.7 φ 12.7
Connections Gas mm
Drain mm φ 18.0 φ 18.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 30 30
Max. Interunit Height Difference m 20 20
Chargeless m 10 10
Amount of Additional Charge of g/m 20 20
Refrigerant
Indoor Unit FTKV50NVM FTKV60NVM
Front Panel Colour Pure White Pure White
H 14.3 (504) 15.4 (544)
M m³/min 12.4 (437) 13.5 (478)
Airflow Rate (cfm)
L 10.1 (356) 11.4 (402)
SL 9.0 (317) 9.9 (350)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 43 43
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof
Running Current (Rated) A 0.19 - 0.18 - 0.18 / 0.19 - 0.18 0.21 - 0.20 - 0.19 / 0.21 - 0.20
Power Consumption (Rated) W 34 40
Power Factor (Rated) % 81.3 - 82.1 - 78.7 / 81.3 - 82.1 86.6 - 87.0 - 87.7 / 86.6 - 87.0
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 290 × 1,050 × 250 290 × 1,050 × 250
Packaged Dimensions (H × W × D) mm 361 × 1,145 × 364 361 × 1,145 × 364
Weight (Mass) kg 12 12
Gross Weight (Gross Mass) kg 17 17
Sound
Pressure H / M / L / SL dB(A) 43 / 39 / 34 / 31 45 / 40 / 35 / 32
Level
Outdoor Unit RKV50NVM RKV60NVM
Casing Colour Ivory White Ivory White
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 2YC40BXD 2YC40BXD
Motor Output W 1,300 1,300
Refrigerant Type FW68DA FW68DA
Oil Charge L 0.650 0.650
Type R-32 R-32
Refrigerant
Charge kg 1.2 1.2
H m³/min 49.5 (1,748) 53.4 (1,886)
Airflow Rate (cfm)
SL 45.8 (1,617) 45.8 (1,617)
Type Propeller Propeller
Fan
Motor Output W 53 53
Running Current (Rated) A 5.81 - 5.52 - 5.32 / 5.81 - 5.52 7.19 - 6.90 - 6.61 / 7.19 - 6.90
Power Consumption (Rated) W 1,266 1,540
Power Factor (Rated) % 99.0 - 99.7 - 99.2 / 99.0 - 99.7 97.4 - 97.0 - 97.1 / 97.4 - 97.0
Starting Current A 3.5 3.5
Dimensions (H × W × D) mm 735 × 825 × 300 735 × 825 × 300
Packaged Dimensions (H × W × D) mm 784 × 960 × 390 784 × 960 × 390
Weight (Mass) kg 43 43
Gross Weight (Gross Mass) kg 48 48
Sound
Pressure H / SL dB(A) 48 / 44 52 / 46
Level
Drawing No. 3D088554 3D088555

Note: „ The data are based on the conditions shown in the table below.
Cooling Piping Length Conversion Formulae

Indoor ; 27°CDB / 19°CWB kcal/h = kW × 860


Outdoor ; 35°CDB / 24°CWB 7.5 m Btu/h = kW × 3412
cfm = m³/min × 35.3

Split Type Air Conditioners FTKV-N Series 5


Dimensions EDMT041424

4. Dimensions
4.1 Indoor Unit

FTKV25/35NVM

3D088952
45˚

FTKV50/60NVM

3D088953

6 Split Type Air Conditioners FTKV-N Series


EDMT041424 Dimensions

4.2 Outdoor Unit

RKV25/35NVM

WALL HEIGHT ON AIR OUTLET SIDE


MINIMUM SPACE FOR AIR PASSAGE
DRAIN OUTLET =LESS THAN 1200

150
4-HOLES FOR ANCHOR BOLTS
(I.Dφ15.9 HOSE FOR CONNECTION) (M8 OR M10)
574 105.5
13 490

100

150
50 50
29.5

50
311

300
50

100
HANDLE BRAND NAME LABEL
285 8 12 765 63
OUTDOOR AIR THERMISTOR
MANUFACTURE'S LIQUID
LABEL STOP VALVE
(φ6.4 CuT)
WIRING
INLET
550

SERVICE
PORT

165
105
196 22

IN CASE OF REMOVING
GAS STOP VALVE
STOP VALVE COVER
(φ9.5 CuT)

3D073893C

RKV50/60NVM

DRAIN OUTLET WALL HEIGHT ON AIR OUTLET SIDE


MINIMUM SPACE FOR AIR PASSAGE
=LESS THAN 1200

100
(I.D.φ15.9 HOSE FOR CONNECTION)

825 78
325
100

124 580
350

2
36

50 50
50
350
350

330

300

100

350

IN CASE OF REMOVING
STOP VALVE COVER
10

25

OUTDOOR AIR TEMPERATURE


NAME PLATE THERMISTOR
4-HOLES FOR ANCHOR BOLTS TERMINAL STRIP
(M8 OR M10) BRAND NAME PLATE WIRING INLET WITH EARTH TERMINAL
735

89 64

LIQUID STOP VALVE 155 18


(φ6.4 CuT) 160 30
GAS STOP VALVE
SERVICE PORT (φ12.7 CuT)

3D083536A

Split Type Air Conditioners FTKV-N Series 7


Wiring Diagrams EDMT041424

5. Wiring Diagrams
5.1 Indoor Unit

FTKV25/35NVM

FIELD WIRING.

PCB3 S27 S26 PCB1 F1U H1 1


~ ~
LED1 RECTIFIER 3.15A X1M 2
H1P V1 BLK 1
3 OUTDOOR
H2
LED2 WHT 2
H2P
RED 3
LED3 H3 GRN/YLW CAUTION
TRANSMISSION
H3P NOTE THAT OPERATION WILL
CIRCUIT
RESTART AUTOMATICALLY IF
FG THE MAIN POWER SUPPLY IS
TURNED OFF AND THEN BACK
S1W
ON AGAIN.
S1
S21 7 RED

R1T HA
BLU FG : FRAME GROUND
BRN F1U : FUSE
M H1P~H3P : PILOT LAMP
ORG
M1F : FAN MOTOR
1 WHT
PCB4 M1F M1S : SWING MOTOR
S36 S35
PCB1~PCB4 : PRINTED CIRCUIT BOARD
INTELLIGENT EYE R1T, R2T : THERMISTOR
S28 S32 1 S6 5
SENSOR S1~S38 : CONNECTOR
S1W : OPERATION SWITCH
X1M : TERMINAL STRIP
ORG
RED

YLW
PNK
BLU

: PROTECTIVE EARTH
PCB2 t˚
S29 R2T
WIRELESS INDOOR
REMOTE SIGNAL M
CONTROLLER RECEIVER
M1S

3D046453H

FTKV50/60NVM

1
PCB3 S49 S46 PCB1 FU1 X1M 2
1 BLK 1 F1U
LED1 H1 BLK 1 3
BLK OUTDOOR
H1P
BLK ∼ 3.15A WHT 2
BLK C102 V1
LED2 RED 3
BLK MR10 H2
H2P GRN
BLK
BLK FIELD WIRING.
LED3
BLK C101 GRN/YLW
H3P H3
9 BLK 9 TRANSMISSION
CIRCUIT CAUTION
SW1 FG NOTE THAT OPERATION WILL RESTART
S21 AUTOMATICALLY IF THE MAIN POWER SUPPLY
t˚ IS TURNED OFF AND THEN BACK ON AGAIN.
HA S1 BZ :BUZZER
7
BZ RTH1 RED C101,C102 :CAPACITOR
R1T FG :FRAME GROUND
F1U :FUSE
4 H1P~H3P :PILOT LAMP
S25 BLU
BLK BRN MS MR10 :MAGNETIC RELAY
PCB4 1
S36
BLK 1 ORG 3~ M1F :FAN MOTOR
M1S,M2S :SWING MOTOR
3 1 WHT
BLK S47 S32 S41 PCB1~PCB4 :PRINTED CIRCUIT BOARD
4 M1F R1T,R2T :THERMISTOR
1 3 1 2 16 8 10 12 14 15 13 11 9 7 S1~S49 :CONNECTOR
INTELLIGENT EYE
SENSOR SW1 :OPERATION SWITCH
V1 :VARISTOR
BLK
BLK
BLK
BLK

BLK

X1M :TERMINAL STRIP


ORG

ORG
RED

RED
YLW

YLW
PNK

PNK
BLU

BLU

:PROTECTIVE EARTH
PCB2 S48

WIRELESS 1 3
INDOOR
REMOTE
R2T MSW MSW
CONTROLLER SIGNAL
RECEIVER
M1S M2S
3D064800F

8 Split Type Air Conditioners FTKV-N Series


EDMT041424 Wiring Diagrams

5.2 Outdoor Unit

RKV25/35NVM

FIELD WIRING

INDOOR N=2 MRM20 WHT


FU3 IPM1
X1M Z3C L1R HR2 DB1
AC120A L1 HR1
1 L 1 BLK
AC2
BRN ~+ +
MRM10 +
2 N 2 WHT V2 HN3
S HN2 HA1 HA2 DB2 C5
3 3 RED BLU
HL3
GRY ~ ~+ +
C119
HL2
V3 ORG +
C6
L FU1 ~
GRN/YLW

MR30 WHT
Q1
3.15A 1 1
N BLK V1
BLK PCB2 DB3 FU2
BLK 3.15A
SA1 S11 BLK S10 ~+
BLK
E1 BLK W V U
BLK IPM2
E2 MR30_A MR30_B 9 BLK 9 ~ +
GRN

MRCW

RED
YLW
BLU
Z2C S50 S100 S20 S90 S40 S70
PCB1 3 1 1 2 1 6 3 S80 1 1 6 2 1 1 4 7 10111213 X11A
N=2
GRN

OUTDOOR
WHT
BLK WHT

RED
YLW
BRN
BRN

BLU
GRY
BLK

WHT

ORG
WHT

ORG

RED

BRN
YLW
BLK
BLK
BLK
BLK
BLK
BLK
NOTE

RED
YLW

BLU
BLK
BLU
BLK
1.REFER TO THE NAME PLATE FOR THE POWER REQUIREMENTS. 4 1
2 1
C5, C6, C119 : CAPACITOR t˚ t˚ t˚
DB1, DB2, DB3 : DIODE BRIDGE X12A S110 M MS Z1C
Q1L N=4 V
FU1, FU2, FU3 : FUSE 3~ U
BLK

BLK

SW1 R1T R2T R3T W


IPM1, IPM2 : INTELLIGENT POWER MODULE Y1E MS
L : LIVE (OUTDOOR) (DISCHARGE) M1F 3~ M1C
PCB3
L1 : COIL (CONDENSER)
L1R : REACTOR PCB1, PCB2, PCB3 : PRINTED CIRCUIT BOARD SW1 : FORCED OPERATION SWITCH
M1C : COMPRESSOR MOTOR S10, S11, S20, S40, S50 V1, V2, V3 : VARISTOR
M1F : FAN MOTOR S70, S80, S90, S100, S110 X1M : TERMINAL STRIP
MRCW, MR30, MRM10, MRM20 : MAGNETIC RELAY HL3, HN3, X11A, X12A : CONNECTOR Y1E : ELECTRONIC EXPANSION VALVE COIL
N : NEUTRAL R1T, R2T, R3T : THERMISTOR Z1C, Z2C, Z3C : FERRITE CORE
Q1L : OVERLOAD PROTECTOR SA1 : SURGE ABSORBER : PROTECTIVE EARTH
: EARTH
3D088119

RKV50/60NVM

3D088286

Split Type Air Conditioners FTKV-N Series 9


Piping Diagrams EDMT041424

6. Piping Diagrams
6.1 Indoor Unit
FTKV25/35NVM FTKV50/60NVM

INDOOR UNIT INDOOR UNIT

MUFFLER ASSY HEAT EXCHANGER


7.0 CuT
(7.9 CuT)
6.4 CuT

THERMISTOR 6.4 CuT HEAT EXCHANGER


7.9 CuT

ON HEAT EXCH.
6.4 CuT
THERMISTOR
ON HEAT EXCH.
CROSS FLOW FAN
FIELD PIPING CROSS FLOW FAN
FIELD PIPING
(6.4 CuT)
M (6.4 CuT)
M
FAN MOTOR FAN MOTOR
FIELD PIPING
FIELD PIPING 9.5 CuT (12.7 CuT) (12.7 CuT)
(9.5 CuT)

REFRIGERANT FLOW
REFRIGERANT FLOW
COOLING COOLING

4D083433C 4D083425B

10 Split Type Air Conditioners FTKV-N Series


EDMT041424 Piping Diagrams

6.2 Outdoor Unit

RKV25/35NVM

OUTDOOR UNIT

HEAT EXCHANGER
7.0 CuT OUTDOOR TEMPERATURE
THERMISTOR
7.0 CuT
7.0 CuT

HEAT EXCHANGER
MOTOR OPERATED
THERMISTOR
VALVE
6.4 CuT 6.4 CuT
9.5 CuT

MUFFLER WITH 4.8 CuT


FILTER

6.4 CuT
7.9 CuT

PROPELLER FAN

FIELD PIPING
LIQUID STOP (6.4 CuT)
DISCHARGE PIPE VALVE
THERMISTOR
COMPRESSOR FIELD PIPING
ACCUMULATOR
9.5 CuT 9.5 CuT 9.5 CuTGAS STOP (9.5 CuT)
MUFFLER
VALVE WITH
SERVICE PORT REFRIGERANT FLOW
COOLING

3D088154

RKV50/60NVM

OUTDOOR UNIT

7.0 CuT HEAT EXCHANGER OUTDOOR TEMPERATURE


THERMISTOR
7.0 CuT

HEAT MUFFLER MOTOR MUFFLER


EXCHANGER WITH OPERATED WITH
THERMISTOR FILTER VALVE FILTER
6.4 CuT
FILTER

M
7.9 CuT

6.4 CuT

PROPELLER FAN

FIELD PIPING
(6.4 CuT)
LIQUID STOP
DISCHARGE PIPE VALVE
THERMISTOR
COMPRESSOR FIELD PIPING
ACCUMULATOR (12.7 CuT)
12.7 CuT GAS STOP
VALVE
REFRIGERANT FLOW
COOLING

3D087640

Split Type Air Conditioners FTKV-N Series 11


Capacity Tables EDMT041424

7. Capacity Tables
7.1 Cooling Only

FTKV25NVM + RKV25NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 7.8
BF 0.05

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.46 1.96 0.42 2.35 1.90 0.46 2.23 1.85 0.50 2.28 1.87 0.51 2.21 1.84 0.53 2.10 1.79 0.57
16.0 22 2.57 1.92 0.42 2.46 1.87 0.46 2.34 1.83 0.50 2.40 1.85 0.51 2.33 1.82 0.54 2.21 1.77 0.58
18.0 25 2.68 2.04 0.42 2.57 1.99 0.46 2.46 1.94 0.50 2.51 1.97 0.51 2.44 1.94 0.54 2.33 1.89 0.58
19.0 27 2.73 2.16 0.42 2.62 2.12 0.46 2.51 2.08 0.50 2.57 2.10 0.52 2.50 2.07 0.54 2.38 2.03 0.58
22.0 30 2.90 2.09 0.43 2.79 2.06 0.47 2.68 2.02 0.51 2.74 2.04 0.52 2.67 2.01 0.54 2.56 1.97 0.58
24.0 32 3.01 2.05 0.43 2.90 2.01 0.47 2.79 1.97 0.51 2.86 2.00 0.52 2.79 1.97 0.55 2.67 1.94 0.59

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)

3D088778

FTKV35NVM + RKV35NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 8.0
BF 0.05

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.97 2.23 0.64 2.97 2.23 0.72 2.97 2.23 0.81 2.97 2.23 0.82 2.97 2.23 0.88 2.93 2.21 0.97
16.0 22 3.60 2.43 0.71 3.44 2.35 0.77 3.28 2.27 0.84 3.36 2.31 0.86 3.26 2.26 0.90 3.10 2.19 0.97
18.0 25 3.75 2.53 0.71 3.59 2.46 0.78 3.44 2.39 0.85 3.52 2.42 0.87 3.42 2.38 0.91 3.26 2.31 0.98
19.0 27 3.83 2.65 0.71 3.67 2.58 0.78 3.51 2.52 0.85 3.60 2.55 0.87 3.50 2.51 0.91 3.34 2.44 0.98
22.0 30 4.06 2.55 0.72 3.90 2.49 0.79 3.75 2.43 0.85 3.84 2.47 0.88 3.74 2.43 0.92 3.58 2.37 0.98
24.0 32 4.21 2.48 0.72 4.06 2.43 0.79 3.90 2.37 0.86 4.00 2.41 0.88 3.90 2.37 0.92 3.74 2.31 0.99

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)

3D088779

12 Split Type Air Conditioners FTKV-N Series


EDMT041424 Capacity Tables

FTKV50NVM + RKV50NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 14.3
BF 0.07

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 5.11 3.86 1.00 4.88 3.74 1.10 4.65 3.63 1.20 4.75 3.68 1.23 4.60 3.61 1.29 4.36 3.49 1.38
16.0 22 5.34 3.79 1.01 5.11 3.68 1.11 4.88 3.58 1.20 4.99 3.62 1.23 4.84 3.56 1.29 4.60 3.45 1.39
18.0 25 5.57 3.98 1.01 5.34 3.88 1.11 5.11 3.78 1.21 5.23 3.83 1.24 5.08 3.77 1.30 4.84 3.67 1.39
19.0 27 5.69 4.21 1.02 5.45 4.11 1.11 5.22 4.01 1.21 5.35 4.06 1.24 5.20 4.00 1.30 4.96 3.91 1.40
22.0 30 6.03 4.06 1.03 5.80 3.97 1.12 5.57 3.89 1.22 5.70 3.94 1.25 5.56 3.89 1.31 5.32 3.80 1.40
24.0 32 6.26 3.95 1.03 6.03 3.88 1.13 5.80 3.80 1.23 5.94 3.85 1.26 5.80 3.80 1.31 5.56 3.72 1.41

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the
BF : Bypass factor figures in the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)

3D088780

FTKV60NVM + RKV60NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 15.4
BF 0.07

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 5.90 4.35 1.22 5.63 4.22 1.34 5.36 4.08 1.45 5.48 4.14 1.49 5.31 4.06 1.56 5.03 3.92 1.68
16.0 22 6.16 4.27 1.23 5.90 4.15 1.34 5.63 4.02 1.46 5.75 4.08 1.50 5.59 4.00 1.57 5.31 3.87 1.69
18.0 25 6.43 4.47 1.23 6.16 4.36 1.35 5.89 4.24 1.47 6.03 4.30 1.51 5.86 4.22 1.58 5.58 4.11 1.69
19.0 27 6.56 4.71 1.24 6.29 4.60 1.35 6.03 4.49 1.47 6.17 4.55 1.51 6.00 4.48 1.58 5.72 4.36 1.70
22.0 30 6.96 4.54 1.25 6.69 4.44 1.36 6.42 4.34 1.48 6.58 4.40 1.52 6.41 4.34 1.59 6.14 4.24 1.71
24.0 32 7.23 4.42 1.25 6.96 4.33 1.37 6.69 4.24 1.49 6.86 4.30 1.53 6.69 4.24 1.60 6.41 4.15 1.71

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the
BF : Bypass factor figures in the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)

3D088781

Split Type Air Conditioners FTKV-N Series 13


Capacity Tables EDMT041424

7.2 Capacity Correction Factor by the Length of Refrigerant Piping (Reference)


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping —
the distance between the indoor unit and the outdoor unit.

7.2.1 25/35 Class

Cooling (R-32)
(%)
100
Capacity correction factor

90

80
Range of the refrigerant
additional charge

5 10 15 20 (m)

Piping length
(R20376)

7.2.2 50/60 Class

Cooling (R-32)
(%)
100
Capacity correction factor

90

80
Range of the refrigerant additional charge

5 10 15 20 25 30 (m)

Piping length
(R20375)

Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.

14 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Limit

8. Operation Limit
RKV25/35NVM

50

46

40

Outdoor temp. (˚CDB)

Continuous operation

Pull-down period
30

20
19.4

10 14 20 23 28 30
Notes :
The graph is based Indoor temp. (˚CWB)
on the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High

4D073983D

RKV50/60NVM

50

46

40
Outdoor temp. (˚CDB)

Continuous operation

Pull-down period

30

20
19.4

Notes : 10 14 20 23 28 30
The graph is based Indoor temp. (˚CWB)
on the following conditions.
• Equivalent piping length 7.5m
• Level difference 0m
• Air flow rate High
4D083533A

Split Type Air Conditioners FTKV-N Series 15


Sound Level EDMT041424

9. Sound Level
9.1 Measuring Location

Indoor Unit Outdoor Unit

1m 1m

0.8 m
MICROPHONE

MICROPHONE

Notes: 1. Operation sound is measured in an anechoic chamber.


2. The data are based on the conditions shown in the table below.

Cooling Piping Length


Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB / 24°CWB 5m

9.2 Indoor Unit


FTKV25NVM FTKV35NVM

70 OVER ALL (dB) 70 OVER ALL (dB)


NC-70 NC-70
50/60Hz 50/60Hz 50/60Hz 50/60Hz
SCALE 220-240/220-230V 220-240/220-230V SCALE 220-240/220-230V 220-240/220-230V
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

60 (H) (L) (H) (L)


60
NC-60 A 37 25 NC-60 A 38 26
(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)
dB (0dB=0.0002µ bar)

50
dB (0dB=0.0002µ bar)

50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz POWER SOURCE 220-240/220-230V 50/60Hz
40 JIS STANDARD 40 JIS STANDARD
NC-40 STANDARD EXTERNAL STATIC PRESSURE NC-40 STANDARD EXTERNAL STATIC PRESSURE
220-240/220-230V 50/60Hz (H) 220-240/220-230V 50/60Hz (H)
30 220-240/220-230V 50/60Hz (L) 30 220-240/220-230V 50/60Hz (L)
NC-30 NC-30

20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING NC-20
FOR CONTINUOUS NC-20
FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D088789 63 125 250 500 1000 2000 4000 8000 4D088807
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

FTKV50NVM FTKV60NVM

70 OVER ALL (dB) 70 OVER ALL (dB)


NC-70 NC-70
50/60Hz 50/60Hz 50/60Hz 50/60Hz
SCALE 220-240/220-230V 220-240/220-230V SCALE 220-240/220-230V 220-240/220-230V
OCTAVE BAND SOUND PRESSURE LEVEL

OCTAVE BAND SOUND PRESSURE LEVEL

60 (H) (L) 60 (H) (L)


NC-60 A 43 34 NC-60 A 45 35

B.G.N IS ALREADY RECTIFIED B.G.N IS ALREADY RECTIFIED


dB (0dB=0.0002µ bar)

50
dB (0dB=0.0002µ bar)

50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz POWER SOURCE 220-240/220-230V 50/60Hz
40 JIS STANDARD JIS STANDARD
40
NC-40 220-240/220-230V 50/60Hz (H) NC-40 220-240/220-230V 50/60Hz (H)
220-240/220-230V 50/60Hz (L) 220-240/220-230V 50/60Hz (L)
30 30
NC-30 NC-30

20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
FOR CONTINUOUS NC-20 FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D083738A 63 125 250 500 1000 2000 4000 8000 4D083739A
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

16 Split Type Air Conditioners FTKV-N Series


EDMT041424 Sound Level

9.3 Outdoor Unit


RKV25NVM RKV35NVM

70 OVER ALL (dB) 70 OVER ALL (dB)


NC-70 NC-70
50/60Hz 50/60Hz
SCALE 220-240/220-230V SCALE 220-240/220-230V

OCTAVE BAND SOUND PRESSURE LEVEL


OCTAVE BAND SOUND PRESSURE LEVEL

60 (H) (H)
60
NC-60 A 46 NC-60 A 47
(B.G.N. IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)

dB (0dB=0.0002µ bar)
dB (0dB=0.0002µ bar)

50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz POWER SOURCE 220-240/220-230V 50/60Hz
40 JIS STANDARD 40 JIS STANDARD
NC-40 220-240/220-230V 50/60Hz (H) NC-40
220-240/220-230V 50/60Hz (H)

30 30
NC-30 NC-30

20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING THRESHOLD HEARING
NC-20 NC-20
FOR CONTINUOUS FOR CONTINUOUS
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D088386A 63 125 250 500 1000 2000 4000 8000 4D088387A
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

RKV50NVM RKV60NVM

70 OVER ALL (dB) 70 OVER ALL (dB)


NC-70 NC-70
50/60Hz 50/60Hz
SCALE SCALE
OCTAVE BAND SOUND PRESSURE LEVEL

220-240/220-230V (H)
OCTAVE BAND SOUND PRESSURE LEVEL

220-240/220-230V (H)
60 60
NC-60 A 48 NC-60 A 52

(B.G.N IS ALREADY RECTIFIED) (B.G.N IS ALREADY RECTIFIED)


dB (0dB=0.0002µ bar)
dB (0dB=0.0002µ bar)

50 50
NC-50 OPERATING CONDITIONS NC-50 OPERATING CONDITIONS
POWER SOURCE 220-240/220-230V 50/60Hz (H) POWER SOURCE 220-240/220-230V 50/60Hz (H)
40 JIS STANDARD 40 JIS STANDARD
NC-40 NC-40
220-240/220-230V 50/60Hz (H) 220-240/220-230V 50/60Hz (H)

30 30
NC-30
NC-30

20 20
APPROXIMATE APPROXIMATE
THRESHOLD HEARING NC-20 THRESHOLD HEARING
FOR CONTINUOUS FOR CONTINUOUS NC-20
NOISE NOISE
63 125 250 500 1000 2000 4000 8000 4D088836 63 125 250 500 1000 2000 4000 8000 4D088837
OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz)

Split Type Air Conditioners FTKV-N Series 17


Electric Characteristics EDMT041424

10. Electric Characteristics

Power supply Compressor OFM IFM


Indoor Unit Outdoor Unit
Hz - Volts Voltage range MCA MFA RHz RLA W FLA W FLA
50 - 220 2.4 0.17 0.15
50 - 230 Max. 50 Hz, 264 V 2.3 0.16 0.14
Min. 50 Hz, 198 V
FTKV25NVM RKV25NVM 50 - 240 8.0 10 42 2.2 33 0.15 40 0.13
60 - 220 Max. 60 Hz, 253 V 2.4 0.17 0.15
60 - 230 Min. 60 Hz, 198 V 2.3 0.16 0.14
50 - 220 4.1 0.17 0.16
50 - 230 Max. 50 Hz, 264 V 3.9 0.16 0.15
Min. 50 Hz, 198 V
FTKV35NVM RKV35NVM 50 - 240 8.8 10 65 3.7 33 0.15 40 0.14
60 - 220 Max. 60 Hz, 253 V 4.1 0.17 0.16
60 - 230 Min. 60 Hz, 198 V 3.9 0.16 0.15
50 - 220 5.6 0.19 0.19
Max. 50 Hz, 264 V
50 - 230 Min. 50 Hz, 198 V 5.3 0.18 0.18
FTKV50NVM RKV50NVM 50 - 240 13.5 15 58 5.1 53 0.17 43 0.18
60 - 220 Max. 60 Hz, 253 V 5.6 0.19 0.19
60 - 230 Min. 60 Hz, 198 V 5.3 0.18 0.18
50 - 220 7.0 0.20 0.21
Max. 50 Hz, 264 V
50 - 230 Min. 50 Hz, 198 V 6.7 0.19 0.20
FTKV60NVM RKV60NVM 50 - 240 13.5 15 69 6.4 53 0.18 43 0.19
60 - 220 Max. 60 Hz, 253 V 7.0 0.20 0.21
60 - 230 Min. 60 Hz, 198 V 6.7 0.19 0.20

Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB
MFA : Max. fuse amps (A) Outdoor temp. 35°CDB.
RHz : Rated operating frequency (Hz) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : Rated load amps (A) 4. Instead of fuse, use circuit breaker.
OFM : Outdoor fan motor 5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
IFM : Indoor fan motor detector capable of handling high harmonics must be used in
W : Fan motor rated output (W) order to prevent malfunctioning of the earth leak detector.)
FLA : Full load amps (A)

3D088732

18 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

11. Installation Manual


11.1 25/35 Class

Split Type Air Conditioners FTKV-N Series 19


Installation Manual EDMT041424

20 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

Split Type Air Conditioners FTKV-N Series 21


Installation Manual EDMT041424

22 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

Split Type Air Conditioners FTKV-N Series 23


Installation Manual EDMT041424

24 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

Split Type Air Conditioners FTKV-N Series 25


Installation Manual EDMT041424

26 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

Split Type Air Conditioners FTKV-N Series 27


Installation Manual EDMT041424

3P363835-4A

28 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

11.2 50/60 Class

Split Type Air Conditioners FTKV-N Series 29


Installation Manual EDMT041424

30 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

Split Type Air Conditioners FTKV-N Series 31


Installation Manual EDMT041424

32 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

Split Type Air Conditioners FTKV-N Series 33


Installation Manual EDMT041424

34 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

Split Type Air Conditioners FTKV-N Series 35


Installation Manual EDMT041424

36 Split Type Air Conditioners FTKV-N Series


EDMT041424 Installation Manual

Split Type Air Conditioners FTKV-N Series 37


Installation Manual EDMT041424

3P363835-5A

38 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

12. Operation Manual

Split Type Air Conditioners FTKV-N Series 39


Operation Manual EDMT041424

40 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 41


Operation Manual EDMT041424

42 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 43


Operation Manual EDMT041424

44 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 45


Operation Manual EDMT041424

46 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 47


Operation Manual EDMT041424

48 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 49


Operation Manual EDMT041424

50 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 51


Operation Manual EDMT041424

52 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 53


Operation Manual EDMT041424

54 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 55


Operation Manual EDMT041424

56 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 57


Operation Manual EDMT041424

58 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 59


Operation Manual EDMT041424

60 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 61


Operation Manual EDMT041424

62 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 63


Operation Manual EDMT041424

64 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 65


Operation Manual EDMT041424

66 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 67


Operation Manual EDMT041424

68 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 69


Operation Manual EDMT041424

70 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

Split Type Air Conditioners FTKV-N Series 71


Operation Manual EDMT041424

72 Split Type Air Conditioners FTKV-N Series


EDMT041424 Operation Manual

3P363834-3A

Split Type Air Conditioners FTKV-N Series 73


Optional Accessories EDMT041424

13. Optional Accessories


13.1 Option List
13.1.1 Indoor Unit

Option Name 25/35/50/60 Class


1 Titanium apatite photocatalytic air-purifying filter (without frame) ★ KAF970A46
2 Remote controller loss prevention with chain KKF910A4

Note: ★ Standard accessory

13.1.2 Outdoor Unit

Option Name 25/35 Class 50/60 Class


1 Air direction adjustment grille KPW937A4 KPW945A4
2 Drain plug KKP937A4

74 Split Type Air Conditioners FTKV-N Series


EDMT041424 Optional Accessories

13.2 <KPW937A4> Air Direction Adjustment Grille


Q Before Installation

Checking the parts Check the following parts


Name Louver Installation manual

Shape

With 4 screws
Quantity 1piece 1piece

Q Installation Procedure
Selection of Installation Location
Use when installing in a location that meets the following conditions.
zWhen installing near the border to a neighbor's house
zIf exhaust blows directly on passers-by because outdoor unit is installed facing a road.
zChanging the fan direction of the outdoor unit to prevent it blowing directly on shrubbery, etc.

Installation of Louver Prepared hole


pitch 435mm
zInstallation is possible in the four directions: Fan partition
upward, downward, rightward, and leftward. Part A
zThe installation screws are attached to the louver. (see figure below)
zFirst temporarily attach the louver with 4 screws,
then check that the angle is correct, and finally Prepared hole
pitch 435mm
tighten the screws fully. Fan partition
CAUTION
1.Install so that a short circuit is prevented.
2.For the use in snowy regions, avoid installation
with the air outlet facing upward. Install so that
the air outlet faces leftward, rightward, or down-
ward. The prepared hole is in between the grating
Snow accumulates in the air outlet of the outdoor of the grille. Part A (prepared hole) cross
section (the shape of either a or b)
unit, causing malfunction of the main body of the
outdoor unit. a) Grille grating b) Grille grating
3.Be advised that if the fan direction is up,
dead leaves and other foreign matter
easily accumulates in the exhaust vent. Prepared hole Prepared hole

4P104499-1A

Split Type Air Conditioners FTKV-N Series 75


Optional Accessories EDMT041424

13.3 <KPW945A4> Air Direction Adjustment Grille

„ Before installation
Check the following parts Name Louver Truss tapping screw Installation manual

Shape

M4×4screws(max.7.5kW class)
Quantity 1piece M5×4screws(8.0/9.0kW class)
1piece

„ Installation Procedure
Selection of Installation Location Space Needed for Installation
Use when installing in a location that meets the following conditions. O A minimum of 100mm is needed
O When installing near the border to a neighbor's house between the back of the outdoor
O If exhaust blows directly on passers-by because outdoor unit is instal- unit and any obstructions
led facing a road. (walls, etc.) 100
t han
O If exhaust blows directly on vegetation
m ore

Installation of Louvers
Caution
Attach the louvers overlapping the standard grille.
Installing the louvers without the grille would allow hands to enter the fan area,
which is dangerous, so be sure to install the standard grille.

When pointing up When pointing down


(1) Remove the 4 attachment screws from (1) Remove the 4 attachment screws from
the standard grille. the standard grille.

(2) Install the louver pointed up. (2) Install the louver pointed down.
O Overlap the standard grille and O Overlap the standard grille and
screw both in together. screw both in together.
O The attachment screws O The attachment screws
are in the louvers. are in the louvers.

(3) Installation complete (3) Installation complete

3P089958-2C

76 Split Type Air Conditioners FTKV-N Series


EDMT041424
EDMT041424

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

ENGINEERING DATA
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.

Split Type Air Conditioners


If you have any enquiries, please contact your local importer, distributor and/or retailer.
Split Type Air Conditioners
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
- Cooling Only -

FTKV-N Series
FTKV-N Series

Specifications, designs and other content appearing in this brochure are current as of May 2014 but subject to change without notice.