'11•SCM-SM-110
updated November 25, 2011
SERVICE MANUAL
CONTENTS
- -
- -
■ Table of models
Capacity 20 25 35 50 60 71
Model
Outdoor unit
Example: SCM 60 Z J-S1
Series code
Inverter type
Product capacity
Model name
(Outdoor unit)
- -
- -
Model SRK71ZK-S
Remote controller
Operation section
FAN SPEED button OPERATION MODE select button
Each time the button is pressed, the Each time the button pressed, the
display is switched over in turn. display is switched over in turn.
CLEAN switch
ACL switch
This switch selects the CLEAN mode.
Switch for resetting microcomputer.
- -
ON TIMER button
This button selects ON TIMER operation.
1.5 sec.
HI POWER Light (green)
ON
Illuminates during HIGH POWER operation. HOT KEEP
OFF
AIR SELECTION button 0.5 sec.
Use this button to switch between the combination of upper and
lower air outlets and upper air outlet.
3 sec.
ON
AIR OUTLET SELECTION light (green) CLEAN operation
Illuminates during upper air outlet operation. OFF
1 sec.
Remote controller signal receiver
- -
Remote controller
Operation section
Each time the button is pressed, the Each time the button pressed, the
display is switched over in turn. display is switched over in turn.
ACL switch
This switch is for resetting microcomputer
and setting time.
- -
・Model SRK20, 25, 35ZJX-S, 50, 60ZJX-S1 ・Model SRK25, 35ZJR-S, 20, 25, 35, 50ZJ-S
- -
• Model SRK20, 25, 35ZJX-S, 50, 60ZJX-S1, 71ZK-S • Model SRK25, 35ZJR-S, 20, 25, 35, 50ZJ-S
SRF25, 35ZJX-S, 50ZJX-S1
SRR25, 35, 50, 60ZJ-S
- 10 -
Note: (1) Default states of the jumper wire (J172 or JA3) and the interface kit at the shipping from factory – On the PCB, the dip switch (SW2-4) is set to enable the annual
cooling function.
(2) To cancel the annual cooling setting, consult your dealer.
• Model SRK20, 25, 35ZJX-S, 50, 60ZJX-S1, 71ZK-S • Model SRK25, 35ZJR-S, 20, 25, 35, 50ZJ-S
SRF25, 35ZJX-S, 50ZJX-S1
SRR25, 35, 50, 60ZJ-S
5 A
Outdoor air temperature ( C)
- 11 -
Mode
Item Cooling Heating
①+0.5 ①-1.0
Temperature
adjustment ②+1.0 ②-2.0
③+1.5 ③-2.5
(8) Flap and louver control (SRK and SRF series only)
S SRK series
Control the flap and louver by AIRFLOW
(UP/DOWN) and
(LEFT/RIGHT) button on the wireless remote controller.
(a) Flap
Each time when you press the AIRFLOW
(UP/DOWN) button the mode changes as follows.
Model SRK71ZK-S
Remote controller
display
COOL , DRY, FAN Approx. 5° Approx. 25° Approx. 35° Approx. 55° Approx. 80°
HEAT Approx. 25° Approx. 40° Approx. 50° Approx. 60° Approx. 80°
- 12 -
(b) Louver
Model SRK20, 25, 35ZJX-S, 50, 60ZJX-S1, 25, 35ZJR-S, 20, 25, 35, 50ZJ-S
Each time when you press the AIRFLOW
(LEFT/RIGHT) button the mode changes as follows.
(Louver stopped)
Model SRK71ZK-S
(Louver stopped)
(Swing)
Angle of Louver
Remote controller
display
Center installation Left Approx. 50° Left Approx. 20° Center Right Approx. 20° Right Approx. 50°
(c) Swing
1) Swing flap 2) Swing louver
Flap moves in upward and downward Louver moves in left and right directions continuously.
directions continuously.
In HEAT operation In COOL, DRY, FAN operation
Approx.5°(10°)
Approx. 20°(25°)
ާ35°ި
Approx. 60°
Approx. 75°(70°)ާ80°ި
Notes (1) Values in ( ) are for the model SRK25, 35ZJR-S, 20, 25, 35, 50ZJ-S.
(2) Values in〔 〕are for the model SRK71ZK-S.
(e) Multi-directional Air Flow (up/down air scroll and left/right air scroll)
〔SRK71ZK-S only〕
Activating both up/down air swing and left/right air swing at the same time results in a multi-directional air flow.
S SRF series
Control the flap by AIRFLOW
(UP/DOWN) button on the wireless remote controller.
(a) Flap
Each time when you press the AIRFLOW
(UP/DOWN) button the mode changes as follows.
(b) Swing
1) Swing flap
Flap moves in upward and downward directions continuously.
In HEAT operation In COOL, DRY, FAN operation
Approx.44° Approx.60°
Approx.12°
Approx.5°
Approx.
5°
(c) Memory flap (Flap stopped)
When45°
Approx. you press the AIRFLOW button once while the flap is operating, it stops swinging at the position. Since this angle is mem-
orized in the microcomputer, the flap will automatically be set at this angle when the next operation is started.
Approx. 60°
(d) When not operating
Approx. 75°
The flap returns to the position of air flow directly below, when operation has stopped.
- 14 -
(a) During Cooling and Heating (Including auto cooling and heating)
1) Air flow selection is determined according to indoor temperature and setting temperature.
- 15 -
2) Air flow direction is controlled according to the indoor temperature and setting temperature.
a) When 3D auto operation starts
Cooling Heating
Flap Up/down Swing
Louver Wide (fixed) Center (fixed)
Cooling Heating
Flap Horizontal blowing (Fixed) Slant forwardl blowing (Fixed)
Louver Left/right Swing
c) After the flap swings for 5 cycles, control is switched to the control in d).
Cooling Heating
Flap Up/down Swing
Louver Center (Fixed)
d) For 5 minutes, the following air flow direction control is carried out.
Cooling Heating
Flap Horizontal blowing (Fixed) Slant forwardl blowing (Fixed)
Louver Wide (Fixed)
e) After 5 minutes have passed, the air flow direction is determined according to the indoor temperature and setting
temperature.
- 16 -
Note (1) If the display shows heating and the operation is fan, Hot Keep will operate.
Example of operating pattern
Cooling Heating
A unit switch Cooling switch Fan Heating
ON ON
Operation Operation Operation Operation Operation Note (1) 〔〕 indicates currect operation.
- 17 -
1) Control A
a) If the float switch detects any anomalous draining condition, the unit stops with the anomalous stop and the
drain pump starts. After detecting the anomalous condition, the drain motor comtinues to be ON.
b) It keeps operating while the float switch is detecting the anomalous condition.
2) Control B
If the float switch detects any anomalous drain condition, the drain motor is turned ON for 5 minutes, and at 10 sec-
onds after the drain motor OFF it checks the float switch. If it is normal, the unit is stopped under the normal mode
or, if there is any anomalous condition, displayed by the flashing of display lights and the drain motor is turned ON.
(The ON condition is maintained during the drain detection.)
- 18 -
The figure below shows the remote control with the cover opened.
Ventilaion display Weekly timer display
Displayed during ventilation operation Displays the settings of the
weekly timer.
VENT button
GRILL button This button is used to operate external
This button has no function. ventilator.
When this button is pressed,
(Invalid Operation)
is displayed, but it does not mean a failure.
LOUVER button
This button is used to operate/stop the
Cover
swing louver.
CHECK button
This button is used at servicing.
RESET button
Press this button while making settings to go back to the
●
previous operation.
TEST button
This button is used during test operation. This button is also used to reset the "FILTER CLEANING" display.
●
* All displays are described in the liguid crystal display for explanation.
- 19 -
The figure below shows the remote control with the cover opened.
Ventilaion display Weekly timer display
Displayed during ventilation operation Displays the settings of the
weekly timer.
VENT button
ESP button This button is used to operate external
This button is used to ventilator.
select the auto static
pressure adjustment mode.
LOUVER button
This button is used to operate/stop the
Cover
swing louver.
CHECK button
This button is used at servicing.
RESET button
Press this button while making settings to go back to the
●
previous operation.
TEST button
This button is used during test operation. This button is also used to reset the "FILTER CLEANING" display.
●
* All displays are described in the liguid crystal display for explanation.
- 20 -
Indication section
Operation section
* All displays are described in the liquid crystal display for explanation
- 21 -
Master/ slave setting when more than one remote controllers are used
A maximum of two remote controllers can be connected to one indoor unit (or one group of indoor units.)
Switch Setting Contents
Indoor units M Master remote controller
SW1
S Slave remote controller
SW2 SW2
A Remote controller cord (no polarity)
Upper
B
親 Master
M SW2
Remote controller Remote controller SW1
SW1 S SW1 "Master" SW1 "Slave" Slave Board
SW1子 SW1
Lower
Set SW1 to “Stave” for the slave remote controller. It was factory set to “Master” for shipment.
Note: The setting “Remote controller thermistor enabled” is only selectable with the master
remote controller in the position where you want to check room temperature.
X Y
The air conditioner operation follows the last operation of the remote controller regardless
of the master / slave setting of it.
Caution
When using multiple remote controllers, the following dispiays or settings
cannot be done with the slave remote controller. It is available only with
the master remote controller.
Louver position setting (set upper or lower limit of swinging range)
Setting indoor unit functions
Setting temperature range
Operation data display
Error data display
Silent mode setting
Test operation of drain pump
Remote controller sensor setting
- 22 -
-3 +3
Room temperature setting temperature
Room temperature (detected with ThI-A) [deg]
Note (1) Room temperature control during auto cooling/auto heating is performed according to the room temperature setting temperature. (DIFF: ±1 deg)
(2) If the indoor heat exchanger temperature rises to 59°C or higher during Heating operation stopped (cooling)
heating operation, it is switched automatically to cooling operation. In
Heating OK
addition, for 1 hour after this switching, the heating operation is not
performed, regardless of the temperature shown at right.
56 59
Indoor heat exchanger temperature (°C)
- 23 -
Sleep timer � � �
OFF timer � � �
ON timer � � �
Weekly timer � � �
- 24 -
b) Once the fan motor is changed from OFF to ON during the thermostat ON, the indoor fan motor is not turned
OFF even if the heat exchanger thermistor detects lower than 25°C.
Note (1) When the defrost control signal is received, it complies with the fan control during defrosting.
c) Once the hot start is completed, it will not restart even if the temperature on the heat exchanger thermistor drops.
2) During the hot start, the louver horizontal control signal is transmitted.
3) When the fan motor is turned OFF for 7 minutes continuously after defrosting, the fan motor is turned ON regardless
of the temperatures detected with the indoor heat exchanger thermistors (ThI-R1, R2).
(iii) Ending condition
1) If one of following conditions is met during the hot start control, this control is terminated, and the fan is operated with
the set airflow volume.
a) Heat exchanger thermistor (ThI-R1 or R2, whichever higher) detects 35°C or higher.
b) It has elapsed 7 minutes after starting the hot start control.
(g) Hot keep
Hot keep control is performed at the start of the defrost control.
1) Control
a) When the indoor heat exchanger temperature (detected with ThI-R1 or R2) drops to 35°C or lower, the speed of
indoor fan is changed to the lower tap at each setting.
b) During the hot keep, the louver horizontal control signal is transmitted.
2) Ending condition
When the indoor fan is at the lower tap at each setting, it returns to the set airflow volume as the indoor heat exchanger
temperature rises to 45°C or higher.
(h) Thermostat operation
(i) Cooling
1) Thermostat is operated with the room temperature control.
2) Thermostat is turned ON or OFF relative to the set room temperature as shown below.
Thermostat ON
Temperature drop
Thermostat OFF
Temperature rise
-1 +1
Set room temperature
3) Thermostat is turned ON when the room temperature is in the range of -1 < Set point < +1 at the start of cooling opera-
tion (including from heating to cooling).
(ii) Heating
1) Thermostat is operated with the room temperature control.
2) Thermostat is turned ON or OFF relative to the set room temperature as shown below.
Thermostat ON
Thermostat OFF
Heater ON
-1 +1
Temperature rise
Heater OFF Temperature drop
-1 +1 ◦
3C
3) Thermostat is turned ON when the room temperature is in the range of -1 < Set point < +1 at the start of cooling opera-
tion (including from cooling to heating).
(iii) Fan control during heating thermostat OFF
1) Following fan controls during the heating thermostat OFF can be selected with the indoor function setting of the wired
remote controller.
① Low fan speed (Factory default), ② Set fan speed, ③ Intermittence, ④ Fan OFF
- 25 -
2) When the “Low fan speed (Factory default)” is selected, the following taps are used for the indoor fans.
・ For AC motor : Lo tap
・ For DC motor : ULo tap
3) When the “Set fan speed” is selected, it is operated with the set fan speed also in the thermostat OFF condition.
4) If the “Intermittence” is selected, following controls are performed:
a) If the thermostat is turned OFF during the heating operation, the indoor unit moves to the hot control and turns
OFF the indoor fan if the heat exchanger thermistors (both ThI-R1 and R2) detect 25°C or lower.
b) Indoor fan OFF is fixed for 5 minutes. After the 5 minutes, the indoor fan is operated at Lo (AC motor) or ULo (DC
motor) for 2 minutes. In the meantime the louver is controlled at level.
c) After operating at Lo (AC motor) or ULo (DC motor) for 2 minutes, the indoor fan moves to the state of a) above.
d) If the thermostat is turned ON, it moves to the hot start control.
e) When the heating thermostat is turned OFF, the remote controller displays the temperature detected at the fan stop
and revises the temperature later when the indoor fan changes from Lo (AC motor) or ULo (DC motor) to stop.
The remote controller uses the operation data display function to display temperatures and updates values of
temperature even when the indoor fan is turned OFF.
f) When the defrosting starts while the heating thermostat is turned OFF or the thermostat is turned OFF during
defrosting, the indoor fan is turned OFF. (Hot keep or hot start control takes priority.) However, the suction
temperature is updated at every 7-minute.
g) When the heating thermostat is turned ON or the operation is changed to another mode (including stop), this
control is stopped immediately, and the operating condition is restored.
5) When the “Fan OFF” is selected, the fan on the indoor unit of which the thermostat has been turned OFF, is turned
OFF. The same occurs also when the remote control sensor is effective.
(2) After the setting time has elapsed, the “FILTER CLEANING” is displayed and, after operating for 24 hours further (counted also during the stop), the
unit stops.
(j) Auto swing control [Applicable model: FDTC and FDEN]
1) Louver control
a) Press the “LOUVER” button to operate the swing louver when the air conditioner is operating.
“SWING ” is displayed for 3 seconds and then the swing louver moves up and down continuously.
b) To fix the swing louver at a position, press one time the “LOUVER” button while the swing louver is moving so that
four stop positions are displayed one after another per second.
When a desired stop position is displayed, press the “LOUVER” button again. The display stops, changes to show
the “STOP 1 ” for 5 seconds and then the swing louver stops.
c) Louver operation at the power on with a unit having the louver 4-position control function
The louver swings one time automatically (without operating the remote controller) at the power on.
This allows inputting the louver motor (LM) position, which is necessary for the microcomputer to recognize the
louver position.
Note (1) If you press the “LOUVER” button, the swing motion is displayed on the louver position LCD for 10 second. The display changes to the
“SWING ” display 3 seconds later.
- 26 -
- 27 -
(m) Drain motor (DM) control [Applicable model: FDTC and FDUM]
( i ) Drain detection switch is turned ON or OFF with the float switch (FS) and the timer.
Drain detection switch ON
[*1] [*2]
[*1] Drain detection switch is turned “ON” when the float switch “Open” is detected for 3 seconds continuously in the
drain detectable space.
[*2] Drain detection switch is turned “OFF” when the float switch “Close” is detected for 10 seconds continuously.
1) It detects always from 30 seconds after turning the power ON.
a) There is no detection of anomalous draining for 10 seconds after turning the drain pump OFF.
b) Turning the drain detection switch “ON” causes to turn ON the drain pump forcibly.
c) Turning the drain detection switch “OFF” releases the forced drain pump ON condition.
(ii) Indoor unit performs the control A or B depending on each operating condition.
1) Control A
a) If the float switch detects any anomalous draining condition, the unit stops with the anomalous stop (displays E9)
and the drain pump starts. After detecting the anomalous condition, the drain motor continues to be ON.
b) It keeps operating while the float switch is detecting the anomalous condition.
2) Control B
If the float switch detects any anomalous drain condition, the drain motor is turned ON for 5 minutes, and at 10
seconds after the drain motor OFF it checks the float switch. If it is normal, the unit is stopped under the normal
mode or, if there is any anomalous condition, E9 is displayed and the drain motor is turned ON. (The ON condition is
maintained during the drain detection.)
(n) Operation check/drain pump test run operation mode
1) If the power is turned on by the dip switch (SW7-1) on the indoor PCB when electric power source is supplied, it enters the
mode of operation check/drain pump test run. It is ineffective (prohibited) to change the switch after turning power on.
2) When the communication with the remote controller has been established within 60 seconds after turning power on by the
dip switch (SW7-1) ON, it enters the operation check mode. Unless the remote controller communication is established, it
enters the drain pump test run mode.
Note (1) To select the drain pump test run mode, disconnect the remote controller connector (CNB) on the indoor PCB to shut down the remote controller
communication.
3) Operation check mode
There is no communication with the outdoor unit but it allows performing operation in respective modes by operating the
remote controller.
4) Drain pump test run mode
As the drain pump test run is established, the drain pump only operates and during the operation protective functions by
the microcomputer of indoor unit become ineffective.
(o) Cooling, dehumidifying frost protection
1) To prevent frosting during cooling mode or dehumidifying mode operation, the of compressor speed is reduced if
the indoor heat exchanger temperature (detected with ThI-R) drops to 1.0 °C or lower at 4 minutes after the start of
compressor operation. If the indoor unit heat exchanger temperature is 1.0 °C or lower after 1 minutes, the compressor
speed is reduced further. If it becomes 2.5 °C or higher, the control terminates. When the indoor heat exchanger
temperature has become as show below after reducing the compressor speed, it is switched to the fan operation. For the
selection of indoor fan speed, refer to item 2).
Cooling operation Symbol
Model A B C D
- 28 -
Compressor ON
56 63
Indoor heat exchanger temperature (°C)
- 29 -
Wirings between
outdoor unit and
indoor units
Indoor unit 0 1 2 3 4 5 C D E F
R
Remote controller
(2) Unit No. may be set at random unless duplicated, it should be better to set orderly like 0, 1, 2…, F to avoid mistake.
- 30 -
1 Optional
2
XR1
CnT 3
XR2 Card key
Blue
4 switch
12V XR3 XR5
5
XR4
6
XR5
*1 Only the “LEVEL INPUT” is acceptable for external input, however when the indoor function setting of
“Level input (Factory default)” or “Pulse input” is selected by the function for “External input” of the wired remote
controller, operation status will be changed as follows.
In case of “Level input” setting In case of “Pulse input” setting
Unit operation from the wired
Unit starts operation
remote controller becomes
*(2)
available*(1)
*(1) In case that “Operation permission/prohibition mode” setting is “Valid” and “External input” setting is “Level
input (Factory default)”;
① When card key switch is ON (CnT-6 ON: Operation permission), start/stop operation of the unit from the
wired remote controller becomes available.
② When card key switch is OFF (CnT-6 OFF: Operation prohibition), the unit stops operation in conjunction
with OFF signal, and start/stop operation of the unit from the wired remote controller becomes not available.
*(2) In case that “Operation permission/prohibition mode” setting is “Valid” and “External input” setting is “Pulse
input (Local setting)”;
① When card key switch is ON (Operation permission), the unit starts operation in conjunction with ON signal.
and also start/stop operation of the unit from the wired remote controller becomes available.
② When card key switch is OFF (Operation prohibition), the unit stops operation in conjunction with OFF signal, and
start/stop operation of the unit from the wired remote controller becomes not available.
(3) This function is invalid only at “Center mode” setting done by central controller.
(v) External input/output control (CnT)
Be sure to connect the wired remote controller to the indoor unit. Without wired remote controller remote operation by CnT is
not possible to perform.
Optional
1
①Operation output (CnT-2: XR1)
2
XR1 ②Heating output (CnT-3: XR2)
CnT 3
Blue
XR2 ③Thermostat ON output (CnT-4: XR3)
4
12V XR3 ④Error output (CnT-5: XR4)
5
XR4
⑤Remote operation input (CnT-6: No-voltage contactor)
6
XR5
- 31 -
3) Remote operation
a) In case of multiple units (Max. 16 indoor units group) are connected to one wired remote controller
When the indoor function setting of wired remote controller for “External control set” is changed from “Individual
(Factory default)” to “ For all units”, all units connected in one wired remote controller system can be controlled by
external operation input.
Outdoor unit SCM**ZJ type
Outdoor unit SCM**ZJ type
Wirings between
outdoor unit and
indoor units
Indoor unit 0 ① ② ③ ④ ⑤ C D E F
R
Remote controller
0
Ex. Indoor units = +①+②+③+④+⑤・・・・ + + +
C D E F ≦16 units
- 32 -
When more than one indoor unit (Max. 16 indoor units) are connected in one wired remote controller system:
(1) With the factory default, external input to CnT-6 is effective for only the unit ⓪.
(2) When setting “For all unit” (Local setting), all units in one remote controller system can be controlled by external
input to CnT-6 on the indoor unit ⓪.
(3) External input to CnT-6 on the other indoor unit than the unit ⓪ is not effective.
(w) Fan control at heating startup (Applicable model: FDTC and FDUM)
1) Start conditions
At the start of heating operation, if the difference of setting temperature and return air temperature is 5°C or higher after
the end of hot start control, this control is performed.
2) Contents of control
a) Sampling is made at each minute and, when the indoor unit heat exchanger temperature (detected with ThI-R) is
37°C or higher, present number of revolutions of indoor unit fan speed is increased by 10min-1.
b) If the indoor unit heat exchanger temperature drops below 37°C at next sampling, present number of revolutions of
indoor unit fan speed is reduced by 10min-1.
3) End conditions
Indoor fan speed is reduced to the setting airflow volume when the compressor OFF is established and at 30 minutes after
the start of heating operation.
-1 +1 +2 +4
Setting temperature Setting temperature
Room temperature (deg) Room temperature (deg)
- 33 -
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum capacity of
the outdoor unit, the demand capacity will be proportionally distributed.
(b) Outdoor compressor speed control
Indoor compressor command total speed value Decision speed
0 rps 0 rps
A rps or less A rps
More than A rps, but B rps or less A rps to B rps
More than B rps B rps
Values of A, B
Model SCM40ZJ-S SCM45ZJ-S SCM50ZJ-S1
Item
A 30 rps 30 rps 30 rps
B 100 rps 120 rps 120 rps
Operation Thermostat OFF Thermostat OFF Fan, stop, abnormal stop Failure
Functional Heating (All indoor units) (Some of indoor units) (Some of indoor units) (Outdoor unit)
components
Multi-operation rpm calculated based 0 0 0 0
Command speed on the rpm required for each indoor unit (All indoor units) (Thermostat off units) (Fan, stop, abnormal stop units) (All units)
Indoor Fixed According to mode switching Hot Keep According to mode switching Hot Keep
unit fan Automatic According to command speed Hot Keep According to command speed Hot Keep
Outdoor unit fan According to outdoor unit speed OFF According to outdoor unit speed OFF
Electronic According to decision According to stop mode According to heating stop unit control According to heating stop unit control According to stop mode
expansion valve speed (Thermostat off units) (Fan, stop, abnormal stop units)
Compressor ON OFF ON ON OFF
- 34 -
40
40
Tho-R
−2
Tho-A Tho-R
(Tho-A)㧙(Tho-R) >
= 0.44 × (Tho-A) + A
Tho-A A
㧙2 °C <= Tho-A 4(6.5)
㧙15 °C <
= Tho-A < 㧙2 °C 6(10.0)
Tho-A < 㧙15 °C 6(10.0)
-5
-5
e
tur
era e
mp ra t
ur
r t te pe
-10 ta m
o ns t te
rat
i -10 s tar
e
op i on
ost rat
fr pe
Defrost operation
o
De start rost
f Defrost operation
-15 De start
-15
-20
-20 -15 -10 -20 -5 0 5 10
Outdoor air-20 -15 (℃) -10
temperature -5 0 5 10
Outdoor air temperature (℃)
Tho-R −2
−2
(b)
Tho-R 20
Tho-R º SCM71, 80, 100, 125
3
Heating operation
Heating operation
Max. 12 minutes and 50 seconds 2~7 minutes※
Max. 12 minutes and 50 seconds 2~7 minutes※
Hot keep operation
Hot keep operation
※ Depends on an operation condition, the time can be longer than 7 minutes.
※ Depends on an operation condition, the time can be longer than 7 minutes.
- 35 -
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum capacity of
the outdoor unit, the demand capacity will be proportionally distributed.
(b) Outdoor compressor speed control
Indoor compressor command total speed value Decision speed
0 rps 0 rps
A rps or less A rps
More than A rps, but B rps or less A rps to B rps
More than B rps B rps
Values of A, B
Model SCM40ZJ-S SCM45ZJ-S SCM50ZJ-S1 SCM60ZJ-S1 SCM71ZJ-S1 SCM80ZJ-S1
A 30 rps 30 rps 30 rps 20 rps 20 rps 20 rps
B 100 rps 120 rps 120 rps 120 rps 120 rps 120 rps
Operation Thermostat OFF Thermostat OFF Fan, stop, abnormal stop Failure
Functional Cooling (All indoor units) (Some of indoor units) (Some of indoor units) (Outdoor unit)
components
Multi-operation rpm calculated based 0 0 0 0
Command speed on the rpm required for each indoor unit (All indoor units) (Thermostat off units) (Fan, stop, abnormal stop units) (All units)
- 36 -
Cooling
27.5
25.5
Heating
18 30
Outdoor air temperature (°C)
1) The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the previous
operation mode, changes the operation mode.
2) When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is se-
lected during heating, cooling or dehumidifying operation, the unit is operated in the previous operation mode.
3) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the sig-
nals of the wireless remote controller and the setting temperature.
4) When the unit is operated automatically with the wired remote controller connected, the cooling operation is controlled accord-
ing to the display temperatures while the setting temperature is compensated by +1°C during dehumidifying or by +2°C during
heating.
Cooling
27.5
25.5
Heating
18 30
Outdoor air temperature (˚C)
- 37 -
1)
a)
b)
c)
2)
3)
4) When the unit is operated automatically with the wired remote controller connected, the cooling operation is controlled ac-
cording to the display temperatures while the setting temperature is compensated by +1°C during dehumidifying or by +2°C
during heating.
(c) FDTC, FDEN and FDUM series
Refer to page 23.
(1) The operation mode is switched over between Permission and Prohibition by releasing the jumper wire (J3)
on the indoor PCB.
When the jumper wire (J3) is short circuited When the jumper wire (J3) is released
Normal operation is enable (when shipping) Permission / Prohibition mode
When CnT input is set to ON, the operation starts When Cnt input is set to ON, the operation mode is
and if the input is set to OFF, the operation stops. changed to permission and if input is set to OFF the
For the CnT and remote control inputs, the input operation is prohibited.
which is activated later has priority and can start and
stop the operation.
- 38 -
• Operation output: Power to engage DC 12V relay (provided by the customer) is outputted during operation.
• Heating output: Power to engage DC 12V relay (provided by the customer) is outputted during the heating operation.
• Compressor OPERATION output: Power to engage DC 12V relay (provided by the customer) is outputted while the
compressor is operating.
• MALFUNCTION output: When any error occurs, the power to engage DC 12V relay (provided by the customer) is outputted.
(2) Control of input signal
Control of input signal (switch input, timer input) connectors (CNT) are provided on the printed circuit board of indoor unit.
However, when the operation of air conditioner is under the Center Mode, the remote control by CnT is invalid.
Unit *ON ON ON
(CASE B) OFF
OFF
ON ON
CnT Input OFF OFF OFF
ON
Unit
(CASE A) OFF OFF
ON ON
Unit
(CASE B) OFF
- 39 -
ON2
Model ON1
SCM40, 45ZJ-S, 50, 60, 71, 80ZJ-S1
Item OFF
Outdoor air temperature
Lower limit speed
40 41 46 47
Model Outdoor air temperature ( ºC )
SCM100, 125ZJ-S1
Item
Outdoor air temperature
Lower limit speed 25 31
8rps
(1)
After lapse of 30 sec. or over
(3)
lower limit
After lapse of 30 sec. or over
(3)
speed 30 rps
0rps
53 58 60
Outdoor heat exchanger temperature (°C)
60 8 20
60
- 40 -
Unit: MPa
HPS P2 P3 P4
NP
20 <
= NP < 30 2.94 – 3.45 3.07 – 3.85 3.15 – 4.05
30 <
= NP < 90 3.45 3.85 4.05
90 <
= NP < 100 3.45 – 3.25 3.85 – 3.60 4.05 – 3.81
100 <
= NP < 110 3.25 – 3.07 3.60 – 3.33 3.81 – 3.53
110 <
= NP 3.07 3.33 3.53
(a) Operating conditions: When the outdoor air temperature (Tho-A) is 22°C or lower continues for 20 seconds while
compressor command speed is other than 0 rps.
(b) Detail of operation:
① The lower limit of compressor command speed is set to B or D rps and even if the speed becomes lower than B or D
rps, the speed is kept to B or D rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
② The upper limit of compressor command speed is set to A or C rps, the speed is kept to A or C rps.
ON Upper limit C rps
Lower limit D rps
ON Upper limit A rps
Lower limit B rps
OFF
0 3 22 25
Outdoor air temperature.(°C)
Values of A ~ D
Model SCM40ZJ-S SCM45ZJ-S SCM50ZJ-S1 SCM60ZJ-S1 SCM71ZJ-S1 SCM80ZJ-S1
A 75 rps 75 rps
B 20 rps 20 rps
C 60 rps 60 rps
D 31 rps 31 rps
(c) Reset conditions: When the either of the following condition is satisfied
① When the outdoor air temperature (Tho-R) becomes 25°C or higher.
② When the compressor command speed is 0rps.
- 41 -
3) Release condition: When the indoor heat exchanger temperature (Th2) has become lower than the release tempera-
ture.
(b) Outdoor unit side
◆Model SCM40, 45, 50, 60, 71, 80
1) Start condition: W
hen the indoor heat exchanger temperature (Th2) has risen to a specified temperature while the
compressor is turned on.
2) Compressor command speed is controlled according to the zones of indoor heat exchanger tem-
perature as shown by the following table.
Th2 < P1 P1 <
= Th2 < P2 P2 <
= Th2 < P3 P3 <
= Th2
Protection control speed (NP) Normal Retention NP-4rps NP-8rps
Sampling time (s) Normal 20 20 20
Unit: MPa
HPS P1 P2 P3 P4
NP
20 <
= NP < 30 2.81 – 2.94 2.94 – 3.45 3.07 – 3.85 3.15 – 4.05
30 <
= NP < 90 2.94 3.45 3.85 4.05
90 <
= NP < 100 2.94 – 2.88 3.45 – 3.25 3.85 – 3.60 4.05 – 3.81
100 <
= NP < 110 2.88 – 2.81 3.25 – 3.07 3.60 – 3.33 3.81 – 3.53
110 <
= NP 2.81 3.07 3.33 3.53
- 42 -
2) Detail of operation
A or C
B or D
B or D when the thermo becomes OFF, the speed is
B or D.
3) Reset conditions: Tho-A 8 (model 60, 71, 80, 100, 125:11 ).
Upper C Unit: rps
Lower D
Upper A Model
Item A B C D
Lower B
SCM40, 45 90 35 75 40
OFF
SCM50 90 35 75 40
SCM60, 71, 80 90 30 75 40
11(8) 13(10) 16 17
Outdoor air temperature(°C) SCM100, 125 90 25 75 31
Note(1) Values in ( ) are for the model SCM40, 45.
(b) Detail of operation:
Normal operation
-8 -6 4 6
Outdoor air temperature(°C)
- 43 -
Compressor Indoor air temperature Indoor air temperature (Th1) and indoor
Unit Duration
command speed (Th1, ℃ ) heat exchanger temperature (Th2)
1 40 (60) rps
Th1 - 4 < Th2
2 50 (70) rps
3 60 (80) rps Th1 - 3 < Th2
10 <= Th1 <
= 40 5 minute
4 70 rps
5 80 rps Th1 - 2 < Th2
6 90 rps
Note (1) Values in ( ) are for the model SCM40, 45, 50.
95 105 115
Discharge pipe temperature (˚C)
105̅115
95̅105 3 minutes
95̅105 3 minutes
- 44 -
2) 115
(c) Current safe control value: Set this using the jumper wire (J1 or J2) on the outdoor PCB. Control starts
when it exceeds the control value.
1) Switching with jumper wire
2) Control value
Unit: A
(Fig. C) The control value “A” and the reset value vary depending
on the compressor speed. Secandary
current Fig.C Fig.C Fig.C Fig.C
Control or reset valve (A)
24 side
22
Control valve A
20
18
16 Reset valve B
14
12
40 50 60 70 80 90 100 110 120 130
Compressor speed (frequency) (rps)
- 45 -
• Values of A, B
Model SCM40ZJ-S SCM45ZJ-S SCM50ZJ-S1 SCM60ZJ-S1 SCM71ZJ-S1 SCM80ZJ-S1 SCM100ZJ-S1 SCM125ZJ-S1
A 30 rps 30 rps 30 rps 20 rps 20 rps 20 rps 20 rps 20 rps
B 60 rps 60 rps 60 rps 60 rps 60 rps 60 rps 60 rps 60 rps
�Model SCM71, 80
Cooling Heating
More than 31 More than 46 More than 31 More than 66
Compressor speed (rps) Less than 31 66 or more Less than 31 85 or more
but 46 or less but 66 or less but 66 or less but 85 or less
Outdoor fan speed 3rd speed 4th speed 5th speed 6th speed 3rd speed 4th speed 5th speed 6th speed
(b) If the outdoor unit’s fan speed drops, the outdoor fan is run for 1 minute at that speed.
- 46 -
(19) Rotor lock (Model SCM40, 45, 50, 60, 71, 80 only)
Outdoor fan
Tho-R
Tho-R
Tho-R
Outdoor fan
- 47 -
Heating
(a) Operating conditions: Tho-A
Cooling
(a) Start condition: When the outdoor air temperature (Tho-A) has risen higher than 41°C for 30 seconds continuously while
the compressor is operating.
Under control
ON
Normal operation
OFF
40 41
Outdoor airUndertemperature(ºC)
control
ON
Normal operation
(b) Contents of control: The
OFFoutdoor unit fan tap is brought up by 3 steps (Higher limit is 6th tap.)
(c) Release condition: When the compressor is turned off or the outdoor heat exchanger temperature (Tho-R) has dropped
40 41
lower than 40°C.
Outdoor airUnder control
temperature(ºC)
Heating ON
Normal operation
(a) Start condition: When OFF
the outdoor air temperature (Tho-A) has risen higher than 13°C for 30 seconds continuously while
the compressor is operating. 10 13
Outdoor heat exchanger temperature(ºC)
Under control
ON
Normal operation
OFF
10 13
Outdoor heat exchanger temperature(ºC)
(b) Contents of control: The outdoor unit fan tap is brought down by 3 steps (Lower limit is 2nd tap.)
(c) Release condition: When the compressor is turned off or the outdoor heat exchanger temperature (Tho-R) has dropped
lower than 10°C.
- 48 -
(25) Control of the flowing noise of refrigerant during cooling operation (SCM100, 125 only)
In order to suppress the flowing noise of refrigerant when operating 1 unit of indoor unit, the compressor is operated at the
Max speed of 40 rps if the dip switch (J31) on the outdoor sub-PCB is set to open.
- 49 -
2 MAINTENANCE DATA
2.1 SRK, SRF and SRR series
(1) Cautions
(3) Troubleshooting procedure (If the air conditioner does not run at all)
Important
NO
YES
NO YES
NO
YES
NO
YES
- 50 -
NO YES
52.
NO
54 ~ 62.
YES
YES
NO
54 ~ 62.
YES
NO
- 51 -
6 times Stays When conditions for turning the indoor unit’s fan motor on exist during air
Indoor fan • Defective fan motor, poor
ON E 16 motor error connector connection
conditioner operation, an indoor unit fan motor speed of 300 (SRF : 150) rpm
flash OFF or lower is measured for 30 seconds or longer. (The air conditioner stops.)
Outdoor air • Broken outdoor air temp. –55ºC or lower is detected for 5 seconds continuously 3 times within
Keeps 1 time 8 times temperature sensor wire, poor connector 40 minutes after initial detection of this anomalous temperature.
E 38 connection Or –55ºC or higher is detected for within 20 seconds after power ON.
flashing flash flash sensor error
• Outdoor main PCB is faulty (The compressor is stopped.)
• Broken heat exchanger sensor –55ºC or lower is detected for 5 seconds continuously 3 times within
Keeps 2 times 8 times Outdoor heat
wire, poor connector 40 minutes after initial detection of this anomalous temperature.
E 37 exchanger
connection Or –55ºC or higher is detected for within 20 seconds after power ON.
flashing flash flash sensor error • Outdoor main PCB is faulty (The compressor is stopped.)
• Broken discharge pipe sensor
Keeps 4 times 8 times Discharge pipe wire, poor connector –25ºC or lower is detected for 5 seconds continuously 3 times within 40
E 39 sensor error connection
minutes after initial detection of this anomalous temperature.
flashing flash flash (The compressor is stopped.)
• Outdoor main PCB is faulty
• Broken suction pipe sensor wire, –55ºC or lower is detected for 5 seconds continuously 3 times within 40
Keeps 5 times 8 times Outdoor suction
poor connector connection
minutes after initial detection of this anomalous temperature.
E 53 pipe sensor error Or –55ºC or higher is detected for within 20 seconds after power ON.
flashing flash flash • Outdoor sub PCB is faulty (The compressor is stopped)
• Compressor locking, open phase The compressor output current exceeds the set value during compressor
1 time 1 time on compressor output, short
ON E 42 Current cut
circuit on power transistor,
start.
flash flash (The air conditioner stops.)
service valve is closed
2 times 2 times When there is an emergency stop caused by trouble in the outdoor unit,
Trouble of • Broken compressor wire
ON E 59 outdoor unit • Compressor blockage or the input current value is found to be lower than the set value.
flash flash (The air conditioner stops.)
3 times 3 times Current safe • Overload operation When the compressor command speed is lower than the set value and
ON E 58 stop • Overcharge the current safe has operated. (the compressor stops)
flash flash • Compressor locking
4 times 1 time Power When the power transistor is judged breakdown while compressor
ON E 51 transistor • Broken power transistor starts.
flash flash error (The compressor is stopped.)
5 times 5 times Over heat of • Gas shortage, defective When the value of the discharge pipe sensor exceeds the set value.
ON E 36 compressor discharge pipe sensor, service (The air conditioner stops.)
flash flash valve is closed
When there is no signal between the indoor PCB and outdoor PCB for
6 times 6 times • Defective power supply, 10 seconds or longer (when the power is turned on), or when there is no
ON E5 Error of signal Broken signal wire, defective
flash flash transmission signal for 7 minute 35 seconds or longer (during operation)(the
indoor/outdoor sub PCB compressor is stopped).
7 times Keeps Outdoor fan • Defective fan motor, poor When the outdoor unit’s fan motor speed continues for 30 seconds or
ON E 48 motor error connector connection longer at 75 rpm or lower. (3 times) (The air conditioner stops.)
flash flashing
2 times 2 times 7 times • Defective compressor If the compressor motor’s magnetic pole positions cannot be correctly
E 60 Rotor lock • Open phase on compressor detected when the compressor starts.
flash flash flash • Defective outdoor PCB (The air conditioner stops.)
5 times 2 times Active filter • Defective active filter When the wrong voltage connected for the power supply.
ON E 47 voltage error When the outdoor main PCB is faulty
.
flash flash
Refrigeration
7 times 2 times cycle system • Service valve is closed.
ON E 57 • Refrigerant is insufficient When refrigeration cycle system protective control operates.
flash flash protective
control
4 times Outdoor sub PCB • Outdoor sub PCB fauly Communication error for 15 minutes: Detected more than 15 seconds
— — E 45 communication • Poor connection of wire between
flash error outdoor sub PCB – main PCB 4 times
The wired remote controller wire Y is open. The wired remote
Stays Error of wired • Broken wired remote controller controller wires X and Y are reversely connected. Noise is penetrating
— — E1 remote controller wire, defective indoor PCB the wired remote controller lines. The wired remote controller or indoor
OFF wiring PCB is faulty. (The communications circuit is faulty.)
- 52 -
(ii) SCM100,125
Indoor unit display panel Outdoor Wired
(2)
remote Description
main PCB controller Cause Display (flashing) condition
RUN TIMER Red LED of trouble
light light display
• Broken heat exchanger sensor When a heat exchanger sensor 1 wire disconnection is detected while
1 time Stays — Heat exchanger 1 wire, poor connector operation is stopped. (If a temperature of –28ºC or lower is detected for
ON connection 15 seconds, it is judged that the wire is disconnected.)
flash OFF sensor 1 error
• Indoor PCB is faulty (Not displayed during operation.)
• Broken room temperature When a room temperature sensor wire disconnection is detected while
2 times Stays Room sensor wire, poor connector operation is stopped. (If a temperature of –45ºC or lower is detected for
ON — temperature connection 15 seconds, it is judged that the wire is disconnected.)
flash OFF sensor error • Indoor PCB is faulty (Not displayed during operation.)
• Broken heat exchanger sensor When a heat exchanger sensor 2 wire disconnection is detected while
3 times Stays Heat exchanger 2 wire, poor connector operation is stopped. (If a temperature of –28ºC or lower is detected for
ON — connection 15 seconds, it is judged that the wire is disconnected.)
flash OFF sensor 2 error
• Indoor PCB is faulty (Not displayed during operation.)
• Defective drain pump (DM),
4 times Stays Drain(3) broken drain pump wire If the float switch OPEN is defected for 3 seconds continuously or if
ON E9 •Anomalousfloat s witchoperation float switch connector or wire is disconnected.
flash OFF trouble
• Defective indoor PCB faulty
6 times Stays When conditions for turning the indoor unit’s fan motor on exist during air
Indoor fan • Defective fan motor, poor
ON E 16 connector connection
conditioner operation, an indoor unit fan motor speed of 300 (SRF : 150) rpm
flash OFF motor error or lower is measured for30 seconds or longer. (The air conditioner stops.)
Outdoor air • Broken outdoor air temp. –55ºC or lower is detected for 5 seconds continuously 3 times within
Keeps 1 time 8 times sensor wire, poor connector 40 minutes after initial detection of this anomalous temperature.
E 38 temperature connection Or –55ºC or higher is detected for within 20 seconds after power ON.
flashing flash flash sensor error • Outdoor main PCB is faulty (The compressor is stopped.)
• Broken heat exchanger sensor –55ºC or lower is detected for 5 seconds continuously 3 times within
Keeps 2 times 8 times Outdoor heat
wire, poor connector 40 minutes after initial detection of this anomalous temperature.
E 37 exchanger connection Or –55ºC or higher is detected for within 20 seconds after power ON.
flashing flash flash sensor error • Outdoor main PCB is faulty (The compressor is stopped.)
• Broken discharge pipe sensor –25ºC or lower is detected for 5 seconds continuously 3 times within 40
Keeps 4 times 8 times Discharge pipe wire, poor connector
E 39 connection
minutes after initial detection of this anomalous temperature.
flashing flash flash sensor error (The compressor is stopped.)
• Outdoor main PCB is faulty
• Broken suction pipe sensor wire, –55ºC or lower is detected for 5 seconds continuously 3 times within 40
Keeps 5 times 8 times Outdoor suction poor connector connection minutes after initial detection of this anomalous temperature.
E 53 pipe sensor error • Outdoor sub PCB is faulty Or –55ºC or higher is detected for within 20 seconds after power ON.
flashing flash flash
(The compressor is stopped)
• Compressor locking, open phase The compressor output current exceeds the set value during compressor
1 time 1 time on compressor output, short
ON E 42 Current cut
circuit on power transistor,
start.
flash flash (The air conditioner stops.)
service valve is closed
2 times 2 times When there is an emergency stop caused by trouble in the outdoor unit,
Trouble of • Broken compressor wire
ON E 59 outdoor unit • Compressor blockage or the input current value is found to be lower than the set value.
flash flash (The air conditioner stops.)
4 times 1 time Inverter and • Outdoor inverter PCB is faulty When power transistor anomaly is detected for 15 minutes continuosly
ON E 51 fan motor • Outdoor controol PCB is faulty (The compressor is stopped.)
flash flash anomaly • Outdoor fan motor is faulty
5 times 5 times Over heat of • Gas shortage, defective When the value of the discharge pipe sensor exceeds the set value.
ON E 36 compressor
discharge pipe sensor, service (The air conditioner stops.)
flash flash valve is closed
When there is no signal between the indoor PCB and outdoor PCB for
6 times 6 times • Defective power supply, 10 seconds or longer (when the power is turned on), or when there is no
ON E5 Error of signal Broken signal wire, defective
flash flash transmission signal for 7 minute 35 seconds or longer (during operation)(the
indoor/outdoor sub PCB compressor is stopped).
7 times Keeps Outdoor fan • Defective fan motor, poor When the outdoor unit’s fan motor speed continues for 30 seconds or
ON E 48 longer at 75 rpm or lower. (3 times) (The air conditioner stops.)
flash flashing motor error connector connection
Cooling high • Overload operation, overcharge When anomalous rise of the high pressure sensor is detected 5 times
Keeps 2 times • Broken high pressure sensor within 1 hour.
ON E 35 pressure wire When high pressure sensor anomaly is detected for 10 minutes
flashing flash protection • Service valve is closed continuously.
Refrigeration
7 times 2 times cycle system • Service valve is closed.
When refrigeration cycle system protective control operates.
ON E 57 protective • Refrigerant is insufficient
flash flash
control
1 time Power transistor When anomalous rise of the power transistor temperature is detected
— — E 41 error
• Power transistor overheat 2 times within 1 hour.
flash
Heating high • Overload operation, overcharge When anomalous rise of the high pressure sensor is detected 5 times
2 times pressure • Broken high pressure sensor within 1 hour.
— — E 40 wire When high pressure sensor anomaly is detected for 10 minutes
flash protection • Service valve is closed continuously.
4 times Outdoor sub PCB • Outdoor sub PCB fauly Communication error for 15 minutes: Detected more than 15 seconds
— — E 45 communication • Poor connection of wire between 4 times.
flash error outdoor sub PCB – main PCB
8 times High pressure • Broken high pressure sensor If the detected for 5 second continuously within 2 minutes to 2 minutes
— — E 54 sensor error wire and 20 seconds after the compressor ON, the compressor stops.
flash
The wired remote controller wire Y is open. The wired remote
Stays Error of wired • Broken wired remote controller controller wires X and Y are reversely connected. Noise is penetrating
— — E1 remote controller wire, defective indoor PCB the wired remote controller lines. The wired remote controller or indoor
OFF wiring PCB is faulty. (The communications circuit is faulty.)
Notes (1) The air conditioner cannot be restarted using the remote controller for 3 minutes after operation stops.
(2) The wired remote controller is optional parts.
(3) SRR series only.
- 53 -
Term Explanation
The service mode is the mode where service data are displayed by flashing of the display lights
Service mode
when the operations in item (b) below are performed with the indoor controller.
These are the contents of error displays and protective stops which occurred in the past in the air
conditioner system. Error display contents and protective stop data from past anomalous
Service data operations of the air conditioner system are saved in the indoor unit controller’s non-volatile
memory (memory which is not erased when the power goes off). There are two types of data,
self-diagnosis data and stop data, described below.
These are the data which display the reason why a stop occurred when an error display(self-
diagnosis display) occurred in an indoor unit. Data are recorded for up to 5 previous occurrences.
Data which are older than the 5th previous occurrence are erased.
Self-diagnosis data In addition, data on the temperature of each sensor (room temperature, indoor heat exchanger,
outdoor heat exchanger, outdoor air temperature, discharge pipe), remote controller information
(operation switching, fan speed switching) are recorded when trouble occurs, so more detailed
information can be checked.
These are the data which display the reason by a stop occurred when the air conditioning system
performed protective stops, etc. in the past. Even if stop data alone are generated, the system
restarts automatically. (After executing the stop mode while the display is normal, the system
restarts automatically.) Data for up to 10 previous occasions are stored. Data older than the 10th
Stop data
previous occasion are erased.
( Important) In cases where transient stop data only are generated, the air conditioner system
may still be normal. However, if the same protective stop occurs frequently (3 or
more times), it could lead to customer complaints.
57.)
.)
- 54 -
1) Self-diagnosis data
- 55 -
(Example)
2) Stop data
Remote controller setting
Operation Fan speed Temperature Displayed data
switching switching setting
21ºC Displays the reason for the stop (stop code) the previous time when the air conditioner was stopped by protective stop control.
22ºC Displays the reason for the stop (stop code) 2 times previous when the air conditioner was stopped by protective stop control.
23ºC Displays the reason for the stop (stop code) 3 times previous when the air conditioner was stopped by protective stop control.
24ºC Displays the reason for the stop (stop code) 4 times previous when the air conditioner was stopped by protective stop control.
25ºC Displays the reason for the stop (stop code) 5 times previous when the air conditioner was stopped by protective stop control.
Cooling LO
26ºC Displays the reason for the stop (stop code) 6 times previous when the air conditioner was stopped by protective stop control.
27ºC Displays the reason for the stop (stop code) 7 times previous when the air conditioner was stopped by protective stop control.
28ºC Displays the reason for the stop (stop code) 8 times previous when the air conditioner was stopped by protective stop control.
29ºC Displays the reason for the stop (stop code) 9 times previous when the air conditioner was stopped by protective stop control.
30ºC Displays the reason for the stop (stop code) 10 times previous when the air conditioner was stopped by protective stop control.
- 56 -
OFF Can not receive signals for 35 Power supply is faulty. When 35 seconds passes without
5 times
05 seconds Power supply cables and signal lines are improperly wired. communications signals from either the outdoor unit or
flash
(if communications have recovered) Indoor or outdoor sub PCB are faulty . the indoor unit being detected correctly.
Cooling overload operation. When the outdoor heat exchanger sensor's value exceeds
5 times
35 Cooling high pressure control Outdoor unit fan speed drops.
flash the set value. (5 times)
Outdoor heat exchanger sensor is short circuit.
6 times Refrigerant is insufficient. When the discharge pipe sensor's value exceeds the set
36 Compressor overheat 115°C Discharge pipe sensor is faulty.
flash value. (2 times)
Service valve is closed.
8 times Outdoor unit's fan motor is Outdoor fan motor is faulty. When a fan speed of 75 rpm or lower continues for 30
48 Connector connections are poor.
flash abnormal seconds or longer. (3 times)
Outdoor main PCB is faulty.
Short circuit in the power
1 time Outdoor main PCB is faulty
. When it is judged that the power transistor was
51 transistor (high side)
flash Power transistor is damaged. damaged at the time the compressor started.
Current cut circuit breakdown
–55°C or lower is detected for 5 seconds continuously 3 times
Suction pipe sensor wire is
within 40 minutes after intial detection of this anomalous
3 times Suction pipe sensor disconnected.
53 temperature.
flash is abnormal Connector connections are poor. (3 times)
Outdoor sub PCB is faulty. Or–55°C higher is detected for 5 seconds continuously
within 20 seconds after compressor ON.
5 times 7 times Service valve is closed. When refrigeration cycle system protective control
57 Refrigeration cycle system
flash flash protective control Refrigerant is insufficient. operates. (3 times)
Indoor or outdoor sub PCB are faulty. When 7 minute 35 seconds passes without
2 times
62 Serial transmission error communications signals from either the outdoor unit or
flash Noise is causing faulty operation.
the indoor unit being detected correctly.
Indoor fan motor is faulty. When the indoor unit's fan motor is detected to be running
Indoor unit's fan motor is
OFF 80 Connector connections are poor. at 300 (SRF : 150) rpm or lower speed with the fan motor
abnormal
Indoor PCB is faulty. in the ON condition while the air conditioner is running.
Indoor heat exchanger sensor Indoor heat exchanger sensor wire is When a temperature of –28°C or lower is sensed
2 times
82 disconnected. continuously for 40 minutes during heating operation.
flash is abnormal (anomalous stop)
Connector connections are poor (the compressor stops).
.
8 times 4 times High humidity condition.
flash 84 Anti-condensation control Anti-condensation prevention control is operating.
flash Humidity sensor is faulty.
5 times Indoor unit fan speed drops. When the anti-frost control operates and the compressor
85 Anti-frost control
flash Indoor heat exchanger sensor is broken wire. stops during cooling operation.
Heating overload operation. When high pressure control operates during heating
6 times
86 Heating high pressure control Indoor unit fan speed drops.
flash operation and the compressor stops.
Indoor heat exchanger sensor is short circuit.
- 57 -
(ii) SCM100,125
Number of flashes when in
service mode Stop coad
Error Auto
RUN TIMER or Error content Cause Occurrence conditions display recovery
light light Error coad
(10's digit) (1's digit)
OFF 0 Normal
OFF Can not receive signals for 35 Power supply is faulty. When 35 seconds passes without
5 times seconds Power supply cables and signal lines are improperly wired. communications signals from either the outdoor unit or
05
flash (if communications have recovered) Indoor or outdoor PCB are faulty. the indoor unit being detected correctly.
6 times Refrigerant is insufficient. When the discharge pipe sensor's value exceeds the set
36 Compressor overheat 115°C Discharge pipe sensor is faulty.
flash value. (2 times)
Service valve is closed.
1 time Power transistor overheat. When anomalous rise of the power transistor temperature
41 Power transistor error
flash Power transistor sensor is short circuit. is detected 2 times within 1 hour. (2 times)
Compressor lock.
Compressor wiring short circuit.
4 times Compressor output is open phase.
flash 2 times Compressor start fails 42 times in succession and the
42 Current cut Outdoor inverter PCB is faulty.
flash reason for the final failure is current cut. (2 times)
Service valve is closed.
Electronic expansion valve is faulty.
Compressor is faulty.
Outdoor sub PCB fauly.
5 times Anomalous outdoor sub Communication error for 15 minutes: Detected more than
45 Poor connection of wire between
flash PCB commuication 15 seconds 4 times.
outdoor sub PCB-control PCB.
Outdoor fan motor is faulty.
8 times Outdoor unit's fan motor is When a fan speed of 75 rpm or lower continues for 30
48 Connector connections are poor.
flash abnormal seconds or longer. (3 times)
Outdoor control PCB is faulty.
Outdoor inverter PCB is faulty.
1 time When power transistor anomaly is detected for 15 minutes
51 Inverter and fan motor anomaly Outdoor control PCB is faulty.
flash continuosly.
Outdoor fan motor is faulty.
Suction pipe sensor wire is –55°C or lower is detected for 5 seconds continuously 3 times
disconnected. within 40 minutes after intial detection of this anomalous
3 times Suction pipe sensor
53 temperature.
flash is abnormal Connector connections are poor. (3 times)
Outdoor control PCB is faulty. Or–55°C higher is detected for 5 seconds continuously
within 20 seconds after compressor ON.
7 times Refrigeration cycle system Service valve is closed. When refrigeration cycle system protective control
flash 57 protective control Refrigerant is insufficient. operates. (3 times)
- 58 -
Indoor heat exchanger sensor Indoor heat exchanger sensor wire is When a temperature of –28°C or lower is sensed
2 times
82 disconnected. continuously for 40 minutes during heating operation.
flash is abnormal (anomalous stop)
Connector connections are poor. (the compressor stops).
8 times 4 times High humidity condition.
flash 84 Anti-condensation control Anti-condensation prevention control is operating.
flash Humidity sensor is faulty.
5 times Indoor unit fan speed drops. When the anti-frost control operates and the compressor
85 Anti-frost control
flash Indoor heat exchanger sensor is broken wire. stops during cooling operation.
Heating overload operation. When high pressure control operates during heating
6 times
86 Heating high pressure control Indoor unit fan speed drops.
flash operation and the compressor stops.
Indoor heat exchanger sensor is short circuit.
- 59 -
&
'
&'
& &
'
&'
&#""'%)
([DPSOH2SHUDWLRQVZLWFKLQJIDQVSHHGVZLWFKLQJFRROLQJ+,
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 60 -
(e) Room temperature sensor, indoor heat exchanger sensor, outdoor air temperature sensor, outdoor heat
exchanger sensor , suction pipe sensor table
Units: °C
TIMER light
(1’s digit)
RUN light
(10’s digit) 0 1 2 3 4 5 6 7 8 9
Buzzer sound
Sensor name Sensor value displayed when the error code is normal
Room temperature sensor -64ºC
Indoor heat exchanger sensor -64ºC
Outdoor air temperature sensor -64ºC
Outdoor heat exchanger sensor -64ºC
Outdoor suction pipe sensor -64ºC
, outdoor
suction pipe
0.1 sec.
ON If the temperature is < 0, the buzzer sounds.
Buzzer sound If the temperature is≧0, the buzzer does not sound.
OFF
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 61 -
Buzzer sound
Sensor value displayed when the error code is normal
-64ºC
([DPSOH'LVFKDUJHSLSHWHPSHUDWXUH³&´
,QWKHFDVHRIGLVFKDUJHSLSHGDWDPXOWLSO\WKHUHDGLQJYDOXHE\%HORZ[ ³&´
0.1 sec.
ON If the temperature is < 0, the buzzer sounds.
Buzzer sound If the temperature is≧0, the buzzer does not sound.
OFF
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 62 -
55)
- 63 -
180 30
160
25
140
Resistance (k )
Resistance (k )
120 20
100
15
80
60 10
40
5
20
0 -10 0 10 20 30 40 50 60 70
0 20 40 60 80 100 120 135
Temperature (˚C) Temperature (˚C)
- 64 -
Limit switch anomaly (SRK20, 25, 35, 50, 60ZJX only) Defective limit switch, defective indoor
control PCB, Defective air inlet panel set
Note(1) Check if the limit switch functions properly or not by seeing whether
the lamp continues to blink or can be reset by pressing the limit swit-
Defective indoor control PCB -ch by hand while the air inlet panel is removed.
Current cut Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
76
sub
main *
*
main 70
main
- 65 -
64)
main
Error of signal transmission Wiring error including power cable, defective indoor/
outdoor PCB
̅
②̅③ indoor
̅
②̅③
indoor
①̅②
outdoor sub
- 66 -
Trouble of outdoor unit Insufficient refregerant amount, Faulty power transistor, Broken compressor wire
Service valve close, Defective EEV, Defective outdoor PCB
(1)
sub
(2)
◆
main (1)
(3)
Notes (1) 76
(2) 70
main
(3) Check coil resistance, See pages 65.
See pages 76 for the fan motor and outdoor main PCB check
outdoor main pro
After making sure the fan motor and outdoor main PCB are
nor
- 67 -
Rotor lock (SCM40, 45, 50, 60, 71, 80 only) Defective compressor, defective
outdoor PCB
main
NO NO Indoor PCB is
Has an overflow developed? Is the float switch operating?
defective.
YES
YES
NO
Is there output for drain motor driver? Repair and clean.
YES
Drain motor is defective. Indoor PCB is defective.
Inspect wiring.
- 68 -
NO
Is the fuse burnt out? (3.15 A) Replace fuse.
YES
YES
① ④ ⑤
DC several V (–)
(4 – 6 V) GND DC 280V
Measuring Resistance when
DC15V point normal
①−③
CNU Indoor PCB
⑥ ⑤ ④ ③ ② ① ④−③
⑤−③ ̅
⑥−③ ̅
⑥ ⑤ ④ ③ ② ①
Yellow
White
Black
Blue
Red
FMI
- 69 -
(Example)
RUN light : ON
Output voltage TIMER light: 2 time flash
(ACV)
0
8~10 sec. 1 sec. 3 min. 1 sec. 3 min. 1 sec.
- 70 -
Models SCM40ZJ-S,45ZJ-S
BK Black Power supply
RD Red 1 Phase
WH White 220-240V 50Hz
OR Orange FUSE
BR Brown RO BK
TB1 250V 15A R
YE Yellow BK BK SO WH
L RIN S YE
Y/G Yellow/Green WH WH SIN WH T1
N S-1 S-2 OR R
Y/G RD T2
Y/G G1 C-1 C-2
5
Y/G G CNMAIN CNSUB
2
CN20V CN20V U RD
V WH M
TB2
1 BK
3~
W BK
WH CM
2 CNA
UNIT A RD
3 PWB 2(SUB) PWB 1(MAIN)
TB3
-
BK
1
71 -
WH
2 CNB
UNIT B BR CNFAN M
3
FM0
t゜
t゜
t゜
20S M M
HEATER See page 76.
EEV EEV Tho-S Tho-R Tho-A Tho-D
A B
'11 • SCM-SM-110
◆Inspection of electronic ◆Inspection of resistance value of sensor
expansion valve Remove the connector and check the resistance value.
See page 76. See the section of sensor characteristics on page 64.
Models SCM50ZJ-S1,60ZJ-S1
BK Black Power supply
BL Blue 1 Phase
RD Red
220-240V 50Hz
WH White FUSE
OR Orange 250V 15A㧛
RO BK
BR Brown TB1 250V 20A R
BK BK RIN SO WH
YE Yellow L S YE
WH WH SIN WH T1
Y㧛G Yellow㧛Green S-1 S-2 OR R
N
Y㧛G RD T2
Y㧛G G1 C-1 C-2
5
Y㧛G G CNMAIN CNSUB
TB2 2 U
CN20V CN20V RD
BK
1
WH V WH M
2 CNA 3㨪
UNIT A RD W BK
3
BK CM
PWB 2㧔SUB㧕 PWB 1㧔MAIN㧕
1
-
WH
2 CNB
72 -
UNIT B BR
3
CNFAN M
1 BK FMo
WH
2 CNC
UNIT C BL
3
tࠑ
tࠑ
tࠑ
'11 • SCM-SM-110
and approx. 20V
Models SCM71ZJ-S1,80ZJ-S1
1 Phase output voltage
BK Black 220-240V 50Hz
BL Blue
BR Brown FUSE
RD Red TB1 250V 20A
WH White BK BK RIN
L BK
OR Orange WH WH SIN RO R
BR Brown
N WH
Y/G SO S YE
YE Yellow Y/G G1 WH T1
S-1 S-2 R
Y/G Yellow/Green
TB2 BK Y/G G RD T2
OR
C-1 C-2
1 5
WH CNA CNMAIN CNSUB
2
UNIT A
3 RD CN20V
2
CN20V U RD
Y/G
V WH M
TB3 BK 3~
1 W BK
WH CNB CM
2
UNIT B BR PWB 2(SUB)
3 PWB 1(MAIN)
Y/G
-
73 -
TB4 BK
1
WH CNC
2
UNIT C
3
BL CNFAN M
Y/G
FMo
TB5 BK
1
WH CND
2
UNIT D YE
3
Y/G
CNHEAT CN20S G2 CNEEV1 CNEEV2 CNTH CNTH
Y/G Y/G
2 2 2 2
WH RD WH RD BL GN
◆Inspection of outdoor
◆Power source and serial fan motor
t゜
t゜
t゜
t゜
20S M M M M
signal inspection HEATER See page 76.
① to ②: AC 220/230/240V EEV EEV EEV EEV Tho-S Tho-R Tho-A Tho-D
'11 • SCM-SM-110
② to ③ : Normal if the voltage A B C D
oscillates between DC 0
and approx. 20V
Model SCM100ZJ-S1
electrical parts in the control box for 5 minutes after the
unit is stopped.
Color Marks
Mark Color POWER SOURCE
BK Black ~ 220/230/240V
Circuit breaker
BL Blue 50Hz
BR Brown Earth leakage breaker L
GN Green
3 TB1 F1
OR Orange L RD
30A 250V
RD TB3 TB5
RD
TB3 TB5
RD
2 +1
RD P1 1 2 P2 RD +
L1 L2
4
CNACT1
CNACT
PK Pink WH
PWB5 PWB3 ~
AC DS (BK) (WH)
N NOISE WH NOISE WH BL N1 N2 BL RD RD
RD Red TB4
FILTER TB6 TB4
FILTER TB6 3
~
-4 4 3
- P P3
Y/G +
WH White CT1 A/F
TB7 TB8 TB7 MODULE
YE Yellow BLC1 BL
Y/G
Y/G
Y/G
N2 N3
Y/G Yellow/Green
PWB2
INV PWB
WH
WH
RD
RD
TB2
RD
BL
1
BK L-IN N-IN CNW
2
WH CNA (BK)
UNIT A 3
RD (WH)
CNA1
-
2
BK CNTRI WH LED1 (WH) F2
1 (WH) 4A
74 -
WH CNB
UNIT B
2
BR (WH) RD
2 TR 250V
3 CNTRO
CNA2
(WH)
BK (GN)
1 LED2 LED3
WH CNC
2 BK
UNIT C 3
BL (WH) CNS2 CNS1 4
PWB4 (BK)
WH
(BK) PWB1 CNI1 BL CNI2
(WH)
TB3 SUB PWB CONTROL PWB
1
BK BK
WH CND CNX2 3
2 (YE) WH CNX1 CNI3 BL
UNIT D 3
YE (WH) (YE) CHECKER PC (WH)
CNI4
BK Y/G
1 G
2
WH CNE CNE CNV
UNIT E 3
OR (WH)
IPM
30A 600V
CNEEV1 CNEEV2 CNEEV3 CNEEV1 CNL1 CNFAN1 CNR1 CNN1
(WH) (WH) (WH) CNTH CNP1 (RD) (BL) (WH) (WH) (RD) W V U
WH
BK
BK
BK
BK
RD
YE
BR
BL
BL
5 5 5 5 5 2 2 2 2 2 5 3 5 2 2
WH RD BL GN BK
t°
t°
t°
t°
t°
5 5 5 5 5
V
◆Power source and serial
Tho-AF
HPS CH 20S W U
Tho-D
Tho-A
Tho-R
Tho-S
M M M M M M M MS
signal inspection CM
3~
EEV EEV EEV EEV EEV EEV-H FM
① to ②: AC 220/230/240V A B C D E
② to ③ : Normal if the voltage
'11 • SCM-SM-110
oscillates between DC 0
and approx. 20V
◆Inspection of electronic ◆Inspection of resistance value of sensor ◆Inspection of outdoor ◆Inspection power transistor
expansion valve Remove the connector and check the fan motor Remove the fasten terminal and test
See page 76. resistance value. See page 76. output voltage
See the section of sensor characteristics
on page 64.
Color Marks
Model SCM125ZJ-S1
Mark Color
BK Black POWER SOURCE
BL Blue ~ 220/230/240V
Circuit breaker
BR Brown 50Hz
GN Green Earth leakage breaker L
OR Orange
3 TB1 F1
PK Pink RD
30A 250V
RD RD RD RD P1 1 2 P2 RD L1 L2
4
L TB3 TB5 TB3 TB5 2 +1 + CNACT1
RD Red PWB5 PWB3 ~
AC DS
CNACT
(BK) (WH)
WH
WH White N NOISE WH TB4 NOISE WH BL N1 4 3 N2 BL RD RD
TB4 TB6 TB6 3 -4 - P P3
Y/G FILTER FILTER ~ +
YE Yellow CT1 A/F
TB7 TB8 TB7 MODULE
Y/G Yellow/Green BL C1 BL
Y/G
Y/G
Y/G
N2 N3
PWB2
INV PWB
WH
WH
RD
RD
TB2
RD
BL
BK L-IN N-IN CNW
-
1
2
WH CNA (BK)
UNIT A 3
RD (WH)
CNA1
75 -
2
BK CNTRI WH
LED1 (WH) F2
1
WH CNB (WH) 4A
UNIT B 2
BR (WH) RD
2 TR 250V
3 CNTRO
CNA2
(WH)
BK (GN)
1 LED2 LED3
WH CNC BK
2
UNIT C 3
BL (WH) CNS2 WH CNS1 4
PWB4 (BK) (BK) PWB1 CNI1 BL CNI2
(WH)
TB3 SUB PWB CONTROL PWB
1
BK BK
WH CND CNX2 CNX1 3
2 WH CNI3 BL
UNIT D 3
YE (WH) (YE) (YE) CHECKER PC (WH)
CNI4
BK Y/G
1 G
2
WH CNE CNE CNV
UNIT E 3
OR (WH)
BK
IPM
1 CNF
2
WH
(WH) CN CN CN CN 30A 600V
UNIT F 3
PK EEV1 EEV2 EEV3 EEV4 CNEEV1 CNL1 CNFAN1 CNR1 CNN1
(WH) (WH) (WH) (WH) CNTH CNP1 (RD) (BL) (WH) (WH) (RD) W V U
WH
BK
BK
BK
BK
RD
YE
BR
BL
BL
5 5 5 5 5 5 2 2 2 2 2 5 3 5 2 2
WH RD BL GN BK YE
t°
t°
t°
t°
t°
5 5 5 5 5 5
V
Tho-AF
U
◆Power source and serial HPS CH 20S W
Tho-D
Tho-A
Tho-R
Tho-S
M M M M M M M M MS
3~
signal inspection EEV A EEV B EEV C EEV D EEV E EEV F EEV-H FM CM
① to ②: AC 220/230/240V
'11 • SCM-SM-110
② to ③ : Normal if the voltage
oscillates between DC 0
and approx. 20V
◆Inspection of electronic ◆Inspection of resistance value of sensor ◆Inspection of outdoor ◆Inspection power transistor
expansion valve Remove the connector and check the fan motor Remove the fasten terminal and test
See page 76. resistance value. See page 76. output voltage
See the section of sensor characteristics
on page 64.
6 5 4 3 2 1
White
Yellow
Orange
Blue
Red
sub
main
outdoor
② (SCM100,125: ⑥)
main
main
FM0 FM0
Orange
Brown
Brown
White
White
Red
Red
Orange
Blue
Blue
⑥ ⑤ ④ ③ ② ① ⑨ ⑧ ⑦ ⑥ ⑤ ④ ③ ② ①
⑥ ⑤ ④ ③ ② ① ⑨ ⑧ ⑦ ⑥ ⑤ ④ ③ ② ①
CNFAN Outdoor main PCB CNFAN Outdoor main PCB
- 76 -
Keeps
Stays OFF Stays OFF — • Normal operation — —
flashing
No-indication Stays OFF Stays OFF Stays OFF Stays OFF Indoor unit power supply • Power OFF, broken wire/blown fuse, broken transformer wire Repair 98
* Remote controller wires • Poor connection, breakage of remote controller wire * For wire breaking at power ON, the LED is OFF. Repair
Keeps
3 times Stays OFF Replacement of 99
flashing Remote controller • Defective remote controller PCB
flash remote controller
Indoor-outdoor units connection
WAIT or Keeps • Poor connection, breakage of indoor-outdoor units connection wire
Stays OFF Stays OFF wire Repair 100~104
INSPECT I/U flashing
Remote controller • Improper setting of master and slave by remote controller
• Poor connection of remote controller signal wire (White)
* Remote controller wires (Noise) * For wire breaking at power ON, the LED is OFF Repair
Keeps • Intrusion of noise in remote controller wire
Stays OFF Stays OFF 105
flashing Replacement of
Remote controller indoor con-
trol PCB *• Defective remote controller or indoor control PCB (defective communication circuit)? remote controller
or PCB
• Poor connection of wire between indoor-outdoor units during operation
2 times Keeps 6 times Indoor-outdoor units connection
(disconnection, loose connection) Repair
flash flashing flash wire
• Anomalous communication between indoor-outdoor units by noise, etc.
Power reset or
(Noise) • CPU-runaway on outdoor control PCB
2 times Keeps 6 times Repair
flash flashing flash 106
Outdoor control PCB *• Occurrence of defective outdoor control PCB on the way of power supply (defective communication Replacement of
circuit)? PCB
2 times Keeps 6 times Outdoor control PCB • Defective outdoor control PCB on the way of power supply
Replacement
flash flashing flash
Fuse • Blown fuse
• Defective indoor heat exchanger temperature thermistor (defective element, broken wire, Replacement,
Indoor heat exchanger tempera-
short-circuit) repair of temper-
1 time Keeps ture thermistor
Stays OFF • Poor contact of temperature thermistor connector ature thermistor 107
flash flashing
Replacement of
Indoor control PCB *• Defective indoor control PCB (Defective temperature thermistor input circuit)? PCB
•D efective indoor return air temperature thermistor (defective element, broken wire, short- Replacement,
Indoor return air temperature
circuit) repair of temper-
1 time Keeps thermistor
Stays OFF • Poor contact of temperature thermistor connector ature thermistor 108
flash flashing
Replacement of
Indoor control PCB *• Defective indoor control PCB (Defective temperature thermistor input circuit)? PCB
Keeps
flashing Installation or operating condi-
• Heating over-load (Anomalously high indoor heat exchanger temperature) Repair
tion
Replacement
1 time Keeps Indoor heat exchanger tempera-
Stays OFF • Defective indoor heat exchanger temperature thermistor (short-circuit) of temperature 109
flash flashing ture thermistor
thermistor
Replacement of
Indoor control PCB *• Defective indoor control PCB (Defective temperature thermistor input circuit)? PCB
Replacement,
Drain trouble • Defective drain pump (DM), broken drain pump wire, disconnected connector
repair of DM
Float switch • Anomalous float switch operation (malfunction) Repair
1 time Keeps (In case of FDTC, FDUM)
Stays OFF 110
flash flashing
Indoor control PCB *• Defective indoor control PCB (Defective float switch input circuit) Replacement of
*• Defective indoor control PCB (Defective DM drive output circuit)? PCB
Option • Defective optional parts (At optional anomalous input setting) Repair
Keeps Number of connected indoor
Stays OFF Stays OFF • When multi-unit control by remote controller is performed, the number of units is over Repair 111
flashing units
Replacement,
1 time Keeps Fan motor • Defective fan motor
Stays OFF repair 112
flash flashing (In case of FDTC, FDUM)
Indoor control PCB • Defective indoor control PCB Replacement
1 time Keeps
Stays OFF Indoor control PCB • Improper operation mode setting Repair 113
flash flashing
1 time Keeps Fan motor • Indoor fan motor rotation speed anomaly Replacement, repair
Stays OFF (In case of FDTC, FDUM) 114
flash flashing Indoor power PCB • Defective indoor power PCB Replacement
Keeps Remote controller temperature
Stays OFF Stays OFF • Broken wire of remote controller temperature thermistor Repair 115
flashing thermistor
Note (1) Normal indicator lamp (Indoor unit: Green) extinguishes (or lights continuously) only when CPU is anomalous. It keeps flashing
in any trouble other than anomalous CPU.
(2) * mark in the Description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing
the part, it is judged consequently that the replaced part was defective.
(3) Value in ( ) is for the FDUM series only.
- 77 -
- 78 -
Replacement of
Outdoor control PCB • Defective outdoor control PCB (Defective high pressure sensor input circuit)?
PCB
Keeps 1 time Replacement of
Stays OFF Power transistor • Power transistor overheat 123
flashing flash PCB or Repair
Outdoor main PCB, Replacement of
Keeps 1 time • Current cut (Anomalous compressor over-current)
Stays OFF compressor PCB 124•125
flashing flash
Installation, operation status • Service valve closing operation Repair
Keeps 4 times Outdoor control PCB • Anomalous outdoor control PCB commuication Replacement of
Stay OFF 126
flashing flash Outdoor sub PCB • Anomalous outdoor sub PCB commuication PCB
- 79 -
- 80 -
Confirmation of
Confirmation remote controller and Replacement/
of power LEDs on the PCB Check of the anomalous Inspection repair of
Trouble supply of indoor unit and operation data on the of the unit/ faulty part,
(Indoor/ outdoor unit (Indoor/ remote controller controller test run,
outdoor unit) outdoor unit, remote adjustment
controller)
SAFETY PRECAUTIONS
● Read the "SAFETY PRECAUTIONS" carefully first of all and then strictly follow it during the replacement in order to protect yourself.
● The precautionary items mentioned below are distinguished into two levels, WARNING and CAUTION.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
WARNING Wrong installation would cause serious consequences such as injuries or death.
CAUTION Wrong installation might cause serious consequences depending on circumstances.
● After completing the replacement, do commissioning to confirm there are no anomaly.
WARNING
● Replacement should be performed by the specialist.
If you replace the PCB by yourself, it may lead to serious trouble such as electric shock or fire.
● Replace the PCB correctly according to these instructions.
Improper replacement may cause electric shock or fire.
● Shut off the power before electrical wiring work.
Replacement during the applying the current would cause the electric shock, unit failure or improper running.
It would cause the damage of connected equipment such as fan motor,etc.
● Fasten the wiring to the terminal securely, and hold the cable securely so as not to apply unexpected stress on the terminal.
Loose connections or hold could result in abnormal heat generation or fire.
● Check the connection of wiring to PCB correctly before turning on the power, after replacement.
Defectiveness of replacement may cause electric shock or fire.
CAUTION
● In connecting connector onto the PCB, connect not to deform the PCB. It may cause breakage or malfunction.
● Insert connecter securely, and hook stopper. It may cause fire or improper running.
● Bundle the cables together so as not to be pinched or be tensioned. It may cause malfunction or electric shock for disconnection or deformation.
- 81 -
④ Control PCB
Parts mounting are different by the kind of PCB.
SW2 (Blue)
Address setting CNW4(Blue)
Power PCB
CNW3(Red)
Power PCB
CNE(White)
RAM checker CNG(Blue)
CNI(Blue)
CNB(White)
CNH(Black)
Float SW
(Return air)
Humidity
Thermistor
controller
sensor
Auto lift
Remote
- 82 -
② Power PCB
Parts mounting are different by the kind of PCB. CNM(White) CNW0(White)
Fan motor Terminal block
T1(Yellow/Green)
Earth
CNW1(Blue)
Control PCB
CNW2(Red)
Control PCB
T2(Yellow/Green)
Earth
T3(Yellow/Green)
Earth
- 83 -
1 2 3 4
ԛControl PCB
Parts mounting are different by the kind of PCB.
㪚㪥㪮㪇㩿㪩㪼㪻䋩 㪪㪮㪉㩷㩿㪙㫃㫌㪼㪀
㪧㪸㫉㫋㩷㫅㫌㫄㪹㪼㫉 㪧㫆㫎㪼㫉㩷㫊㫆㫌㫉㪺㪼 㪘㪻㪻㫉㪼㫊㫊㩷㫊㪼㫋㫋㫀㫅㪾
㪚㪥㪮㪉㩿㪙㫃㪸㪺㫂䋩
㪚㪥㪮㪈䋨㪮㪿㫀㫋㪼䋩 㪪㪼㪺㫆㫅㪻㪸㫉㫐
㪧㫉㫀㫄㪸㫉㫐㩷㫋㫉㪸㫅㫊㪽㫆㫉㫄㪼㫉 㫋㫉㪸㫅㫊㪽㫆㫉㫄㪼㫉
㪚㪥㪙㩿㪮㪿㫀㫋㪼䋩
㪩㪼㫄㫆㫋㪼
㪚㪥㪤㪊䋨㪮㪿㫀㫋㪼䋩 㪺㫆㫅㫋㫉㫆㫃㫃㪼㫉
㪝㪸㫅㩷㫄㫆㫋㫆㫉
㪚㪥㪡㪉㩿㪙㫃㫌㪼䋩 㪚㪥㪞䋨㪙㫃㫌㪼䋩
㪣㫆㫌㫍㪼㫉㩷㫄㫆㫋㫆㫉
㪪㪮㪎
㪚㪥㪩㩿㪮㪿㫀㫋㪼䋩
㪛㫉㪸㫀㫅㩷㫇㫌㫄㫇
㪚㪥㪜䋨㪮㪿㫀㫋㪼䋩
㪩㪘㪤㩷㪺㪿㪼㪺㫂㪼㫉
㪚㪥㪭㩿㪙㫃㪸㪺㫂䋩
㪚㪥㪟㩿㪙㫃㪸㪺㫂䋩
㪚㪥㪱㩿㪮㪿㫀㫋㪼㪀
㪚㪥㪨㩿㪮㪿㫀㫋㪼㪀
㩿㪩㪼㫋㫌㫉㫅㩷㪸㫀㫉㪀
㪚㪥㪡㩿㪮㪿㫀㫋㪼㪀
㪫㪿㪼㫉㫄㫀㫊㫋㫆㫉
㪚㪥㪥㩿㪰㪼㫃㫃㫆㫎䋩
㪚㪥㪪㩿㪙㫃㫌㪼䋩
㪚㪥㪫㩿㪙㫃㫌㪼䋩
㪣㫆㫌㫍㪼㫉㩷㪪㪮
㪚㪥㪦㩿㪩㪼㪻䋩
㪚㪥㪠㩿㪙㫃㫌㪼䋩
㪝㫃㫆㪸㫋㩷㪪㪮
㪫㪿㪼㫉㫄㫀㫊㫋㫆㫉
㪼㫏㪺㪿㪸㫅㪾㪼㫉㪀
㪘㫌㫋㫆㩷㫃㫀㪽㫋
㪟㪼㪸㫋㪼㫉
㪦㫇㫋㫀㫆㫅
㪣㫆㫍㪼㫉㩷㫄㫆㫋㫆㫉
㪟㪘
㩿㪟㪼㪸㫋
㪧㫌㫃㫊㪼
- 84 -
1 2 3 4
④ Control PCB
Parts mounting are different by the kind of PCB.
CNR(White)
SW5 Drain motor
Master/Slave
setting
SW2(Blue)
Address setting CNW2(White)
Power PWB
CNE(White)
RAM checker
CNN(Yellow)
Thermistor
(Heat exchanger)
- 85 -
② Power PCB
Parts mounting are different by the kind of PCB.
CNW1(White)
Control pwb
- 86 -
SW2 Address No. setting at plural indoor units control by 1 R/C 0 0-F
SW6-1
SW6-2
Model selection As per model See table 1
SW6-3
SW6-4
SW7-1 Test run, Drain motor Normal*/Test run OFF Normal
SW7-2 Reserved OFF keep OFF
SW7-3 Powerful mode Valid*/Invalid ON Valid
SW7-4 Reserved OFF keep OFF
JSL1 Superlink terminal spare Normal*/switch to spare With
* Default setting
- 87 -
➆ Upon operation of the button, the current operation data is 38 (Pulse of The Outdoor Unit Expansion Valve EEVC)
39 (Pulse of The Outdoor Unit Expansion Valve EEVH)
displayed in order from data number 01.
The items displayed are in the above table.
*Depending on models, the items that do not have corresponding data are not displayed.
➇ To display the data of a different indoor unit, press the button, which allows you to go back to the indoor unit
selection screen.
➈ Pressing the button will stop displaying data.
Pressing the (RESET) button during remote control unit operation will undo your last operation and allow you to go back to
the previous screen.
If two (2) remote controllers are connected to one (1) inside unit, only the master controller is available for trial operation and
confirmation of operation data. (The slave remote controller is not available.)
- 88 -
Cyclically ● ON
Red White ○ OFF
U Black
V
Faston terminal W
Connect to the terminal of the wires which are disconnected from compressor.
- 89 -
- 90 -
It is normal.
(This unit is designed to
Is the start in the soft start mode
temperature differnce Does the by detecting the under dome
between return and supply air YES heat load increase after NO
temperature of compressor
10-20degC at installtion?
when it restart after power
cooling?
2. Error detection method reset.
YES
NO
Note:
- 91 -
It is normal.
(This unit is designed to
Is the start in the soft start mode
temperature differnce Does the by detecting the under
between return and supply air YES heat load increase after NO dome temperature of
10-30degC at installtion? compressor when it restart
heating?
2. Error detection method after power reset.
YES
NO
It is necessary to replace to
Mistake in model selection. higher capacity one or to
Calculate heat load once again. install additional unit.
Is the compressor
operating? NO
Compressor may be
stopped by the error
YES
NO
detection control.
For the contents of control,
3. Condition of Error displayed refer to anomalous stop
control by controlling
compressor rotation speed
of microcomputor control
functions.
Is the
Inspect the followings.
compressor rotation NO
speed low?
• Minor clogging of filter
• Minor clogging of heat
exchanger
YES • Minor short-circuit
• Minor shortage of
Check which control “Determination control of refrigerant amount
conpressor rotation speed” or “Protective control • Poor compression of
by controlling compressor rotation speed” is compressor
appropriate to this phenomenon.
4. Presumable cause Considering appropriate
operation control, check
• Faulty 4-way valve operation (1)
suspicious points.
Are the Inspect the followings for
• Poor compression of temperature conditions
compressor of room and outdoor air close YES reference.
• Faulty expansion valve to the rated • Major clogging of filter
conditions?
operation Note (1) Outdoor: 7°C, Indoor: 20°C
• Major clogging of heat
NO exchanger
• Major short-circuit
• Major shortage of
The unit is operating normally but is refrigerant amount
operating under the contol for protecting • Compressor protection ON
compressor or other respective parts.
• Indoor fan tap
Note:
- 92 -
Are OK the
insulation resistance and NO Replace compressor.*
coil resistance of
compressor?
YES
YES
Note:
- 93 -
If excessive noise/vibration
Does persists when sufficient
noise/vibration time has elapsed after
occur during or soon
NO
stopping the unit, it is
after stopping operation considered that the air-
of air-conditioner? conditioner is not the
source.
Check the installed
2. Error detection method YES condition carefully, and
Does the correct the position or
installation of insert rubber cushions
YES
indoor/outdoor or others into the gap, if
unit loose? necessary.
YES
[Installation work]
NO
Prevent the vibration from
Does noise/vibration transmitting to wall and etc
occur not only from the by fixing pipes on the wall
air-conditioner or wrapping rubber cushion
but also from entire
Are pipes around the pipe which
building? YES goes through the hole in
touching the wall, etc?
the wall or applying other
appropriate means.
NO Strength of ceiling
NO wall, floor, etc. may be
insufficient. Review the
installing position or
reinforce it.
3. Condition of Error displayed
[Product]
Is there a fan
Check for leaning of
Does noise/vibration
YES or louver touching other YES installed unit or anomalous
occur from operating
fan (fan only)? components? mounting of fan, louver
or motor and specify the
contacting point and correct
it.
Note:
- 94 -
To next page
The noise/vibration occurs
Are hissing sounds when the refrigerant starts
heard at the startup or YES
or stops flowing. It is
stopping? normal.
NO
When the defrosting starts
or stops during heating,
the refrigerant flow is
reversed due to switching
Is blowing sound 4-way valve. This causes
3. Condition of Error displayed heard at the start/stop a large change in pressure
YES
of defrosting during which produces a blowing
heating? sound. It may accompany
also the hissing sounds as
mentioned above. They are
NO normal.
After the start or stop of
heating operation or during
Is cracking noise defrosting, abrupt changes
heard during heating YES
in temperature cause resin
operation? parts to shrink or expand.
This is normal.
NO
It is the sound produced
4. Presumable cause by the drain pump that
discharges drain from the
Hissing noise is indoor unit. The pump
heard during cooling continues to run for 5
YES
operation or after minutes after stopping the
stopping. cooling operation. This is
normal.
Apply the damper sealant
NO
at places considered to
be the sources such as
the pressure reducing
mechanism (expansion
valve), capillary, etc.
Note:
- 95 -
If insufficient cooling/
Adjustment heating problem happens
during commissioning
Does noise/vibration occur when the
due to anomalous operating
cooling/heating operation is in conditions at cooling/
2. Error detection method anomalous condition? heating, followings are
suspicious.
• Overcharge of refrigerant
YES
• Insufficient charge of
refrigerant
• Intrusion of air, nitrogen,
etc.
In such occasion, it is
necessary to recover
refrigerant, vacuum-dry
and recharge refrigerant.
Note:
- 96 -
Operate after
waiting for more
than 1 minute.
Is LM wiring
broken?
NO
YES
Is LM locked? NO
Defective indoor control
PCB ➞ Replace.
Is the louver
operable with the remote YES Normal
controller?
3. Condition of Error displayed
NO Adjust LM lever and then
check again.
4. Presumable cause
• Defective LM
• LM wire breakage
• Faulty indoor control PCB
Note:
- 97 -
Are fuses
OK (F200, F201)? NO
Is the
check of resistance between NO Defective indoor control or
YES
�-� of CNW0 power PCB ➞ Replace.
OK?
YES
Is the
checked result
of resistance of FM, NO Replace FM, LM, etc.
LM, etc
OK?
FDTC, FDUM YES Replace fuse.
FDEN, Series Series
YES
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty indoor control or Is JX1 open? NO Open JX1.
power PCB
• Broken harness
• Faulty outdoor control PCB YES
(Noise filter) Defective indoor control
PCB ➞ Replace.
Note:
- 98 -
NO
NO
Disconnect remote
controller wires.
Is DC15V or
higher detected between X-Y YES Replace remote controller.
of indoor unit terminal
block?
3. Condition of Error displayed
NO
FDTC, FDUM
FDEN, Series Series
Is DC180V
between �-� of CNW2 NO Defective indoor power
(FDUM:CNW1)? PCB➞Replace.
YES
Defective indoor control
PCB➞Replace.
4. Presumable cause
Is 24V or higher
• Remote controller wire between (Brown-Brown) of NO Replace transformer.
breakage/short-circuit transformer secondary
• Defective remote controller side?
• Malfunction by noise
• Faulty indoor power PCB
• Broken harness YES Defective indoor control
• Faulty indoor control PCB PCB➞Replace.
Note:
- 99 -
Are 2 units
of remote controller
connected?
YES
NO
⑴,
⑵
⑵
Set one remote controller Is it set
for “Master” and the other at the slave remote YES Set SW1 on remote
for “Slave” controller? controller PCB at “Master”.
2. Error detection method
Note (1) Use SW1 to set at
master or slave. Note (2)
“Slave” is displayed
Communication between indoor on the remote
unit and remote controller controller LCD.
is disabled for more than 30 NO
Does it
minutes after the power on. become normal?
NO
Do more than
one indoor units have the YES Set address again. (SW2 on
same address? indoor control PCB)
NO
3. Condition of Error displayed
NO
• Improper setting
• Surrounding environment
• Defective remote controller Does DM
communication circuit start 60 seconds later YES Defective indoor control
• Faulty indoor control PCB automatically. PCB➞Replace.
Note: If any error is detected 30 minutes after displaying “ WAIT ” on the remote controller, the display changes to
“INSPECT I/U”.
- 100 -
NO
Does remote
controller display YES Change remote controller
2. Error detection method “Slave”? setting to “Master”. (SW1
on remote controller PCB)
NO
Indoor unit cannot communicate
for more than 30 minutes after
the power on with remote Do more than
controller. one indoor units have the YES Change address. (SW2 on
same address? indoor control PCB)
NO
Is it set to
a slave indoor unit. YES Change to master. (SW5-1,
SW5-1, 2? 2 on indoor control PCB)
NO
Is there loose
or wrong connection at the termanal
of wiring between indoor and YES Correct
outdoor units?
3. Condition of Error displayed
NO
Same as above
Is the
grounding wire connected NO Correct
properly?
YES
Is approx.
DC20V detected between �-� NO Defective outdoor sub PCB
on the outdoor unit terminal
block? ➞Replace.
YES
Note: If any error is detected 30 minutes after displaying “ WAIT ” on the remote controller, the display changes to
“INSPECT I/U”.
- 101 -
NO
YES
Is AC220/240V
detected at the secondary side of NO
Defective outdoor sub
outdoor sub PCB? PCB→Replace.
YES
Is the
green LED of indoor unit NO Defective indoor control
flashing? PCB→Replace.
YES
Replace indoor control
Are wires PCB.
3. Condition of Error displayed connected properly between NO Correct connection wires
the indoor and the outdoor between indoor and
units?
outdoor units.
YES
Is approx.
DC20V detected between �-� NO Defective outdoor sub
on the outdoor unit terminal PCB→Replace.
block?
YES
• Blown fuse
• Faulty outdoor sub PCB
• Connection between PCB’s
• Faulty indoor control PCB
• Defective remote controller
• Broken remote controller wire
Note: I f any anomaly is detected during communication, the error code E5 is displayed. Inspection procedure is same as above. (Excluding
matters related to connection) When the power supply is reset after the occurrence of E5, the LED will display “ WAIT ” if the anomaly
continues. If the breaker ON/OFF is repeated in a short period of time (within 1 minute), “ WAIT ” may be displayed. In such occasion,
turn the breaker off and wait for 3 minutes.
- 102 -
Aren’t there
2. Error detection method cracks or burning on the power
ransistor module or diode NO
stack?
Replace the outdoor
main PCB
YES
Replace the
reactor.
YES
Replace fuse.
4. Presumable cause
• Blown fuse
• Faulty outdoor sub PCB
• Faulty outdoor main PCB
• Faulty reactor
Note:
- 103 -
Is the
green LED on the indoor unit
flashing? NO
Is the
2. Error detection method fuse on the indoor control NO Replace fuse.
PCB OK?
YES
YES (1)
Is AC
19V or higher detected
between Red-Red at the secondary side of NO Defective transformer
indoor unit transformer?
Is
approx. 10-11V detected
between wires at the remote controller NO Short-circuit on remote
side after disconnecting the
remote controller? controller wire
YES
Is approx.
DC20V detected between �-� NO Defective outdoor sub
on the outdoor unit terminal
block? PCB➞Replace.
YES
Is approx
DC20V detected between �-�
on the indoor unit terminal NO Defective connection wire
block? (Broken wire)
4. Presumable cause Noise
Note:
- 104 -
NO
Same as above
4. Presumable cause
• Defective communication
circuit between remote
controller-indoor unit
• Noise
• Defective remote controller
• Faulty indoor control PCB
Note:If the indoor unit cannot communicate normally with the remote controller for 180 seconds, the indoor contnrol PCB starts
to reset automatically.
- 105 -
YES
2. Error detection method Note (2) Check for faulty connection or breakage of
Is the signal wires between indoor-outdoor units.
When normal communication connection of signal
NO Repair signal wires.
between indoor and outdoor wires between indoor-outdoor
units OK?
unit is interrupted for more than
2 minutes. YES
Power reset
4. Presumable cause
Note:
- 106 -
Is the
connection of indoor heat
exchanger temperature thermistor NO Correct. ➞ Insert connector
connector OK? securely.
YES
(Shot circuit)
0 10 20 30 40 50
4. Presumable cause Temperature (°C)
Note:
- 107 -
Is the
connection of return
air temperature thermistor NO Correct. ➞ Connect
connector OK? connector.
YES
5kΩ at 25°C
5
4. Presumable cause
(Shot circuit)
0 10 20 30 40 50
• Defective return air
temperature thermistor Temperature (°C)
connector
• Defective return air
temperature thermistor
• Faulty indoor control PCB
Note:
- 108 -
YES Wash.
Is the unit
operating in the state of NO Check refrigerant system.
heating overload?
3. Condition of Error displayed
Note: During heating operation; After starting compressor, compressor rotation speed is decreased by detecting indoor heat
exchanger temperature (ThI-R) in order to control high pressure.
- 109 -
Is DC 12V
at CNI connector.
NO
Is
there any
anomaly on the optional NO Defective indoor control
Is the humidifier connected? equipment? PCB ➞ Replace.
Is the
humidifier Drain Motor
interlocked by the indoor unit function NO Correct setting to
3. Condition of Error displayed setting of remote
controller? NO “Humidifier DM interlock”.
Note: When this error occurred at power ON, disconnection of wire or connector of the float switch is suspected. Check and
correct it (or replace it, if necessary).
- 110 -
Same as above
4. Presumable cause
Note:
- 111 -
Does any
foreign material
intervene in rotational area YES Remove foreign material.
of fan propeller?
NO
Is DC280V (1)
detected between �-� of NO
fan motor connector
CNM?
4. Presumable cause
Note:
- 112 -
E19 occurs
when the power ON
Same as above
4. Presumable cause
Note:
- 113 -
Error code LED Green Red Content Indoor fan motor rotation
Remote controller: E20 Indoor Keeps flashing 1 time flash speed anomaly
Outdoor Keeps flashing Stays OFF (FDTC and FDUM series)
Does any
foreign material
intervene in rotational area YES Remove foreign material.
of fan propeller?
NO
4. Presumable cause
Note:
- 114 -
Note: A
fter 10 seconds has passed since remote controller thermistor was switched from valid to invalid, E28 will not be displayed even if the
thermistor harness is disconnected. At same time the thermistor, which is effective, is switched from remote controller thermistor to indoor return
air temperature thermistor. Even though the remote controller thermistor is set to be Effective, the return air temperature displayed on remote
controller for checking still shows the value detected by indoor return air temperature thermistor, not by remote controller temperature thermistor.
- 115 -
YES
Is
3. Condition of Error displayed the temperature
(measured actually) at NO Defective outdoor main
direction of error
PCB➞Replace.
When anomalous outdoor heat correct?
exchanger temperature occurs
5 times within 60 minutes YES Excessive refrigerant
or 60°C or higher continues amount: Recharge
for 10 minutes, including the refrigerant by weighing
compressor stop. proper amount on a scale.
4. Presumable cause
Note:
- 116 -
YES
YES
Is
3. Condition of Error displayed the pressure
(measured actually) at NO Defective outdoor control
direction of error
PCB➞Replace.
• When anomalous rise of correct?
the high pressure sensor is
detected 5 times within 1 hour. YES Excessive refrigerant
• When high pressure sensor amount: Recharge
anomaly is detected for 10 refrigerant by weighing
minutes continuously. proper amount on a scale.
4. Presumable cause
Note:
- 117 -
YES
Is the
discharge pipe
2. Error detection method temperature error persisted
during cooling
YES Insufficient refrigerant
operation?
amount : Recharge
refrigerant by weighing
For the error detection method, proper amount on a scale.
refer to the protective control by
controlling compressor rotation NO
speed and cooling high pressure
protective control of micro
computer control function for
corresponding models. Is the
discharge pipe temperature NO Control operation check *
control normal?
YES
Is the
temperature (measured
actually) at detection of NO Defective outdoor main
3. Condition of Error displayed error correct? (control) PCB➞Replace.
Note:
- 118 -
Is the
outdoor heat
exchanger temperature
sensor connector NO Correct connector.
connected
properly?
YES
2. Error detection method
For the characteristics of outdoor heat exchanger
Detection of anomalously low temperature sensor, see the following graph.
temperature (resistance) on Are the
characteristics of
the outdoor heat exchanger outdoor heat exchanger
temperature sensor temperature
NO Defective outdoor heat
sensor exchanger temperature
OK? sensor➞Replace.
2 minutes to 2 minutes 20
seconds after the compressor
ON, the compressor stops.
After 3-minutes delay, the 10
compressor starts again
automatically, but if this
anomalous temperature is
detected 3 times within 40
minutes. 5
5kΩ at 25°C
• When -55 °C or lower is
detected for within 20 second
after power ON.
(Shot circuit)
0 10 20 30 40 50
4. Presumable cause Temperature (°C)
Note:
- 119 -
Is
the suction pipe
temperature sensor connector NO Correct connector.
connected properly?
YES
For the characteristics of suction pipe
Is the temperature sensor, see the following graph.
Defective outdoor air
2. Error detection method characteristics of the
suction pipe temperature NO temperature sensor➞
sensor Replace.
Detection of anomalously low OK?
temperature (resistance) on
outdoor air temperature sensor YES Defective outdoor main
(control) PCB➞Replace.
(Defective outdoor air
temperature sensor input
circuit)
Note:
- 120 -
Is the
discharge pipe
temperature sensor NO Correct connector.
connector connected
properly?
YES
4. Presumable cause
• Defective outdoor main
(control) PCB
• Broken sensor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
- 121 -
YES
YES
Is
3. Condition of Error displayed the pressure
(measured actually) at NO Defective outdoor control
direction of error
PCB➞Replace.
• When anomalous rise of correct?
the high pressure sensor is
detected 5 times within 1 hour. YES Excessive refrigerant
• When high pressure sensor amount: Recharge
anomaly is detected for 10 refrigerant by weighing
minutes continuously. proper amount on a scale.
4. Presumable cause
Note:
- 122 -
Is the
installation space of outdoor NO
unit enough?
YES Correct.
Is the power
transistor temperature thermistor connector NO
connection OK?
YES Connect.
Is it OK the fixing
to power transistor radiator fin?
・Fixed screw NO Fix properly.
3. Condition of Error displayed ・Application of radiation
silicone
When anomalous rise of the
power transistor temperature is YES
detected 2 times within 1 hour.
Does it recur?
NO OK
* Characteristics of power transistor temperature thermistor
Temperature-resistance characteristics
Temperature thermistor resistance (kΩ)
200
180
160
140
4. Presumable cause 120
100
80
• Defective inverter PCB
• Defective outdoor fan motor 60
• Delective power transistor 40
temperature thermistor 20
• Inadequate installation space 0
0 20 40 60 80 100 120 140
Temperature (°C)
Note:
- 123 -
Is the
Power supply NO Check power supply.
voltage OK?
YES
4. Presumable cause
Note:
- 124 -
Is the
checked result of power NO • Defective outdoor main
transistor module
OK? PCB➞Replace.
In order to prevent from • Is the space for installation of indoor and/or outdoor unit enough?
• Is there any short circuit of air on indoor and/or outdoor unit?
overcurrent of inverter, • At cooling, does the outdoor fan motor run?
if the current exceeds the Are the service valves fully opened?
specifications, it makes the Is the filter clogged?
compressor stopping. • At heating, does the indoor fan motor run?
Are the service valves fully opened?
Is the filter clogged?
• Is there any liquid flooding?
Is the superheat within normal range?
Is the suction pipe temperature thermistor normal?
• Is there any anoumalous sound on the compressor?
YES
After
resetting power for
several times does it NO •D
efective outdoor main
3. Condition of Error displayed become normal? PCB➞Replace.
4. Presumable cause
Note:
- 125 -
Is the connector
connection between the outdoor
main PCB and the outdoor sub NO Correct connector.
PCB OK?
YES
2. Error detection method Is the power supply voltage OK? NO Check why power is not
supplied to outdoor sub
Detected communication error PCB.
of more than 15 seconds 4 times
in 15 minutes.
YES
Is the
communication wire
between the main PCB and the outdoor sub NO Connect communication
PCB connected properly? wire securely.
YES
3. Condition of Error displayed
Replace the outdoor main PCB.
When communication is not
established between the outdoor
sub PCB and the outdoor main
PCB.
4. Presumable cause
Note:
- 126 -
YES
Check
soldered surfaces on the
outdoor sub PCB for foreign matter NO Remove foreign matter like
like dust, fouling, dust, fouling, etc.
etc.
Same as above
4. Presumable cause
Note:
- 127 -
Does any
foreign material intervene
in rotational area of fan
YES Remove foreign matter.
propeller?
NO
Does the
2. Error detection method fan rotate smoothly when turned NO Replace fan motor.
by hand? If resistance between ➀
Detected by rotation speed of (Vm):white -➃(GND)
outdoor fan motor 〔SCM100, 125: ➆(Vm):
white-➃(GND)〕 :blue is
YES detected 1kΩ or lower, it is
faulty.
Is DC308~336V
detected between (CNFAN � (blue)-� (red))
〔SCM100,125: CNFAN � (blue)–� (red)〕 NO
of fan motor connector?
Is F3 (250V1A)
ާSCM100, 125: F4 (250V4A)ި NO Check power supply
YES voltage.
3. Condition of Error displayed Power supply reset YES Replace faulty fan motor
and outdoor main PCB.
When actual rotation speed
of outdoor fan motor drops to
75min-1 or lower for 30 minutes
continuously, the compressor Is normal state restored? NO Replace fan motor (If
and the outdoor fan motor stop. anomaly persists after
After 3-minutes delay, it starts replacing fan motor, replace
again automatically, but if this outdoor main PCB.)
anomaly occurs 3 times within
60 minutes after the initial
detection. YES Malfunction by temporary
noise
4. Presumable cause
Note: W
hen E48 error occurs, in almost cases F3 (SCM100, 125: F4) fuse on the outdoor main (control) PCB is blown. There are a lot of cases that fuse
is blown and E48 occurs due to defective fan motor. And even though only the outdoor main (control) PCB ( or fuse) is replaced,, another trouble
could occur. Therefore when fuse is blown, check whether the fan motor is OK or not.
After confirming the fan motor normal, check by power ON. (Don't power ON without confirming the fan motor normal.)
- 128 -
Check soldered
surfaces on the outdoor main PCB for
foreign matter like dust,
NO Remove foreign matter
fouling,etc. like dust, fouling, etc.
2. Error detection method YES
4. Presumable cause
• Faulty outdoor main PCB
• Dust on outdoor main PCB
• Blown F2 fuse
Note:
- 129 -
Is DC15V
detected between the connector
CNI4 �-� on the YES Defective inverter PCB➞
inverter PCB? Replace.
NO
Is DC15V
2. Error detection method detected between the
hanesses at the control PCB side after YES Broken harness wire
disconnecting the connector
When power transistor anomaly (CNI4)?
is detected for 15 minutes
continuously
NO
Is DC15V
detected on the fan motor YES Replace fan motor.
connector?
NO
Same as above
4. Presumable cause
Note:
- 130 -
Is
the suction pipe
temperature sensor connector NO Correct connector.
connected properly?
YES
For the characteristics of suction pipe
Is the temperature sensor, see the following graph.
Defective suction pipe
2. Error detection method characteristics of the
suction pipe temperature NO temperature sensor➞
sensor Replace.
Detection of anomalously low OK?
temperature (resistance) on
suction pipe temperature sensor YES Defective outdoor sub
PCB➞Replace.
(Defective suction pipe
temperature sensor input
circuit)
Note:
- 131 -
Are the
connection of high pressure
sensor connectors (at sensor side NO Correct high pressure sensor
and PCB side) OK? connector connection.
YES
Are the
2. Error detection method pressure (actual
measurement) matched with the value Is refrigerant amount
YES
indicated on the remote charged properly?
controller?
When anomalous voltage Is there any anomaly on the
(pressure) is detected refrigeration circuit?
NO
Is
normal condition NO Defective outdoor control
restored? PCB➞Replace.
(Defective high pressure
sensor input circuit)
3. Condition of Error displayed
Note:
- 132 -
Is the
service valve fully NO Open fully.
opened?
YES
Are the
connections of indoor
heat exchanger and/or return air NO Correct indoor heat
2. Error detection method temperature thermistor
exchanger, return air
connectors OK?
temperature thermistor
• Judge insufficient refrigerant connector connections.
amount by detecting the YES
temperature differnce between
indoor heat exchanger (ThI-R) Are the
and indoor return air (ThI-A). characteristics of indoor heat
exchanger and/or return air NO Defective indoor heat
temperature thermistor exchanger, return air
OK? temperature thermistor ➞
Replace.
YES
Is the low
pressure during operation NO Charge refrigerant.
normal?
15
Temperature thermistor resistance (kΩ)
10
Note:
- 133 -
Is the refrigerant
NO Adjust the refrigerant
amount nomal ?
amount properly.
YES
Inspect
NO Replace compressor.
compressor
Same as above
Inspect
outdor air temp. NO Replace sensor.
sensor
Note:
- 134 -
Compressor does not start at all. Disconnect the outdoor fan motor
Neither noise nor vibration cannot be heard connector and try to startup
Does
compressor YES Replace outdoor fan motor
startup?
NO
2. Error detection method
Is power
If it fails to change over to the supply voltage NO Check power supply
rotor detection operation of OK? voltage
compressor motor
YES
Is
the pressure balance NO Check refrigerant amount
at starting OK? and refrigerant circuit
YES
Is the
insulation resistance
and coil resistance of NO Repalce compressor
compressor OK ?
3. Condition of Error displayed
YES
Is
4. Presumable cause the output of inverter NO Defective outdoor main
checker OK ? PCB➞Replace
• Faulty outdoor fan motor
YES
• Faulty outdoor main PCB
• Anomalous power supply Note: Several times restarting
may resolve it, because migrated
voltage Try to startup liquid refrigerant in the
• Improper refrigerant amount several times compresser is discharged from
and refrigerant circuit the compressor.
• Faulty compressor (Motor
bearing)
Does it start? NO Repalce compressor
- 135 -
Is the
power supply voltage NO Check and correct the
OK? power supply voltage
YES
Does the
compressor run without
occurrence of
NO Correct it based on the
E42?
troubleshooting of E42
3. Condition of Error displayed
Is the
output from inverter NO Defective outdoor main
If it fails again to detect the checker OK?
rotor position after shifting to PCB➞Replace.
the compressor rotor position
detection operation, the
compressor stops. YES
Is the noise
or vibration of compressor NO Replace compressor.
normal?
- 136 -
CNHEAT CN20S G2 CNEEV1 CNTH CNTH ・High voltage is produced in the control box. don't touch
Y/G electrical parts in the control box for 5 minutes after
2 2 2 2 cutting power supply.
WH RD WH RD
t゜
t゜
t゜
t゜
20S M M
HEATER
EEV EEV Tho-S Tho-R Tho-A Tho-D
A B
'11 • SCM-SM-110
OR Orange EEV A,EEV B Electric expansion valve (outdoor unit)
BR Brown (coil) Tho-A Outdoor air temp. sensor
FMo Fan motor Tho-D Discharge pipe temp. sensor
HEATER Crank case heater Tho-S Suction pipe temp. sensor
CNHEAT CN20S G2 CNEEV1 CNEEV3 CNTH CNTH High voltage is produced in the control box. don't touch
Y㧛G electrical parts in the control box for 5 minutes after
2 2 2 2 cutting power supply.
WH RD WH RD BL
tࠑ
tࠑ
tࠑ
tࠑ
20S M M M
HEATER
EEV EEV EEV Tho-S Tho-R Tho-A Tho-D
A B C
'11 • SCM-SM-110
WH White EEV A,EEV B Electric expansion valve 㧔outdoor unit㧕
OR Orange EEV C 㧔coil㧕 Tho-A Outdoor air temp. sensor
FMo Fan motor Tho-D Discharge pipe temp. sensor
HEATER Crank case heater Tho-S Suction pipe temp. sensor
Y㧛G
CNHEAT CN20S G2 CNEEV1 CNEEV2 CNTH CNTH
139 -
tࠑ
tࠑ
tࠑ
20S M M M M
HEATER
EEV EEV EEV EEV Tho-S Tho-R Tho-A Tho-D
A B C D
'11 • SCM-SM-110
GN Green Y㧛G Yellow㧛Green EEV A,EEV B Electric expansion valve 㧔outdoor unit㧕
OR Orange EEV C,EEV D 㧔coil㧕 Tho-A Outdoor air temp. sensor
FMo Fan motor Tho-D Discharge pipe temp. sensor
HEATER Crank case heater Tho-S Suction pipe temp. sensor
Y/G
F Fuse
FM Fan motor
HPS High pressure sensor
IPM Intelligent power module
PWB2 L Reactor
INV PWB LED1 Indicator lamp㧔Red-Inspection indicator㧕
WH
WH
RD
RD
RD
BL
1
BK L-IN N-IN CNW LED3 Indicator lamp㧔Green-For service㧕
UNIT A WH CNA 㧔BK㧕
2
RD 㧔WH㧕 TB Terminal block
3 CNA1
CNTRI WH2 㧔WH㧕 F2 Tho-A Thermistor㧔outdoor air temperature㧕
BK
㧔WH㧕 LED1 4A
UNIT B 1
2
WH CNB 2 TR Tho-D Thermistor㧔discharge pipe㧕
3
BR 㧔WH㧕 CNTRO RD 250V
CNA2 Tho-R Thermistor㧔heat exchanger㧕
BK
㧔WH㧕 㧔GN㧕
UNIT C 1
2
WH CNC
BK
LED2 LED3 Tho-S Thermistor㧔suction pipe㧕
BL 㧔WH㧕 CNS2 CNS1 4 Tho-AF Thermistor㧔power transistor㧕
3
PWB4 㧔BK㧕 WH PWB1 CNI1 BL CNI2
㧔BK㧕
TB3 㧔WH㧕 TR Trance former
SUB PWB CONTROL PWB
BK BK 3 20S 4-way valve coil
UNIT D 1
WH CND CNX2 CNX1 CNI3 BL CNI4
2
Y 㧔WH㧕 㧔Y㧕 WH 㧔Y㧕 CHECKER PC
3 㧔WH㧕
-
BK Y/G
1
CNE G CNE※ CNV̪
UNIT E
140 - #
2
WH
3
OR 㧔WH㧕
IPM Mark Color
CN CN CN CN CN
EEV1 EEV2 EEV3 EEV1 CNL1 FAN1 CNR1 CNN1
30A 600V BK Black
㧔WH㧕 㧔WH㧕 㧔WH㧕 CNTH CNP1 㧔RD㧕 㧔BL㧕 㧔WH㧕 㧔WH㧕 㧔RD㧕 W V U BL Blue
WH
BR Brown
RD
BK
BK
BK
BK
BR
BL
BL
5 5 5 5 5 5 3 5 2 2
Y
2 2 2 2 2
WH RD BL GN BK GN Green
5 5 5 5 5 OR Orange
V
t°
t°
t°
t°
t°
PK Pink
Tho-AF
W U
Tho-D
HPS CH 20S
Tho-R
Tho-A
Tho-S
M M M M M M M MS RD Red
3㨪
EEV EEV EEV EEV EEV CM
EEV-H FM WH White
A B C D E Y Yellow
1.Instructions for correct operation
2.Error indication Y㧛G Yellow㧛Green
٧Before you turn on power,please carefully read the installation
ޓmanual and the operation manual supplied with the unit. INDICATION LAMP COLOR FUNCTION
٧Please check the following points before operation. LED E 㧔1㧕 RED WARNING LAMP
Ԙ This unit is designed exclusively for use with R410A. Do not use ޓޓ SELF DIAGNOSIS FUNCTION BY LED E
1 TIME FLASH CURRENT CUT
ޓany refrigerant other than R410A.
2 TIME FLASH TROUBLE OF OUTDOOR UNIT
ԙ To protect the compressor,turn on power for the air conditioner 3 TIME FLASH OVER CURRENT
ޓ6 hours before operation so as warm up sufficiently the dome 4 TIME FLASH TRANSMISSION ERROR ※used only at our factory
ޓtemperature of compressor. 5 TIME FLASH OVER HEAT OF COMPRESSOR
Ԛ Open the service valves of liquid pipe at first. Secondarily open 6 TIME FLASH ERROR OF SIGNAL TRANSMISSION
'11 • SCM-SM-110
8 TIME FLASH SENSOR ERROR
ޓthe one of gas pipe. Before you operate the unit,make sure again 㧔EXCEPT DISCHARGE PIPE SENSOR㧕
RWC000Z247
ޓthat the service valves are in open position. LIGHT ON OUTDOOR FAN MOTOR ERROR
ԛ Please note that the pressure valves detected at the charge port FOUR SEC LIGHT
ޓin the unit and the gas service valves are different during the AND DISCHARGE PIPE SENSOR ERROR
ޓcooling operation and the heating operation. High pressure is FOUR SEC OFF
ޓreplaced with the low pressure depending on whether it is in the
ޓcooling or heating operation.
Model SCM125ZJ-S1
POWER SOURCE L A/F MODULE Active filter module
㨪 220/230/240V CH Crankcase heater
TB1 F1
50Hz 30A 250V RD P1 P2 4 CM Compressor motor
+L1 CNACT
L2 CNACT1
L RD RD RD RD RD
1 2
TB3 TB5 TB3 TB5 2 +1
PWB5 PWB3 㨪 㧔WH㧕 CNA㨪Z Connector
N
WH NOISE NOISE
ACDS N1 N2 㧔BK㧕
WH WH 3 -4 BL 4 3 BL - RD RD CT Current sensor
Y/G TB4 FILTER TB6 TB4 FILTER TB6 㨪 P P3
A㧛F + DS Diode stack
CT1
3 TB7 TB8 TB7 MODULE
C1 EEV Electronic expansion coil
N2 BL BL N3
Y/G
Y/G
EEV-H
F Fuse
FM Fan motor
HPS High pressure sensor
IPM Intelligent power module
PWB2 L Reactor
INV PWB LED1 Indicator lamp㧔Red-Inspection indicator㧕
WH
WH
RD
RD
RD
BL
1
BK L-IN N-IN CNW LED3 Indicator lamp㧔Green-For service㧕
UNIT A WH CNA 㧔BK㧕
2
RD 㧔WH㧕 TB Terminal block
3 CNA1
BK
CNTRI WH2 LED1 㧔WH㧕 F2 Tho-A Thermistor㧔outdoor air temperature㧕
UNIT B 1
CNB 㧔WH㧕 4A
2
WH 2 TR 250V Tho-D Thermistor㧔discharge pipe㧕
3
BR 㧔WH㧕 CNTRO RD CNA2 Thermistor㧔heat exchanger㧕
㧔WH㧕 Tho-R
BK 㧔GN㧕
UNIT C 1
2
WH CNC BK
LED2 LED3 Tho-S Thermistor㧔suction pipe㧕
3
BL 㧔WH㧕 CNS2 WH CNS1 4 Tho-AF Thermistor㧔power transistor㧕
PWB4 㧔BK㧕 㧔BK㧕 PWB1 CNI1 BL
㧔WH㧕 CNI2 TR Trance former
TB3 SUB PWB CONTROL PWB
1 BK BK 3 20S 4-way valve coil
UNIT D WH CND CNX2 CNX1 CNI3 BL
2
Y 㧔WH㧕 㧔Y㧕 WH CHECKER PC CNI4
3 㧔Y㧕 㧔WH㧕
-
BK Y/G
1
CNE G CNE※ CNV※
UNIT E WH
141- #
2
3
OR 㧔WH㧕
IPM Mark Color
BK
UNIT F 1
WH CNF CN CN CN CN CN CN 30A 600V BK Black
2
3
PK 㧔WH㧕EEV1 EEV2 EEV3 EEV4 EEV1 CNL1 FAN1 CNR1 CNN1
㧔WH㧕 㧔WH㧕 㧔WH㧕 㧔WH㧕 CNTH CNP1 㧔RD㧕 㧔BL㧕 㧔WH㧕 㧔WH㧕 㧔RD㧕 W V U BL Blue
BR Brown
WH
BK
BK
BK
BK
BR
BL
RD
BL
5 5 5 5 5 5 5 3 5 2 2
Y
2 2 2 2 2
WH RD BL GN BK Y GN Green
5 5 5 5 5 5 OR Orange
V
t°
t°
t°
t°
Tho-AF t°
W U PK Pink
Tho-D
Tho-R
Tho-A
Tho-S
HPS CH 20S
M M M M M M M M MS RD Red
3㨪
CM
EEV EEV EEV EEV EEV EEV EEV-H FM WH White
A B C D E F Y Yellow
1.Instructions for correct operation
2.Error indication Y㧛G Yellow㧛Green
٧Before you turn on power,please carefully read the installation
ޓmanual and the operation manual supplied with the unit. INDICATION LAMP COLOR FUNCTION
٧Please check the following points before operation. LED E 㧔1㧕 RED WARNING LAMP
Ԙ This unit is designed exclusively for use with R410A. Do not use ޓޓ SELF DIAGNOSIS FUNCTION BY LED E
1 TIME FLASH CURRENT CUT
ޓany refrigerant other than R410A.
2 TIME FLASH TROUBLE OF OUTDOOR UNIT
ԙ To protect the compressor,turn on power for the air conditioner 3 TIME FLASH OVER CURRENT
ޓ6 hours before operation so as warm up sufficiently the dome 4 TIME FLASH TRANSMISSION ERROR ※used only at our factory
ޓtemperature of compressor. 5 TIME FLASH OVER HEAT OF COMPRESSOR
Ԛ Open the service valves of liquid pipe at first. Secondarily open 6 TIME FLASH ERROR OF SIGNAL TRANSMISSION
'11 • SCM-SM-110
8 TIME FLASH SENSOR ERROR
ޓthe one of gas pipe. Before you operate the unit,make sure again 㧔EXCEPT DISCHARGE PIPE SENSOR㧕
RWC000Z244
ޓthat the service valves are in open position. LIGHT ON OUTDOOR FAN MOTOR ERROR
ԛ Please note that the pressure valves detected at the charge port FOUR SEC LIGHT
ޓin the unit and the gas service valves are different during the AND DISCHARGE PIPE SENSOR ERROR
ޓcooling operation and the heating operation. High pressure is FOUR SEC OFF
ޓreplaced with the low pressure depending on whether it is in the
ޓcooling or heating operation.
CNS
SC-BIKN-E
142 -
Color Marks
Y㧛G G Mark Color
BK Black
U Va RD BL Blue
WH S㧛N 1
F 3
BK RD Red
RD J WH
HEAT 250V CNU 4
Y
M WH White
EXCHANGER 3.15A 5
BK L 6
BL Y Yellow
FMI
Y㧛G Yellow㧛Green
Power source
1 phase 220 - 240 V 50Hz
T
TO OUTDOOR UNIT
1
'11 • SCM-SM-110
2㧛N
POWER WIRES 1 2/N
RWA000Z227
3
SIGNAL WIRE 3
HEAT
EXCHANGER
SC-BIKN-E
Y/G G
U Va RD Color Marks
WH S/N 1
F 3
BK Mark Color
RD J WH
HEAT 250V CNU 4
Y
M BK Black
EXCHANGER 3.15A 5
BK L 6
BL
FMI
BL Blue
RD Red
Power source WH White
~220/230/240V 50Hz
T Y Yellow
TO OUTDOOR UNIT
1 Y/G Yellow/Green
2/N
POWER WIRES 1 2/N
'11 • SCM-SM-110
3
RWA000Z236
SIGNAL WIRE 3
HEAT
EXCHANGER
BL
Humidity sensor
Y
HD
CNY CNX CNM 1 3 4 5 6 ThI Room temp. sensor
CNU Th2,3 Heat exch. sensor
G
DS Diode stack
F Fuse
PRINTED T Terminal block
CIRCUIT Va Varistor
BOARD
Y/G
HEAT
F
㨪
EXCHANGER
L
Mark Color
-
250V 3.15A
144 -
BK Black
U Va BL Blue
S/N RD Red
DS
㨪 J
WH
Y
Y㧛G
White
Yellow
Yellow㧛Green
HEAT
EXCHANGER
CNS CNF CNE CNG
5 2 8 2 2 2
o o o
DISPLAY t t t
Y/G
WH
INTERFACE KIT
RD
BK
WIRELESS
1 2/N 3 T
RWA000Z226 A
'11 • SCM-SM-110
1 Phase
HD BACK-UP SW
Th3 Th2 ThI 220㧛230㧛240V 50Hz
̪
̪35,50
ONLY
TO OUTDOOR
UNIT
Model SRK71ZK-S
FMI Fan motor
DISPLAY
8
5
M LM1 SM1 Flap motor
WIRELESS RECEIVER CNE CNX1
BACK-UP SW LM1,2 Louver motor
PRINTED 5
M LM2 Th1 Room temp. sensor
Th1 t CIRCUIT Th21,2 Heat exch. sensor
BOARD 5
M SM1 Th3 Humidity sensor
CNX2 DS Diode stack
Th21 t
CNG DS
F Fuse
T Terminal block
Th22 t
Va Varistor
2
Th3 CNF
-
INTERFACE KIT 5
CNS
145 -
SC-BIKN-E
Color Marks
Y/G G Mark Color
BK Black
U Va RD
BL Blue
WH S/N 1
RD Red
BK
RD J F 3
HEAT
EXCHANGER
250V CNU 4 WH
Y
M WH White
3.15A 5 Y Yellow
BL
BK L 6 FMI
Y/G Yellow/Green
Power source
~220/230/240V 50Hz
T
TO OUTDOOR UNIT
1
'11 • SCM-SM-110
2/N 1 2/N
POWER WIRES
RWA000Z400
3
SIGNAL WIRE 3
HEAT
EXCHANGER
INTERFACE KIT 5
-
CNS
SC-BIKN-E
146 -
Color Marks
Y㧛G G Mark Color
BK Black
U Va RD BL Blue
WH S㧛N 1
F 3
BK RD Red
RD J WH
HEAT 250V CNU 4
YE
M WH White
EXCHANGER 3.15A 5
BK L 6
BL YE Yellow
FMI
Y㧛G Yellow㧛Green
Power source
1 phase 220 - 240 V 50Hz
T
TO OUTDOOR UNIT
1
'11 • SCM-SM-110
2㧛N
POWER WIRES 1 2/N
RWB000Z052
3
SIGNAL WIRE 3
HEAT
EXCHANGER
Model SRF50ZJX-S1
WIRELESS RECEIVER 10 DM1
CNE SM1,2 Flap motor
BACK-UP SW CNX1
AIR SELECTION SW PRINTED DM1 Damper motor
CIRCUIT 5 5
M DM2
BOARD DM2 Damper arm motor
Th1 t Th1 Room temp. sensor
5 5
DS M SM1 Th2 1,2 Heat exch. sensor
Th2 1 t CNX2 Th3 Humidity sensor
CNG
5 5
M SM2 DS Diode stack
F Fuse
Th2 2 t
T Terminal block
Va Varistor
2
Th3 CNF
INTERFACE KIT 5
-
CNS
SC-BIKN-E
147 -
Color Marks
Y/G G Mark Color
BK Black
U Va RD BL Blue
WH S/N 1
F 3
BK RD Red
RD J WH
HEAT 250V CNU 4
Y
M WH White
EXCHANGER 3.15A 5
BK L 6
BL
FMI
Y Yellow
Y/G Yellow/Green
Power source
∼220/230/240V 50Hz
T
TO OUTDOOR UNIT
1
2/N 1 2/N
POWER WIRES
'11 • SCM-SM-110
3
RWB000Z054
SIGNAL WIRE 3
HEAT
EXCHANGER
YE
BL
1 3 4 5 6
CNU
5
INTERFACE KIT
CNS
SC-BIKN-E
F
250V
DM 0.16A S㧛N WH
RD
M CNW U Va
1㨪 RD
L BK
F
250V 3.15A RD
J
FS WH
Y㧛G
-
PRINTED CIRCUIT G
WH
CNY BOARD
148 -
Y㧛G
WH
RD
BK
2 CNE CNG
BK
BK 8
OR
BK
BK
2 2 2 T
1 2/N 3
10 Power source
BK
'11 • SCM-SM-110
BL Blue Y㧛G Yellow㧛Green F Fuse Th2 Heat exch. sensor 1
RWA000Z230
Remote controller
TB2 Control PCB
WH FS
X X 1 CNB 1
WH 1 WH 1 RD
ThC t° BK WH CNI
Y Y 3
BL 2 WH 2 WH 2 RD
Y/GN
LED・2 LED・3 CNI2
WH
BL 3 BL 1 BK
1
Y/GN Y/GN CNH t° ThI-A
BK 2 BL 4 BL 2 BK
Power PCB 1
RD
1 CNH2
Y/GN
RD WH
Connecting line between Y/GN 7 CNW2
2 2
CNW3
[ ]
indoor unit and outdoor unit F200(3.15A) 3
RD
3 SW2 1 RD 5 RD 1 BK
RD 5 RD RD RD
1
Power circuit
4
RD
4
RD 6 RD 2 BK
t° ThI-R1
Power source line 1 2 WH 3 5 5 2
-
2
Signal line 3
3 BL 1 F201(3.15A) CNW1 BL
149 -
1 2
Earth BL 2 BL SW5 Y 7 Y 3 BK
1
CNW0 3 BL CNW4 CNN
3
Y/GN X4 3 t° ThI-R2
TB1 WH F203 F202 4 BL
4
BL
SW6 Y 4 Y 8 Y 4 BK
(0.16A) (1.0A) 5 BL
5
1 3 1 4 5 6 7 SW7 BK 9 BK 5 BK
5
CNR WH BR RD BL BR OR WH CNM t° ThI-R3
WH WH 1 BK 1 BK 6 BK 10 BK 6 BK
1
2 1 LM1 2 BK 2 BK CNC CNN2
CNR2 5 6 4 3 2
CNM3 3 BK 3 BK
2
WH BK
BL Y Y M 3
RD BL BR OR WH RD 4 BK 4 BK
4
5 BK 5 BK
5
M 5 6 4 3 2 1 BK 6 BK
DM 1∼
CNM4 LM2 2 BK 7 BK
6
RD BL BR OR WH WH
3 BK 8 BK
7
Option
M 8 +12 1
4 BK 9 BK
9 2 XR1 (Operation)
FMI M 5 BK 10 BK
10 CNJ CNT 3 (Heating)
XR2
BK BK
LM3
1 11
11 WH BL 4 XR3 (Compressor ON)
2 BK 12 BK
12 5 XR4 (Inspection)
M 3 BK 13 BK
13 6
4 BK 14 BK
14 XR5(Remote operation input:volt-free contact)
5 BK 15 BK
15
1 BK 16 BK
Notes 1. indicates wiring on site. LM4 16
PJA003Z340 B
2 BK 17 BK
'11 • SCM-SM-110
17
2. TB1 is the terminal block for heavy current(connecting line between M 3 BK 18 BK
18
4 BK 19 BK
indoor unit and outdoor unit), 5 BK 20 BK
19
Model FDEN50VD
CFI 1
t t t t
Trl
CNB ޓZ Connector
LM M
220㨺240V F Fuse
FMI 1 Fan motor㧔with thermostat㧕
OR
RD
BR
BL
P
RD
RD
BK
BK
BK
BK
BR
BR
BK
BK
BK
BK
BK
BK
C 19V 24V
Connecting line between TB1 1 2 3 4 5 CNW1 CNW2 1 2 3 4 5 6 1 2 Option LED2 Indication lamp㧔Green-Normal operation㧕
indoor unit and outdoor unit RD 5 CNJ WH WH BK CNN Y CNH +12 1
1 RD
F㧔3.15A㧕 WH 3
BK 2 XR1 㧔Operation㧕 LED3 Indication lamp㧔Red-Inspection㧕
SW5 XR2
Power source line 1 2 2 X6 X2
X4 LED2 LED3 SW2 CNT 3 㧔Heating㧕
Louver motor
WH
F㧔3.15A㧕 BL SW6
BL 4 XR3 㧔Compressor ON㧕 LM
Signal line 3 3
1
X1 X3 5 XR4 㧔Inspection㧕
CNW0 SW2 Remote controller communication address
Earth Y㧛GN RD CNR CNI CNB WH SW7 6
1 3 5 7 9 WH 1 3 BL 1 3 Control PCB XR5㧔Remote operation input : Plural units Master㧛Slave setting
volt-free contact㧕 SW5
CNM3 C UH H M L
WH
WH
BK
WH
SW6 Model capacity setting
WH
Wireless specification
RD
BR
BK
BL
Wired specification
X Y TB2 SW7-1 Operation check, Drain motor test run
CNB
AMP SW4 SW1 TB1 Terminal blockާPower source㧕㧔غmark㧕
CNF1
WH 5
Terminal blockާSignal line㧕㧔غmark㧕
LED2 LED3 LED4 TB2 Remote TB2
CNB2 controller
Y㧛GN X X
FMI 1 M WH Receiver PCB Thc Thc ThermistorާRemote controller㧕
1 Y Y t
Thl -A ThermistorާReturn air㧕
-
CNFI 1
WH
OR
OR
ThermistorާHeat exchanger㧕
150 -
'11 • SCM-SM-110
P Pink
Model FDUM50VF
DM Drain motor
F1~3 Fuse
FS Float switch
Remote controller Control PCB RD Reactor
ThC 1 L
WH t° Th I-R1
X X 1 CNB 2
RD LED · E2 Indication lamp (Green-Normal operation)
Y Y
BK
3 WH CNN
t° Y 3
Y
Indication lamp (Red-Inspection)
Th I-R2 LED · E3
TB2 LED • E2 LED • E3 Y
t°
L 4 Remote controller communication address
BK
SW2
CNWR2 CNW0 Power PCB 5
Connecting line between WH Y/GN 1 WH t° Th I-R3 SW5 Plural units Master/Slave setting
BK
indoor unit and outdoor unit RD RD 3
F1 (3.15A) 1 WH
1
6
1 2 WH SW2 SW6 Model capacity setting
WH 5 Power circuit 3 WH
2
Power source line 1 2 2 4 WH
3
Operation check, Drain motor test run
F2 (3.15A) CNW1 4 CNW2 1
BK SW7-1
Signal line 3 3 WH
5
6
WH
WH
5 WH CNH t° ThI-A
7 WH
6
BK 2
BK TB1 Terminal block (Powerce) ( mark)
Earth WH 1 CNW3 8 WH
7
SW5
TB1 9 WH
8
Terminal block (Signal line) ( mark)
Y/GN BL 3 WH 9 TB2
10 WH
10 RD
FS
SW6
-
BL RD
F3 2 Thermistor (Return air)
(2A) SW7 Th I-A
WH
Option Color Marks
+12 1
'11 • SCM-SM-110
sheet of remote controller in case that the total length is more than 100m.
4. Do not put remote controller line alongside power source line.
Sensor
Service valve
(Gas) (Tho-A)
Gas line (φ9.52)
(φ9.52)
Indoor unit
Check joint 4 way valve
Sensor Muffler
*1 (Tho-D)
Humidity Sensor Discharge Heat exchanger
-
sensor
152 -
(Th22)
(Th3) Sensor
(Tho-S)
'11 • SCM-SM-110
*1 Humidity sensor
SRK35ZJR-S, 35ZJ-S and SRF series only.
1 Sensor
(Ǿ9.52 or Ǿ12.7)
(Tho-A)
1
(Ǿ9.52 or Ǿ12.7)
2
Humidity 4way valve
sensor
(Th3) Indoor Unit
Heat exchanger
Sensor
(Th22)
Heat exchanger
Sensor Muffler
Sensor
-
(Th21)
(Tho-D) Discharge
153 -
Sensor Capillary
(Th1) Sensor
tube
(Tho-R)
Sensor
Compressor (Tho-S)
Suction Accumlator Accumlator
Service valve Electronic Receiver
(Liquid) expansion valve
(Ǿ6.35) EEVA
Strainer
(Ǿ6.35) EEVB
(Ǿ6.35) EEVC
'11 • SCM-SM-110
Liquid line Capillary
tube
1 Heat exchanger
(Ǿ9.52 or Ǿ12.7)
Sensor
1 (Tho-A)
(Ǿ9.52 or Ǿ12.7)
1 4way valve
(Ǿ9.52 or Ǿ12.7)
1
Humidity
Oil
sensor separator Capillary tube
(Th3) Indoor Unit
Sensor Sensor
(Th22) Sensor (Tho-S)
Heat (Tho-D)
exchanger
Discharge
-
Sensor
154 -
(Th21)
Compressor
Sensor Suction
(Th1) Accumlator Accumlator Sensor
Service valve Electronic
expansion valve (Tho-R)
(Liquid)
EEVA Receiver
(Ǿ6.35)
Strainer
EEVB
(Ǿ6.35)
EEVC
(Ǿ6.35)
EEVD
'11 • SCM-SM-110
Liquid line (Ǿ6.35) Capillary
tube
1 Gas line
Model 20, 25, 35 : Ǿ9.52
Model 50, 60 : Ǿ12.7
2 Humidity sensor
SRK50, 60ZJX-S1, SRK35ZJR-S, 35, 50ZJ-S and SRF series only.
Model SCM100ZJ-S1
*1 Service valve (Gas)
Gas line (φ9.52 or φ12.7 or φ15.88) Heat exchanger
*1 Thermistor
(φ9.52 or φ12.7 or φ15.88)
*1 (Tho-A)
(φ9.52 or φ12.7 or φ15.88)
*1 Muffler
(φ9.52 or φ12.7 or φ15.88)
(φ9.52 or φ12.7 4way valve
or φ15.88) *1 Hige preeure
sensor
(HPS)
Oil
separator
Indoor Unit
Sensor Thermistor
(Th22) Thermistor Strainer (Tho-S)
Heat (Tho-D)
exchanger
Discharge
Sensor
-
(Th21)
155 -
Humidity *2 Compressor
sensor
(Th3)
Sensor Suction
(Th1) Service valve Electronic Accumlator Accumlator
(Liquid) expansion valve
EEVA
Thermistor
(φ6.35) (Tho-R)
EEVB
(φ6.35)
EEVC
Strainer Strainer
(φ6.35)
EEVD Electronic
expansion valve
(φ6.35)
Strainer (EEV-H)
EEVE Receiver
'11 • SCM-SM-110
Liquid line (φ6.35) Capillary
tube
Model SCM125ZJ-S1
*1 Service valve (Gas)
Gas line (φ9.52 or φ12.7 or φ15.88)
*1 Heat exchanger
(φ9.52 or φ12.7 or φ15.88)
Thermistor
*1
(φ9.52 or φ12.7 or φ15.88) (Tho-A)
*1
(φ9.52 or φ12.7 or φ15.88)
Muffler
*1
(φ9.52 or φ12.7 or φ15.88)
4way valve
(φ9.52 or φ12.7 Hige preeure
or φ15.88) *1 sensor
(HPS)
Oil
separator
Indoor Unit
Sensor Thermistor
(Th22) Thermistor Strainer (Tho-S)
Heat (Tho-D)
exchanger
Discharge
Sensor
-
(Th21)
156 -
Humidity*2 Compressor
sensor
(Th3)
Sensor Suction
(Th1) Service valve Electronic Accumlator Accumlator
(Liquid) expansion valve
EEVA
Thermistor
(φ6.35)
(Tho-R)
EEVB
(φ6.35)
EEVC
Strainer Strainer
(φ6.35)
EEVD Electronic
expansion valve
(φ6.35)
(EEV-H)
EEVE Receiver
'11 • SCM-SM-110
(φ6.35)
Strainer EEVF
Liquid line (φ6.35) Capillary
tube
5. INSTALLATION MANUAL
5.1 Outdoor units RPC012A915A
(1) Models SCM40ZJ-S, 45ZJ-S
INSTALLATION MANUAL FOR OUTDOOR UNIT MULTI TYPE AIR CONDITIONER
R410A REFRIGERANT USED
• This installation manual deals with outdoor units and general installation specifications only. For indoor units, refer to page 173 to 198.
the respective installation manuals supplied with the units.
• When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height differences between
indoor and outdoor units, power supply voltage and etc.) and installation spaces. • Do not ins
below.
SAFETY PRECAUTIONS • Locations
the outdo
• Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it during the installation • Keep the installation manual together with owner’s manual at a place where any user can read
• Locations
work in order to protect yourself. at any time. Moreover if necessary, ask to hand them to a new user.
directly to
• The precautionary items mentioned below are distinguished into two levels, WARNING and • For installing qualified personnel, take precautions in respect to themselves by using suitable plant etc.
CAUTION . protective clothing, groves, etc., and then perform the installation works. • Locations
WARNING : Wrong installation would cause serious consequences such as injuries or death. • Please pay attention not to fall down the tools, etc. when installing the unit at the high position. transmitte
CAUTION : Wrong installation might cause serious consequences depending on • If unusual noise can be heard during operation, consult the dealer. • Locations
circumstances. • The meanings of “Marks” used here are shown as follows: by the ou
Both mentions the important items to protect your health and safety so strictly follow them by the place
Never do it under any Always do it according to the • Locations
any means. circumstances. instruction.
• Be sure to confirm no anomaly on the equipment by commissioning after completed installation is placed
• Locations
and explain the operating methods as well as the maintenance methods of this equipment to
It can affec
the user according to the owner’s manual. • Do not ins
of combus
WARNING If leaked ga
• Installation must be carried out by the qualified • Use the prescribed pipes, flare nuts and tools for • This appliance must be connected to main power • Do not ins
installer. R410A. supply by means of a circuit breaker or switch sulfurous
If you install the system by yourself, it may cause serious Using existing parts (for R22 or R407C) can cause the unit (fuse:25A) with a contact separation of at least 3mm. thinner an
trouble such as water leaks, electric shocks, fire and failure and serious accidents due to burst of the refrigerant • Arrange the wiring in the control box so that it cannot collect, or
personal injury, as a result of a system malfunction. Do not circuit. be pushed up further into the box. Install the service
carry out the installation and maintenance work except the • Tighten the flare nut by torque wrench with specified panel correctly.
by qualified installer. method. Incorrect installation may result in overheating and fire. Check before
• Install the system in full accordance with the If the flare nut were tightened with excess torque, this may • Use the prescribed cables for electrical connection,
installation manual. cause burst and refrigerant leakage after a long period. tighten the cables securely in terminal block and • Model name and
Incorrect installation may cause bursts, personal injury, • Do not open the operation valves for liquid line and relieve the cables correctly to prevent overloading the • Refrigerant piping
water leaks, electric shocks and fire. gas line until completed refrigerant piping work, air terminal blocks. • Piping, wiring and
• Be sure to use only for household and residence. tightness test and evacuation. Loose connections or cable mountings can cause
If this appliance is installed in inferior environment such as If the compressor is operated in state of opening operation anomalous heat production or fire. • Indoor unit installa
machine shop and etc., it can cause malfunction. valves before completed connection of refrigerant piping • Be sure to fix up the service panels.
• When installing in small rooms, take prevention work, air can be sucked into refrigerant circuit, which can Incorrect fixing can cause electric shocks or fire due to
measures not to exceed the density limit of refrigerant cause bust or personal injury due to anomalously high intrusion of dust or water. Accessories f
in the event of leakage, referred by the formula pressure in the refrigerant. • Be sure to switch off the power supply in the event of
(accordance with ISO5149). • The electrical installation must be carried out by the installation, inspection or servicing. 1 Grommet (Heat
If the density of refrigerant exceeds the limit, please consult qualified electrician in accordance with “the norm for If the power supply is not shut off, there is a risk of electric 2 Drain elbow (He
the dealer and install the ventilation system, otherwise lack electrical work” and “national wiring regulation”, and shocks, unit failure or personal injury due to the unexpected
of oxygen can occur, which can cause serious accident. the system must be connected to the dedicated start of fan.
• Use the original accessories and the specified circuit. • Stop the compressor before removing the pipe after
components for installation. Power supply with insufficient capacity and incorrect shutting the service valve on pump down work.
If parts other than those prescribed by us are used, It may function done by improper work can cause electric shocks If the pipe is removed when the compressor is in operation
cause water leaks, electric shocks, fire and personal injury. and fire. with the service valve open, air would be mixed in the
• Install the unit in a location with good support. • Be sure to shut off the power before starting electrical refrigeration circuit and it could cause explosion and injuries 1 SELECT
Unsuitable installation locations can cause the unit to fall work. due to abnormal high pressure in the cooling cycle.
and cause material damage and personal injury. Failure to shut off the power can cause electric shocks, unit • Only use prescribed optional parts. The installation
• Ensure the unit is stable when installed, so that it can
withstand earthquakes and strong winds.
failure or incorrect function of equipment.
• Be sure to use the cables conformed to safety
must be carried out by the qualified installer.
If you install the system by yourself, it can cause serious
Install at
Unsuitable installation locations can cause the unit to fall standard and cable ampacity for power distribution trouble such as water leaks, electric shocks, fire.
and cause material damage and personal injury. work. • Be sure to wear protective goggles and gloves while ● Where th
• Ventilate the working area well in the event of Unconformable cables can cause electric leak, anomalous at work. ● Where ra
refrigerant leakage during installation. heat production or fire. • Earth leakage breaker must be installed. ● Also, whe
If the refrigerant comes into contact with naked flames, If the earth leakage breaker is not installed, it can cause
poisonous gas is produced. electric shocks. a location
enhance
• Ensure that no air enters in the refrigerant circuit • Do not bundling, winding or processing for the power • Do not perform any change of protective device itself
● Where bl
when the unit is installed and removed. cord. Or, do not deforming the power plug due to or its setup condition.
If air enters in the refrigerant circuit, the pressure in the tread it. The forced operation by short-circuiting protective device of ● Where th
refrigerant circuit becomes too high, which can cause burst This may cause fire or heating. pressure switch and temperature controller or the use of ● Where th
and personal injury. • Do not run the unit with removed panels or non specified component can cause fire or burst. ● Where w
• Do not processing, splice the power cord, or share a protections.
socket with other power plugs. Touching rotating equipments, hot surfaces or high voltage ※ Please a
This may cause fire or electric shock due to defecting parts can cause personal injury due to entrapment, burn or ● Where th
contact, defecting insulation and over-current etc. electric shocks. locations
CAUTION ● Where th
● Where th
• Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to
short-circuiting.
• Use the circuit breaker of correct capacity. Circuit Insufficient space can result in accident such as personal • When perform the air conditioner operation (cooling
breaker should be the one that disconnect all poles
under over current.
injury due to falling from the installation place.
• Take care when carrying the unit by hand.
or drying operation) in which ventilator is installed in
the room. In this case, using the air conditioner in
Installatio
Using the incorrect one could cause the system failure and If the unit weights more than 20kg, it must be carried by two parallel with the ventilator, there is the possibility that
fire. or more persons. Do not carry by the plastic straps, always drain water may backflow in accordance with the
① Ancho
• Install isolator or disconnect switch on the power use the carry handle when carrying the unit by hand. Use room lapse into the negative pressure status.
supply wiring in accordance with the local codes and gloves to minimize the risk of cuts by the aluminum fins. Therefore, set up the opening port such as 1
regulations. • Dispose of any packing materials correctly. incorporate the air into the room that may appropriate
The isolator should be locked in OFF state in accordance Any remaining packing materials can cause personal injury to ventilation (For example; Open the door a little). In
with EN60204-1. as it contains nails and wood. And to avoid danger of addition, just as above, so set up the opening port if
290
• After maintenance, all wiring, wiring ties and the like, suffocation, be sure to keep the plastic wrapper away from the room lapse into negative pressure status due to
should be returned to their original state and wiring children and to dispose after tear it up. register of the wind for the high rise apartment etc.
route, and the necessary clearance from all metal • Be sure to insulate the refrigerant pipes so as not to
parts should be secured. condense the ambient air moisture on them.
• Secure a space for installation, inspection and Insufficient insulation can cause condensation, which can 20
maintenance specified in the manual. lead to moisture damage on the ceiling, floor, furniture and
any other valuables.
• Do not install the unit in the locations listed below. • Locations where any machines which generate high • Locations with any obstacles which can prevent inlet and ● In installi
• Locations where carbon fiber, metal powder or any frequency harmonics are used. outlet air of the unit.
● The prot
powder is floating. • Locations with salty atmospheres such as coastlines. • Locations where short circuit of air can occur (in case of
• Locations where any substances that can affect the unit • Locations with heavy snow (If installed, be sure to provide multiple units installation). ● Securely
such as sulphide gas, chloride gas, acid and alkaline can base flame and snow hood mentioned in the manual). • Locations where strong air blows against the air outlet of ● Refer to
occur. • Locations where the unit is exposed to chimney smoke. outdoor unit.
• Vehicles and ships. • Locations at high altitude (more than 1000m high). • Locations where something located above the unit could ● Install th
• Locations where cosmetic or special sprays are often • Locations with ammonic atmospheres. fall.
used. • Locations where heat radiation from other heat source can It can cause remarkable decrease in performance, corrosion
Improper
• Locations with direct exposure of oil mist and steam such affect the unit. and damage of components, malfunction and fire.
as kitchen and machine plant. • Locations without good air circulation.
- 157 -
12 Intake
may appropriate Fasten with bolts
door a little). In (M10-12)
opening port if
290
314
340
status due to
partment etc.
prevent inlet and ● In installing the unit, fix the unit’s legs with bolts specified on the left.
● The protrusion of an anchor bolt on the front side must be kept within 15 mm.
occur (in case of
● Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.
t the air outlet of ● Refer to the above illustrations for information regarding concrete foundations.
ve the unit could ● Install the unit in a level area. (With a gradient of 5 mm or less.)
rmance, corrosion
Improper installation can result in a compressor failure, broken piping within the unit and abnormal noise generation.
and fire.
- 158 -
A
Liquid side 9.1dia. If a conventional flare tool is used, please use copper pipe gauge or a similar
BEWAR
Press Gas side instrument to check protrusion so that you can keep measurement B to a correct value. 7 REFRIG
Remove 9.52 : 13.2dia
Indoor unit
Connection unit B
Outdoor
Gas Leakage Test [Limit]
Liquid side unit A
●Ensure that there are no gas leaks from the pipe one indoor unit MAX 25m
Gas side piping length
all indoor unit MAX 30m
joints by using a leak detector or soap water.
indoor
unit
MAX 15m
○Connect the pipes on both liquid and gas sides. indoor
hight difference
EARTHIN
MAX outdoor
unit unit
○Tighten the nuts to the following torque. 25m
Liquid side : 14.0∼18.0N・m (1.4∼1.8kgf・m)
Gas side ( 9.52): 33.0∼42.0N・m (3.3∼4.2kgf・m) MAX 15m
indoor
○ Earth work sh
unit shock and no
length of chargeless ○ The connectio
refrigerant pipe 30m dangerous fai
Town gas pip
- 159 -
4 AIR PURGING NOTE : Fully open the operation valves (on both liquid and gas sides) after completing air purging.
● Since the system uses service ports differing in diameter from those found ● Please use an anti-reverse flow type vacuum pump adapter so as to prevent
on the conventional models, a charge hose (for R22) presently in use is not vacuum pump oil from running back into the system. Oil running back into
applicable. Please use one designed specifically for R410A. an air-conditioning system may cause the refrigerant cycle to break down.
● Remove the cap on both gas and liquid sides before starting operation. ● Conduct air purging for all connected indoor units.
● After completing the operation, do not forget to tighten the cap (gas may leak).
Operation Valve Compound pressure gauge
Cap Pressure gauge
Operation Valve
Procedure (two-way valve) -0.1MPa
Gauge Manifold
(Designed specifically for R410A)
(-76cmHg)
(1) Secure all flare nuts on both indoor and outdoor sides to Handle Lo Handle Hi.
prevent leaks from the pipes.
Operation Valve Charge hose
(2) Connect the operation valves, charge hose, manifold (three-way valve) (Designed specifically for R410A)
valve and vacuum pump as shown in the right figure.
Vacuum pump adapter
(3) Fully open the handle Lo for the manifold valve, and Operation Valve (Anti-reverse flow type)
pump a vacuum for 15 minutes. Ensure that the meter Cap (Designed specifically for R410A)
Operation valve
is indicating -0.1MPa (-76cmHg).
for room B Vacuum pump
(4) After vacuuming, fully open the operation valve (both Check joint Charge hose
unit A unit B
liquid and gas sides) with a hexagon wrench. Operation valve
(Designed specifically for R410A)
for room A
rminal block Securely tighten the operation valve cap and the check joint blind nut after adjustment.
Operation valve size Operation valve cap Check joint blind nut
(mm) tightening torque (N·m) tightening torque (N·m)
Open Open
φ6.35 (1/4")
(5) Remove the charge hose from service port. 20 30 10 12
φ9.52 (3/8")
(6) Repeat the above steps (1) ~ (5) for all connected indoor units.
(7) Ensure that there are no gas leaks from the joints in the indoor and outdoor units.
- 160 - RPC012A915A
RPC012A916C
WARNING
• Installation must be carried out by the qualified • Use the prescribed pipes, flare nuts and tools for • This appliance must be connected to main power Check before
installer. R410A. supply by means of a circuit breaker or switch
If you install the system by yourself, it may cause serious Using existing parts (for R22 or R407C) can cause the unit (fuse:25A) with a contact separation of at least 3mm. • Model name and p
trouble such as water leaks, electric shocks, fire and failure and serious accidents due to burst of the refrigerant • Arrange the wiring in the control box so that it cannot • Refrigerant piping
personal injury, as a result of a system malfunction. Do not circuit. be pushed up further into the box. Install the service • Piping, wiring and
carry out the installation and maintenance work except the • Tighten the flare nut by torque wrench with specified panel correctly. • Indoor unit installa
by qualified installer. method. Incorrect installation may result in overheating and fire.
• Install the system in full accordance with the If the flare nut were tightened with excess torque, this may • Use the prescribed cables for electrical connection,
installation manual. cause burst and refrigerant leakage after a long period. tighten the cables securely in terminal block and Accessories f
Incorrect installation may cause bursts, personal injury, • Do not open the operation valves for liquid line and relieve the cables correctly to prevent overloading the
water leaks, electric shocks and fire. gas line until completed refrigerant piping work, air terminal blocks. 1 Grommet (Heat
• Be sure to use only for household and residence. tightness test and evacuation. Loose connections or cable mountings can cause 2 Drain elbow (He
If this appliance is installed in inferior environment such as If the compressor is operated in state of opening operation anomalous heat production or fire. Variable diamete
machine shop and etc., it can cause malfunction. valves before completed connection of refrigerant piping • Be sure to fix up the service panels. 3
φ9.52⇒φ12.7
• When installing in small rooms, take prevention work, air can be sucked into refrigerant circuit, which can Incorrect fixing can cause electric shocks or fire due to
measures not to exceed the density limit of refrigerant cause bust or personal injury due to anomalously high intrusion of dust or water. Note: Provide flare nut
in the event of leakage, referred by the formula pressure in the refrigerant. • Be sure to switch off the power supply in the event of diameter joint (fo
(accordance with ISO5149). • The electrical installation must be carried out by the installation, inspection or servicing.
If the density of refrigerant exceeds the limit, please consult qualified electrician in accordance with “the norm for If the power supply is not shut off, there is a risk of electric
the dealer and install the ventilation system, otherwise lack electrical work” and “national wiring regulation”, and shocks, unit failure or personal injury due to the unexpected
of oxygen can occur, which can cause serious accident. the system must be connected to the dedicated start of fan. CAUTION
• Use the original accessories and the specified circuit. • Stop the compressor before removing the pipe after
components for installation. Power supply with insufficient capacity and incorrect shutting the service valve on pump down work.
If parts other than those prescribed by us are used, It may function done by improper work can cause electric shocks If the pipe is removed when the compressor is in operation
cause water leaks, electric shocks, fire and personal injury. and fire. with the service valve open, air would be mixed in the
• Install the unit in a location with good support. • Be sure to shut off the power before starting electrical refrigeration circuit and it could cause explosion and injuries 1 SELECT
Unsuitable installation locations can cause the unit to fall work. due to abnormal high pressure in the cooling cycle.
and cause material damage and personal injury. Failure to shut off the power can cause electric shocks, unit • Only use prescribed optional parts. The installation
• Ensure the unit is stable when installed, so that it can
withstand earthquakes and strong winds.
failure or incorrect function of equipment.
• Be sure to use the cables conformed to safety
must be carried out by the qualified installer.
If you install the system by yourself, it can cause serious
Install at
Unsuitable installation locations can cause the unit to fall standard and cable ampacity for power distribution trouble such as water leaks, electric shocks, fire.
and cause material damage and personal injury. work. • Be sure to wear protective goggles and gloves while ● Where th
• Ventilate the working area well in the event of Unconformable cables can cause electric leak, anomalous at work. ● Where ra
refrigerant leakage during installation. heat production or fire. • Earth leakage breaker must be installed. ● Also, whe
If the refrigerant comes into contact with naked flames, If the earth leakage breaker is not installed, it can cause
poisonous gas is produced. electric shocks. a location
enhance
• Ensure that no air enters in the refrigerant circuit • Do not bundling, winding or processing for the power • Do not perform any change of protective device itself
● Where bl
when the unit is installed and removed. cord. Or, do not deforming the power plug due to or its setup condition.
If air enters in the refrigerant circuit, the pressure in the tread it. The forced operation by short-circuiting protective device of ● Where th
refrigerant circuit becomes too high, which can cause burst This may cause fire or heating. pressure switch and temperature controller or the use of ● Where th
and personal injury. • Do not run the unit with removed panels or non specified component can cause fire or burst. ● Where w
• Do not processing, splice the power cord, or share a protections.
socket with other power plugs. Touching rotating equipments, hot surfaces or high voltage ※ Please a
This may cause fire or electric shock due to defecting parts can cause personal injury due to entrapment, burn or ● Where th
contact, defecting insulation and over-current etc. electric shocks. locations
CAUTION ● Where th
● Where th
• Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to
short-circuiting.
• Use the circuit breaker of correct capacity. Circuit Insufficient space can result in accident such as personal • When perform the air conditioner operation (cooling
breaker should be the one that disconnect all poles
under over current.
injury due to falling from the installation place.
• Take care when carrying the unit by hand.
or drying operation) in which ventilator is installed in
the room. In this case, using the air conditioner in
Installatio
Using the incorrect one could cause the system failure and If the unit weights more than 20kg, it must be carried by two parallel with the ventilator, there is the possibility that
fire. or more persons. Do not carry by the plastic straps, always drain water may backflow in accordance with the
① Anchor
• Install isolator or disconnect switch on the power use the carry handle when carrying the unit by hand. Use room lapse into the negative pressure status.
supply wiring in accordance with the local codes and gloves to minimize the risk of cuts by the aluminum fins. Therefore, set up the opening port such as 1
regulations. • Dispose of any packing materials correctly. incorporate the air into the room that may appropriate
The isolator should be locked in OFF state in accordance Any remaining packing materials can cause personal injury to ventilation (For example; Open the door a little). In
with EN60204-1. as it contains nails and wood. And to avoid danger of addition, just as above, so set up the opening port if
290
• After maintenance, all wiring, wiring ties and the like, suffocation, be sure to keep the plastic wrapper away from the room lapse into negative pressure status due to
should be returned to their original state and wiring children and to dispose after tear it up. register of the wind for the high rise apartment etc.
route, and the necessary clearance from all metal • Be sure to insulate the refrigerant pipes so as not to
parts should be secured. condense the ambient air moisture on them.
• Secure a space for installation, inspection and Insufficient insulation can cause condensation, which can 20
maintenance specified in the manual. lead to moisture damage on the ceiling, floor, furniture and
any other valuables.
• Do not install the unit in the locations listed below. • Locations where any machines which generate high • Locations with any obstacles which can prevent inlet and ● In installi
• Locations where carbon fiber, metal powder or any frequency harmonics are used. outlet air of the unit.
● The protr
powder is floating. • Locations with salty atmospheres such as coastlines. • Locations where short circuit of air can occur (in case of
• Locations where any substances that can affect the unit • Locations with heavy snow (If installed, be sure to provide multiple units installation). ● Securely
such as sulphide gas, chloride gas, acid and alkaline can base flame and snow hood mentioned in the manual). • Locations where strong air blows against the air outlet of ● Refer to
occur. • Locations where the unit is exposed to chimney smoke. outdoor unit.
• Vehicles and ships. • Locations at high altitude (more than 1000m high). • Locations where something located above the unit could ● Install the
• Locations where cosmetic or special sprays are often • Locations with ammonic atmospheres. fall.
used. • Locations where heat radiation from other heat source can It can cause remarkable decrease in performance, corrosion
Improper
• Locations with direct exposure of oil mist and steam such affect the unit. and damage of components, malfunction and fire.
as kitchen and machine plant. • Locations without good air circulation.
- 161 -
012A916C CAUTION
• Do not install the outdoor unit in the locations listed handled. • Do not use any materials other than a fuse with the
CONDITIONER below. Corrosive gas can cause corrosion of heat exchanger, correct rating in the location where fuses are to be
RANT USED • Locations where discharged hot air or operating sound of breakage of plastic parts and etc. And combustible gas can used.
the outdoor unit can bother neighborhood. cause fire. Connecting the circuit with copper wire or other metal
ied with the units. • Locations where outlet air of the outdoor unit blows • Do not install nor use the system close to the thread can cause unit failure and fire.
es between directly to plants. The outlet air can affect adversely to the equipment that generates electromagnetic fields or • Do not touch any buttons with wet hands.
plant etc. high frequency harmonics. It can cause electric shocks.
• Locations where vibration can be amplified and Equipment such as inverters, standby generators, medical • Do not touch any refrigerant pipes with your hands
transmitted due to insufficient strength of structure. high frequency equipments and telecommunication when the system is in operation.
• Locations where vibration and operation sound generated equipments can affect the system, and cause malfunctions During operation the refrigerant pipes become extremely hot
any user can read by the outdoor unit can affect seriously (on the wall or at and breakdowns. The system can also affect medical or extremely cold depending the operating condition, and it
the place near bed room). equipment and telecommunication equipment, and obstruct can cause burn injury or frost injury.
by using suitable • Locations where an equipment affected by high harmonics its function or cause jamming. • Do not touch the suction or aluminum fin on the
is placed (TV set or radio receiver is placed within 1m). • Do not install the outdoor unit in a location where outdoor unit.
the high position. • Locations where drainage cannot run off safely. insects and small animals can inhabit. This may cause injury.
It can affect surrounding environment and cause a claim. Insects and small animals can enter the electric parts and • Do not put anything on the outdoor unit and operating
• Do not install the unit near the location where leakage cause damage or fire. Instruct the user to keep the unit.
of combustible gases can occur. surroundings clean. This may cause damage the objects or injury due to falling
If leaked gases accumulate around the unit, it can cause fire. • Do not use the base flame for outdoor unit which is to the object.
• Do not install the unit where corrosive gas (such as corroded or damaged due to long periods of • Do not use the unit for special purposes such as
sulfurous acid gas etc.) or combustible gas (such as operation. storing foods, cooling precision instruments and
thinner and petroleum gases) can accumulate or Using an old and damage base flame can cause the unit preservation of animals, plants or art.
collect, or where volatile combustible substances are falling down and cause personal injury. • Do not clean up the unit with water.
a risk of electric
o the unexpected
CAUTION ● This model requires a minimum of 2 indoor units.
the pipe after
wn work.
or is in operation
mixed in the
osion and injuries 1 SELECTION OF INSTALLATION LOCATION
ng cycle.
he installation
staller.
cause serious
Install at location that meets the following conditions after getting approval from the customer.
ks, fire.
Where the following installation space is available, and where air does not gather. ① Installation Space (on a flat surface)
d gloves while ●
● Where rain and sunlight do not directly hit the unit, and where there is enough air circulation.
ed. ● Also, where the unit cannot be buried by snow. ◎Blowing out port and suction port on the back side
, it can cause of the unit can be installed at a distance of 10cm
a location which can sustain the weight of the unit, and where noises and vibrations are not
from walls.
enhanced.
ive device itself In case the barrier is 1.2m or above in height,
● Where blasts of cold or hot air and noise do not bother the neighbors.
or is overhead, the sufficient space between
otective device of ● Where the unit does not receive heat radiation from other heat sources.
the unit and wall shall be secured.
r or the use of ● Where there are no obstructions (animals, plants, etc.) to the suction inlet and blowing outlet.
r burst. ● Where water may drain out. ○When the unit is installed, the space of the following
※ Please avoid the following locations. dimension and above shall be secured.
● Where there is constant exposure to harsh winds such as the top floors of a building. Also,
locations with exposure to salty air.
● Where there are oil splashes, vapor, and smoke. Air intake
10cm MIN
● Where there are possibilities of flammable gas leaks. 10cm
MIN
shocks due to No obstacles
(Service space
for electrical
ration (cooling
parts)
r is installed in
onditioner in
Installation Air
intake
e possibility that
nce with the
① Anchor bolt fixed position ② Notabilia for installation Air outlet 60cm MIN
status. 50
ch as
12
12 Intake
may appropriate Fasten with bolts
door a little). In (M10-12)
opening port if
290
314
340
status due to
partment etc.
prevent inlet and ● In installing the unit, fix the unit’s legs with bolts specified on the left.
● The protrusion of an anchor bolt on the front side must be kept within 15 mm.
occur (in case of
● Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.
t the air outlet of ● Refer to the above illustrations for information regarding concrete foundations.
ve the unit could ● Install the unit in a level area. (With a gradient of 5 mm or less.)
rmance, corrosion
Improper installation can result in a compressor failure, broken piping within the unit and abnormal noise generation.
and fire.
- 162 -
Liquid side 9.1dia. If a conventional flare tool is used, please use copper pipe gauge or a similar
Press A instrument to check protrusion so that you can keep measurement B to a correct value.
Gas side [Correct conn
Remove 9.52 : 13.2dia
12.7 : 16.2dia.
Measurement B
○Remove the flared nuts. ○Install the removed flared nuts to the pipes
(on both liquid and gas sides) to be connected, then flare the pipes.
CAUTION CAUTION
Indoor unit
Do not apply excess torque to the flared nuts. Do not apply refrigerating machine
Flaring
Otherwise, the flared nuts may crack depending oil to the flared surface. block Copper pipe unit C
on the conditions and refrigerant leak may occur.
unit B
Connection unit A
Outdoor
Gas Leakage Test [Limit]
Liquid side
●Ensure that there are no gas leaks from the pipe one indoor unit MAX 25m
Gas side piping length
all indoor unit MAX 40m
joints by using a leak detector or soap water.
indoor
unit
- 163 -
4 AIR PURGING NOTE : Fully open the operation valves (on both liquid and gas sides) after completing air purging.
● Since the system uses service ports differing in diameter from those found ● Please use an anti-reverse flow type vacuum pump adapter so as to prevent
on the conventional models, a charge hose (for R22) presently in use is not vacuum pump oil from running back into the system. Oil running back into
applicable. Please use one designed specifically for R410A. an air-conditioning system may cause the refrigerant cycle to break down.
● Remove the cap on both gas and liquid sides before starting operation. ● Conduct air purging for all connected indoor units.
● After completing the operation, do not forget to tighten the cap (gas may leak).
Operation Valve Compound pressure gauge
Cap Pressure gauge
Operation Valve
Procedure (two-way valve) -0.1MPa
Gauge Manifold
(Designed specifically for R410A)
(-76cmHg)
(1) Secure all flare nuts on both indoor and outdoor sides to Handle Lo Handle Hi.
prevent leaks from the pipes.
Operation Valve Charge hose
(2) Connect the operation valves, charge hose, manifold (three-way valve) (Designed specifically for R410A)
valve and vacuum pump as shown in the right figure.
Operation valve Vacuum pump adapter
(3) Fully open the handle Lo for the manifold valve, and Operation Valve (Anti-reverse flow type)
for room C
pump a vacuum for 15 minutes. Ensure that the meter Cap (Designed specifically for R410A)
Operation valve
is indicating -0.1MPa (-76cmHg).
for room B Vacuum pump
(4) After vacuuming, fully open the operation valve (both Check joint Charge hose
unit A unit B unit C
liquid and gas sides) with a hexagon wrench. Operation valve
(Designed specifically for R410A)
for room A
rminal block Securely tighten the operation valve cap and the check joint blind nut after adjustment.
Operation valve size Operation valve cap Check joint blind nut
(mm) tightening torque (N·m) tightening torque (N·m)
Open Open
φ6.35 (1/4")
(5) Remove the charge hose from service port. 20 30
φ9.52 (3/8") 10 12
(6) Repeat the above steps (1) ~ (5) for all connected indoor units.
3
(7) Ensure that there are no gas leaks from the joints in the indoor and outdoor units. φ12.7 (1/2") 25 35
RPC012A916C
- 164 -
*/45"--"5*0/."/6"-'03065%0036/*5 .6-5*5:1&"*3$0/%*5*0/&3
3"3&'3*(&3"/564&% t%POPUJOTU
CFMPX
refer to page173 to 208.
t5IJTJOTUBMMBUJPONBOVBMEFBMTXJUIPVUEPPSVOJUTBOEHFOFSBMJOTUBMMBUJPOTQFDJmDBUJPOTPOMZ'PSJOEPPSVOJUT
SFGFSUPUIFSFTQFDUJWFJOTUBMMBUJPONBOVBMTTVQQMJFEXJUIUIFVOJUT t-PDBUJPOT
t8IFOJOTUBMMUIFVOJU
CFTVSFUPDIFDLXIFUIFSUIFTFMFDUJPOPGJOTUBMMBUJPOQMBDF
QPXFSTVQQMZTQFDJmDBUJPOT
VTBHFMJNJUBUJPO QJQJOHMFOHUI
IFJHIUEJGGFSFODFTCFUXFFO UIFPVUEPP
JOEPPSBOEPVUEPPSVOJUT
QPXFSTVQQMZWPMUBHFBOEFUD
BOEJOTUBMMBUJPOTQBDFT t-PDBUJPOT
EJSFDUMZUP
4"'&5:13&$"65*0/4 QMBOUFUD
t-PDBUJPOT
t3FBEUIFi4"'&5:13&$"65*0/4wDBSFGVMMZmSTUPGBMMBOETUSJDUMZGPMMPXJUEVSJOHUIFJOTUBMMBUJPO t,FFQUIFJOTUBMMBUJPONBOVBMUPHFUIFSXJUIPXOFSTNBOVBMBUBQMBDFXIFSFBOZVTFSDBOSFBE USBOTNJUUF
XPSLJOPSEFSUPQSPUFDUZPVSTFMG BUBOZUJNF.PSFPWFSJGOFDFTTBSZ
BTLUPIBOEUIFNUPBOFXVTFS t-PDBUJPOT
8"3/*/(
t5IFQSFDBVUJPOBSZJUFNTNFOUJPOFECFMPXBSFEJTUJOHVJTIFEJOUPUXPMFWFMT
BOE t'PSJOTUBMMJOHRVBMJmFEQFSTPOOFM
UBLFQSFDBVUJPOTJOSFTQFDUUPUIFNTFMWFTCZVTJOHTVJUBCMF CZUIFPVU
$"65*0/
QSPUFDUJWFDMPUIJOH
HSPWFT
FUD
BOEUIFOQFSGPSNUIFJOTUBMMBUJPOXPSLT UIFQMBDF
8"3/*/(
8SPOHJOTUBMMBUJPOXPVMEDBVTFTFSJPVTDPOTFRVFODFTTVDIBTJOKVSJFTPSEFBUI t1MFBTFQBZBUUFOUJPOOPUUPGBMMEPXOUIFUPPMT
FUDXIFOJOTUBMMJOHUIFVOJUBUUIFIJHIQPTJUJPO t-PDBUJPOT
$"65*0/
8SPOHJOTUBMMBUJPONJHIUDBVTFTFSJPVTDPOTFRVFODFTEFQFOEJOHPO t*GVOVTVBMOPJTFDBOCFIFBSEEVSJOHPQFSBUJPO
DPOTVMUUIFEFBMFS JTQMBDFE
DJSDVNTUBODFT t5IFNFBOJOHTPGi.BSLTwVTFEIFSFBSFTIPXOBTGPMMPXT t-PDBUJPOT
#PUINFOUJPOTUIFJNQPSUBOUJUFNTUPQSPUFDUZPVSIFBMUIBOETBGFUZTPTUSJDUMZGPMMPXUIFNCZ *UDBOBGGFDU
/FWFSEPJUVOEFSBOZ "MXBZTEPJUBDDPSEJOHUPUIF t%POPUJOTU
BOZNFBOT DJSDVNTUBODFT JOTUSVDUJPO PGDPNCVT
t#FTVSFUPDPOmSNOPBOPNBMZPOUIFFRVJQNFOUCZDPNNJTTJPOJOHBGUFSDPNQMFUFEJOTUBMMBUJPO *GMFBLFEHB
BOEFYQMBJOUIFPQFSBUJOHNFUIPETBTXFMMBTUIFNBJOUFOBODFNFUIPETPGUIJTFRVJQNFOUUP t%POPUJOTU
UIFVTFSBDDPSEJOHUPUIFPXOFSTNBOVBM TVMGVSPVTB
UIJOOFSBOE
8"3/*/( DPMMFDU
PS
t*OTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFE t6TFUIFQSFTDSJCFEQJQFT
nBSFOVUTBOEUPPMTGPS t5IJTBQQMJBODFNVTUCFDPOOFDUFEUPNBJOQPXFS
JOTUBMMFS 3" TVQQMZCZNFBOTPGBDJSDVJUCSFBLFSPSTXJUDI $IFDLCFGPSF
*GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUNBZDBVTFTFSJPVT 6TJOHFYJTUJOHQBSUT GPS3PS3$
DBODBVTFUIFVOJU GVTF"
XJUIBDPOUBDUTFQBSBUJPOPGBUMFBTUNN
USPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSFBOE GBJMVSFBOETFSJPVTBDDJEFOUTEVFUPCVSTUPGUIFSFGSJHFSBOU t"SSBOHFUIFXJSJOHJOUIFDPOUSPMCPYTPUIBUJUDBOOPU t.PEFMOBNFBOEQ
QFSTPOBMJOKVSZ
BTBSFTVMUPGBTZTUFNNBMGVODUJPO%POPU DJSDVJU CFQVTIFEVQGVSUIFSJOUPUIFCPY*OTUBMMUIFTFSWJDF t3FGSJHFSBOUQJQJOH
DBSSZPVUUIFJOTUBMMBUJPOBOENBJOUFOBODFXPSLFYDFQUUIF t5JHIUFOUIFnBSFOVUCZUPSRVFXSFODIXJUITQFDJmFE QBOFMDPSSFDUMZ t1JQJOH
XJSJOHBOE
CZRVBMJmFEJOTUBMMFS NFUIPE *ODPSSFDUJOTUBMMBUJPONBZSFTVMUJOPWFSIFBUJOHBOEmSF t*OEPPSVOJUJOTUBMMB
t*OTUBMMUIFTZTUFNJOGVMMBDDPSEBODFXJUIUIF *GUIFnBSFOVUXFSFUJHIUFOFEXJUIFYDFTTUPSRVF
UIJTNBZ t6TFUIFQSFTDSJCFEDBCMFTGPSFMFDUSJDBMDPOOFDUJPO
JOTUBMMBUJPONBOVBM DBVTFCVSTUBOESFGSJHFSBOUMFBLBHFBGUFSBMPOHQFSJPE UJHIUFOUIFDBCMFTTFDVSFMZJOUFSNJOBMCMPDLBOE
*ODPSSFDUJOTUBMMBUJPONBZDBVTFCVSTUT
QFSTPOBMJOKVSZ
t%POPUPQFOUIFPQFSBUJPOWBMWFTGPSMJRVJEMJOFBOE SFMJFWFUIFDBCMFTDPSSFDUMZUPQSFWFOUPWFSMPBEJOHUIF "DDFTTPSJFTGP
XBUFSMFBLT
FMFDUSJDTIPDLTBOEmSF HBTMJOFVOUJMDPNQMFUFESFGSJHFSBOUQJQJOHXPSL
BJS UFSNJOBMCMPDLT
t#FTVSFUPVTFPOMZGPSIPVTFIPMEBOESFTJEFODF UJHIUOFTTUFTUBOEFWBDVBUJPO -PPTFDPOOFDUJPOTPSDBCMFNPVOUJOHTDBODBVTF (SPNNFU )FBUQ
*GUIJTBQQMJBODFJTJOTUBMMFEJOJOGFSJPSFOWJSPONFOUTVDIBT *GUIFDPNQSFTTPSJTPQFSBUFEJOTUBUFPGPQFOJOHPQFSBUJPO BOPNBMPVTIFBUQSPEVDUJPOPSmSF %SBJOFMCPX )FB
NBDIJOFTIPQBOEFUD
JUDBODBVTFNBMGVODUJPO WBMWFTCFGPSFDPNQMFUFEDPOOFDUJPOPGSFGSJHFSBOUQJQJOH t#FTVSFUPmYVQUIFTFSWJDFQBOFMT 7BSJBCMFEJBNFUFS
t8IFOJOTUBMMJOHJOTNBMMSPPNT
UBLFQSFWFOUJPO XPSL
BJSDBOCFTVDLFEJOUPSFGSJHFSBOUDJSDVJU
XIJDIDBO *ODPSSFDUmYJOHDBODBVTFFMFDUSJDTIPDLTPSmSFEVFUP /PUF1SPWJEFnBSFOVUT
NFBTVSFTOPUUPFYDFFEUIFEFOTJUZMJNJUPGSFGSJHFSBOU DBVTFCVTUPSQFSTPOBMJOKVSZEVFUPBOPNBMPVTMZIJHI JOUSVTJPOPGEVTUPSXBUFS EJBNFUFSKPJOU GPS
JOUIFFWFOUPGMFBLBHF
SFGFSSFECZUIFGPSNVMB QSFTTVSFJOUIFSFGSJHFSBOU t#FTVSFUPTXJUDIPGGUIFQPXFSTVQQMZJOUIFFWFOUPG
BDDPSEBODFXJUI*40
t5IFFMFDUSJDBMJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIF JOTUBMMBUJPO
JOTQFDUJPOPSTFSWJDJOH
*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJU
QMFBTFDPOTVMU RVBMJmFEFMFDUSJDJBOJOBDDPSEBODFXJUIiUIFOPSNGPS *GUIFQPXFSTVQQMZJTOPUTIVUPGG
UIFSFJTBSJTLPGFMFDUSJD
UIFEFBMFSBOEJOTUBMMUIFWFOUJMBUJPOTZTUFN
PUIFSXJTFMBDL FMFDUSJDBMXPSLwBOEiOBUJPOBMXJSJOHSFHVMBUJPOw
BOE TIPDLT
VOJUGBJMVSFPSQFSTPOBMJOKVSZEVFUPUIFVOFYQFDUFE
PGPYZHFODBOPDDVS
XIJDIDBODBVTFTFSJPVTBDDJEFOU UIFTZTUFNNVTUCFDPOOFDUFEUPUIFEFEJDBUFE TUBSUPGGBO $"65*0/
t6TFUIFPSJHJOBMBDDFTTPSJFTBOEUIFTQFDJmFE DJSDVJU t4UPQUIFDPNQSFTTPSCFGPSFSFNPWJOHUIFQJQFBGUFS
DPNQPOFOUTGPSJOTUBMMBUJPO 1PXFSTVQQMZXJUIJOTVGmDJFOUDBQBDJUZBOEJODPSSFDU TIVUUJOHUIFTFSWJDFWBMWFPOQVNQEPXOXPSL
*GQBSUTPUIFSUIBOUIPTFQSFTDSJCFECZVTBSFVTFE
*UNBZ GVODUJPOEPOFCZJNQSPQFSXPSLDBODBVTFFMFDUSJDTIPDLT *GUIFQJQFJTSFNPWFEXIFOUIFDPNQSFTTPSJTJOPQFSBUJPO
DBVTFXBUFSMFBLT
FMFDUSJDTIPDLT
mSFBOEQFSTPOBMJOKVSZ BOEmSF XJUIUIFTFSWJDFWBMWFPQFO
BJSXPVMECFNJYFEJOUIF
t*OTUBMMUIFVOJUJOBMPDBUJPOXJUIHPPETVQQPSU t#FTVSFUPTIVUPGGUIFQPXFSCFGPSFTUBSUJOHFMFDUSJDBM SFGSJHFSBUJPODJSDVJUBOEJUDPVMEDBVTFFYQMPTJPOBOEJOKVSJFT 4&-&$5
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMM XPSL EVFUPBCOPSNBMIJHIQSFTTVSFJOUIFDPPMJOHDZDMF
BOEDBVTFNBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ 'BJMVSFUPTIVUPGGUIFQPXFSDBODBVTFFMFDUSJDTIPDLT
VOJU t0OMZVTFQSFTDSJCFEPQUJPOBMQBSUT5IFJOTUBMMBUJPO
t&OTVSFUIFVOJUJTTUBCMFXIFOJOTUBMMFE
TPUIBUJUDBO GBJMVSFPSJODPSSFDUGVODUJPOPGFRVJQNFOU NVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS *OTUBMMBU
XJUITUBOEFBSUIRVBLFTBOETUSPOHXJOET t#FTVSFUPVTFUIFDBCMFTDPOGPSNFEUPTBGFUZ *GZPVJOTUBMMUIFTZTUFNCZZPVSTFMG
JUDBODBVTFTFSJPVT
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMM TUBOEBSEBOEDBCMFBNQBDJUZGPSQPXFSEJTUSJCVUJPO USPVCMFTVDIBTXBUFSMFBLT
FMFDUSJDTIPDLT
mSF
BOEDBVTFNBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ XPSL t#FTVSFUPXFBSQSPUFDUJWFHPHHMFTBOEHMPWFTXIJMF ●8IFSFUI
t7FOUJMBUFUIFXPSLJOHBSFBXFMMJOUIFFWFOUPG 6ODPOGPSNBCMFDBCMFTDBODBVTFFMFDUSJDMFBL
BOPNBMPVT BUXPSL ● 8IFSFSB
SFGSJHFSBOUMFBLBHFEVSJOHJOTUBMMBUJPO IFBUQSPEVDUJPOPSmSF t&BSUIMFBLBHFCSFBLFSNVTUCFJOTUBMMFE ●"MTP
XIF
*GUIFSFGSJHFSBOUDPNFTJOUPDPOUBDUXJUIOBLFEnBNFT
*GUIFFBSUIMFBLBHFCSFBLFSJTOPUJOTUBMMFE
JUDBODBVTF
QPJTPOPVTHBTJTQSPEVDFE FMFDUSJDTIPDLT BMPDBUJPO
FOIBODF
t&OTVSFUIBUOPBJSFOUFSTJOUIFSFGSJHFSBOUDJSDVJU t%POPUCVOEMJOH
XJOEJOHPSQSPDFTTJOHGPSUIFQPXFS t%POPUQFSGPSNBOZDIBOHFPGQSPUFDUJWFEFWJDFJUTFMG ●8IFSFCM
XIFOUIFVOJUJTJOTUBMMFEBOESFNPWFE DPSE0S
EPOPUEFGPSNJOHUIFQPXFSQMVHEVFUP PSJUTTFUVQDPOEJUJPO
*GBJSFOUFSTJOUIFSFGSJHFSBOUDJSDVJU
UIFQSFTTVSFJOUIF USFBEJU 5IFGPSDFEPQFSBUJPOCZTIPSUDJSDVJUJOHQSPUFDUJWFEFWJDFPG ●8IFSFUI
SFGSJHFSBOUDJSDVJUCFDPNFTUPPIJHI
XIJDIDBODBVTFCVSTU 5IJTNBZDBVTFmSFPSIFBUJOH QSFTTVSFTXJUDIBOEUFNQFSBUVSFDPOUSPMMFSPSUIFVTFPG ● 8IFSFUI
BOEQFSTPOBMJOKVSZ t%POPUSVOUIFVOJUXJUISFNPWFEQBOFMTPS OPOTQFDJmFEDPNQPOFOUDBODBVTFmSFPSCVSTU ●8IFSFX
t%POPUQSPDFTTJOH
TQMJDFUIFQPXFSDPSE
PSTIBSFB QSPUFDUJPOT
TPDLFUXJUIPUIFSQPXFSQMVHT 5PVDIJOHSPUBUJOHFRVJQNFOUT
IPUTVSGBDFTPSIJHIWPMUBHF ※1MFBTFB
5IJTNBZDBVTFmSFPSFMFDUSJDTIPDLEVFUPEFGFDUJOH QBSUTDBODBVTFQFSTPOBMJOKVSZEVFUPFOUSBQNFOU
CVSOPS ●8IFSFUI
DPOUBDU
EFGFDUJOHJOTVMBUJPOBOEPWFSDVSSFOUFUD FMFDUSJDTIPDLT MPDBUJPOT
$"65*0/ ●8IFSFUI
●8IFSFUI
t$BSSZPVUUIFFMFDUSJDBMXPSLGPSHSPVOEMFBEXJUIDBSF
%POPUDPOOFDUUIFHSPVOEMFBEUPUIFHBTMJOF
XBUFSMJOF
MJHIUOJOHDPOEVDUPSPSUFMFQIPOFMJOFTHSPVOEMFBE*ODPSSFDUHSPVOEJOHDBODBVTFVOJUGBVMUTTVDIBTFMFDUSJDTIPDLTEVFUP
TIPSUDJSDVJUJOH
t6TFUIFDJSDVJUCSFBLFSPGDPSSFDUDBQBDJUZ$JSDVJU *OTVGmDJFOUTQBDFDBOSFTVMUJOBDDJEFOUTVDIBTQFSTPOBM t8IFOQFSGPSNUIFBJSDPOEJUJPOFSPQFSBUJPO DPPMJOH
CSFBLFSTIPVMECFUIFPOFUIBUEJTDPOOFDUBMMQPMFT JOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF PSESZJOHPQFSBUJPO
JOXIJDIWFOUJMBUPSJTJOTUBMMFEJO *OTUBMMBUJP
VOEFSPWFSDVSSFOU t5BLFDBSFXIFODBSSZJOHUIFVOJUCZIBOE UIFSPPN*OUIJTDBTF
VTJOHUIFBJSDPOEJUJPOFSJO
6TJOHUIFJODPSSFDUPOFDPVMEDBVTFUIFTZTUFNGBJMVSFBOE *GUIFVOJUXFJHIUTNPSFUIBOLH
JUNVTUCFDBSSJFECZUXP QBSBMMFMXJUIUIFWFOUJMBUPS
UIFSFJTUIFQPTTJCJMJUZUIBU ①"ODIPS
mSF PSNPSFQFSTPOT%POPUDBSSZCZUIFQMBTUJDTUSBQT
BMXBZT ESBJOXBUFSNBZCBDLnPXJOBDDPSEBODFXJUIUIF
t*OTUBMMJTPMBUPSPSEJTDPOOFDUTXJUDIPOUIFQPXFS VTFUIFDBSSZIBOEMFXIFODBSSZJOHUIFVOJUCZIBOE6TF SPPNMBQTFJOUPUIFOFHBUJWFQSFTTVSFTUBUVT
TVQQMZXJSJOHJOBDDPSEBODFXJUIUIFMPDBMDPEFTBOE HMPWFTUPNJOJNJ[FUIFSJTLPGDVUTCZUIFBMVNJOVNmOT 5IFSFGPSF
TFUVQUIFPQFOJOHQPSUTVDIBT
SFHVMBUJPOT t%JTQPTFPGBOZQBDLJOHNBUFSJBMTDPSSFDUMZ JODPSQPSBUFUIFBJSJOUPUIFSPPNUIBUNBZBQQSPQSJBUF
5IFJTPMBUPSTIPVMECFMPDLFEJO0''TUBUFJOBDDPSEBODF "OZSFNBJOJOHQBDLJOHNBUFSJBMTDBODBVTFQFSTPOBMJOKVSZ UPWFOUJMBUJPO 'PSFYBNQMF0QFOUIFEPPSBMJUUMF
*O
XJUI&/ BTJUDPOUBJOTOBJMTBOEXPPE"OEUPBWPJEEBOHFSPG BEEJUJPO
KVTUBTBCPWF
TPTFUVQUIFPQFOJOHQPSUJG
- 165 -
"#
$0/%*5*0/&3 $"65*0/
3"/564&% t%POPUJOTUBMMUIFPVUEPPSVOJUJOUIFMPDBUJPOTMJTUFE IBOEMFE t%POPUVTFBOZNBUFSJBMTPUIFSUIBOBGVTFXJUIUIF
CFMPX $PSSPTJWFHBTDBODBVTFDPSSPTJPOPGIFBUFYDIBOHFS
DPSSFDUSBUJOHJOUIFMPDBUJPOXIFSFGVTFTBSFUPCF
MJFEXJUIUIFVOJUT t-PDBUJPOTXIFSFEJTDIBSHFEIPUBJSPSPQFSBUJOHTPVOEPG CSFBLBHFPGQMBTUJDQBSUTBOEFUD"OEDPNCVTUJCMFHBTDBO VTFE
FTCFUXFFO UIFPVUEPPSVOJUDBOCPUIFSOFJHICPSIPPE DBVTFmSF $POOFDUJOHUIFDJSDVJUXJUIDPQQFSXJSFPSPUIFSNFUBM
t-PDBUJPOTXIFSFPVUMFUBJSPGUIFPVUEPPSVOJUCMPXT t%POPUJOTUBMMOPSVTFUIFTZTUFNDMPTFUPUIF UISFBEDBODBVTFVOJUGBJMVSFBOEmSF
EJSFDUMZUPQMBOUT5IFPVUMFUBJSDBOBGGFDUBEWFSTFMZUPUIF FRVJQNFOUUIBUHFOFSBUFTFMFDUSPNBHOFUJDmFMETPS t%POPUUPVDIBOZCVUUPOTXJUIXFUIBOET
QMBOUFUD IJHIGSFRVFODZIBSNPOJDT *UDBODBVTFFMFDUSJDTIPDLT
t-PDBUJPOTXIFSFWJCSBUJPODBOCFBNQMJmFEBOE &RVJQNFOUTVDIBTJOWFSUFST
TUBOECZHFOFSBUPST
NFEJDBM t%POPUUPVDIBOZSFGSJHFSBOUQJQFTXJUIZPVSIBOET
BOZVTFSDBOSFBE USBOTNJUUFEEVFUPJOTVGmDJFOUTUSFOHUIPGTUSVDUVSF IJHIGSFRVFODZFRVJQNFOUTBOEUFMFDPNNVOJDBUJPO XIFOUIFTZTUFNJTJOPQFSBUJPO
t-PDBUJPOTXIFSFWJCSBUJPOBOEPQFSBUJPOTPVOEHFOFSBUFE FRVJQNFOUTDBOBGGFDUUIFTZTUFN
BOEDBVTFNBMGVODUJPOT %VSJOHPQFSBUJPOUIFSFGSJHFSBOUQJQFTCFDPNFFYUSFNFMZIPU
CZVTJOHTVJUBCMF CZUIFPVUEPPSVOJUDBOBGGFDUTFSJPVTMZ POUIFXBMMPSBU BOECSFBLEPXOT5IFTZTUFNDBOBMTPBGGFDUNFEJDBM PSFYUSFNFMZDPMEEFQFOEJOHUIFPQFSBUJOHDPOEJUJPO
BOEJU
UIFQMBDFOFBSCFESPPN
FRVJQNFOUBOEUFMFDPNNVOJDBUJPOFRVJQNFOU
BOEPCTUSVDU DBODBVTFCVSOJOKVSZPSGSPTUJOKVSZ
UUIFIJHIQPTJUJPO t-PDBUJPOTXIFSFBOFRVJQNFOUBGGFDUFECZIJHIIBSNPOJDT JUTGVODUJPOPSDBVTFKBNNJOH t%POPUUPVDIUIFTVDUJPOPSBMVNJOVNmOPOUIF
JTQMBDFE 57TFUPSSBEJPSFDFJWFSJTQMBDFEXJUIJON
t%POPUJOTUBMMUIFPVUEPPSVOJUJOBMPDBUJPOXIFSF PVUEPPSVOJU
t-PDBUJPOTXIFSFESBJOBHFDBOOPUSVOPGGTBGFMZ JOTFDUTBOETNBMMBOJNBMTDBOJOIBCJU 5IJTNBZDBVTFJOKVSZ
*UDBOBGGFDUTVSSPVOEJOHFOWJSPONFOUBOEDBVTFBDMBJN *OTFDUTBOETNBMMBOJNBMTDBOFOUFSUIFFMFDUSJDQBSUTBOE t%POPUQVUBOZUIJOHPOUIFPVUEPPSVOJUBOEPQFSBUJOH
t%POPUJOTUBMMUIFVOJUOFBSUIFMPDBUJPOXIFSFMFBLBHF DBVTFEBNBHFPSmSF*OTUSVDUUIFVTFSUPLFFQUIF VOJU
PGDPNCVTUJCMFHBTFTDBOPDDVS TVSSPVOEJOHTDMFBO 5IJTNBZDBVTFEBNBHFUIFPCKFDUTPSJOKVSZEVFUPGBMMJOH
*GMFBLFEHBTFTBDDVNVMBUFBSPVOEUIFVOJU
JUDBODBVTFmSF t%POPUVTFUIFCBTFnBNFGPSPVUEPPSVOJUXIJDIJT UPUIFPCKFDU
t%POPUJOTUBMMUIFVOJUXIFSFDPSSPTJWFHBT TVDIBT DPSSPEFEPSEBNBHFEEVFUPMPOHQFSJPETPG t%POPUVTFUIFVOJUGPSTQFDJBMQVSQPTFTTVDIBT
TVMGVSPVTBDJEHBTFUD
PSDPNCVTUJCMFHBT TVDIBT PQFSBUJPO TUPSJOHGPPET
DPPMJOHQSFDJTJPOJOTUSVNFOUTBOE
UIJOOFSBOEQFUSPMFVNHBTFT
DBOBDDVNVMBUFPS 6TJOHBOPMEBOEEBNBHFCBTFnBNFDBODBVTFUIFVOJU QSFTFSWBUJPOPGBOJNBMT
QMBOUTPSBSU
DPMMFDU
PSXIFSFWPMBUJMFDPNCVTUJCMFTVCTUBODFTBSF GBMMJOHEPXOBOEDBVTFQFSTPOBMJOKVSZ t%POPUDMFBOVQUIFVOJUXJUIXBUFS
NBJOQPXFS
PSTXJUDI $IFDLCFGPSFJOTUBMMBUJPOXPSL
PGBUMFBTUNN 8SFODILFZ )FYBHPO
<NN>
TPUIBUJUDBOOPU t.PEFMOBNFBOEQPXFSTPVSDF 0QUJPOQBSUT 2UZ /FDFTTBSZUPPMTGPSUIFJOTUBMMBUJPOXPSL
7BDVVNQVNQ
UBMMUIFTFSWJDF t3FGSJHFSBOUQJQJOHMFOHUI
B 4FBMJOHQMBUF 1MVTIFBEFEESJWFS 7BDVVNQVNQBEBQUFS "OUJSFWFSTFnPXUZQF
t1JQJOH
XJSJOHBOENJTDFMMBOFPVTTNBMMQBSUT
UJOHBOEmSF t*OEPPSVOJUJOTUBMMBUJPONBOVBM C 4MFFWF ,OJGF %FTJHOFETQFDJmDBMMZGPS3"
F
BODBVTF (SPNNFU )FBUQVNQUZQFPOMZ
IPTF
4QBOOFSXSFODI (BTMFBLEFUFDUPS %FTJHOFETQFDJmDBMMZGPS3"
%SBJOFMCPX )FBUQVNQUZQFPOMZ
1JQJOHDPWFS GPSJOTVMBUJPO 5PSRVFXSFODI<_/rN _LHGrN
> (BVHFGPSQSPKFDUJPOBEKVTUNFOU 6TFEXIFOnBSFJT
G
7BSJBCMFEJBNFUFSKPJOUφ⇒φ PGDPOOFDUJPOQJQJOH
)PMFDPSFESJMM NNJOEJBNFUFS
NBEFCZVTJOHDPOWFOUJPOBMnBSFUPPM
PSmSFEVFUP /PUF1SPWJEFnBSFOVUTXIFOVTJOHUIFWBSJBCMF
EJBNFUFSKPJOU GPSφ
ZJOUIFFWFOUPG
BSJTLPGFMFDUSJD
UPUIFVOFYQFDUFE
$"65*0/ ● 5IJTNPEFMSFRVJSFTBNJOJNVNPGJOEPPSVOJUT
HUIFQJQFBGUFS
PXOXPSL
TPSJTJOPQFSBUJPO
NJYFEJOUIF
MPTJPOBOEJOKVSJFT 4&-&$5*0/0'*/45"--"5*0/-0$"5*0/
JOHDZDMF
IFJOTUBMMBUJPO
OTUBMMFS *OTUBMMBUMPDBUJPOUIBUNFFUTUIFGPMMPXJOHDPOEJUJPOTBGUFSHFUUJOHBQQSPWBMGSPNUIFDVTUPNFS
DBVTFTFSJPVT
LT
mSF ①*OTUBMMBUJPO4QBDF POBáBUTVSGBDF
DIBT *OUBLF
NBZBQQSPQSJBUF 'BTUFOXJUICPMUT
.
EPPSBMJUUMF
*O
PQFOJOHQPSUJG
FTUBUVTEVFUP
QBSUNFOUFUD
0VUMFU 6TFBMPOHCMPDLUP
*NQSPQFSJOTUBMMBUJPODBOSFTVMUJOBDPNQSFTTPSGBJMVSF
CSPLFOQJQJOHXJUIJOUIFVOJUBOEBCOPSNBMOPJTFHFOFSBUJPO
NBODF
DPSSPTJPO
BOEmSF
- 166 -
*/45"--"5*0/0'065%0036/*5 "*3163
1SPDFEVSF
5IFTDSFXPGUIFTFSWJDFQBOFMJTUJHIUFOFETFDVSFMZ
$POOFDUJPO PG UIF QPXFS TVQQMZ DBCMF BOE UIF DPOOFDUJOH DBCMFT
4FDVSFBMMá
GPS JOEPPS BOE PVUEPPS VOJUT 5FSNJOBMDPWFS QSFWFOUMFB
● 5IJTNVMUJUZQFSPPNBJSDPOEJUJPOFSSFDFJWFTJUTQPXFSGSPNPVUTJEF
$POOFDUUI
● 5PFOTVSFDPSSFDUDPOOFDUJPOT
NBSLFBDIFOETPGUIFDBCMFTXJUIOVNCFS
"UP%*U WBMWFBOE
JTJNQPSUBOUUPVTFUIFTBNFOVNCFSUIFDPSSFTQPOEJOHDBCMFTBOEQJQFT VOJU$ VOJU%
'VMMZ PQFO
● "OFBSUIMFBLBHFCSFBLFSBOEBDJSDVJUCSFBLFSNVTUCFJOTUBMMFE
QVNQBWB
4DSFX
5IFJSDBQBDJUJFTBSF"
108&3
4611-: VOJU" VOJU# JTJOEJDBUJO
"GUFSWBDVV
①3FNPWFUIFTFSWJDFQBOFM 3FNPWFUIFTFUTTDSFXTPGUIFTFSWJDFQBOFM
MJRVJEBOE
②3FNPWFUIFUFSNJOBMDPWFS 3FNPWFUIFTFUTTDSFXTPGUIFUFSNJOBMDPWFS
7JFXPG5FSNJOBMCMPDL
③$POOFDUUIFQPXFSTVQQMZDBCMFBOEUIFDPOOFDUJPOXJSFTFDVSFMZUPUIFUFSNJOBMCMPDL
〔108&34611-:$0%&〕
4FSWJDFQBOFM
$&/&-&$DPEFGPSDBCMFTSFRVJSJOHàFMETDBCMFT)3/3(
〔*/5&3$0//&$5*/(8*3*/($0%&〕 PVUEPPSVOJU
$&/&-&$DPEFGPSDBCMFTSFRVJSJOHàFMETDBCMFT)3/3(
3FNPWFUI
VOJU" VOJU# VOJU$ VOJU%
3FQFBUUIF
*OXJSJOH
NBLFTVSFUIBUUIFXJSFUFSNJOBMOVNCFSTPGPVUEPPSVOJUUFSNJOBM
&OTVSFUIBU
CMPDLBSFNBUDIUPUIFXJSFUFSNJOBMOVNCFSTPGJOEPPSVOJUUFSNJOBMCMPDL
5FSNJOBMOVNCFS"PGUIFPVUEPPSVOJUJTVTFEGPS"JOEPPSVOJUBOEUFSNJOBM - /
OVNCFS#GPS#JOEPPSVOJUSFTQFDUJWFMZ
④"GUFSDPOOFDUJOHUIFXJSF
VTFXJSJOHDMBNQTUPTFDVSFUIFXJSJOH
)&"5*/
$JSDVJU &BSUI
⑤'JUUIFUFSNJOBMDPWFSBOEUIFTFSWJDFQBOFM CSFBLFS MFBLBHF VOJU" VOJU# VOJU$ VOJU%
CSFBLFS
JOEPPSVOJU )FBUJOTVMBUJP
7JOZM
UBQF
$0//&$5*0/0'3&'3*(&3"/51*1*/(4
● 3FHBSEJOHUIFDIBOHFJOUIFTJ[FTPGHBTTJEFQJQFT VTBHFPGUIFWBSJBCMFKPJOUT
<&YBNQMFTPGVTFPGWBSJBCMFEJBNFUFSKPJOUT>
*GB
LXDMBTT JOEPPS VOJU HBT TJEF QJQF
JT HPJOH UP CF DPOOFDUFE UP UIF
●$POOFDUJPOPGJOEPPSVOJUPG$MBTTUP"VOJU
PQFSBUJPOWBMWFT
WBSJBCMFKPJOUTBWBJMBCMFBTBDDFTTPSJFTNVTUCFBQQMJFEUPUIF
Liquid side operation valve (φ6.35)
HBTTJEFPQFSBUJPOWBMWFT φ6.35 pipe 5.0 kw
● 4FDVSFMZàUUIFDPQQFSQBDLJOHCFUXFFOUIFPQFSBUJPOWBMWFBOEUIFWBSJBCMF Operation Indoor unit
valve for room A
EJBNFUFSKPJOUUPQSFWFOUTIJGUJOH φ12.7 pipe
Gas side operation
valve (φ9.52) Copper packing ① Variable diameter joint
(φ 9.52 - φ12.7)
<$POOFDUJPOPGQJQFT>
/05&
● $PWFSUIFQJQFTXJUIUBQFTPUIBUEVTUBOETBOEEPOPUFOUFSUIFQJQFVOUJMUIFZBSF Measurement B (mm) #&8"3
DPOOFDUFE Copper pipe Clutch type flare tool for Conventional (R22) flare tool
3&'3*(
● 8IFODPOOFDUJOHUIFQJQFTUPUIFPVUEPPSVOJU
CFDBSFGVMBCPVUUIFEJTDIBSHFPGáVPSPDBSCPO
diameter R410A Clutch type Wing nut type
HBTPSPJM φ ∼0.5 ∼1.5 ∼2.0 ● .BLFTVSFUP
● .BLFTVSFUPNBUDIUIFQJQFTCFUXFFOUIFJOEPPSVOJUBOEUIFPVUEPPSVOJUXJUIUIF φ ∼0.5 ∼1.5 ∼2.0 PVUEPPSVOJU
φ ∼0.5 ∼1.5 ∼2.5
DPSSFDUPQFSBUJPOWBMWFT ● #FDBSFGVMCF
Use a flare tool designed for R410A or a conventional flare tool. Please note that DBOOPUCFBD
0VUEPPS %JNFOTJPO" measurement B (protrusion from the flaring block) will vary depending on the type of a
flare tool in use.
±°
-JRVJETJEFEJB If a conventional flare tool is used, please use a copper pipe gauge or a similar
1SFTT "
(BTTJEF instrument to check protrusion so that you can keep measurement B to a correct value. <$PSSFDUDPO
3FNPWF φEJB
φEJB
.FBTVSFNFOU#
○3FNPWFUIFáBSFEOVUT ○*OTUBMMUIFSFNPWFEáBSFEOVUTUPUIFQJQFT
POCPUIMJRVJEBOEHBTTJEFT
UPCFDPOOFDUFE
UIFOáBSFUIFQJQFT
*OEPPSVOJU
$"65*0/ $"65*0/
%VOJU
%POPUBQQMZFYDFTTUPSRVFUPUIFáBSFEOVUT Do not apply refrigerating machine
'MBSJOH
0UIFSXJTF
UIF áBSFE OVUT NBZ DSBDL EFQFOEJOH oil to the flared surface. CMPDL $PQQFSQJQF
POUIFDPOEJUJPOTBOESFGSJHFSBOUMFBLNBZPDDVS $VOJU
#VOJU
$POOFDUJPO
0VUEPPS "VOJU
● 8IFO UIF UPUBM SFGSJHFSBOU QJQF MFOHIU GPS BMM UIF [-JNJU]
-JRVJETJEF SPPNT FYDFFET UIF MFOHIU PG UIF VODIBSHFE QJQF POFJOEPPSVOJU."9N
(BTTJEF QJQJOHMFOHUI
BMMJOEPPSVOJU."9N
N
BEEJUJPOBMSFGSJHFSBOUJTSFRVJSFE
*GNPSMFTT
BEEJUJPOBMDIBSHFJTOPUSFRVJSFE
JOEPPS
"EEJUJPOBMDIBSHFBNPVOUQFSNFUFSHN VOJU
."9N
JOEPPS
VOJU
&"35)*/
○$POOFDUUIFQJQFTPOCPUIMJRVJEBOEHBTTJEFT IJHIUEJGGFSFODF ."9 PVUEPPS ○ &BSUIXPSLTI
○5JHIUFOUIFOVUTUPUIFGPMMPXJOHUPSRVF (BT-FBLBHF5FTU N
VOJU JOEPPS
VOJU TIPDLBOEOP
-JRVJETJEF∼/・N ∼LHG・N
○ 5IFDPOOFDUJP
●&OTVSFUIBUUIFSFBSFOPHBTMFBLTGSPNUIFQJQF ."9N
(BTTJEF φ
∼/・N ∼LHG・N
JOEPPS
EBOHFSPVTGBJ
φ
∼/・N ∼LHG・N
KPJOUTCZVTJOHBMFBLEFUFDUPSPSTPBQXBUFS VOJU
5PXOHBTQJQ
MFOHUIPGDIBSHFMFTT
SFGSJHFSBOUQJQF N
- 167 -
● 4JODF UIF TZTUFN VTFT TFSWJDF QPSUT EJGGFSJOH JO EJBNFUFS GSPN UIPTF GPVOE ● 1MFBTFVTFBOBOUJSFWFSTFáPXUZQFWBDVVNQVNQBEBQUFSTPBTUPQSFWFOU
PO UIF DPOWFOUJPOBMNPEFMT
BDIBSHFIPTF GPS3
QSFTFOUMZJOVTFJTOPU WBDVVNQVNQPJMGSPNSVOOJOHCBDLJOUPUIFTZTUFN0JMSVOOJOHCBDLJOUP
BQQMJDBCMF1MFBTFVTFPOFEFTJHOFETQFDJàDBMMZGPS3" BOBJSDPOEJUJPOJOHTZTUFNNBZDBVTFUIFSFGSJHFSBOUDZDMFUPCSFBLEPXO
● 3FNPWFUIFDBQPOCPUIHBTBOEMJRVJETJEFTCFGPSFTUBSUJOHPQFSBUJPO ● $POEVDUBJSQVSHJOHGPSBMMDPOOFDUFEJOEPPSVOJUT
● "GUFSDPNQMFUJOHUIFPQFSBUJPO
EPOPUGPSHFUUPUJHIUFOUIFDBQ HBTNBZMFBL
0QFSBUJPO7BMWF $PNQPVOEQSFTTVSFHBVHF
$BQ 1SFTTVSFHBVHF
0QFSBUJPO7BMWF
1SPDFEVSF UXPXBZWBMWF
.1B
(BVHF.BOJGPME
%FTJHOFETQFDJàDBMMZGPS3"
DN)H
4FDVSFBMMáBSFOVUTPOCPUIJOEPPSBOEPVUEPPSTJEFTUP )BOEMF-P )BOEMF)J
QSFWFOUMFBLTGSPNUIFQJQFT
0QFSBUJPO7BMWF $IBSHFIPTF
$POOFDUUIFPQFSBUJPOWBMWFT
DIBSHFIPTF
NBOJGPME UISFFXBZWBMWF
%FTJHOFETQFDJàDBMMZGPS3"
WBMWFBOEWBDVVNQVNQBTTIPXOJOUIFSJHIUàHVSF 0QFSBUJPOWBMWF
7BDVVNQVNQBEBQUFS
$ VOJU%
'VMMZ PQFO UIF IBOEMF -P GPS UIF NBOJGPME WBMWF
BOE GPSSPPN% 0QFSBUJPO7BMWF "OUJSFWFSTFáPXUZQF
JTJOEJDBUJOH.1B DN)H
GPSSPPN$
JU" VOJU#
0QFSBUJPOWBMWF 7BDVVNQVNQ
"GUFSWBDVVNJOH
GVMMZPQFOUIFPQFSBUJPOWBMWF CPUI GPSSPPN# $IFDLKPJOU $IBSHFIPTF
MJRVJEBOEHBTTJEFT
XJUIBIFYBHPOXSFODI 0QFSBUJPOWBMWF %FTJHOFETQFDJàDBMMZGPS3"
FSNJOBMCMPDL GPSSPPN"
4FDVSFMZUJHIUFOUIFPQFSBUJPOWBMWFDBQBOEUIFDIFDLKPJOUCMJOEOVUBGUFSBEKVTUNFOU
0QFO 0QFO
φ
3FNPWFUIFDIBSHFIPTFGSPNTFSWJDFQPSU ~
$ VOJU% φ
~
3FQFBUUIFBCPWFTUFQT
_
GPSBMMDPOOFDUFEJOEPPSVOJUT
φ
~
&OTVSFUIBUUIFSFBSFOPHBTMFBLTGSPNUIFKPJOUTJOUIFJOEPPSBOEPVUEPPSVOJUT
)&"5*/46-"5*0/'03+0*/54 5&4536/"/%)"/%-*/(*/4536$5*0/4
VOJU%
)FBUJOTVMBUJPOGPSKPJOUT
7JOZM
*OTUBMMBUJPOUFTUDIFDLQPJOUT
UBQF 1PTJUJPOTP
UIFTMJU $PWFSUIFKPJOUXJUI $IFDL UIF GPMMPXJOH QPJOUT BHBJO BGUFS DPNQMFUJPO PG UIF JOTUBMMBUJPO
BOE CFGPSF
DPNFTPOUPQ JOTVMBUJPONBUFSJBM UVSOJOHPOUIFQPXFS
GPSUIFJOEPPSVOJU
BOEUBQFJU $POEVDUBUFTUSVOBHBJOBOEFOTVSFUIBUUIFVOJUPQFSBUFTQSPQFSMZ
"U UIF TBNF UJNF
FYQMBJO UP UIF DVTUPNFS IPX UP VTF UIF VOJU BOE IPX UP UBLF
DBSFPGUIFVOJUGPMMPXJOHUIFJOTUBMMBUJPONBOVBM
*GUIFDPNQSFTTPSEPFTOPUPQFSBUFBGUFSUIFPQFSBUJPOIBTTUBSUFE
XBJUGPS
NJOVUFT 5IJTNBZCFEVFUPEFMBZFETUBSU
5ISFFNJOVUFSFTUBSUQSFWFOUJWFUJNFS
31$"#
- 168 -
WARNING
Check before
• Installation must be carried out by the qualified • Use the prescribed pipes, flare nuts and tools for • This appliance must be connected to main power
installer. R410A. supply by means of a circuit breaker or switch • Model name and
If you install the system by yourself, it may cause serious Using existing parts (for R22 or R407C) can cause the unit (fuse:30A) with a contact separation of at least 3mm. • Refrigerant piping
trouble such as water leaks, electric shocks, fire and failure and serious accidents due to burst of the refrigerant • Arrange the wiring in the control box so that it cannot • Piping, wiring and
personal injury, as a result of a system malfunction. Do not circuit. be pushed up further into the box. Install the service • Indoor unit installa
carry out the installation and maintenance work except the • Tighten the flare nut by torque wrench with specified panel correctly.
by qualified installer. method. Incorrect installation may result in overheating and fire.
• Install the system in full accordance with the If the flare nut were tightened with excess torque, this may • Use the prescribed cables for electrical connection, Accessories f
installation manual. cause burst and refrigerant leakage after a long period. tighten the cables securely in terminal block and
Incorrect installation may cause bursts, personal injury, • Do not open the operation valves for liquid line and relieve the cables correctly to prevent overloading the 1 Grommet (Heat
water leaks, electric shocks and fire. gas line until completed refrigerant piping work, air terminal blocks. 2 Drain elbow (He
• Be sure to use only for household and residence. tightness test and evacuation. Loose connections or cable mountings can cause 3 Variable diamete
If this appliance is installed in inferior environment such as If the compressor is operated in state of opening operation anomalous heat production or fire.
4 Variable diamete
machine shop and etc., it can cause malfunction. valves before completed connection of refrigerant piping • Be sure to fix up the service panels.
• When installing in small rooms, take prevention work, air can be sucked into refrigerant circuit, which can Incorrect fixing can cause electric shocks or fire due to Note: Provide flare nut
measures not to exceed the density limit of refrigerant cause bust or personal injury due to anomalously high intrusion of dust or water. diameter joint (fo
in the event of leakage, referred by the formula pressure in the refrigerant. • Be sure to switch off the power supply in the event of
(accordance with ISO5149). • The electrical installation must be carried out by the installation, inspection or servicing.
If the density of refrigerant exceeds the limit, please consult qualified electrician in accordance with “the norm for If the power supply is not shut off, there is a risk of electric
the dealer and install the ventilation system, otherwise lack electrical work” and “national wiring regulation”, and shocks, unit failure or personal injury due to the unexpected CAUTION
of oxygen can occur, which can cause serious accident. the system must be connected to the dedicated start of fan.
• Use the original accessories and the specified circuit. • Stop the compressor before removing the pipe after
components for installation. Power supply with insufficient capacity and incorrect shutting the service valve on pump down work.
If parts other than those prescribed by us are used, It may function done by improper work can cause electric shocks If the pipe is removed when the compressor is in operation
cause water leaks, electric shocks, fire and personal injury. and fire. with the service valve open, air would be mixed in the
• Install the unit in a location with good support. • Be sure to shut off the power before starting electrical refrigeration circuit and it could cause explosion and injuries 1 SELECT
Unsuitable installation locations can cause the unit to fall work. due to abnormal high pressure in the cooling cycle.
and cause material damage and personal injury. Failure to shut off the power can cause electric shocks, unit • Only use prescribed optional parts. The installation
• Ensure the unit is stable when installed, so that it can
withstand earthquakes and strong winds.
failure or incorrect function of equipment.
• Be sure to use the cables conformed to safety
must be carried out by the qualified installer.
If you install the system by yourself, it can cause serious
Install at
Unsuitable installation locations can cause the unit to fall standard and cable ampacity for power distribution trouble such as water leaks, electric shocks, fire. ● Where th
and cause material damage and personal injury. work. • Be sure to wear protective goggles and gloves while
• Ventilate the working area well in the event of Unconformable cables can cause electric leak, anomalous at work. does not
refrigerant leakage during installation. heat production or fire. • Earth leakage breaker must be installed. ● Where ra
If the refrigerant comes into contact with naked flames, If the earth leakage breaker is not installed, it can cause there is e
poisonous gas is produced. electric shocks.
● Also, whe
• Ensure that no air enters in the refrigerant circuit • Do not bundling, winding or processing for the power • Do not perform any change of protective device itself A location
when the unit is installed and removed. cord. Or, do not deforming the power plug due to or its setup condition. noises an
If air enters in the refrigerant circuit, the pressure in the tread it. The forced operation by short-circuiting protective device of
● Where b
refrigerant circuit becomes too high, which can cause burst This may cause fire or heating. pressure switch and temperature controller or the use of
and personal injury. • Do not run the unit with removed panels or non specified component can cause fire or burst. neighbor
• Do not processing, splice the power cord, or share a protections. ● Where th
socket with other power plugs. Touching rotating equipments, hot surfaces or high voltage sources.
This may cause fire or electric shock due to defecting parts can cause personal injury due to entrapment, burn or
contact, defecting insulation and over-current etc. electric shocks. ● Where th
suction in
CAUTION ● Where w
• Carry out the electrical work for ground lead with care. ※ Please a
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as electric shocks due to
short-circuiting. ● Where th
top floors
• Use the circuit breaker of correct capacity. Circuit Insufficient space can result in accident such as personal • When perform the air conditioner operation (cooling ● Where th
breaker should be the one that disconnect all poles injury due to falling from the installation place. or drying operation) in which ventilator is installed in
under over current. • Take care when carrying the unit by hand. the room. In this case, using the air conditioner in ● Where th
Using the incorrect one could cause the system failure and If the unit weights more than 20kg, it must be carried by two parallel with the ventilator, there is the possibility that
fire. or more persons. Do not carry by the plastic straps, always drain water may backflow in accordance with the
• Install isolator or disconnect switch on the power use the carry handle when carrying the unit by hand. Use room lapse into the negative pressure status.
supply wiring in accordance with the local codes and gloves to minimize the risk of cuts by the aluminum fins. Therefore, set up the opening port such as
regulations. • Dispose of any packing materials correctly. incorporate the air into the room that may appropriate Installatio
The isolator should be locked in OFF state in accordance Any remaining packing materials can cause personal injury to ventilation (For example; Open the door a little). In
with EN60204-1. as it contains nails and wood. And to avoid danger of addition, just as above, so set up the opening port if ● In install
• After maintenance, all wiring, wiring ties and the like, suffocation, be sure to keep the plastic wrapper away from the room lapse into negative pressure status due to the right.
should be returned to their original state and wiring children and to dispose after tear it up. register of the wind for the high rise apartment etc.
route, and the necessary clearance from all metal • Be sure to insulate the refrigerant pipes so as not to
● The protr
parts should be secured. condense the ambient air moisture on them. within 15
• Secure a space for installation, inspection and Insufficient insulation can cause condensation, which can ● Securely
maintenance specified in the manual. lead to moisture damage on the ceiling, floor, furniture and earthqua
any other valuables.
● Refer to
• Do not install the unit in the locations listed below. • Locations where any machines which generate high • Locations with any obstacles which can prevent inlet and concrete
• Locations where carbon fiber, metal powder or any frequency harmonics are used. outlet air of the unit.
● Install the
powder is floating. • Locations with salty atmospheres such as coastlines. • Locations where short circuit of air can occur (in case of
• Locations where any substances that can affect the unit • Locations with heavy snow (If installed, be sure to provide multiple units installation). Improper
such as sulphide gas, chloride gas, acid and alkaline can base flame and snow hood mentioned in the manual). • Locations where strong air blows against the air outlet of piping wi
occur. • Locations where the unit is exposed to chimney smoke. outdoor unit.
• Vehicles and ships. • Locations at high altitude (more than 1000m high). • Locations where something located above the unit could
• Locations where cosmetic or special sprays are often • Locations with ammonic atmospheres. fall.
used. • Locations where heat radiation from other heat source can It can cause remarkable decrease in performance, corrosion
• Locations with direct exposure of oil mist and steam such affect the unit. and damage of components, malfunction and fire.
as kitchen and machine plant. • Locations without good air circulation.
- 169 -
2A918 C CAUTION
• Do not install the outdoor unit in the locations listed handled. • Do not use any materials other than a fuse with the
CONDITIONER below. Corrosive gas can cause corrosion of heat exchanger, correct rating in the location where fuses are to be
RANT USED • Locations where discharged hot air or operating sound of breakage of plastic parts and etc. And combustible gas can used.
the outdoor unit can bother neighborhood. cause fire. Connecting the circuit with copper wire or other metal
lied with the units. • Locations where outlet air of the outdoor unit blows • Do not install nor use the system close to the thread can cause unit failure and fire.
es between directly to plants. The outlet air can affect adversely to the equipment that generates electromagnetic fields or • Do not touch any buttons with wet hands.
plant etc. high frequency harmonics. It can cause electric shocks.
• Locations where vibration can be amplified and Equipment such as inverters, standby generators, medical • Do not touch any refrigerant pipes with your hands
transmitted due to insufficient strength of structure. high frequency equipments and telecommunication when the system is in operation.
• Locations where vibration and operation sound generated equipments can affect the system, and cause malfunctions During operation the refrigerant pipes become extremely hot
any user can read by the outdoor unit can affect seriously (on the wall or at and breakdowns. The system can also affect medical or extremely cold depending the operating condition, and it
the place near bed room). equipment and telecommunication equipment, and obstruct can cause burn injury or frost injury.
by using suitable • Locations where an equipment affected by high harmonics its function or cause jamming. • Do not touch the suction or aluminum fin on the
is placed (TV set or radio receiver is placed within 1m). • Do not install the outdoor unit in a location where outdoor unit.
t the high position. • Locations where drainage cannot run off safely. insects and small animals can inhabit. This may cause injury.
It can affect surrounding environment and cause a claim. Insects and small animals can enter the electric parts and • Do not put anything on the outdoor unit and operating
• Do not install the unit near the location where leakage cause damage or fire. Instruct the user to keep the unit.
of combustible gases can occur. surroundings clean. This may cause damage the objects or injury due to falling
If leaked gases accumulate around the unit, it can cause fire. • Do not use the base flame for outdoor unit which is to the object.
• Do not install the unit where corrosive gas (such as corroded or damaged due to long periods of • Do not use the unit for special purposes such as
sulfurous acid gas etc.) or combustible gas (such as operation. storing foods, cooling precision instruments and
thinner and petroleum gases) can accumulate or Using an old and damage base flame can cause the unit preservation of animals, plants or art.
collect, or where volatile combustible substances are falling down and cause personal injury. • Do not clean up the unit with water.
a risk of electric
• This model requires normally a minimum of 4 indoor units.
to the unexpected CAUTION • This model requires a minimum of 3 indoor units in case of SRK-ZK-S, SRK-ZJX-S, FDEN type combination only.
• This model requires a minimum of 2 indoor units in case of SRK71ZK-S type only.
g the pipe after
own work.
or is in operation
mixed in the
losion and injuries 1 SELECTION OF INSTALLATION LOCATION
ing cycle.
he installation
staller.
cause serious
Install at location that meets the following conditions after getting approval from the customer.
ks, fire. ● Where the following installation space is available, and where air
nd gloves while ① Installation Space (on a flat surface)
does not gather.
ed. ● Where rain and sunlight do not directly hit the unit, and where ● Walls surrounding the unit in the four sides are not acceptable.
d, it can cause there is enough air circulation. ● There must be a 1-meter or large space in the above.
● Also, where the unit cannot be buried by snow. ● Where a danger of short-circuiting exists, install guide louvers.
ive device itself A location which can sustain the weight of the unit, and where ● When more than one unit are installed, provide sufficient intake space
noises and vibrations are not enhanced. consciously so that short-circuiting may not occur.
rotective device of ● When piling snow can bury the outdoor unit, provide proper snow guards.
● Where blasts of cold or hot air and noise do not bother the
er or the use of
r burst. neighbors.
● Where the unit does not receive heat radiation from other heat (mm)
sources. Examples of Air intake L3
installation Ⅰ Ⅱ Ⅲ L2
● Where there are no obstructions (animals, plants, etc.) to the Demensions No obstacles
suction inlet and blowing outlet. L1 Open Open 500 Air
(Service space for
intake electrical parts)
● Where water may drain out. L2 300 5 Open
Air outlet
※ Please avoid the following locations.
L3 150 300 150 ( Service
space ) L1
shocks due to
● Where there is constant exposure to harsh winds such as the
top floors of a building. Also, locations with exposure to salty air.
ration (cooling ● Where there are oil splashes, vapor, and smoke.
r is installed in
onditioner in ● Where there are possibilities of flammable gas leaks.
e possibility that
nce with the
status.
ch as
may appropriate Installation
door a little). In
opening port if ● In installing the unit, fix the unit’s legs with bolts specified on ① Anchor bolt fixed position ② Notabilia for installation
status due to the right.
partment etc. 76
19
● The protrusion of an anchor bolt on the front side must be kept 15 Intake
within 15 mm. Fasten with
bolts (M10-12)
● Securely install the unit so that it does not fall over during
370
rmance, corrosion
and fire.
- 170 -
①Remove the service panel. (Remove the screw of the service panel.)
②Remove the terminal cover. (Remove the screw of the terminal cover.)
③Connect the power supply cable and the connection wire securely to the terminal block. View of Terminal block
1) In wiring, make sure that the wire terminal numbers of outdoor unit terminal L N
block are match to the wire terminal numbers of indoor unit terminal block.
2) Terminal number A of the outdoor unit is used for A indoor unit and terminal 5 HEAT IN
number B for B indoor unit respectively. 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
Circuit Earth Heat insulati
④After connecting the wire, use wiring clamps to secure the wiring. breaker leakage unit A unit B unit C unit D unit E unit F
breaker Vinyl
⑤Fit the terminal cover and the service panel. indoor unit tape
Connection unit B
Outdoor
Liquid side ● When the total refrigerant pipe length for all the [Limit] unit A
Gas side rooms exceeds the length of the uncharged pipe piping length one indoor unit MAX 25m
(50m), additional refrigerant is required. all indoor unit MAX 90m
(If 50m or less, additonal charge is not required.) indoor
unit
Additonal charge amount per meter = 20g/m
indoor
unit EARTHIN
MAX 20m
○Connect the pipes on both liquid and gas sides. indoor
outdoor unit ○ Earth work sh
○Tighten the nuts to the following torque. Gas Leakage Test hight difference
Liquid side : 14.0∼18.0N・m (1.4∼1.8kgf・m)
MAX unit
indoor shock and no
25m unit
●Ensure that there are no gas leaks from the pipe ○ The connectio
Gas side ( 9.52): 33.0∼42.0N・m (3.3∼4.2kgf・m)
joints by using a leak detector or soap water.
(between the
indoor unit ) indoor
( 12.7): 49.0∼61.0N・m (4.9∼6.1kgf・m) MAX 20m unit dangerous fai
( 15.88): 68.0∼82.0N・m (6.8∼8.2kgf・m) indoor
Town gas pipe
unit
length of chargeless
refrigerant pipe 50m
- 171 -
4 AIR PURGING NOTE : Fully open the operation valves (on both liquid and gas sides) after completing air purging.
● Since the system uses service ports differing in diameter from those found ● Please use an anti-reverse flow type vacuum pump adapter so as to prevent
d securely. on the conventional models, a charge hose (for R22) presently in use is not vacuum pump oil from running back into the system. Oil running back into
applicable. Please use one designed specifically for R410A. an air-conditioning system may cause the refrigerant cycle to break down.
Terminal ● Remove the cap on both gas and liquid sides before starting operation. ● Conduct air purging for all connected indoor units.
cover
● After completing the operation, do not forget to tighten the cap (gas may leak).
Operation Valve Compound pressure gauge
Screw
Cap Pressure gauge
Operation Valve
Procedure (two-way valve) -0.1MPa
Gauge Manifold
(Designed specifically for R410A)
(-76cmHg)
(1) Secure all flare nuts on both indoor and outdoor sides to Handle Lo Handle Hi.
prevent leaks from the pipes.
Operation Valve Charge hose
(2) Connect the operation valves, charge hose, manifold Operation valve (three-way valve) (Designed specifically for R410A)
valve and vacuum pump as shown in the right figure. for room F
Vacuum pump adapter
(3) Fully open the handle Lo for the manifold valve, and Operation valve Operation Valve (Anti-reverse flow type)
pump a vacuum for 15 minutes. Ensure that the meter for room E Cap (Designed specifically for R410A)
is indicating -0.1MPa (-76cmHg). Operation valve
(4) After vacuuming, fully open the operation valve (both for room D Check joint Vacuum pump
Charge hose
liquid and gas sides) with a hexagon wrench. Operation valve (Designed specifically for R410A)
for room C
unit E unit F
Operation valve Securely tighten the operation valve cap and the check joint blind nut after adjustment.
for room B
Operation valve size Operation valve cap Check joint blind nut
Operation valve (mm) tightening torque (N·m) tightening torque (N·m)
block for room A
Open Open φ6.35 (1/4")
20 30
φ9.52 (3/8")
(5) Remove the charge hose from service port. 10 12
(6) Repeat the above steps (1) ~ (5) for all connected indoor units. φ12.7 (1/2") 25 35
unit E unit F (7) Ensure that there are no gas leaks from the joints in the indoor and outdoor units. φ15.88 (5/8") 30 40
2 3 1 2 3
RPC012A918 C
- 172 -
• Read the “SAFETY PRECAUTIONS” carefully first of all and strictly follow it • Keep the installation manual together with owner’s manual at a place where • Use the circuit breaker of correct capacity. Circuit breaker should falling from the installation place.
during the installation work in order to protect yourself. any user can read at any time. Moreover if necessary, ask to hand them to a be the one that disconnect all poles under over current. • For installation work, be careful not to get injured with the heat
• The precautionary items mentioned below are distinguished into two levels, new user. Using the incorrect one could cause the system failure and fire. exchanger, piping flare portion or screws etc.
WARNING and CAUTION . • For installing qualified personnel, take precautions in respect to themselves by • Install isolator or disconnect switch on the power supply wiring in • Be sure to insulate the refrigerant pipes so as not to condense the
WARNING : Wrong installation would cause serious consequences such using suitable protective clothing, groves, etc., and then perform the accordance with the local codes and regulations. ambient air moisture on them.
as injuries or death. installation works. The isolator should be locked in OFF state in accordance with EN60204-1. Insufficient insulation can cause condensation, which can lead to moisture
CAUTION : Wrong installation might cause serious consequences • Please pay attention not to fall down the tools, etc. when installing the unit at • Be sure to install indoor unit properly according to the installation damage on the ceiling, floor, furniture and any other valuables.
depending on circumstances. the high position. manual in order to run off the drainage smoothly. • When perform the air conditioner operation (cooling or drying opera-
Both mentions the important items to protect your health and safety so strictly • If unusual noise can be heard during operation, consult the dealer. Improper installation of indoor unit can cause dropping water into the room tion) in which ventilator is installed in the room. In this case, using the
follow them by any means. • The meanings of “Marks” used here are shown as follows: and damaging personal property. air conditioner in parallel with the ventilator, there is the possibility
• Be sure to confirm no anomaly on the equipment by commissioning after com- • Install the drainage pipe to run off drainage securely according to that drain water may backflow in accordance with the room lapse into
Never do it under any Always do it according to the
pleted installation and explain the operating methods as well as the maintenance the installation manual. the negative pressure status. Therefore, set up the opening port such
circumstances. instruction.
methods of this equipment to the user according to the owner’s manual. Incorrect installation of the drainage pipe can cause dropping water into the as incorporate the air into the room that may appropriate to ventila-
room and damaging personal property. tion (For example; Open the door a little). In addition, just as above, so
WARNING • Be sure to install the drainage pipe with descending slope of 1/100
or more, and not to make traps and air-bleedings.
set up the opening port if the room lapse into negative pressure status
due to register of the wind for the high rise apartment etc.
• Installation must be carried out by the qualified installer. • Tighten the flare nut by torque wrench with specified method. Check if the drainage runs off securely during commissioning and ensure • Be sure to perform air tightness test by pressurizing with nitrogen
If you install the system by yourself, it may cause serious trouble such as If the flare nut were tightened with excess torque, this may cause burst and the space for inspection and maintenance. gas after completed refrigerant piping work.
water leaks, electric shocks, fire and personal injury, as a result of a system refrigerant leakage after a long period. • Secure a space for installation, inspection and maintenance If the density of refrigerant exceeds the limit in the event of refrigerant
malfunction. Do not carry out the installation and maintenance work except • The electrical installation must be carried out by the qualified specified in the manual. leakage in the small room, lack of oxygen can occur, which can cause
the by qualified installer. electrician in accordance with “the norm for electrical work” and Insufficient space can result in accident such as personal injury due to serious accidents.
-
• Install the system in full accordance with the installation manual. “national wiring regulation”, and the system must be connected to
• Do not install the unit in the locations listed below. If leaked gases accumulate around the unit, it can cause fire.
173 -
Incorrect installation may cause bursts, personal injury, water leaks, electric the dedicated circuit.
shocks and fire. Power supply with insufficient capacity and incorrect function done by • Locations where carbon fiber, metal powder or any powder is floating. • Do not install the unit where corrosive gas (such as sulfurous acid
• Be sure to use only for household and residence. improper work can cause electric shocks and fire. • Locations where any substances that can affect the unit such as sulphide gas etc.) or combustible gas (such as thinner and petroleum gases)
If this appliance is installed in inferior environment such as machine shop • Be sure to shut off the power before starting electrical work. gas, chloride gas, acid and alkaline can occur. can accumulate or collect, or where volatile combustible
and etc., it can cause malfunction. Failure to shut off the power can cause electric shocks, unit failure or • Vehicles and ships. substances are handled.
• Use the original accessories and the specified components for incorrect function of equipment. • Locations where cosmetic or special sprays are often used. Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
installation. • Be sure to use the cables conformed to safety standard and cable • Locations with direct exposure of oil mist and steam such as kitchen and parts and etc. And combustible gas can cause fire.
If parts other than those prescribed by us are used, It may cause water ampacity for power distribution work. machine plant. • Do not use the indoor unit at the place where water splashes may
leaks, electric shocks, fire and personal injury. Unconformable cables can cause electric leak, anomalous heat production • Locations where any machines which generate high frequency harmonics occur such as in laundries.
• Install the unit in a location with good support. or fire. are used. Since the indoor unit is not waterproof, it can cause electric shocks and fire.
Unsuitable installation locations can cause the unit to fall and cause • This appliance must be connected to main power supply by means • Locations with salty atmospheres such as coastlines. • Do not install nor use the system close to the equipment that
material damage and personal injury. of a circuit breaker or switch (fuse:16A) with a contact separation of • Locations with heavy snow (If installed, be sure to provide base flame and generates electromagnetic fields or high frequency harmonics.
• Ventilate the working area well in the event of refrigerant leakage at least 3mm. snow hood mentioned in the manual). Equipment such as inverters, standby generators, medical high frequency
during installation. • When plugging this appliance, a plug conforming to the norm • Locations where the unit is exposed to chimney smoke. equipments and telecommunication equipments can affect the system, and
If the refrigerant comes into contact with naked flames, poisonous gas is IEC60884-1 must be used. • Locations at high altitude (more than 1000m high). cause malfunctions and breakdowns. The system can also affect medical
produced. • Use the prescribed cables for electrical connection, tighten the • Locations with ammonic atmospheres. equipment and telecommunication equipment, and obstruct its function or
• When installing in small rooms, take prevention measures not to cables securely in terminal block and relieve the cables correctly • Locations where heat radiation from other heat source can affect the unit. cause jamming.
exceed the density limit of refrigerant in the event of leakage, to prevent overloading the terminal blocks. • Locations without good air circulation. • Do not place any variables which will be damaged by getting wet
referred by the formula (accordance with ISO5149). Loose connections or cable mountings can cause anomalous heat • Locations with any obstacles which can prevent inlet and outlet air of the unit. under the indoor unit.
If the density of refrigerant exceeds the limit, please consult the dealer and production or fire. • Locations where short circuit of air can occur (in case of multiple units When the relative humidity is higher than 80% or drainage pipe is clogged,
install the ventilation system, otherwise lack of oxygen can occur, which • Arrange the wiring in the control box so that it cannot be pushed up installation). condensation or drainage water can drop and it can cause the damage of
can cause serious accident. further into the box. Install the service panel correctly. • Locations where strong air blows against the air outlet of outdoor unit. valuables.
• After completed installation, check that no refrigerant leaks from Incorrect installation may result in overheating and fire. • Locations where something located above the unit could fall. • Do not install the remote control at the direct sunlight.
the system. • Be sure to switch off the power supply in the event of installation, It can cause remarkable decrease in performance, corrosion and damage It can cause malfunction or deformation of the remote control.
If refrigerant leaks into the room and comes into contact with an oven or inspection or servicing. of components, malfunction and fire. • Do not use the unit for special purposes such as storing foods,
other hot surface, poisonous gas is produced. If the power supply is not shut off, there is a risk of electric shocks, unit • Do not install the indoor unit in the locations listed below (Be sure cooling precision instruments and preservation of animals, plants or
• Use the prescribed pipes, flare nuts and tools for R410A. failure or personal injury due to the unexpected start of fan. to install the indoor unit according to the installation manual for art.
'11 • SCM-SM-110
Using existing parts (for R22 or R407C) can cause the unit failure and • Be sure to wear protective goggles and gloves while at work. each model because each indoor unit has each limitation). It can cause the damage of the items.
serious accidents due to burst of the refrigerant circuit. • Earth leakage breaker must be installed. • Locations with any obstacles which can prevent inlet and outlet air of the • Do not use any materials other than a fuse with the correct rating
If the earth leakage breaker is not installed, it can cause electric shocks. unit. in the location where fuses are to be used.
• Locations where vibration can be amplified due to insufficient strength of Connecting the circuit with copper wire or other metal thread can cause
• Do not put the drainage pipe directly into drainage channels where • Do not processing, splice the power cord, or share a socket with structure. unit failure and fire.
poisonous gases such as sulphide gas can occur. other power plugs. • Locations where the infrared receiver is exposed to the direct sunlight or • Do not touch any buttons with wet hands.
Poisonous gases will flow into the room through drainage pipe and This may cause fire or electric shock due to defecting contact, defecting the strong light beam (in case of the infrared specification unit). It can cause electric shocks.
seriously affect the user’s health and safety. This can also cause the insulation and over-current etc. • Locations where an equipment affected by high harmonics is placed (TV • Do not touch any refrigerant pipes with your hands when the
corrosion of the indoor unit and a resultant unit failure or refrigerant leak. • Do not bundling, winding or processing for the power cord. Or, do set or radio receiver is placed within 5m). system is in operation.
• Ensure that no air enters in the refrigerant circuit when the unit is not deforming the power plug due to tread it. • Locations where drainage cannot run off safely. During operation the refrigerant pipes become extremely hot or extremely
installed and removed. This may cause fire or heating. It can affect performance or function and etc. cold depending the operating condition, and it can cause burn injury or
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit • Do not install the unit near the location where leakage of frost injury.
becomes too high, which can cause burst and personal injury. combustible gases can occur.
7.7
49
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
Necessary tools for the installation work
Indoor side Outdoor side b Top b c
295.7
35
222.5
35
48
48
1 Plus headed driver 5 Turn to
65 a tighten
58 54
'11 • SCM-SM-110
8 Hole core drill (65mm in diameter) left rear, left downward, right or
Piping in the left direction Piping in the right direction downward direction.
Drain hose
9 Wrench key (Hexagon) [4m/m] [Drain hose changing procedures]
Hold the bottom of the Tape only the portion
Indoor unit Installation Steps How to remove the indoor unit from the installation board
Latch 1 Pass the pipe through Wall
(2 locations) ① Push up at the marked portion of the indoor unit base lower latch, and slightly pull it
the hole in the wall, toward you. (both right and left hand sides) (The indoor unit base lower latch can be
and hook the upper removed from the installation board) Pipe accommodating section
part of the indoor unit ② Push up the indoor unit upward. So the indoor unit will be removed from the installation
to the installation board. board.
Drainage
Installation borad 2 Gently push the lower Arrange the drain hose in a downward angle CAUTION Go through all installation steps and check if the
Wall Installation part to secure the unit. Avoid the following drain piping. drainage is all right. Otherwise water leak may occur.
borad
Odor from
the gutter
The marked portion of the indoor
unit base lower latch. Higher than specified The drain hose Wavy The gap to the ground is The drain hose
tip is in water. 5 cm or less. tip is in the gutter.
Pour water to the drain pan located under the heat exchanger, and ensure that the water is discharged outdoor.
When the extended drain hose is indoor, securely insulate it with a heat insulator available in the market.
Liquid side ø6.35 : 9.1 (mm) Do not apply refrigerating machine ø6.35 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0
A Gas side ø9.52 : 13.2 (mm) oil to the flared surface.
Press ø9.52 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0
175 -
Flaring Use a flare tool designed for R410A or a conventional flare tool.
Remove the flared nuts. (on both liquid and gas sides) Install the removed flared nuts to the pipes to be connected, Please note that measurement B (protrusion from the flaring block) will vary depending on the
block
then flared the pipes. Copper pipe type of a flare tool in use.
If a coventional flare tool is used, please use a copper pipe gauge or a similar instrument to
check protrusion so that you can keep measurement B to a correct value.
Connection Insulation of the connection portion
Indoor Liquid side Cover the coupling with insulator and then cover it with tapes. Finishing work and fixing
Gas side
Vinyl tape Use an attached insulation pad for heat insulation.
Refrigerant piping
(Do not turn)
Connection wiring, Cover the exterior portion with outer tape and
Earth wiring shape the piping so it will match the contours
Connect the pipes on both liquid and gas sides. Outer tape of the route that the piping to take.
Tighten the nuts to the following torque. Position it so that the slit area faces upward. Also fix the wiring and pipings to the wall with
Drain hose
Liquid side (ø6.35) : 14.0 - 18.0 N·m (1.4 - 1.8 kgf·m) clamps.
Cover the indoor unit’s flare-connected joints, after they are checked for a gas leak, with an indoor Wood screw
Gas side (ø9.52) : 34.0 - 42.0 N·m (3.4 - 4.2 kgf·m)
unit heat insulating material and then wrap them with a tape with an attached insulation pad placed
(ø12.7) : 49.0 - 61.0 N·m (4.9 - 6.1 kgf·m)
over the heat insulating material’s slit area. Clamp
Open/close and detachment/attachment of the air inlet panel How to remove and fit the front panel
To open, pull the panel at both ends of lower part Removing
'11 • SCM-SM-110
and release latches, then pull up the panel until ① Remove the air inlet panel.
Set screws latch
you feel resistance. ② Remove the 5 set screws.
(The panel stops at approx. 60 open position) ③ Remove the 4 latches in the upper section.
To close, hold the panel at both ends of lower ④ Move the lower part of the panel forward and
part to lower downward and push it slightly until push upwards to remove.
the latch works.
To remove, pull up the panel to the position Fitting
shown in right illustration and pull it toward you. ① Do remove the air filter.
To install, insert the panel arm into the slot on the ② Cover the body with the front panel.
front panel from the position shown in right ③ Fit the 4 latches in the upper section.
illustration, hold the panel at both ends of lower ④ Tighten the 5 set screws.
part, lower it downward slowly, then push it ⑤ Fit the air filter.
slightly until the latch warks. ⑥ Fit the air inlet panel.
Preparation of indoor unit CAUTION 1. Open the air inlet panel and remove the air filters.
2. Install the filter holders, with the air-cleaning filters installed in the holders.
In case of faulty wiring connection, the indoor unit stops, and Service panel In the air conditioner.
then the run lamp turns on and the timer lamp blinks. • Each air-cleaning filter can be installed in the left or right filter holder.
Mounting of connecting wires 3. Install the air filters and close the inlet panel.
① Open the air inlet panel. Use cables for interconnection wiring to avoid loosening of the
② Remove the service panel. wires. Terminal block
③ Remove the wiring clamp CENELEC code for cables Required field cables.
④ Connect the connecting wire securely to the terminal block.
1 ) Connect the connection wire securely to the terminal H05RNR4G1.5 (example) or 245IEC57
block. If the wire is not affixed completely, contact will be H Harmonized cable type
poor, and it is dangerous as the terminal block may heat 05 300/500 volts
up and catch fire. R Natural-and/or synth, rubber wire insulation
2 ) Take care not to confuse the terminal numbers for indoor N Polychloroprene rubber conductors insulation
R Stranded core
and outdoor connections.
4or5 Number of conductors
3 ) Fix the connection wire using the wiring clamp.
G One conductor of the cable is the earth conductor
⑤ Fix the connecting wire by wiring clamp. (yellow/green) Clamp
⑥ Attach the service panel. 1.5 Section of copper wire (mm2)
⑦ Close the air inlet panel. Filter holder
Air-cleaning filter
Power cables and crossover wires are securely fixed to the terminal board.
176 -
HOW TO RELOCATE OR DISPOSE OF THE UNIT CONCERNING TERMINAL CONNECTION FOR AN INTERFACE
In order to protect the environment, be sure to pump down (recovery of refrigerant). Forced cooling operation
Pump down is the method of recovering refrigerant from the indoor unit to the Turn on a power supply again after a while after turn off a power supply. ① Remove the front panel and lid of control.
outdoor unit when the pipes are removed from the unit. Then press continually the ON/OFF button 5 seconds or more. ② There is a terminal (respectively marked with CNS) for the indoor control board.
In connecting an interface, connect to the respective terminal securely with the connection harness supplied
<How to pump down> with an optional “Interface connection kit SC-BIKN-E” and fasten the connection harness onto the indoor control
① Connect charge hose to service port of outdoor unit. box with the clamp supplied with the kit.
② Liquid side : Close the liquid valve with hexagon wrench key. For more details, please refer to the user's manual of your “Interface connection kit SC-BIKN-E”.
Gas side : Fully open the gas valve
Carry out cooling operation . (If indoor temperature is low, operate
forced cooling operation.)
'11 • SCM-SM-110
③ After low pressure gauge become 0.01MPa, stop cooling operation
and close the gas valve.
Unit ON/OFF button
the by qualified installer. electrician in accordance with “the norm for electrical work” and Insufficient space can result in accident such as personal injury due to serious accidents.
177 -
• Install the system in full accordance with the installation manual. “national wiring regulation”, and the system must be connected to
Incorrect installation may cause bursts, personal injury, water leaks, electric the dedicated circuit. • Do not install the unit in the locations listed below. If leaked gases accumulate around the unit, it can cause fire.
shocks and fire. Power supply with insufficient capacity and incorrect function done by • Locations where carbon fiber, metal powder or any powder is floating. • Do not install the unit where corrosive gas (such as sulfurous acid
• Be sure to use only for household and residence. improper work can cause electric shocks and fire. • Locations where any substances that can affect the unit such as sulphide gas etc.) or combustible gas (such as thinner and petroleum gases)
If this appliance is installed in inferior environment such as machine shop • Be sure to shut off the power before starting electrical work. gas, chloride gas, acid and alkaline can occur. can accumulate or collect, or where volatile combustible
and etc., it can cause malfunction. Failure to shut off the power can cause electric shocks, unit failure or • Vehicles and ships. substances are handled.
• Use the original accessories and the specified components for incorrect function of equipment. • Locations where cosmetic or special sprays are often used. Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
installation. • Be sure to use the cables conformed to safety standard and cable • Locations with direct exposure of oil mist and steam such as kitchen and parts and etc. And combustible gas can cause fire.
If parts other than those prescribed by us are used, It may cause water ampacity for power distribution work. machine plant. • Do not use the indoor unit at the place where water splashes may
leaks, electric shocks, fire and personal injury. Unconformable cables can cause electric leak, anomalous heat production • Locations where any machines which generate high frequency harmonics occur such as in laundries.
• Install the unit in a location with good support. or fire. are used. Since the indoor unit is not waterproof, it can cause electric shocks and fire.
Unsuitable installation locations can cause the unit to fall and cause • This appliance must be connected to main power supply by means • Locations with salty atmospheres such as coastlines. • Do not install nor use the system close to the equipment that
material damage and personal injury. of a circuit breaker or switch (fuse:16A) with a contact separation of • Locations with heavy snow (If installed, be sure to provide base flame and generates electromagnetic fields or high frequency harmonics.
• Ventilate the working area well in the event of refrigerant leakage at least 3mm. snow hood mentioned in the manual). Equipment such as inverters, standby generators, medical high frequency
during installation. • When plugging this appliance, a plug conforming to the norm • Locations where the unit is exposed to chimney smoke. equipments and telecommunication equipments can affect the system, and
If the refrigerant comes into contact with naked flames, poisonous gas is IEC60884-1 must be used. • Locations at high altitude (more than 1000m high). cause malfunctions and breakdowns. The system can also affect medical
produced. • Use the prescribed cables for electrical connection, tighten the • Locations with ammonic atmospheres. equipment and telecommunication equipment, and obstruct its function or
• When installing in small rooms, take prevention measures not to cables securely in terminal block and relieve the cables correctly to • Locations where heat radiation from other heat source can affect the unit. cause jamming.
exceed the density limit of refrigerant in the event of leakage, prevent overloading the terminal blocks. • Locations without good air circulation. • Do not place any variables which will be damaged by getting wet
referred by the formula (accordance with ISO5149). Loose connections or cable mountings can cause anomalous heat • Locations with any obstacles which can prevent inlet and outlet air of the unit. under the indoor unit.
If the density of refrigerant exceeds the limit, please consult the dealer and production or fire. • Locations where short circuit of air can occur (in case of multiple units When the relative humidity is higher than 80% or drainage pipe is clogged,
install the ventilation system, otherwise lack of oxygen can occur, which • Arrange the wiring in the control box so that it cannot be pushed up installation). condensation or drainage water can drop and it can cause the damage of
can cause serious accident. further into the box. Install the service panel correctly. • Locations where strong air blows against the air outlet of outdoor unit. valuables.
• After completed installation, check that no refrigerant leaks from Incorrect installation may result in overheating and fire. • Locations where something located above the unit could fall. • Do not install the remote control at the direct sunlight.
the system. • Be sure to switch off the power supply in the event of installation, It can cause remarkable decrease in performance, corrosion and damage It can cause malfunction or deformation of the remote control.
If refrigerant leaks into the room and comes into contact with an oven or inspection or servicing. of components, malfunction and fire. • Do not use the unit for special purposes such as storing foods,
other hot surface, poisonous gas is produced. If the power supply is not shut off, there is a risk of electric shocks, unit • Do not install the indoor unit in the locations listed below (Be sure cooling precision instruments and preservation of animals, plants or
• Use the prescribed pipes, flare nuts and tools for R410A. failure or personal injury due to the unexpected start of fan. to install the indoor unit according to the installation manual for art.
'11 • SCM-SM-110
Using existing parts (for R22 or R407C) can cause the unit failure and • Be sure to wear protective goggles and gloves while at work. each model because each indoor unit has each limitation). It can cause the damage of the items.
serious accidents due to burst of the refrigerant circuit. • Earth leakage breaker must be installed. • Locations with any obstacles which can prevent inlet and outlet air of the • Do not use any materials other than a fuse with the correct rating in
If the earth leakage breaker is not installed, it can cause electric shocks. unit. the location where fuses are to be used.
• Locations where vibration can be amplified due to insufficient strength of Connecting the circuit with copper wire or other metal thread can cause
• Do not put the drainage pipe directly into drainage channels where • Do not processing, splice the power cord, or share a socket with structure. unit failure and fire.
poisonous gases such as sulphide gas can occur. other power plugs. • Locations where the infrared receiver is exposed to the direct sunlight or • Do not touch any buttons with wet hands.
Poisonous gases will flow into the room through drainage pipe and This may cause fire or electric shock due to defecting contact, defecting the strong light beam (in case of the infrared specification unit). It can cause electric shocks.
seriously affect the user’s health and safety. This can also cause the insulation and over-current etc. • Locations where an equipment affected by high harmonics is placed (TV • Do not touch any refrigerant pipes with your hands when the
corrosion of the indoor unit and a resultant unit failure or refrigerant leak. • Do not bundling, winding or processing for the power cord. Or, do set or radio receiver is placed within 1m). system is in operation.
• Ensure that no air enters in the refrigerant circuit when the unit is not deforming the power plug due to tread it. • Locations where drainage cannot run off safely. During operation the refrigerant pipes become extremely hot or extremely
installed and removed. This may cause fire or heating. It can affect performance or function and etc. cold depending the operating condition, and it can cause burn injury or
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit • Do not install the unit near the location where leakage of frost injury.
becomes too high, which can cause burst and personal injury. combustible gases can occur.
BEFORE INSTALLATION
○ Before installation check that the power supply matches the air conditioner.
SELECTION OF INSTALLATION LOCATION 5 cm mi
nim
(Install at location that meets the following conditions, after getting approval from the customer)
from the um
wall 6.5 cm minimum from the ceiling
Indoor unit
Standard accessories (Installation kit) Installation board
Q’ty ○ Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed.
10 cm mi
Accessories for indoor unit ○ A solid place where the unit or the wall will not vibrate. nim
○ A place where there will be enough space for servicing. (Where space mentioned below can be secured) from the um
Installation board wall
1 1 ○ Where wiring and the piping work will be easy to conduct.
(Attached to the rear of the indoor unit) ○ The place where receiving part is not exposed to the direct rays of the sun or the strong rays of the street lighting.
○ A place where it can be easily drained.
2 Wireless remote control 1 ○ A place separated at least 1m away from the television or the radio. (To prevent interference to images and sounds.)
○ Places where this unit is not affected by the high frequency equipment or electric equipment.
○ Avoid installing this unit in place where there is much oil mist.
3 Remote control holder 1
○ Places where there is no electric equipment or household under the installing unit.
Tapping screws Wireless remote control
4 (for installation board ø4 X 25mm) 5
○ A place where the air conditioner can be received the signal surely during operating the wireless remote control.
Wood screws ○ Places where there is no affected by the TV and radio etc. CAUTION Indoor side Outdoor side
5 (for remote control switch holder ø3.5 X 16mm) 2 ○ Do not place where exposed to direct sunlight or near heat devices such as a stove. Completely seal the hole on putty Sleeve
the wall with putty. Otherwise,
6 Battery [R03 (AAA, Micro) 1.5V] 2
INSTALLATION OF INDOOR UNIT furniture, or other, may be
wetted by leaked water or putty
(sold separately)
Sealing plate 1 Mating mark for Mounting Relation between setting plate and indoor unit
level surface board
Mounting
Max.10
Sleeve 1
board INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
Indoor unit
65 Space for service
Piping cover
(for insulation of connection piping)
1
Drilling of holes and fixture of sleeve (Option parts)
Downloaded from www.Manualslib.com manuals search engine
279.1
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
47
WARNING • Be sure to install the drainage pipe with descending slope of 1/100
or more, and not to make traps and air-bleedings.
set up the opening port if the room lapse into negative pressure status
due to register of the wind for the high rise apartment etc.
• Installation must be carried out by the qualified installer. • Tighten the flare nut by torque wrench with specified method. Check if the drainage runs off securely during commissioning and ensure • Be sure to perform air tightness test by pressurizing with nitrogen
If you install the system by yourself, it may cause serious trouble such as If the flare nut were tightened with excess torque, this may cause burst and the space for inspection and maintenance. gas after completed refrigerant piping work.
water leaks, electric shocks, fire and personal injury, as a result of a system refrigerant leakage after a long period. • Secure a space for installation, inspection and maintenance If the density of refrigerant exceeds the limit in the event of refrigerant
malfunction. Do not carry out the installation and maintenance work except • The electrical installation must be carried out by the qualified specified in the manual. leakage in the small room, lack of oxygen can occur, which can cause
the by qualified installer. electrician in accordance with “the norm for electrical work” and Insufficient space can result in accident such as personal injury due to serious accidents.
• Install the system in full accordance with the installation manual. “national wiring regulation”, and the system must be connected to
Incorrect installation may cause bursts, personal injury, water leaks, electric the dedicated circuit. • Do not install the unit in the locations listed below. If leaked gases accumulate around the unit, it can cause fire.
shocks and fire. Power supply with insufficient capacity and incorrect function done by • Locations where carbon fiber, metal powder or any powder is floating. • Do not install the unit where corrosive gas (such as sulfurous acid
• Be sure to use only for household and residence. improper work can cause electric shocks and fire. • Locations where any substances that can affect the unit such as sulphide gas etc.) or combustible gas (such as thinner and petroleum gases)
If this appliance is installed in inferior environment such as machine shop • Be sure to shut off the power before starting electrical work. gas, chloride gas, acid and alkaline can occur. can accumulate or collect, or where volatile combustible
and etc., it can cause malfunction. Failure to shut off the power can cause electric shocks, unit failure or • Vehicles and ships. substances are handled.
• Use the original accessories and the specified components for incorrect function of equipment. • Locations where cosmetic or special sprays are often used. Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
installation. • Be sure to use the cables conformed to safety standard and cable • Locations with direct exposure of oil mist and steam such as kitchen and parts and etc. And combustible gas can cause fire.
If parts other than those prescribed by us are used, It may cause water ampacity for power distribution work. machine plant. • Do not use the indoor unit at the place where water splashes may
leaks, electric shocks, fire and personal injury. Unconformable cables can cause electric leak, anomalous heat production • Locations where any machines which generate high frequency harmonics occur such as in laundries.
• Install the unit in a location with good support. or fire. are used. Since the indoor unit is not waterproof, it can cause electric shocks and fire.
Unsuitable installation locations can cause the unit to fall and cause • This appliance must be connected to main power supply by means • Locations with salty atmospheres such as coastlines. • Do not install nor use the system close to the equipment that
material damage and personal injury. of a circuit breaker or switch (fuse:16A) with a contact separation of • Locations with heavy snow (If installed, be sure to provide base flame and generates electromagnetic fields or high frequency harmonics.
• Ventilate the working area well in the event of refrigerant leakage at least 3mm. snow hood mentioned in the manual). Equipment such as inverters, standby generators, medical high frequency
during installation. • When plugging this appliance, a plug conforming to the norm • Locations where the unit is exposed to chimney smoke. equipments and telecommunication equipments can affect the system, and
If the refrigerant comes into contact with naked flames, poisonous gas is IEC60884-1 must be used. • Locations at high altitude (more than 1000m high). cause malfunctions and breakdowns. The system can also affect medical
produced. • Use the prescribed cables for electrical connection, tighten the • Locations with ammonic atmospheres. equipment and telecommunication equipment, and obstruct its function or
• When installing in small rooms, take prevention measures not to cables securely in terminal block and relieve the cables correctly to • Locations where heat radiation from other heat source can affect the unit. cause jamming.
exceed the density limit of refrigerant in the event of leakage, prevent overloading the terminal blocks. • Locations without good air circulation. • Do not place any variables which will be damaged by getting wet
referred by the formula (accordance with ISO5149). Loose connections or cable mountings can cause anomalous heat • Locations with any obstacles which can prevent inlet and outlet air of the unit. under the indoor unit.
If the density of refrigerant exceeds the limit, please consult the dealer and production or fire. • Locations where short circuit of air can occur (in case of multiple units When the relative humidity is higher than 80% or drainage pipe is clogged,
install the ventilation system, otherwise lack of oxygen can occur, which • Arrange the wiring in the control box so that it cannot be pushed up installation). condensation or drainage water can drop and it can cause the damage of
can cause serious accident. further into the box. Install the service panel correctly. • Locations where strong air blows against the air outlet of outdoor unit. valuables.
• After completed installation, check that no refrigerant leaks from Incorrect installation may result in overheating and fire. • Locations where something located above the unit could fall. • Do not install the remote control at the direct sunlight.
the system. • Be sure to switch off the power supply in the event of installation, It can cause remarkable decrease in performance, corrosion and damage It can cause malfunction or deformation of the remote control.
If refrigerant leaks into the room and comes into contact with an oven or inspection or servicing. of components, malfunction and fire. • Do not use the unit for special purposes such as storing foods,
other hot surface, poisonous gas is produced. If the power supply is not shut off, there is a risk of electric shocks, unit • Do not install the indoor unit in the locations listed below (Be sure cooling precision instruments and preservation of animals, plants or
• Use the prescribed pipes, flare nuts and tools for R410A. failure or personal injury due to the unexpected start of fan. to install the indoor unit according to the installation manual for art.
Using existing parts (for R22 or R407C) can cause the unit failure and • Be sure to wear protective goggles and gloves while at work. each model because each indoor unit has each limitation). It can cause the damage of the items.
serious accidents due to burst of the refrigerant circuit. • Earth leakage breaker must be installed. • Locations with any obstacles which can prevent inlet and outlet air of the • Do not use any materials other than a fuse with the correct rating in
If the earth leakage breaker is not installed, it can cause electric shocks. unit. the location where fuses are to be used.
• Locations where vibration can be amplified due to insufficient strength of Connecting the circuit with copper wire or other metal thread can cause
• Do not put the drainage pipe directly into drainage channels where • Do not processing, splice the power cord, or share a socket with structure. unit failure and fire.
poisonous gases such as sulphide gas can occur. other power plugs. • Locations where the infrared receiver is exposed to the direct sunlight or • Do not touch any buttons with wet hands.
Poisonous gases will flow into the room through drainage pipe and This may cause fire or electric shock due to defecting contact, defecting the strong light beam (in case of the infrared specification unit). It can cause electric shocks.
seriously affect the user’s health and safety. This can also cause the insulation and over-current etc. • Locations where an equipment affected by high harmonics is placed (TV • Do not touch any refrigerant pipes with your hands when the
corrosion of the indoor unit and a resultant unit failure or refrigerant leak. • Do not bundling, winding or processing for the power cord. Or, do set or radio receiver is placed within 1m). system is in operation.
• Ensure that no air enters in the refrigerant circuit when the unit is not deforming the power plug due to tread it. • Locations where drainage cannot run off safely. During operation the refrigerant pipes become extremely hot or extremely
installed and removed. This may cause fire or heating. It can affect performance or function and etc. cold depending the operating condition, and it can cause burn injury or
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit • Do not install the unit near the location where leakage of frost injury.
becomes too high, which can cause burst and personal injury. combustible gases can occur.
BEFORE INSTALLATION
○ Before installation check that the power supply matches the air conditioner.
SELECTION OF INSTALLATION LOCATION 5 cm mi
nim
(Install at location that meets the following conditions, after getting approval from the customer)
from the um
wall 6.5 cm minimum from the ceiling
Indoor unit
Standard accessories (Installation kit) Installation board
Q’ty ○ Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed.
10 cm mi
Accessories for indoor unit ○ A solid place where the unit or the wall will not vibrate. nim
○ A place where there will be enough space for servicing. (Where space mentioned below can be secured) from the um
Installation board wall
1 1 ○ Where wiring and the piping work will be easy to conduct.
(Attached to the rear of the indoor unit) ○ The place where receiving part is not exposed to the direct rays of the sun or the strong rays of the street lighting.
○ A place where it can be easily drained.
2 Wireless remote control 1 ○ A place separated at least 1m away from the television or the radio. (To prevent interference to images and sounds.)
○ Places where this unit is not affected by the high frequency equipment or electric equipment.
○ Avoid installing this unit in place where there is much oil mist.
3 Remote control holder 1
○ Places where there is no electric equipment or household under the installing unit.
Tapping screws Wireless remote control
4 (for installation board ø4 X 25mm) 5
○ A place where the air conditioner can be received the signal surely during operating the wireless remote control.
Wood screws ○ Places where there is no affected by the TV and radio etc. CAUTION Indoor side Outdoor side
5 (for remote control switch holder ø3.5 X 16mm) 2 ○ Do not place where exposed to direct sunlight or near heat devices such as a stove. Completely seal the hole on putty Sleeve
the wall with putty. Otherwise,
6 Battery [R03 (AAA, Micro) 1.5V] 2
INSTALLATION OF INDOOR UNIT furniture, or other, may be
wetted by leaked water or putty
(sold separately)
Sealing plate 1 Mating mark for Mounting Relation between setting plate and indoor unit
level surface board
Mounting
Max.10
Sleeve 1
board INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
Indoor unit
Inclination plate 1 be conducted with four screws in a temporary tightened state. Installation board
○ Adjust so the board will be 50 Space for service Space for service 100
178 -
7.7
48.9
Piping cover
(for insulation of connection piping)
1
Drilling of holes and fixture of sleeve (Option parts)
279.1
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
47
Necessary tools for the installation work
b Top b c
5
4 Tape measure Installing the support of piping • Matters of special notice when piping from left or central/rear of the unit.
[Top view] [Drain hose changing procedures]
5 Hammer In case of piping in the right rear direction Left-hand-side piping Right-hand-side piping 1. Remove the drain hose 2. Remove the drain cap.
Shaping of pipings Taping of the exterior Piping in the left rear direction Piping in the right rear direction
6 Spanner wrench
Pipings
7 Torque wrench ( 14.0
(1.4 ~ 6.1kgf·m) )
~ 61.0N·m
8 Hole core drill (65mm in diameter) Piping in the left direction Piping in the right direction ○ Remove the screw and drain hose, ○ Remove it with hand or pliers.
'11 • SCM-SM-110
Drain hose making it rotate.
9 Wrench key (Hexagon) [4m/m] ○ Hold the bottom of the ○ Tape only the portion Piping is possible in the rear, left, left rear, left downward, right or downward direction. 3. Insert the drain cap. 4. Connect the drain hose.
piping and fix direction that goes through the
10 Flaring tool set ( Designed specifically
for R410A ) before stretching it and
shaping it.
wall.
○ Always tape the wiring Right
Gas leak detector ( )
Designed specifically with the piping.
11 for R410A
Sufficient care must be taken not to damage
Gauge for projection adjustment
the panel when connecting pipes.
( )
12 Used when flare is made by using Rear ○ Insert the drain cap which was removed ○ Insert the drain hose securely, making
Left
conventional flare tool Downward rear at procedure “2” securely using a rotate. And install the screw.
Left hexagonal wrench etc. Note: Be careful that If it is not Inserted
Left downward Note: Be careful that If it is not Inserted securely, water leakage may
13 Pipe bender securely, water leakage may occur. occur.
Fixing of indoor unit Since this air conditioner has been designed to collect dew drops on the rear
Gutter
surface to the drain pan, do not attach the power cord above the gutter.
Latch (2 locations) Installation Steps • How to remove the indoor unit from the installation board
Wall
1 Pass the pipe through 1 Push up at the marked portion of the indoor unit base lower latch, and slightly
the hole in the wall, pull it toward you. (both right and left hand sides) (The indoor unit base lower
Indoor unit and hook the upper latch can be removed from the installation board) Pipe accommodating section
part of the indoor unit 2 Push up the indoor unit upward. So the indoor unit will be removed from the
to the installation board. installation board.
Drainage
2 Gently push the lower
○ Arrange the drain hose in a downward angle. CAUTION Go through all installation steps and check if the
part to secure the unit.
○ Avoid the following drain piping. drainage is all right. Otherwise water leak may occur.
Installation board
Wall
Installation board Odor from
the gutter
Indoor unit base latch Higher than specified The drain hose Wavy The gap to the ground is The drain hose
tip is in water. 5 cm or less. tip is in the gutter.
The marked portion of the indoor unit base lower latch.
○ Pour water to the drain pan located under the heat exchanger, and ensure that the water is discharged outdoor.
○ When the extended drain hose is indoor, securely insulate it with a heat insulator available in the market.
Indoor CAUTION Indoor Liquid side Cover the coupling with insulator and then cover it with tapes.
Dimension A Gas side
90 ± 0.5˚
Liquid side ø6.35 : 9.1 (mm) Do not apply refrigerating machine Vinyl tape Use an attached insulation pad for heat insulation.
A
-
Press Gas side ø9.52 : 13.2 (mm) oil to the flared surface.
(Do not turn) (Do not turn)
Remove ø12.7 : 16.6 (mm)
179 -
○ Remove the flared nuts. (on both liquid and gas sides) ○ Install the removed flared nuts to the pipes to be connected, ○ Connect the pipes on both liquid and gas sides.
then flared the pipes. ○ Tighten the nuts to the following torque. Position it so that the slit area faces upward.
Liquid side (ø6.35) : 14.0 - 18.0 N·m (1.4 - 1.8 kgf·m)
• Flaring work Gas side (ø9.52) : 34.0 - 42.0 N·m (3.4 - 4.2 kgf·m) • Cover the indoor unit s flare-connected joints, after they are checked for a gas leak,
Measurement B (mm)
(ø12.7) : 49.0 - 61.0 N·m (4.9 - 6.1 kgf·m) with an indoor unit heat insulating material and then wrap them with a tape with an
Copper pipe diameter Clutch type flare tool for Conventional (R22) flare tool attached insulation pad placed over the heat insulating material’s slit area.
Measurement B R410A Clutch type Wing nut type
CAUTION
ø6.35 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0
ø9.52 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0
Do not apply excess torque to the flared nuts. Finishing work and fixing
Otherwise, the flared nuts may check depending.
ø12.7 0.0 - 0.5 1.0 - 1.5 2.0 - 2.5
Refrigerant piping
Flaring Use a flare tool designed for R410A or a conventional flare tool.
block Please note that measurement B (protrusion from the flaring block) will vary depending on the Connection wiring, Cover the exterior portion with outer tape and
Copper pipe type of a flare tool in use. Earth wiring shape the piping so it will match the contours
If a conventional flare tool is used, please use a copper pipe gauge or a similar instrument to Outer tape of the route that the piping to take.
check protrusion so that you can keep measurement B to a correct value. Drain hose Also fix the wiring and pipings to the wall with
Wood screw clamps.
Clamp
Open/close and detachment/attachment of the air inlet panel How to remove and fit the front panel
○ To open, pull the panel at both ends of lower part ○ Removing
and release latches, then pull up the panel until 1 Remove the air inlet panel.
'11 • SCM-SM-110
you feel resistance. 2 Remove the 2 set screws.
(The panel stops at approx. 60° open position) 3 Remove the 3 latches in the upper section.
○ To close, hold the panel at both ends of lower 4 Move the lower part of the panel forward and
part to lower downward and push it slightly until push upwards to remove.
the latch works.
○ To remove, pull up the panel to the position ○ Fitting
shown in right illustration and pull it toward you. 1 Do remove the air filter.
○ To install, insert the panel arm into the slot on the 2 Cover the body with the front panel.
front panel from the position shown in right 3 Fit the 3 latches in the upper section.
illustration, hold the panel at both ends of lower 4 Tighten the 2 set screws.
part, lower it downward slowly, then push it 5 Fit the air filter.
slightly until the latch works. 6 Fit the air inlet panel.
Set screws
ELECTRICAL WIRING WORK The screws of the lid and the terminal
cover are tightened securely. Lid
Installing the air-cleaning filters
Preparation of indoor unit CAUTION 1. Open the air inlet panel and remove the air filters.
2. Install the filter holders, with the air-cleaning filters installed in the holders.
In case of faulty wiring connection, the indoor unit stops, and Terminal In the air conditioner.
then the run lamp turns on and the timer lamp blinks. Terminal block
cover • Each air-cleaning filter can be installed in the left or right filter holder.
Mounting of connecting wires 3. Install the air filters and close the inlet panel.
1 Remove the lid. Use cables for interconnection wiring to avoid loosening of the
2 Remove the terminal cover. wires.
3 Remove the wiring clamp. CENELEC code for cables Required field cables.
4 Connect the connecting wire securely to the terminal block. 1 2N 3
1) Connect the connection wire securely to the terminal H05RNR4G1.5 (example) or 245IEC57
block. If the wire is not affixed completely, contact will be H Harmonized cable type
poor, and it is dangerous as the terminal block may heat 05 300/500 volts
up and catch fire. R Natural-and/or synth, rubber wire insulation
2) Take care not to confuse the terminal numbers for indoor N Polychloroprene rubber conductors insulation
R Stranded core Air-cleaning filter
and outdoor connections. Filter holder
5 Fix the connecting wire by wiring clamp. 4or5 Number of conductors
6 Attach the terminal cover. G One conductor of the cable is the earth conductor
7 Attach the lid. (yellow/green)
1.5 Section of copper wire (mm2)
Clamp
90 ± 0.5˚
Liquid side ø6.35 : 9.1 (mm) Do not apply refrigerating machine Vinyl tape Use an attached insulation pad for heat insulation.
Press A Gas side ø9.52 : 13.2 (mm) oil to the flared surface.
(Do not turn) (Do not turn)
Remove ø12.7 : 16.6 (mm)
○ Remove the flared nuts. (on both liquid and gas sides) ○ Install the removed flared nuts to the pipes to be connected, ○ Connect the pipes on both liquid and gas sides.
then flared the pipes. ○ Tighten the nuts to the following torque. Position it so that the slit area faces upward.
Liquid side (ø6.35) : 14.0 - 18.0 N·m (1.4 - 1.8 kgf·m)
• Flaring work Gas side (ø9.52) : 34.0 - 42.0 N·m (3.4 - 4.2 kgf·m) • Cover the indoor unit s flare-connected joints, after they are checked for a gas leak,
Measurement B (mm)
(ø12.7) : 49.0 - 61.0 N·m (4.9 - 6.1 kgf·m) with an indoor unit heat insulating material and then wrap them with a tape with an
Copper pipe diameter Clutch type flare tool for Conventional (R22) flare tool attached insulation pad placed over the heat insulating material’s slit area.
Measurement B R410A Clutch type Wing nut type
CAUTION
ø6.35 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0
ø9.52 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0
Do not apply excess torque to the flared nuts. Finishing work and fixing
Otherwise, the flared nuts may check depending.
ø12.7 0.0 - 0.5 1.0 - 1.5 2.0 - 2.5
Refrigerant piping
Flaring Use a flare tool designed for R410A or a conventional flare tool.
block Please note that measurement B (protrusion from the flaring block) will vary depending on the Connection wiring, Cover the exterior portion with outer tape and
Copper pipe type of a flare tool in use. Earth wiring shape the piping so it will match the contours
If a conventional flare tool is used, please use a copper pipe gauge or a similar instrument to Outer tape of the route that the piping to take.
check protrusion so that you can keep measurement B to a correct value. Drain hose Also fix the wiring and pipings to the wall with
Wood screw clamps.
Clamp
Open/close and detachment/attachment of the air inlet panel How to remove and fit the front panel
○ To open, pull the panel at both ends of lower part ○ Removing
and release latches, then pull up the panel until 1 Remove the air inlet panel.
you feel resistance. 2 Remove the 2 set screws.
(The panel stops at approx. 60° open position) 3 Remove the 3 latches in the upper section.
○ To close, hold the panel at both ends of lower 4 Move the lower part of the panel forward and
part to lower downward and push it slightly until push upwards to remove.
the latch works.
○ To remove, pull up the panel to the position ○ Fitting
shown in right illustration and pull it toward you. 1 Do remove the air filter.
○ To install, insert the panel arm into the slot on the 2 Cover the body with the front panel.
front panel from the position shown in right 3 Fit the 3 latches in the upper section.
illustration, hold the panel at both ends of lower 4 Tighten the 2 set screws.
part, lower it downward slowly, then push it 5 Fit the air filter.
slightly until the latch works. 6 Fit the air inlet panel.
Set screws
ELECTRICAL WIRING WORK The screws of the lid and the terminal
cover are tightened securely. Lid
Installing the air-cleaning filters
Preparation of indoor unit CAUTION 1. Open the air inlet panel and remove the air filters.
2. Install the filter holders, with the air-cleaning filters installed in the holders.
In case of faulty wiring connection, the indoor unit stops, and Terminal In the air conditioner.
then the run lamp turns on and the timer lamp blinks. Terminal block
cover • Each air-cleaning filter can be installed in the left or right filter holder.
Mounting of connecting wires 3. Install the air filters and close the inlet panel.
1 Remove the lid. Use cables for interconnection wiring to avoid loosening of the
2 Remove the terminal cover. wires.
3 Remove the wiring clamp. CENELEC code for cables Required field cables.
4 Connect the connecting wire securely to the terminal block. 1 2N 3
1) Connect the connection wire securely to the terminal H05RNR4G1.5 (example) or 245IEC57
block. If the wire is not affixed completely, contact will be H Harmonized cable type
poor, and it is dangerous as the terminal block may heat 05 300/500 volts
up and catch fire. R Natural-and/or synth, rubber wire insulation
2) Take care not to confuse the terminal numbers for indoor N Polychloroprene rubber conductors insulation
R Stranded core Air-cleaning filter
and outdoor connections. Filter holder
5 Fix the connecting wire by wiring clamp. 4or5 Number of conductors
6 Attach the terminal cover. G One conductor of the cable is the earth conductor
7 Attach the lid. (yellow/green)
1.5 Section of copper wire (mm2)
Clamp
The screws of the lid and the terminal cover are tightened securely.
CAUTION Operation valve is fully open.
6 Battery The pipe joints for indoor and outdoor pipes have been insulated.
Do not use new and
old batteries together. Test run
2 Wireless remote control Air conditioning operation is normal. Operation of the unit has been explained to the customer.
No abnormal noise. (Three-minutes restart preventive timer)
Cover 5 Wood screws Water drains smoothly. When the air conditioner is restarted or when changing the operation, the unit
ø3.5 X 16 Protective functions are not working. will not start operating for approximately 3 minutes.
The remote control is normal. This is to protect the unit and it is not a malfunction.
HOW TO RELOCATE OR DISPOSE OF THE UNIT CONCERNING TERMINAL CONNECTION FOR AN INTERFACE
○ In order to protect the environment, be sure to pump down (recovery of refrigerant). • Forced cooling operation 1 Remove the front panel and lid of control.
○ Pump down is the method of recovering refrigerant from the indoor unit to the Turn on a power supply again after a while after turn off a power supply. 2 Remove the control. Indoor unit PCB
outdoor unit when the pipes are removed from the unit. Then press continually the ON/OFF button 5 seconds or more. 3 There is a terminal (respectively marked with CNS) for the indoor control board.
In connecting an interface, connect to the respective terminal securely with the connection harness Lid of control
<How to pump down> supplied with an optional “Interface connection kit SC-BIKN-E” and fasten the connection harness
1 Connect charge hose to check joint of outdoor unit. onto the indoor control box with the clamp supplied with the kit.
2 Liquid side : Close the liquid valve with hexagon wrench key. For more details, please refer to the user’s manual of your “Interface connection kit SC-BIKN-E”.
Gas side : Fully open the gas valve.
Carry out cooling operation. (If indoor temperature is low, operate
'11 • SCM-SM-110
forced cooling operation.) CNS terminal
3 After low pressure gauge become 0.01MPa, stop cooling operation
and close the gas valve.
malfunction. Do not carry out the installation and maintenance work except • The electrical installation must be carried out by the qualified specified in the manual. leakage in the small room, lack of oxygen can occur, which can cause
the by qualified installer. electrician in accordance with “the norm for electrical work” and Insufficient space can result in accident such as personal injury due to serious accidents.
181 -
• Install the system in full accordance with the installation manual. “national wiring regulation”, and the system must be connected to
Incorrect installation may cause bursts, personal injury, water leaks, electric the dedicated circuit. • Do not install the unit in the locations listed below. If leaked gases accumulate around the unit, it can cause fire.
shocks and fire. Power supply with insufficient capacity and incorrect function done by • Locations where carbon fiber, metal powder or any powder is floating. • Do not install the unit where corrosive gas (such as sulfurous acid
• Be sure to use only for household and residence. improper work can cause electric shocks and fire. • Locations where any substances that can affect the unit such as sulphide gas etc.) or combustible gas (such as thinner and petroleum gases)
If this appliance is installed in inferior environment such as machine shop • Be sure to shut off the power before starting electrical work. gas, chloride gas, acid and alkaline can occur. can accumulate or collect, or where volatile combustible
and etc., it can cause malfunction. Failure to shut off the power can cause electric shocks, unit failure or • Vehicles and ships. substances are handled.
• Use the original accessories and the specified components for incorrect function of equipment. • Locations where cosmetic or special sprays are often used. Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
installation. • Be sure to use the cables conformed to safety standard and cable • Locations with direct exposure of oil mist and steam such as kitchen and parts and etc. And combustible gas can cause fire.
If parts other than those prescribed by us are used, It may cause water ampacity for power distribution work. machine plant. • Do not use the indoor unit at the place where water splashes may
leaks, electric shocks, fire and personal injury. Unconformable cables can cause electric leak, anomalous heat production • Locations where any machines which generate high frequency harmonics occur such as in laundries.
• Install the unit in a location with good support. or fire. are used. Since the indoor unit is not waterproof, it can cause electric shocks and fire.
Unsuitable installation locations can cause the unit to fall and cause • This appliance must be connected to main power supply by means • Locations with salty atmospheres such as coastlines. • Do not install nor use the system close to the equipment that
material damage and personal injury. of a circuit breaker or switch (fuse:20A) with a contact separation of • Locations with heavy snow (If installed, be sure to provide base flame and generates electromagnetic fields or high frequency harmonics.
• Ventilate the working area well in the event of refrigerant leakage at least 3mm. snow hood mentioned in the manual). Equipment such as inverters, standby generators, medical high frequency
during installation. • When plugging this appliance, a plug conforming to the norm • Locations where the unit is exposed to chimney smoke. equipments and telecommunication equipments can affect the system, and
If the refrigerant comes into contact with naked flames, poisonous gas is IEC60884-1 must be used. • Locations at high altitude (more than 1000m high). cause malfunctions and breakdowns. The system can also affect medical
produced. • Use the prescribed cables for electrical connection, tighten the • Locations with ammonic atmospheres. equipment and telecommunication equipment, and obstruct its function or
• When installing in small rooms, take prevention measures not to cables securely in terminal block and relieve the cables correctly to • Locations where heat radiation from other heat source can affect the unit. cause jamming.
exceed the density limit of refrigerant in the event of leakage, prevent overloading the terminal blocks. • Locations without good air circulation. • Do not place any variables which will be damaged by getting wet
referred by the formula (accordance with ISO5149). Loose connections or cable mountings can cause anomalous heat • Locations with any obstacles which can prevent inlet and outlet air of the unit. under the indoor unit.
If the density of refrigerant exceeds the limit, please consult the dealer and production or fire. • Locations where short circuit of air can occur (in case of multiple units When the relative humidity is higher than 80% or drainage pipe is clogged,
install the ventilation system, otherwise lack of oxygen can occur, which • Arrange the wiring in the control box so that it cannot be pushed up installation). condensation or drainage water can drop and it can cause the damage of
can cause serious accident. further into the box. Install the service panel correctly. • Locations where strong air blows against the air outlet of outdoor unit. valuables.
• After completed installation, check that no refrigerant leaks from Incorrect installation may result in overheating and fire. • Locations where something located above the unit could fall. • Do not install the remote control at the direct sunlight.
the system. • Be sure to switch off the power supply in the event of installation, It can cause remarkable decrease in performance, corrosion and damage It can cause malfunction or deformation of the remote control.
If refrigerant leaks into the room and comes into contact with an oven or inspection or servicing. of components, malfunction and fire. • Do not use the unit for special purposes such as storing foods,
other hot surface, poisonous gas is produced. If the power supply is not shut off, there is a risk of electric shocks, unit • Do not install the indoor unit in the locations listed below (Be sure cooling precision instruments and preservation of animals, plants or
• Use the prescribed pipes, flare nuts and tools for R410A. failure or personal injury due to the unexpected start of fan. to install the indoor unit according to the installation manual for art.
'11 • SCM-SM-110
Using existing parts (for R22 or R407C) can cause the unit failure and • Be sure to wear protective goggles and gloves while at work. each model because each indoor unit has each limitation). It can cause the damage of the items.
serious accidents due to burst of the refrigerant circuit. • Earth leakage breaker must be installed. • Locations with any obstacles which can prevent inlet and outlet air of the • Do not use any materials other than a fuse with the correct rating in
If the earth leakage breaker is not installed, it can cause electric shocks. unit. the location where fuses are to be used.
• Locations where vibration can be amplified due to insufficient strength of Connecting the circuit with copper wire or other metal thread can cause
• Do not put the drainage pipe directly into drainage channels where • Do not processing, splice the power cord, or share a socket with structure. unit failure and fire.
poisonous gases such as sulphide gas can occur. other power plugs. • Locations where the infrared receiver is exposed to the direct sunlight or • Do not touch any buttons with wet hands.
Poisonous gases will flow into the room through drainage pipe and This may cause fire or electric shock due to defecting contact, defecting the strong light beam (in case of the infrared specification unit). It can cause electric shocks.
seriously affect the user’s health and safety. This can also cause the insulation and over-current etc. • Locations where an equipment affected by high harmonics is placed (TV • Do not touch any refrigerant pipes with your hands when the
corrosion of the indoor unit and a resultant unit failure or refrigerant leak. • Do not bundling, winding or processing for the power cord. Or, do set or radio receiver is placed within 1m). system is in operation.
• Ensure that no air enters in the refrigerant circuit when the unit is not deforming the power plug due to tread it. • Locations where drainage cannot run off safely. During operation the refrigerant pipes become extremely hot or extremely
installed and removed. This may cause fire or heating. It can affect performance or function and etc. cold depending the operating condition, and it can cause burn injury or
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit • Do not install the unit near the location where leakage of frost injury.
becomes too high, which can cause burst and personal injury. combustible gases can occur.
BEFORE INSTALLATION
○ Before installation check that the power supply matches the air conditioner.
SELECTION OF INSTALLATION LOCATION 5 cm minimum
from the wall
(Install at location that meets the following conditions, after getting approval from the customer)
6.5 cm minimum from the ceiling
Indoor unit
Installation board
Standard accessories (Installation kit) Q’ty ○ Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed. 10 cm mi
Accessories for indoor unit ○ A solid place where the unit or the wall will not vibrate. nim
from the um
○ A place where there will be enough space for servicing. (Where space mentioned below can be secured) wall
Installation board ○ Where wiring and the piping work will be easy to conduct.
1 (Attached to the rear of the indoor unit) 1
○ The place where receiving part is not exposed to the direct rays of the sun or the strong rays of the street lighting.
○ A place where it can be easily drained.
2 Wireless remote control 1 ○ A place separated at least 1m away from the television or the radio. (To prevent interference to images and sounds.)
○ Places where this unit is not affected by the high frequency equipment or electric equipment.
○ Avoid installing this unit in place where there is much oil mist.
3 Remote control holder 1
○ Places where there is no electric equipment or household under the installing unit.
Tapping screws Wireless remote control
4 (for installation board ø4 X 25mm) 10
○ A place where the air conditioner can be received the signal surely during operating the wireless remote control.
Wood screws ○ Places where there is no affected by the TV and radio etc. CAUTION Indoor side Outdoor side
5 (for remote control switch holder ø3.5 X 16mm) 2 ○ Do not place where exposed to direct sunlight or near heat devices such as a stove. Completely seal the hole on Sleeve (sold separately)
putty
the wall with putty. Otherwise,
6 Battery [R03 (AAA, Micro) 1.5V] 2
INSTALLATION OF INDOOR UNIT furniture, or other, may be
wetted by leaked water or putty
7 Air-cleaning filters 2 Installation of Installation board dewing.
Sealing plate 1 Mating mark for Mounting Relation between setting plate and indoor unit
board
level surface Mounting
Max.10
Sleeve 1
board INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
Indoor unit
○ Adjustment of the installation board in the horizontal direction is to
Installation board
Inclination plate 1 be conducted with eight screws in a temporary tightened state.
○ Adjust so the board will be Space Space
50 for service for service 100
for service
65 Space
8.5
Piping cover
(for insulation of connection piping)
1
Downloaded from www.Manualslib.com manuals search engineDrilling of holes and fixture of sleeve (Option parts)
01.8
25
21.5
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
4.5
4.5
WARNING • Be sure to install the drainage pipe with descending slope of 1/100
or more, and not to make traps and air-bleedings.
set up the opening port if the room lapse into negative pressure status
due to register of the wind for the high rise apartment etc.
• Installation must be carried out by the qualified installer. • Tighten the flare nut by torque wrench with specified method. Check if the drainage runs off securely during commissioning and ensure • Be sure to perform air tightness test by pressurizing with nitrogen
If you install the system by yourself, it may cause serious trouble such as If the flare nut were tightened with excess torque, this may cause burst and the space for inspection and maintenance. gas after completed refrigerant piping work.
water leaks, electric shocks, fire and personal injury, as a result of a system refrigerant leakage after a long period. • Secure a space for installation, inspection and maintenance If the density of refrigerant exceeds the limit in the event of refrigerant
malfunction. Do not carry out the installation and maintenance work except • The electrical installation must be carried out by the qualified specified in the manual. leakage in the small room, lack of oxygen can occur, which can cause
the by qualified installer. electrician in accordance with “the norm for electrical work” and Insufficient space can result in accident such as personal injury due to serious accidents.
• Install the system in full accordance with the installation manual. “national wiring regulation”, and the system must be connected to
Incorrect installation may cause bursts, personal injury, water leaks, electric the dedicated circuit. • Do not install the unit in the locations listed below. If leaked gases accumulate around the unit, it can cause fire.
shocks and fire. Power supply with insufficient capacity and incorrect function done by • Locations where carbon fiber, metal powder or any powder is floating. • Do not install the unit where corrosive gas (such as sulfurous acid
• Be sure to use only for household and residence. improper work can cause electric shocks and fire. • Locations where any substances that can affect the unit such as sulphide gas etc.) or combustible gas (such as thinner and petroleum gases)
If this appliance is installed in inferior environment such as machine shop • Be sure to shut off the power before starting electrical work. gas, chloride gas, acid and alkaline can occur. can accumulate or collect, or where volatile combustible
and etc., it can cause malfunction. Failure to shut off the power can cause electric shocks, unit failure or • Vehicles and ships. substances are handled.
• Use the original accessories and the specified components for incorrect function of equipment. • Locations where cosmetic or special sprays are often used. Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
installation. • Be sure to use the cables conformed to safety standard and cable • Locations with direct exposure of oil mist and steam such as kitchen and parts and etc. And combustible gas can cause fire.
If parts other than those prescribed by us are used, It may cause water ampacity for power distribution work. machine plant. • Do not use the indoor unit at the place where water splashes may
leaks, electric shocks, fire and personal injury. Unconformable cables can cause electric leak, anomalous heat production • Locations where any machines which generate high frequency harmonics occur such as in laundries.
• Install the unit in a location with good support. or fire. are used. Since the indoor unit is not waterproof, it can cause electric shocks and fire.
Unsuitable installation locations can cause the unit to fall and cause • This appliance must be connected to main power supply by means • Locations with salty atmospheres such as coastlines. • Do not install nor use the system close to the equipment that
material damage and personal injury. of a circuit breaker or switch (fuse:20A) with a contact separation of • Locations with heavy snow (If installed, be sure to provide base flame and generates electromagnetic fields or high frequency harmonics.
• Ventilate the working area well in the event of refrigerant leakage at least 3mm. snow hood mentioned in the manual). Equipment such as inverters, standby generators, medical high frequency
during installation. • When plugging this appliance, a plug conforming to the norm • Locations where the unit is exposed to chimney smoke. equipments and telecommunication equipments can affect the system, and
If the refrigerant comes into contact with naked flames, poisonous gas is IEC60884-1 must be used. • Locations at high altitude (more than 1000m high). cause malfunctions and breakdowns. The system can also affect medical
produced. • Use the prescribed cables for electrical connection, tighten the • Locations with ammonic atmospheres. equipment and telecommunication equipment, and obstruct its function or
• When installing in small rooms, take prevention measures not to cables securely in terminal block and relieve the cables correctly to • Locations where heat radiation from other heat source can affect the unit. cause jamming.
exceed the density limit of refrigerant in the event of leakage, prevent overloading the terminal blocks. • Locations without good air circulation. • Do not place any variables which will be damaged by getting wet
referred by the formula (accordance with ISO5149). Loose connections or cable mountings can cause anomalous heat • Locations with any obstacles which can prevent inlet and outlet air of the unit. under the indoor unit.
If the density of refrigerant exceeds the limit, please consult the dealer and production or fire. • Locations where short circuit of air can occur (in case of multiple units When the relative humidity is higher than 80% or drainage pipe is clogged,
install the ventilation system, otherwise lack of oxygen can occur, which • Arrange the wiring in the control box so that it cannot be pushed up installation). condensation or drainage water can drop and it can cause the damage of
can cause serious accident. further into the box. Install the service panel correctly. • Locations where strong air blows against the air outlet of outdoor unit. valuables.
• After completed installation, check that no refrigerant leaks from Incorrect installation may result in overheating and fire. • Locations where something located above the unit could fall. • Do not install the remote control at the direct sunlight.
the system. • Be sure to switch off the power supply in the event of installation, It can cause remarkable decrease in performance, corrosion and damage It can cause malfunction or deformation of the remote control.
If refrigerant leaks into the room and comes into contact with an oven or inspection or servicing. of components, malfunction and fire. • Do not use the unit for special purposes such as storing foods,
other hot surface, poisonous gas is produced. If the power supply is not shut off, there is a risk of electric shocks, unit • Do not install the indoor unit in the locations listed below (Be sure cooling precision instruments and preservation of animals, plants or
• Use the prescribed pipes, flare nuts and tools for R410A. failure or personal injury due to the unexpected start of fan. to install the indoor unit according to the installation manual for art.
Using existing parts (for R22 or R407C) can cause the unit failure and • Be sure to wear protective goggles and gloves while at work. each model because each indoor unit has each limitation). It can cause the damage of the items.
serious accidents due to burst of the refrigerant circuit. • Earth leakage breaker must be installed. • Locations with any obstacles which can prevent inlet and outlet air of the • Do not use any materials other than a fuse with the correct rating in
If the earth leakage breaker is not installed, it can cause electric shocks. unit. the location where fuses are to be used.
• Locations where vibration can be amplified due to insufficient strength of Connecting the circuit with copper wire or other metal thread can cause
• Do not put the drainage pipe directly into drainage channels where • Do not processing, splice the power cord, or share a socket with structure. unit failure and fire.
poisonous gases such as sulphide gas can occur. other power plugs. • Locations where the infrared receiver is exposed to the direct sunlight or • Do not touch any buttons with wet hands.
Poisonous gases will flow into the room through drainage pipe and This may cause fire or electric shock due to defecting contact, defecting the strong light beam (in case of the infrared specification unit). It can cause electric shocks.
seriously affect the user’s health and safety. This can also cause the insulation and over-current etc. • Locations where an equipment affected by high harmonics is placed (TV • Do not touch any refrigerant pipes with your hands when the
corrosion of the indoor unit and a resultant unit failure or refrigerant leak. • Do not bundling, winding or processing for the power cord. Or, do set or radio receiver is placed within 1m). system is in operation.
• Ensure that no air enters in the refrigerant circuit when the unit is not deforming the power plug due to tread it. • Locations where drainage cannot run off safely. During operation the refrigerant pipes become extremely hot or extremely
installed and removed. This may cause fire or heating. It can affect performance or function and etc. cold depending the operating condition, and it can cause burn injury or
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit • Do not install the unit near the location where leakage of frost injury.
becomes too high, which can cause burst and personal injury. combustible gases can occur.
BEFORE INSTALLATION
○ Before installation check that the power supply matches the air conditioner.
SELECTION OF INSTALLATION LOCATION 5 cm minimum
from the wall
(Install at location that meets the following conditions, after getting approval from the customer)
6.5 cm minimum from the ceiling
Indoor unit
Installation board
Standard accessories (Installation kit) Q’ty ○ Where there is no obstructions to the air flow and where the cooled and heated air can be evenly distributed. 10 cm mi
Accessories for indoor unit ○ A solid place where the unit or the wall will not vibrate. nim
from the um
○ A place where there will be enough space for servicing. (Where space mentioned below can be secured) wall
Installation board ○ Where wiring and the piping work will be easy to conduct.
1 (Attached to the rear of the indoor unit) 1
○ The place where receiving part is not exposed to the direct rays of the sun or the strong rays of the street lighting.
○ A place where it can be easily drained.
2 Wireless remote control 1 ○ A place separated at least 1m away from the television or the radio. (To prevent interference to images and sounds.)
○ Places where this unit is not affected by the high frequency equipment or electric equipment.
○ Avoid installing this unit in place where there is much oil mist.
3 Remote control holder 1
○ Places where there is no electric equipment or household under the installing unit.
Tapping screws Wireless remote control
4 (for installation board ø4 X 25mm) 10
○ A place where the air conditioner can be received the signal surely during operating the wireless remote control.
Wood screws ○ Places where there is no affected by the TV and radio etc. CAUTION Indoor side Outdoor side
5 (for remote control switch holder ø3.5 X 16mm) 2 ○ Do not place where exposed to direct sunlight or near heat devices such as a stove. Completely seal the hole on Sleeve (sold separately)
putty
the wall with putty. Otherwise,
6 Battery [R03 (AAA, Micro) 1.5V] 2
INSTALLATION OF INDOOR UNIT furniture, or other, may be
wetted by leaked water or putty
7 Air-cleaning filters 2 Installation of Installation board dewing.
Sealing plate 1 Mating mark for Mounting Relation between setting plate and indoor unit
board
level surface Mounting
Max.10
Sleeve 1
board INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
Indoor unit
○ Adjustment of the installation board in the horizontal direction is to
Installation board
1
-
for service
182 -
65 Space
level by turning the board
Putty 1 with the standard hole as
Standard 886 106
hole 450 299
the center. 106 349
Drain hose (extension hose) 1 50 50
49.5
8.5
Piping cover
(for insulation of connection piping)
1
Drilling of holes and fixture of sleeve (Option parts)
301.8
25
221.5
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.
44.5
44.5
Necessary tools for the installation work
b Top b c
5 53.5 77
15 Space
Piping for Liquid 703.5
2 For bolt anchor
Knife Indoor side Outdoor side Thickness of the wall + 1.5cm Indoor side Outdoor side Installed state and nut anchor Drain hose 772 (ø16)
3 ○ Drill a hole with whole core drill. ○ In case of rear piping draw out, cut off the lower Piping hole (ø65)
Saw (Unit : mm)
and the right side portions of the sleeve collar.
4 Tape measure Installing the support of piping • Matters of special notice when piping from left or central/rear of the unit.
[Top view] [Drain hose changing procedures]
5 Hammer In case of piping in the right rear direction Left-hand-side piping Right-hand-side piping 1. Remove the drain hose 2. Remove the drain cap.
Shaping of pipings Taping of the exterior Piping in the left rear direction Piping in the right rear direction
6 Spanner wrench
Pipings
7 Torque wrench ( 14.0
(1.4 ~ 8.2kgf·m) )
~ 82.0N·m
8 Hole core drill (65mm in diameter) Piping in the left direction Piping in the right direction ○ Remove the screw and drain hose, ○ Remove it with hand or pliers.
'11 • SCM-SM-110
Drain hose making it rotate.
9 Wrench key (Hexagon) [4m/m] ○ Hold the bottom of the ○ Tape only the portion Piping is possible in the rear, left, left rear, left downward, right or downward direction. 3. Insert the drain cap. 4. Connect the drain hose.
piping and fix direction that goes through the
10 Flaring tool set ( Designed specifically
for R410A ) before stretching it and
shaping it.
wall.
○ Always tape the wiring Right
Gas leak detector ( )
Designed specifically with the piping.
11 for R410A
Sufficient care must be taken not to damage
Gauge for projection adjustment
the panel when connecting pipes.
( )
12 Used when flare is made by using Rear ○ Insert the drain cap which was removed ○ Insert the drain hose securely, making
Left
conventional flare tool Downward rear at procedure “2” securely using a rotate. And install the screw.
Left hexagonal wrench etc. Note: Be careful that If it is not Inserted
Left downward Note: Be careful that If it is not Inserted securely, water leakage may
13 Pipe bender securely, water leakage may occur. occur.
Fixing of indoor unit Since this air conditioner has been designed to collect dew drops on the rear
Gutter
surface to the drain pan, do not attach the power cord above the gutter.
Latch (2 locations) Installation Steps • How to remove the indoor unit from the installation board
Wall
1 Pass the pipe through 1 Push up at the marked portion of the indoor unit base lower latch, and slightly
the hole in the wall, pull it toward you. (both right and left hand sides) (The indoor unit base lower
Indoor unit and hook the upper latch can be removed from the installation board) Pipe accommodating section
part of the indoor unit 2 Push up the indoor unit upward. So the indoor unit will be removed from the
to the installation board. installation board.
Drainage
2 Gently push the lower
○ Arrange the drain hose in a downward angle. CAUTION Go through all installation steps and check if the
part to secure the unit.
○ Avoid the following drain piping. drainage is all right. Otherwise water leak may occur.
Indoor CAUTION Indoor Liquid side Cover the coupling with insulator and then cover it with tapes.
Dimension A Gas side
90 ± 0.5˚
Liquid side ø6.35 : 9.1 (mm) Do not apply refrigerating machine Vinyl tape Use an attached insulation pad for heat insulation.
A
-
Press Gas side ø9.52 : 13.2 (mm) oil to the flared surface.
(Do not turn) (Do not turn)
Remove ø12.7 : 16.6 (mm)
183 -
Open/close and detachment/attachment of the air inlet panel How to remove and install the front panel
○ To open, pull the panel at both ends of lower part ○Removing Latch
and release latches, then pull up the panel until ① Remove the air inlet panel.
'11 • SCM-SM-110
you feel resistance. ② Remove the screw (A) 2pcs / screw Air inlet panel
(The panel stops at approx. 60° open position) (B) 3pcs fixing to the front panel. Air filter
○ To close, hold the panel at both ends of lower ③ Remove the 3 latches in the upper
part to lower downward and push it slightly until section of the front panel and then
the latch works. remove the front panel from the unit.
○ To remove, pull up the panel to the position
shown in right illustration and pull it toward you. ○Installing
○ To install, insert the panel arm into the slot on the ① Remove the air filter.
front panel from the position shown in right Approx. 80° ② Cover the unit with the front panel.
To remove / To install
illustration, hold the panel at both ends of lower ③ Tighten the screw (A) 2pcs / screw
part, lower it downward slowly, then push it (B) 3pcs to fix the front panel. Front panel
Screw (A) Screw (A)
slightly until the latch works. ④ Install the air filter.
⑤ Install the air inlet panel.
Screw (B) Screw (B)
Screw (B)
90 ± 0.5˚
Liquid side ø6.35 : 9.1 (mm) Do not apply refrigerating machine Vinyl tape Use an attached insulation pad for heat insulation.
Press A Gas side ø9.52 : 13.2 (mm) oil to the flared surface.
(Do not turn) (Do not turn)
Remove ø12.7 : 16.6 (mm)
ø15.88 : 19.7 (mm)
○ Remove the flared nuts. (on both liquid and gas sides) ○ Install the removed flared nuts to the pipes to be connected, ○ Connect the pipes on both liquid and gas sides.
then flared the pipes. ○ Tighten the nuts to the following torque. Position it so that the slit area faces upward.
Liquid side (ø6.35) : 14.0 - 18.0 N·m (1.4 - 1.8 kgf·m)
• Flaring work Gas side (ø9.52) : 34.0 - 42.0 N·m (3.4 - 4.2 kgf·m) • Cover the indoor unit s flare-connected joints, after they are checked for a gas leak,
Measurement B (mm)
(ø12.7) : 49.0 - 61.0 N·m (4.9 - 6.1 kgf·m) with an indoor unit heat insulating material and then wrap them with a tape with an
Copper pipe diameter Clutch type flare tool for Conventional (R22) flare tool (ø15.88) : 68.0 - 82.0 N·m (6.8 - 8.2 kgf·m) attached insulation pad placed over the heat insulating material’s slit area.
Measurement B R410A Clutch type Wing nut type
ø6.35 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0 CAUTION
ø9.52 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0 Finishing work and fixing
Do not apply excess torque to the flared nuts.
ø12.7 0.0 - 0.5 1.0 - 1.5 2.0 - 2.5 Otherwise, the flared nuts may check depending.
ø15.88 0.0 - 0.5 1.0 - 1.5 2.0 - 2.5 Refrigerant piping
Flaring
block Connection wiring, Cover the exterior portion with outer tape and
Copper pipe Use a flare tool designed for R410A or a conventional flare tool. Earth wiring
Please note that measurement B (protrusion from the flaring block) will vary depending on the shape the piping so it will match the contours
type of a flare tool in use. Outer tape of the route that the piping to take.
If a conventional flare tool is used, please use a copper pipe gauge or a similar instrument to Drain hose Also fix the wiring and pipings to the wall with
check protrusion so that you can keep measurement B to a correct value. Wood screw clamps.
Clamp
Open/close and detachment/attachment of the air inlet panel How to remove and install the front panel
○ To open, pull the panel at both ends of lower part ○Removing Latch
and release latches, then pull up the panel until ① Remove the air inlet panel.
you feel resistance. ② Remove the screw (A) 2pcs / screw Air inlet panel
(The panel stops at approx. 60° open position) (B) 3pcs fixing to the front panel. Air filter
○ To close, hold the panel at both ends of lower ③ Remove the 3 latches in the upper
part to lower downward and push it slightly until section of the front panel and then
the latch works. remove the front panel from the unit.
○ To remove, pull up the panel to the position
shown in right illustration and pull it toward you. ○Installing
○ To install, insert the panel arm into the slot on the ① Remove the air filter.
front panel from the position shown in right Approx. 80° ② Cover the unit with the front panel.
To remove / To install
illustration, hold the panel at both ends of lower ③ Tighten the screw (A) 2pcs / screw
part, lower it downward slowly, then push it (B) 3pcs to fix the front panel. Front panel
Screw (A) Screw (A)
slightly until the latch works. ④ Install the air filter.
⑤ Install the air inlet panel.
Screw (B) Screw (B) Screw (B)
HOW TO RELOCATE OR DISPOSE OF THE UNIT CONCERNING TERMINAL CONNECTION FOR AN INTERFACE
Control cover
○ In order to protect the environment, be sure to pump down (recovery of refrigerant). • Forced cooling operation 1 Remove the air inlet panel, lid and front panel.
○ Pump down is the method of recovering refrigerant from the indoor unit to the Turn on a power supply again after a while after turn off a power supply. 2 Remove the control cover. (Remove the screw.)
outdoor unit when the pipes are removed from the unit. Then press continually the ON/OFF button 5 seconds or more. 3 There is a terminal (respectively marked with CNS) for the indoor control board.
Indoor unit PCB
In connecting an interface, connect to the respective terminal securely with the connection harness
<How to pump down> supplied with an optional “ Interface connection kit SC-BIKN-E” and fasten the connection harness
1 Connect charge hose to check joint of outdoor unit. onto the indoor control box with the clamp supplied with the kit.
2 Liquid side : Close the liquid valve with hexagon wrench key. For more details, please refer to the user’s manual of your “ Interface connection kit SC-BIKN-E”.
Gas side : Fully open the gas valve.
Carry out cooling operation. (If indoor temperature is low, operate
'11 • SCM-SM-110
forced cooling operation.) Screw
3 After low pressure gauge become 0.01MPa, stop cooling operation
and close the gas valve.
CNS terminal
Unit ON/OFF button
TIPDLTBOEGJSF 1PXFSTVQQMZXJUIJOTVGGJDJFOUDBQBDJUZBOEJODPSSFDUGVODUJPOEPOFCZ
t#FTVSFUPVTFPOMZGPSIPVTFIPMEBOESFTJEFODF JNQSPQFSXPSLDBODBVTFFMFDUSJDTIPDLTBOEGJSF t-PDBUJPOTXIFSFBOZTVCTUBODFTUIBUDBOBGGFDUUIFVOJUTVDIBTTVMQIJEF HBTFUD
PSDPNCVTUJCMFHBT TVDIBTUIJOOFSBOEQFUSPMFVNHBTFT
*GUIJTBQQMJBODFJTJOTUBMMFEJOJOGFSJPSFOWJSPONFOUTVDIBTNBDIJOFTIPQ t#FTVSFUPTIVUPGGUIFQPXFSCFGPSFTUBSUJOHFMFDUSJDBMXPSL HBT
DIMPSJEFHBT
BDJEBOEBMLBMJOFDBOPDDVS DBOBDDVNVMBUFPSDPMMFDU
PSXIFSFWPMBUJMFDPNCVTUJCMF
BOEFUD
JUDBODBVTFNBMGVODUJPO 'BJMVSFUPTIVUPGGUIFQPXFSDBODBVTFFMFDUSJDTIPDLT
VOJUGBJMVSFPS t7FIJDMFTBOETIJQT TVCTUBODFTBSFIBOEMFE
t6TFUIFPSJHJOBMBDDFTTPSJFTBOEUIFTQFDJGJFEDPNQPOFOUTGPS JODPSSFDUGVODUJPOPGFRVJQNFOU t-PDBUJPOTXIFSFDPTNFUJDPSTQFDJBMTQSBZTBSFPGUFOVTFE $PSSPTJWFHBTDBODBVTFDPSSPTJPOPGIFBUFYDIBOHFS
CSFBLBHFPGQMBTUJD
JOTUBMMBUJPO t#FTVSFUPVTFUIFDBCMFTDPOGPSNFEUPTBGFUZTUBOEBSEBOEDBCMF t-PDBUJPOTXJUIEJSFDUFYQPTVSFPGPJMNJTUBOETUFBNTVDIBTLJUDIFOBOE QBSUTBOEFUD"OEDPNCVTUJCMFHBTDBODBVTFGJSF
*GQBSUTPUIFSUIBOUIPTFQSFTDSJCFECZVTBSFVTFE
*UNBZDBVTFXBUFS BNQBDJUZGPSQPXFSEJTUSJCVUJPOXPSL NBDIJOFQMBOU t%POPUVTFUIFJOEPPSVOJUBUUIFQMBDFXIFSFXBUFSTQMBTIFTNBZ
MFBLT
FMFDUSJDTIPDLT
GJSFBOEQFSTPOBMJOKVSZ 6ODPOGPSNBCMFDBCMFTDBODBVTFFMFDUSJDMFBL
BOPNBMPVTIFBUQSPEVDUJPO t-PDBUJPOTXIFSFBOZNBDIJOFTXIJDIHFOFSBUFIJHIGSFRVFODZIBSNPOJDT PDDVSTVDIBTJOMBVOESJFT
t*OTUBMMUIFVOJUJOBMPDBUJPOXJUIHPPETVQQPSU PSGJSF BSFVTFE 4JODFUIFJOEPPSVOJUJTOPUXBUFSQSPPG
JUDBODBVTFFMFDUSJDTIPDLTBOEGJSF
6OTVJUBCMFJOTUBMMBUJPOMPDBUJPOTDBODBVTFUIFVOJUUPGBMMBOEDBVTF t5IJTBQQMJBODFNVTUCFDPOOFDUFEUPNBJOQPXFSTVQQMZCZNFBOT t-PDBUJPOTXJUITBMUZBUNPTQIFSFTTVDIBTDPBTUMJOFT t%POPUJOTUBMMOPSVTFUIFTZTUFNDMPTFUPUIFFRVJQNFOUUIBU
NBUFSJBMEBNBHFBOEQFSTPOBMJOKVSZ PGBDJSDVJUCSFBLFSPSTXJUDI GVTF"
XJUIBDPOUBDUTFQBSBUJPOPG t-PDBUJPOTXJUIIFBWZTOPX *GJOTUBMMFE
CFTVSFUPQSPWJEFCBTFGMBNFBOE HFOFSBUFTFMFDUSPNBHOFUJDGJFMETPSIJHIGSFRVFODZIBSNPOJDT
t7FOUJMBUFUIFXPSLJOHBSFBXFMMJOUIFFWFOUPGSFGSJHFSBOUMFBLBHF BUMFBTUNN TOPXIPPENFOUJPOFEJOUIFNBOVBM
&RVJQNFOUTVDIBTJOWFSUFST
TUBOECZHFOFSBUPST
NFEJDBMIJHIGSFRVFODZ
EVSJOHJOTUBMMBUJPO t8IFOQMVHHJOHUIJTBQQMJBODF
BQMVHDPOGPSNJOHUPUIFOPSN t-PDBUJPOTXIFSFUIFVOJUJTFYQPTFEUPDIJNOFZTNPLF FRVJQNFOUTBOEUFMFDPNNVOJDBUJPOFRVJQNFOUTDBOBGGFDUUIFTZTUFN
BOE
*GUIFSFGSJHFSBOUDPNFTJOUPDPOUBDUXJUIOBLFEGMBNFT
QPJTPOPVTHBTJT *&$NVTUCFVTFE t-PDBUJPOTBUIJHIBMUJUVEF NPSFUIBONIJHI
DBVTFNBMGVODUJPOTBOECSFBLEPXOT5IFTZTUFNDBOBMTPBGGFDUNFEJDBM
QSPEVDFE t6TFUIFQSFTDSJCFEDBCMFTGPSFMFDUSJDBMDPOOFDUJPO
UJHIUFOUIF t-PDBUJPOTXJUIBNNPOJDBUNPTQIFSFT FRVJQNFOUBOEUFMFDPNNVOJDBUJPOFRVJQNFOU
BOEPCTUSVDUJUTGVODUJPOPS
t8IFOJOTUBMMJOHJOTNBMMSPPNT
UBLFQSFWFOUJPONFBTVSFTOPUUP DBCMFTTFDVSFMZJOUFSNJOBMCMPDLBOESFMJFWFUIFDBCMFTDPSSFDUMZUP t-PDBUJPOTXIFSFIFBUSBEJBUJPOGSPNPUIFSIFBUTPVSDFDBOBGGFDUUIFVOJU DBVTFKBNNJOH
FYDFFEUIFEFOTJUZMJNJUPGSFGSJHFSBOUJOUIFFWFOUPGMFBLBHF
QSFWFOUPWFSMPBEJOHUIFUFSNJOBMCMPDLT t-PDBUJPOTXJUIPVUHPPEBJSDJSDVMBUJPO t%POPUQMBDFBOZWBSJBCMFTXIJDIXJMMCFEBNBHFECZHFUUJOHXFU
SFGFSSFECZUIFGPSNVMB BDDPSEBODFXJUI*40
-PPTFDPOOFDUJPOTPSDBCMFNPVOUJOHTDBODBVTFBOPNBMPVTIFBU t-PDBUJPOTXJUIBOZPCTUBDMFTXIJDIDBOQSFWFOUJOMFUBOEPVUMFUBJSPGUIFVOJU VOEFSUIFJOEPPSVOJU
*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJU
QMFBTFDPOTVMUUIFEFBMFSBOE QSPEVDUJPOPSGJSF t-PDBUJPOTXIFSFTIPSUDJSDVJUPGBJSDBOPDDVS JODBTFPGNVMUJQMFVOJUT 8IFOUIFSFMBUJWFIVNJEJUZJTIJHIFSUIBOPSESBJOBHFQJQFJTDMPHHFE
JOTUBMMUIFWFOUJMBUJPOTZTUFN
PUIFSXJTFMBDLPGPYZHFODBOPDDVS
XIJDI t"SSBOHFUIFXJSJOHJOUIFDPOUSPMCPYTPUIBUJUDBOOPUCFQVTIFEVQ JOTUBMMBUJPO
DPOEFOTBUJPOPSESBJOBHFXBUFSDBOESPQBOEJUDBODBVTFUIFEBNBHFPG
DBODBVTFTFSJPVTBDDJEFOU GVSUIFSJOUPUIFCPY*OTUBMMUIFTFSWJDFQBOFMDPSSFDUMZ t-PDBUJPOTXIFSFTUSPOHBJSCMPXTBHBJOTUUIFBJSPVUMFUPGPVUEPPSVOJU WBMVBCMFT
t"GUFSDPNQMFUFEJOTUBMMBUJPO
DIFDLUIBUOPSFGSJHFSBOUMFBLTGSPN *ODPSSFDUJOTUBMMBUJPONBZSFTVMUJOPWFSIFBUJOHBOEGJSF t-PDBUJPOTXIFSFTPNFUIJOHMPDBUFEBCPWFUIFVOJUDPVMEGBMM t%POPUJOTUBMMUIFSFNPUFDPOUSPMBUUIFEJSFDUTVOMJHIU
UIFTZTUFN t#FTVSFUPTXJUDIPGGUIFQPXFSTVQQMZJOUIFFWFOUPGJOTUBMMBUJPO
*UDBODBVTFSFNBSLBCMFEFDSFBTFJOQFSGPSNBODF
DPSSPTJPOBOEEBNBHF *UDBODBVTFNBMGVODUJPOPSEFGPSNBUJPOPGUIFSFNPUFDPOUSPM
*GSFGSJHFSBOUMFBLTJOUPUIFSPPNBOEDPNFTJOUPDPOUBDUXJUIBOPWFOPS JOTQFDUJPOPSTFSWJDJOH PGDPNQPOFOUT
NBMGVODUJPOBOEGJSF t%POPUVTFUIFVOJUGPSTQFDJBMQVSQPTFTTVDIBTTUPSJOHGPPET
PUIFSIPUTVSGBDF
QPJTPOPVTHBTJTQSPEVDFE *GUIFQPXFSTVQQMZJTOPUTIVUPGG
UIFSFJTBSJTLPGFMFDUSJDTIPDLT
VOJU t%POPUJOTUBMMUIFJOEPPSVOJUJOUIFMPDBUJPOTMJTUFECFMPX #FTVSF DPPMJOHQSFDJTJPOJOTUSVNFOUTBOEQSFTFSWBUJPOPGBOJNBMT
QMBOUTPS
t6TFUIFQSFTDSJCFEQJQFT
GMBSFOVUTBOEUPPMTGPS3" GBJMVSFPSQFSTPOBMJOKVSZEVFUPUIFVOFYQFDUFETUBSUPGGBO UPJOTUBMMUIFJOEPPSVOJUBDDPSEJOHUPUIFJOTUBMMBUJPONBOVBMGPS BSU
6TJOHFYJTUJOHQBSUT GPS3PS3$
DBODBVTFUIFVOJUGBJMVSFBOE t#FTVSFUPXFBSQSPUFDUJWFHPHHMFTBOEHMPWFTXIJMFBUXPSL FBDINPEFMCFDBVTFFBDIJOEPPSVOJUIBTFBDIMJNJUBUJPO
*UDBODBVTFUIFEBNBHFPGUIFJUFNT
TFSJPVTBDDJEFOUTEVFUPCVSTUPGUIFSFGSJHFSBOUDJSDVJU t&BSUIMFBLBHFCSFBLFSNVTUCFJOTUBMMFE t-PDBUJPOTXJUIBOZPCTUBDMFTXIJDIDBOQSFWFOUJOMFUBOEPVUMFUBJSPGUIF t%POPUVTFBOZNBUFSJBMTPUIFSUIBOBGVTFXJUIUIFDPSSFDUSBUJOHJO
'11 • SCM-SM-110
*GUIFFBSUIMFBLBHFCSFBLFSJTOPUJOTUBMMFE
JUDBODBVTFFMFDUSJDTIPDLT VOJU UIFMPDBUJPOXIFSFGVTFTBSFUPCFVTFE
t-PDBUJPOTXIFSFWJCSBUJPODBOCFBNQMJGJFEEVFUPJOTVGGJDJFOUTUSFOHUIPG $POOFDUJOHUIFDJSDVJUXJUIDPQQFSXJSFPSPUIFSNFUBMUISFBEDBODBVTF
t%POPUQVUUIFESBJOBHFQJQFEJSFDUMZJOUPESBJOBHFDIBOOFMTXIFSF t%POPUQSPDFTTJOH
TQMJDFUIFQPXFSDPSE
PSTIBSFBTPDLFUXJUI TUSVDUVSF VOJUGBJMVSFBOEGJSF
QPJTPOPVTHBTFTTVDIBTTVMQIJEFHBTDBOPDDVS PUIFSQPXFSQMVHT t-PDBUJPOTXIFSFUIFJOGSBSFESFDFJWFSJTFYQPTFEUPUIFEJSFDUTVOMJHIUPS t%POPUUPVDIBOZCVUUPOTXJUIXFUIBOET
1PJTPOPVTHBTFTXJMMGMPXJOUPUIFSPPNUISPVHIESBJOBHFQJQFBOE 5IJTNBZDBVTFGJSFPSFMFDUSJDTIPDLEVFUPEFGFDUJOHDPOUBDU
EFGFDUJOH UIFTUSPOHMJHIUCFBN JODBTFPGUIFJOGSBSFETQFDJGJDBUJPOVOJU
*UDBODBVTFFMFDUSJDTIPDLT
TFSJPVTMZBGGFDUUIFVTFSTIFBMUIBOETBGFUZ5IJTDBOBMTPDBVTFUIF JOTVMBUJPOBOEPWFSDVSSFOUFUD t-PDBUJPOTXIFSFBOFRVJQNFOUBGGFDUFECZIJHIIBSNPOJDTJTQMBDFE 57 t%POPUUPVDIBOZSFGSJHFSBOUQJQFTXJUIZPVSIBOETXIFOUIF
DPSSPTJPOPGUIFJOEPPSVOJUBOEBSFTVMUBOUVOJUGBJMVSFPSSFGSJHFSBOUMFBL t%POPUCVOEMJOH
XJOEJOHPSQSPDFTTJOHGPSUIFQPXFSDPSE0S
EP TFUPSSBEJPSFDFJWFSJTQMBDFEXJUIJON
TZTUFNJTJOPQFSBUJPO
t&OTVSFUIBUOPBJSFOUFSTJOUIFSFGSJHFSBOUDJSDVJUXIFOUIFVOJUJT OPUEFGPSNJOHUIFQPXFSQMVHEVFUPUSFBEJU t-PDBUJPOTXIFSFESBJOBHFDBOOPUSVOPGGTBGFMZ %VSJOHPQFSBUJPOUIFSFGSJHFSBOUQJQFTCFDPNFFYUSFNFMZIPUPSFYUSFNFMZ
JOTUBMMFEBOESFNPWFE 5IJTNBZDBVTFGJSFPSIFBUJOH *UDBOBGGFDUQFSGPSNBODFPSGVODUJPOBOEFUD DPMEEFQFOEJOHUIFPQFSBUJOHDPOEJUJPO
BOEJUDBODBVTFCVSOJOKVSZPS
*GBJSFOUFSTJOUIFSFGSJHFSBOUDJSDVJU
UIFQSFTTVSFJOUIFSFGSJHFSBOUDJSDVJU t%POPUJOTUBMMUIFVOJUOFBSUIFMPDBUJPOXIFSFMFBLBHFPG GSPTUJOKVSZ
CFDPNFTUPPIJHI
XIJDIDBODBVTFCVSTUBOEQFSTPOBMJOKVSZ DPNCVTUJCMFHBTFTDBOPDDVS
Putty 1
Drilling of holes and fixture of sleeve (Option parts) Installing the support of piping
Latch
Drain hose (extention hose) 1 When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately. In case of piping in the right rear direction
Piping cover Indoor side b Top b c
(for insulation of connection piping)
1 Outdoor side Taping of the exterior
5 Turn to Tape only the portion
65 a tighten that goes through the
Necessary tools for the installation work Thicknese of the wall + 1.5cm
wall.
Indoor side Outdoor side Installed state Always tape the wiring
with the piping.
1 Plus headed driver Drill a hole with whole core drill. In case of rear piping draw out, cut off the lower
and the right side portions of the sleeve collar.
Sufficient care must be taken not to damage
2 Knife the panel when connecting pipes.
Indoor unit piping direction
3 Saw Piping is possible in the rear, For Right or Left rear piping For Right or Left piping For Right or Left bottom piping CAUTION
left,left rear, left downward, Be careful not to
4 Tape measure right or downward direction. stress the connecting
80
100 60
larger than 5 kgf.) If
470
45
Left downward
8 Hole core drill (65mm in diameter) 65 65 Right bottom piping
Left rear piping Right rear piping 60
'11 • SCM-SM-110
10 Flaring tool set ( Designed specifically
for R410A ) Arrange the drain hose in a downward angle
Avoid the following drain piping.
CAUTION Go through all installation steps and check if the
dralnage is all right. Otherwise water leak may occur.
Higher than specified The drain hose Wavy The gap to the ground is The drain hose
13 Pipe bender tip is in water 5 cm or less tip is in the gutter
5
726
585
5
585
726 156.
585 5
595
)
(600)
38 8
585
595
(2 19 )
(600)
38
30.5 (2
Standard hole
Fixing on concrete wall
5 Use of nut anchor
25.5 18
Bolt
(M6 12) Adjustment of the installation board in the horizontal
If there is an obstacle such as a cable cover, direction is to be conducted with five screws in a temporary When practicing the half-console, make sure to fix the unit securely.
cut off the hatched part before installation. tightened state. Otherwise, it could fall.
Installation Adjust so the board will be level by turning the board with
board the standard hole as the center.
CONNECTION OF REFRIGERANT PIPINGS CAUTION Be careful not to stress the connecting refrigerant pipes.
(Do not pull with a force of larger than 5 kgf.)
Preparation Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. Connection Finishing work and fixing
from entering them.
Connect the pipes on both liquid and gas sides.
Indoor (Do not turn) (Do not turn)
Dimension A Indoor Liquid side Tighten the nuts to the following torque. Refrigerant piping
90 ± 0.5°
Clamp
CAUTION
Do not apply refrigerating machine oil to the flared surface. Insulation of the connection portion
Flaring work Pass the refrigerant pipe through the piping hole to Cover the coupling with insulator and then cover it with tapes.
Measurement B (mm) CAUTION
indoor side. Use an attached pipe cover for heat insulation.
Measurement B Copper pipe diameter Clutch type flare tool for Conventional (R22) flare tool Arrange the pipes according to the direction of piping. If heat insulation is insufficient, water leakage
R410A Clutch type Wing nut type may occur. In addition, the room temperature
ø6.35 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0 Refrigerant sensor may give a false alert due to heat
Refrigerant Refrigerant
pipe pipe radiation from the pipes.
ø9.52 0.0 - 0.5 1.0 - 1.5 1.5 - 2.0 155 pipe
ø12.7 0.0 - 0.5 1.0 - 1.5 2.0 - 2.5 105 Slit Slit
Cover the indoor unit’s flare-connected joints, after
Flaring Use a flare tool designed for R410A or a conventional flare tool. they are checked for a gas leak, with an indoor unit
block ⑨Pipe cover
Copper pipe Please note that measurement B (protrusion from the flaring block) will vary depending 45 Add heat insulating material and then wrap them with a
on the type of a flare tool in use. Tape ⑩band
tape with an attached pipe cover placed over the
If a coventional flare tool is used, please use a copper pipe gauge or a similar heat insulating material’s slit area.
instrument to check protrusion so that you can keep measurement B to a correct value. 130
140 Position it so that the slit area faces upward.
Latch
ELECTRICAL WIRING WORK CAUTION
During installation, do not lean on the control box or the display, as they
How to fit the front panel
may be damaged. Fitting
Preparation of indoor unit CAUTION
Pass the connecting wire securely through the wiring holder. If it passes 1 Do remove the air filter.
In case of faulty wiring connection, the indoor unit
on the sensor, it may not detect suction temperature and/or humidity. 2 Cover the body with the front panel.
stops, and then the run lamp turns on and the timer
Mounting of connecting wires 3 Fit the 6 latches in the lower section.
lamp blinks.
1 Remove the fixing screw of clamp. then 3 latches in the upper section.
2 Connect the connecting wire securely to the terminal block. 4 Tighten the 5 set screws.
Use cables for interconnection wiring to avoid
1 ) Connect the connection wire securely to the terminal 5 Fit the air filter.
loosening of the wires.
block. If the wire is not affixed completely, contact will be CENELEC code for cables Required field cables. Terminal block 6 Fit the air inlet panel.
poor, and it is dangerous as the terminal block may heat
Close and attachment of the air inler panel
'11 • SCM-SM-110
up and catch fire. H05RNR4G1.5 (example) or 245IEC57 Latch
2 ) Take care not to confuse the terminal numbers for indoor H Harmonized cable type
and outdoor connections. 05 300/500 volts To close, attach the panel after pulling
3 Fix the connecting wire by wiring clamp. R Natural-and/or synth, rubber wire insulation the strings, hold the panel at both ends of
4 Pass the connecting wire through the wiring holder. N Polychloroprene rubber conductors insulation upper part to lower downward and push it
Clamp
R Stranded core slightly until the latch works.
4or5 Number of conductors
G One conductor of the cable is the earth
conductor (yellow/green) Fixing screw Wiring holder
1.5 Section of copper wire (mm2)
Sensor
CAUTION
Incorrect installation may cause problems such as non-cooling,
non-warming, and condensation water leaking into the room. JP171 CUSTOM
JP170 REMOTE/ SWITCH
AUTORESTART
JP173 AIR FLOW
JP172 COOL ONLY
Air-cleaning filter Filter holder
Cut 2 - 3cm CAUTION
When installing an air-cleaning filter in the indoor unit, be careful not to injure
your hand with the heat exchanger.
'11 • SCM-SM-110
malfunction. Do not carry out the installation and maintenance work except • The electrical installation must be carried out by the qualified specified in the manual. leakage in the small room, lack of oxygen can occur, which can cause
the by qualified installer. electrician in accordance with “the norm for electrical work” and Insufficient space can result in accident such as personal injury due to serious accidents.
189 -
• Install the system in full accordance with the installation manual. “national wiring regulation”, and the system must be connected to
Incorrect installation may cause bursts, personal injury, water leaks, electric the dedicated circuit. • Do not install the unit in the locations listed below. If leaked gases accumulate around the unit, it can cause fire.
shocks and fire. Power supply with insufficient capacity and incorrect function done by • Locations where carbon fiber, metal powder or any powder is floating. • Do not install the unit where corrosive gas (such as sulfurous acid
• Be sure to use only for household and residence. improper work can cause electric shocks and fire. • Locations where any substances that can affect the unit such as sulphide gas etc.) or combustible gas (such as thinner and petroleum gases)
If this appliance is installed in inferior environment such as machine shop • Be sure to shut off the power before starting electrical work. gas, chloride gas, acid and alkaline can occur. can accumulate or collect, or where volatile combustible
and etc., it can cause malfunction. Failure to shut off the power can cause electric shocks, unit failure or • Vehicles and ships. substances are handled.
• Use the original accessories and the specified components for incorrect function of equipment. • Locations where cosmetic or special sprays are often used. Corrosive gas can cause corrosion of heat exchanger, breakage of plastic
installation. • Be sure to use the cables conformed to safety standard and cable • Locations with direct exposure of oil mist and steam such as kitchen and parts and etc. And combustible gas can cause fire.
If parts other than those prescribed by us are used, It may cause water ampacity for power distribution work. machine plant. • Do not use the indoor unit at the place where water splashes may
leaks, electric shocks, fire and personal injury. Unconformable cables can cause electric leak, anomalous heat production • Locations where any machines which generate high frequency harmonics occur such as in laundries.
• Install the unit in a location with good support. or fire. are used. Since the indoor unit is not waterproof, it can cause electric shocks and fire.
Unsuitable installation locations can cause the unit to fall and cause • This appliance must be connected to main power supply by means • Locations with salty atmospheres such as coastlines. • Do not install nor use the system close to the equipment that
material damage and personal injury. of a circuit breaker or switch (fuse:16A) with a contact separation of • Locations with heavy snow (If installed, be sure to provide base flame and generates electromagnetic fields or high frequency harmonics.
• Ventilate the working area well in the event of refrigerant leakage at least 3mm. snow hood mentioned in the manual). Equipment such as inverters, standby generators, medical high frequency
during installation. • When plugging this appliance, a plug conforming to the norm • Locations where the unit is exposed to chimney smoke. equipments and telecommunication equipments can affect the system, and
If the refrigerant comes into contact with naked flames, poisonous gas is IEC60884-1 must be used. • Locations at high altitude (more than 1000m high). cause malfunctions and breakdowns. The system can also affect medical
produced. • Use the prescribed cables for electrical connection, tighten the • Locations with ammonic atmospheres. equipment and telecommunication equipment, and obstruct its function or
• When installing in small rooms, take prevention measures not to cables securely in terminal block and relieve the cables correctly to • Locations where heat radiation from other heat source can affect the unit. cause jamming.
exceed the density limit of refrigerant in the event of leakage, prevent overloading the terminal blocks. • Locations without good air circulation. • Do not place any variables which will be damaged by getting wet
referred by the formula (accordance with ISO5149). Loose connections or cable mountings can cause anomalous heat • Locations with any obstacles which can prevent inlet and outlet air of the unit. under the indoor unit.
If the density of refrigerant exceeds the limit, please consult the dealer and production or fire. • Locations where short circuit of air can occur (in case of multiple units When the relative humidity is higher than 80% or drainage pipe is clogged,
install the ventilation system, otherwise lack of oxygen can occur, which • Arrange the wiring in the control box so that it cannot be pushed up installation). condensation or drainage water can drop and it can cause the damage of
can cause serious accident. further into the box. Install the service panel correctly. • Locations where strong air blows against the air outlet of outdoor unit. valuables.
• After completed installation, check that no refrigerant leaks from Incorrect installation may result in overheating and fire. • Locations where something located above the unit could fall. • Do not install the remote control at the direct sunlight.
the system. • Be sure to switch off the power supply in the event of installation, It can cause remarkable decrease in performance, corrosion and damage It can cause malfunction or deformation of the remote control.
If refrigerant leaks into the room and comes into contact with an oven or inspection or servicing. of components, malfunction and fire. • Do not use the unit for special purposes such as storing foods,
other hot surface, poisonous gas is produced. If the power supply is not shut off, there is a risk of electric shocks, unit • Do not install the indoor unit in the locations listed below (Be sure cooling precision instruments and preservation of animals, plants or
• Use the prescribed pipes, flare nuts and tools for R410A. failure or personal injury due to the unexpected start of fan. to install the indoor unit according to the installation manual for art.
'11 • SCM-SM-110
Using existing parts (for R22 or R407C) can cause the unit failure and • Be sure to wear protective goggles and gloves while at work. each model because each indoor unit has each limitation). It can cause the damage of the items.
serious accidents due to burst of the refrigerant circuit. • Earth leakage breaker must be installed. • Locations with any obstacles which can prevent inlet and outlet air of the • Do not use any materials other than a fuse with the correct rating in
If the earth leakage breaker is not installed, it can cause electric shocks. unit. the location where fuses are to be used.
• Locations where vibration can be amplified due to insufficient strength of Connecting the circuit with copper wire or other metal thread can cause
• Do not put the drainage pipe directly into drainage channels where • Do not processing, splice the power cord, or share a socket with structure. unit failure and fire.
poisonous gases such as sulphide gas can occur. other power plugs. • Locations where the infrared receiver is exposed to the direct sunlight or • Do not touch any buttons with wet hands.
Poisonous gases will flow into the room through drainage pipe and This may cause fire or electric shock due to defecting contact, defecting the strong light beam (in case of the infrared specification unit). It can cause electric shocks.
seriously affect the user’s health and safety. This can also cause the insulation and over-current etc. • Locations where an equipment affected by high harmonics is placed (TV • Do not touch any refrigerant pipes with your hands when the
corrosion of the indoor unit and a resultant unit failure or refrigerant leak. • Do not bundling, winding or processing for the power cord. Or, do set or radio receiver is placed within 1m). system is in operation.
• Ensure that no air enters in the refrigerant circuit when the unit is not deforming the power plug due to tread it. • Locations where drainage cannot run off safely. During operation the refrigerant pipes become extremely hot or extremely
installed and removed. This may cause fire or heating. It can affect performance or function and etc. cold depending the operating condition, and it can cause burn injury or
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit • Do not install the unit near the location where leakage of frost injury.
becomes too high, which can cause burst and personal injury. combustible gases can occur.
⑨ Flat head wood screw (for remote control holder φ3.5x16) 2 B Ceiling hanging bolts (M8) 4 ● Charge hose (Designed specifically for R410A)
● Flaring tool set (Designed specifically for R410A)
⑩ Flat head machine screw (for wireless receiver M3.5x10) 2 C Nuts (M8) 8
● Gas leak detector (Designed specifically for R410A)
⑪ Tapping screw (for clamp, φ4x8) 1 D Spring lock washers (M8) 4
● Gauge for projection adjustment
⑫ Plate (display) 1 (Used when flare is made by using conventional flare tool)
⑨ Flat head wood screw (for remote control holder φ3.5x16) 2 B Ceiling hanging bolts (M8) 4 ● Charge hose (Designed specifically for R410A)
● Flaring tool set (Designed specifically for R410A)
⑩ Flat head machine screw (for wireless receiver M3.5x10) 2 C Nuts (M8) 8
● Gas leak detector (Designed specifically for R410A)
⑪ Tapping screw (for clamp, φ4x8) 1 D Spring lock washers (M8) 4
● Gauge for projection adjustment
⑫ Plate (display) 1 (Used when flare is made by using conventional flare tool)
● A firm location that may sustain the weight of the unit, and do not cause the unit or the (Fit the poles with the indication marks, + & − without fail)
190 -
ceiling to vibrate.
● A location that allows room for maintenance.
● Where wiring and plumbing may be performed with ease.
● Where water may be drained easily. ⑦ Battery
● Where the unit is not influenced by the television, stereo, radio, or the lights.
● Where the unit is not influenced by high frequency equipment and wiring equipment.
● Where oil splashes do not occur frequently.
● Where sunlight and strong lights do not directly hit the receiver.
Sleeve
● A flat ceiling surface (bottom of ceiling). CAUTION Indoor side Outdoor side (sold separately) Cover
● Where the suction inlet of the unit is located far from the air inlet on the ceiling, the entire Completely seal the hole on putty
the wall with putty. Otherwise,
inside of ceiling acts as an air suction duct so that the capacity is reduced at the startup. furniture, or other, may be
In such occasion, it is recommended to install a duct at the air suction side. wetted by leaked water or putty
● Where the suction inlet of the unit does not match the air inlet and there is not sufficient dewing.
clearance between the unit and the ceiling face, the capacity is reduced. It is necessary to
enable the air suction from the back by using optional parts © (Back side suction filter set Fixing to pillar or wall
model RBF12).
○ Conventionally, operate the wireless remote control by holding in
Wireless remote control your hand.
○ In the case of stationary operation service as by mounting on the
● Where the main unit can definitely detect the signals from the wireless remote control.
● Where it is not influenced by television or stereo.
holder for the wireless remote control, make sure that the locating
● Avoid locations with direct sunlight or around heaters.
place is satisfactory for access service before installing it.
○ Avoid installing it on a clay wall etc.
● Do not attach to weak walls such as a mud wall.
'11 • SCM-SM-110
Maximum pipe length
The maximum lengths and height differences for the pipes differ according to their
outdoor unit. Please refer the Installation Instructions for the outdoor unit.
② Remote control holder
Clamp
⑨ Wood screw
φ3.5×16
① Wireless remote control Adjust the installation to vertical attitude.
Avoid projecting the screw head.
Installation dimensions
740 Flaring
35 670 35 Front Side block
Hanging bolt pitch
30
740 106 455 38
Gas side pipes
11
Hanging bolt pitch
(2) Connection
Plan
515
455
Indoor
230
150
Liquid side
Gas side
236
30
Drain hose 135 78 Liquid side pipes
(Connection opening diameter ø16) (Do not
30
2 INSTALLATION OF INDOOR UNIT Securing thethe
Connecting ceiling
Drainhanging
Hose bolts
If steel embedded ceiling If wooden ceiling
Drilling of holes in the wall and fixture of sleeve Holes for ceiling hanging bolts
4 HEAT INSU
⑪ Tapping screw
Inserts Square bars for hanging the air conditioner
● The connecting wires may touch the metal inside the wall and cause danger so it is necessary to
always use the sleeve. (unit : mm)
Heat insul
Traps
○ Secure the ceiling hanging
Inclination plate Opposite slope
Indoor side Outdoor side Sleeve Sleeve Pipe bolts firmly following the
Concrete
Holed anchor illustrations and other Vinyl tape
⑤ Drain hose
Holed plug
Hanging bolts M8 Clamps Beams
Bumps
instructions.
φ65 ⑥ Clamp
Wall thickness + 15
Sealing plate Assembled state
InstallingNOTE
● Drilla hole with a 65 whole ● When the pipe is connected at the rear, cut off the lower and the right side
core drill. portions of the sleeve collar (as shown by the broken line).
the main unit
○
Conduct
Attach the theand
washers installation correctly,
nuts to the ceilingand ensure
hanging that the water is draining correctly.
bolts.
It may lead to water leaks.
○ Attach the hanging tool to the above nuts, and tighten the nuts.
Preparations for the main frame 5 TEST RUN
M8 handling bolt M8 nut
not turn)
be poor, and it is dangerous as the terminal block may control lid is Liquid side 9.1(mm)
□ Earthing wor
tightened securely. ○ Insert the wireless receiver ③ inA the installationGas side ④, and fix the Do
frame not apply
calking refrigerating machine oil to
section.
heat up and catch fire. the flared □ The screw of
2) Take care not to confuse the terminal numbers for
○ Fix the installationRemove
Press
frame ④ on the wall using the φflat
9.52 : 13.2(mm)
head machine screws ⑩.surface.
φ12.7 : 16.2(mm)
indoor andoutdoor connections. ○ Fix the plate (display) ⑫ on the
○ Remove the flared nuts.
installation frame ④ using the flat head machine screws packed together
○ Install the removed flared nuts to the pipes
3) Affix the connection wire using the wiring clamp. with theliquid
(on both plate sides) ⑫.
(display)
and gas to be connected, then flare the pipes.
'11 • SCM-SM-110
740 106 455 38 similar instrument to check protrusion so that you can keep measurement B to a correct it shall never be do
Gas side pipes value.
TV antenna, lightni
11
Hanging bolt pitch
Indoor
230
150
Liquid side
○ Connect the pipes on both liquid and gas sides.
Gas side ○ Tighten the nuts to the following torque.
236
Liquid side : 14.0 ~ 18.0 N·m (1.4Air
~ filter
1.8 kgf·m)
30
90 ± 0.5°
(Do not turn)
be poor, and it is dangerous as the terminal block may control lid is
A
Liquid side 9.1(mm)
Do not apply refrigerating machine oil to
tightened securely. Gas side
heat up and catch fire. Press φ9.52 : 13.2(mm) the flared surface.
2) Take care not to confuse the terminal numbers for Remove φ12.7 : 16.2(mm)
indoor andoutdoor connections. ○ Remove the flared nuts. ○ Install the removed flared nuts to the pipes
3) Affix the connection wire using the wiring clamp. (on both liquid and gas sides) to be connected, then flare the pipes.
740 106 455 38 similar instrument to check protrusion so that you can keep measurement B to a correct
Gas side pipes value.
11
Hanging bolt pitch
(2) Connection
Plan
515
455
Indoor
230
150
Liquid side
○ Connect the pipes on both liquid and gas sides.
Gas side ○ Tighten the nuts to the following torque.
236
Liquid side : 14.0 ~ 18.0 N·m (1.4 ~ 1.8 kgf·m)
30
Drain hose 135 78 Liquid side pipes
(Connection opening diameter ø16) (Do not turn) Gas side (φ9.52) : 33.0 ~ 42.0 N·m (3.3 ~ 4.2 kgf·m)
30
indoor units (gas side pipe 12.7) is going to be connected to the operation valves (9.52), variable joints available as □ No gas leaks from the joints of the operation valve. □ No abnormal noise.
accessories must be applied to the gas side operation valves. □ Power cables and crossover wires are securely fixed to □ Water drains smoothly.
192 -
③Wireless receiver
the terminal board. □ Protective functions are not working.
[Connection of pipes] Calking
Cut off this section if it interferes
with the wall.
□ Each indoor and outdoor unit is properly connected (no □ Operation of the unit has been
wrong wiring or piping). explained to the customer.
NOTE □ Operation valve is fully open. □ The wireless remote control is normal.
● Coverthe pipes with tape so that dust and sand do not enter the pipe until they are connected.
Flat head ⑩ Flat head □ Refrigerant has been additionally charged (when the total
● When connecting the pipesmachine
machine screw to thescrew
outdoor unit, be careful about the discharge of fluorocarbon gas or oil.
pipe length exceeds the refrigerant charged pipe length).
● Make sure to
(In match the
the pack of ⑫) pipes between the indoor unit and the outdoor unit with the correct operation valves.
□ The pipe joints for indoor and outdoor pipes have been
(1)○Preparations
Open a through-hole on the wall to install the reception face for the wireless receiver ③. insulated.
○ Insert the wireless receiver ③ in the installation frame ④, and fix the calking section. □ Earthing work has been conducted properly.
block Clamp ○ Indoor
Fix the installation frame ④ on the wall using the flat head
Dimension A machine screws ⑩. CAUTION □ The screw of the control lid is tightened securely.
90 ± 0.5°
'11 • SCM-SM-110
38 similar instrument to check protrusion so that you can keep
Filter measurement B to a correct
guide
Gas side pipes value.
(2) Connection
Indoor Air filter
Liquid side
○ Connect the pipes on both liquid and gas sides.
Gas side ○ Tighten the nuts to the following torque.
236
Liquid side : 14.0 ~ 18.0 N·m (1.4 ~ 1.8 kgf·m)
135 78 Liquid side pipes
16) (Do not turn) Gas side (φ9.52) : 33.0 ~ 42.0 N·m (3.3 ~ 4.2 kgf·m)
(φ12.7) : 49.0 ~ 61.0 N·m (4.9 ~ 6.1 kgf·m)
Unit main body
RJD012A201B
- 193 -
A012D786
A012D781 ① Before installation ③ Preparation before installation
l Install correctly according to the installation manual. l If suspension bolt becomes longer, do reinforcement of earthquake resistant.
l Confirm the following points: For grid ceiling
Unit type/Power supply specification Pipes/Wires/Small parts Accessory items When suspension bolt length is over 500mm, or the gap between the ceiling and roof is over
700mm, apply earthquake resistant brace to the bolt.
Accessory itme In case the unit is hanged directly from the slab and is installed on the ceiling plane which has
For unit hanging For refrigerant pipe For draom pipe
enough strength.
Flat washer Level gauge
Pipe cover(big)
Pipe cover
Strap Pipe cover(big) Pipe cover(small) Drain hose Hose clamp
When suspension bolt length is over 1000mm, apply the earthquake resistant brace to the bolt.
QSPQFSFBSUIDPVME (M10) (Insulation) (small)
l Prepare four (4) sets of suspension bolt, nut and spring washer (M10 or M8) on site.
. Improper
Ceiling opening, Suspension bolts pitch, Pipe position
8 4 1 1 4 1 1 1 1
For adjustment For heat For heat For heat For heat
DPOOFDUBMM For unit hanging in hoisting in the insulation insulation
For pipe cover
fixing
insulation insulation
For drain pipe
connecting
For drain hose
mounting 530 (Suspension bolts pitch) F Decorative panel
unit's main body of gas pipe of liquid tube of drain socket of drain socket
326
350
) or Areas where the indoor unit can deliver hot and cold wind sufficiently. Suggest to the user to use
NBCMFHBT TVDI
or volatile a circulator if the ceiling height is over 3m to avoid warm air being accumulated on the ceiling.
556
DFTBSFIBOEMFE
67
VMEDBVTFmSF
MEDBVTFmSF Areas where there is enough space to install and service. Control Air return
35
185 box Air supply grille
uld cause fire. Areas where it can be drained properly. Areas where drain pipe descending slope can be taken. 190 223
D
21 □413
Areas where there is no obstruction of airflow on both air return grille and air supply port. 200 48 □700
DF Drain hose piece
Areas where fire alarm will not be accidentally activated by the air conditioner. (Accessory)
precision Areas where the supply air does not short-circuit. □570
(Installed on site)
140 6-φ4
Areas where it is not influenced by draft air. A B 145
325
C E
60 Holes for
tapping screws
DJTJPO Areas not exposed to direct sunlight.
88
Hole
wave or Areas where dew point is lower than around 28°C and relative humidity is lower than 80%.
140
248
This indoor unit is tested under the condition of JIS (Japan Industrial Standard) high humidity
210
192
100
132
88
IJHIIBSNPOJDT
JHIIBSNPOJDT condition and confirmed there is no problem. However, there is some risk of condensation drop 100
45 or more
kdown. Or the
FMFDPNNVOJDBUJPO if the air conditioner is operated under the severer condition than mentioned above.
35
Hanger plate for F
suspension bolt
their medical
EJUJPOFSNJHIU If there is a possibility to use it under such a condition, attach additional insulation of 10 to
SDBVTFKBNNJOH
20mm thick for entire surface of indoor unit, refrigeration pipe and drain pipe.
Areas where TV and radio stays away more than 1m. (It could cause jamming and noise.)
Areas where any items which will be damaged by getting wet are not placed such as food, table
wares, server, or medical equipment under the unit. ④ Installation of indoor unit
TQFDJBMTQSBZTBSF Areas where there is no influence by the heat which cookware generates.
Areas where not exposed to oil mist, powder and/or steam directly such as above fryer. Work procedure
loride gas,
CFBDI
Areas where lighting device such as fluorescent light or incandescent light doesn’t affect the 1. This units is designed for 2 x 2 grid ceiling.
BGGFDUFECZ operation. If necessary, please detach the T bar temporarily before you install it.
(A beam from lighting device sometimes affects the infrared receiver for the wireless remote If it is installed on a ceiling other than 2 x 2 grid ceiling, provide an inspection port on the control box
controller and the air conditioner might not work properly.) side.
SVOJU k Check if the place where the air conditioner is installed can hold the weight of the unit. If it is not 2. Arrange the suspension bolt at the right position (530mm×530mm).
DIMJNJUBUJPO
able to hold, reinforce the structure with boards and beams strong enough to hold it. If the strength 3. Make sure to use four suspension bolts and fix them so as to be able to hold 500N load.
is not enough, it could cause injury due to unit falling. 4. Ensure that the lower end of the suspension bolt should be 45mm above the ceiling plane.
l If there are 2 units of wireless type, keep them away for more than 5m to avoid malfunction due to Temporarily put the four lower nuts 88mm above the ceiling plane and the upper nuts on distant
BTFPGUIF
oner. cross communication. place from the lower nuts in order not to obstruct hanging the indoor unit or adjust the indoor unit
DFEXJUIJON
dFEXJUIJON
it damages m When plural indoor units are installed nearby, keep them away for more than 4m. position, and then hang the indoor unit.
Control box
a long Space for installation and service
OFS T bar Ceiling
VTFSTCFMPOHJOHT
l When it is not possible to keep enough space between indoor unit and wall or between indoor units, panel
close the air supply port where it is not possible to keep space and confirm there is no short circuit
HQFSJPEPGVTF
ne near the
of airflow.
l Install the indoor unit at a height of more than 2.5m above the floor.
d leakage of
FOFBSUIFVOJU
FBLBHFPGXBUFS
5. Adjust the indoor unit position after hanging it by inserting the level gauge attached on the package
4000mm or more into the air supply port and checking if the gap between the ceiling plane and the indoor unit is
longings. appropriate. In order to adjust the indoor unit position, adjust the lower nuts while the upper nuts are
is Indoor unit Indoor unit put on distant place. Confirm there is no backlash between the hanger plate for suspension bolt and
OHJOHT
the lower nut and washer.
VOJU
Drain piping
FODZPGPYZHFO
UP
ODZPGPYZHFO
UP Suspension bolt
or unit. Ceiling Refrigerant piping
ciency of
BOUQJQJOHXPSL Wall surface
BOUQJQJOHXPSL 1000mm or more
Nut (upper)
LPGPYZHFODBO
PGPYZHFODBO Decorative panel 2500mm or more
not to
1000mm or more Flat washer
UPNBLFUSBQT
UPNBLFUSBQT
Obstacle
nd Spring washer
NBJOUFOBODF Floor Nut (lower)
ater. 88mm
S
bles. 45mm
T Level gauge
mals.
BMT
e.MTInstruct the Ceiling surface
OTUSVDUUIFVTFSUP
Use level gauges as Use level gauges as
reference, adjust the reference, adjust the
place, moving bottom to the face of bottom to the face of
30
30
Touch the nut (lower) and Play is left between the fixture
washer without any play and the nut (lower) and washer.
yBVTFJOKVSZ
cause injury.
BVTFJOKVSZ
- 194 -
④ Installation of indoor unit (continued) ⑥ Drain pipe (continued) ⑥ Drain pipe (co
6. Make sure to install the indoor unit horizontally. Confirm the Work procedure Drain test
levelness of the indoor unit with a level gauge or transparent Indoor unit 1. Make sure to insert the drain hose (the end mode of soft PVC) to the end of the step part of drain l After installation of drain
hose filled with water. Keep the height difference at both ends of
the indoor unit within 3mm. hose
socket. leakage from joint and d
7. Tighten four upper nuts and fix the unit after height and levelness Attach the hose clamp to the drain hose around 10mm from the end, and fasten the screw within l Do drain test even if ins
adjustment. 5mm left to the nut. l For new building cases,
l Do not apply adhesives on this end. hanging the ceiling.
Caution 1. Pour water of about 100
pipe cover (big) Joint for VP-20
(For insulation) (Prepare on site) pump so as not to get th
l Do not adjust the height by adjusting upper nuts. It will cause unexpected stress on the indoor unit (Accessory)
2. Make sure that water is
and it will lead to deformation of the unit, failure of attaching a panel, and generating noise from the
leakage from any joints
fan. Unit
l Make sure to install the indoor unit horizontally and set the gap between the unit underside and The step part Drain hose Confirm that the water i
Drain socket
the ceiling plane properly. Improper installation may cause air leakage, dew condensation, water Drain hose VP-20 is operating. At the drain
leakage and noise. (Accessory) (Prepare on site) check if the water is dra
Connect
l Even after decorative panel attached, still the unit height can be adjusted finely. Refer to the Clamp 3. Unplug the drain plug o
Drain socket (Accessory Pipe cover (small)
installation manual for decorative panel for details. (For insulation) on the drain pan after th
l Make sure there is no gap between decoration panel and ceiling surface, and between decoration No adhesive allowed Pipe cover (small) (Prepare on site)
pipe properly finally.
(For insulation)
panel and the indoor unit. The gap may cause air leakage, dew condensation and water leakage. (Accessory)
l In case decorative panel is not installed at the same time, or ceiling material is installed after the Drain pump operation
unit installed, put the cardboard template for installation attached on the package (packing material Fasten the screw within 5 mm left to the nut.
of cardboard box) on the bottom of the unit in order to avoid dust coming into the indoor unit. Drain hose
In case electrical wiring
Hose clamp
Drain pump can be ope
Drain socket
For the operation metho
⑤ Refrigerant pipe work.
In case electrical wiring
Caution
Metal plate Drain pump will run con
l Use the new refrigerant pipe. 10mm the Connector CNB is d
When re-using the existing pipe system for R22 or R407C, pay attention to the following items. [ ① and ②] or [ Ⓛ and
Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare parts. Make sure to turn OFF
Do not use thin-walled pipes. 2. Prepare a joint for connecting VP-20 pipe, adhere and connect the joint to the drain hose (the end
l Use phosphorus deoxidized copper alloy seamless pipe (C1220T specified in JIS H3300) for made of rigid PVC), and adhere and connect VP-20 pipe (prepare on site).
refrigeration pipe installation. As for drain pipe, apply VP-20 made of rigid PVC which is on the market.
In addition, make sure there is no damage both inside and outside of the pipe, and no harmful l Make sure that the adhesive will not get into the supplied drain hose. ⑦ Wiring-out po
substances such as sulfur, oxide, dust or a contaminant stuck on the pipes. It may cause the flexible part broken after the adhesive is dried up and gets rigid.
l Do not use any refrigerant other than R410A. l Electrical installation wo
l Do not bend or make an excess offset on the drain hose as shown in the picture.
Using other refrigerant except R410A (R22 etc.) may degrade inside refrigeration oil. And air getting installation service prov
into refrigeration circuit may cause over-pressure and resultant it may result in bursting, etc. Bend or excess offset will cause drain leakage.
to the technical standar
l Store the copper pipes indoors and seal the both end of them until they are brazed in order to avoid Be sure to use an exclu
any dust, dirt or water getting into pipe. Otherwise it will cause degradation of refrigeration oil and l Use specified cord, fast
compressor breakdown, etc.
not to apply unexpected
l Use special tools for R410 refrigerant. Over 20mm l Do not put both power s
miscommunication and
Work procedure
l Be sure to do D type ea
1. Remove the flare nut and blind flanges on the pipe of the indoor unit. l For the details of electri
Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving 3. Make sure to make descending slope of greater than 1/100 and do not make up-down bend and/or
torque to the nut with another spanner in order to avoid unexpected stress to the copper pipe, 1. Remove a lid of the con
trap in the midway.
and then remove them.
l Pay attention not to give stress on the pipe on the indoor unit side, and support and fix the pipe 2. Hold each wiring inside
(Gas may come out at this time, but it is not abnormal.)
l Pay attention whether the flare nut pops out. (as the indoor unit is sometimes pressured.) as close place to the unit as possible when connecting the drain pipe. 3. Fix the wiring with clam
2. Make a flare on liquid pipe and gas pipe, and connect the refrigeration pipes on the indoor unit. l Do not set up air vent. 4. Install a lid of the contro
Bend the pipe with as big radius as possible and do not bend the pipe repeatedly. In addition, do
not twist and crush the pipes.
1.5m ~ 2m Supporting metal Trapped air will
Do a flare connection as follows: No bump
generate noises.
l Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving Air vent No trap
torque to the nut with another spanner in order to avoid unexpected stress to the copper pipe, Not touching the water
and then remove them. Insulation material
l When fastening the flare nut, align the refrigeration pipe with the center of flare nut, screw the Descending slope greater than 1/100
nut for 3-4 times by hand and then tighten it by spanner with the specified torque mentioned
in the table below. Make sure to hold the pipe on the indoor unit securely by a spanner when As wide as possible
tightening the nut in order to avoid unexpected stress on the copper pipe. l When sharing a drain pipe for more than one (about100mm)
3. Cover the flare connection part of the indoor unit with attached insulation material after a gas unit, lay the main pipe 100mm below the drain
leakage inspection, and tighten both ends with attached straps. outlet of the unit. In addition, select VP-30 or
l Make sure to insulate both gas pipes and liquid pipes completely. bigger size for main drain pipe.
Incomplete insulation may cause dew condensation or water dropping. VP-30 or bigger
4. Refrigerant is charged in the outdoor unit. Descending stop greater than 1/100
4. Insulate the drain pipe.
As for the additional refrigerant charge for the indoor unit and piping, refer to the installation manual l Be sure to insulate the drain socket and rigid PVC pipe installed indoors otherwise it may cause
attached to the outdoor unit. dew condensation and water leakage.
Strap (Accessory) Pipe cover (Accessory) After drainage test implementation, cover the drain socket part with pipe cover (small size),
Pipe diameter Tightening torque N·m then use the pipe cover (big size) to cover the pipe cover (small size), clamps and part of the
f 6.35 14 to 18 drain hose, and fix and wrap it with tapes to wrap and make joint part gapless.
f 9.52 34 to 42
f 12.7 49 to 61
f 15.88 68 to 82 Drain up
f 19.05 100 to 120 The thickness of insulation should be 20mm or more.
l The position for drain pipe outlet can be raised up to 600mm above the ceiling. Use elbows for
installation to avoid obstacles inside ceiling. If the horizontal drain pipe is too long before vertical
pipe, the backflow of water will increase when the unit is stopped, and it may cause overflow of
⑥ Drain pipe water from the drain pan on the indoor unit. In order to avoid overflow, keep the horizontal pipe
length and offset of the pipe within the limit shown in the figure below.
Caution
l Install the drain pipe according to the installation manual in order to drain properly. 295 to 325mm 100 or less
Imperfection in draining may cause flood indoors and wetting the household goods,etc.
l Do not put the drain pipe directly into the ditch where toxic gas such as sulfur, the other harmful and Drain hose
600mm or less
inflammable gas is generated. Toxic gas would flow into the room and it would cause serious
damage to user’s health and safety (some poisoning or deficiency of oxygen). In addition, it may
cause corrosion of heat exchanger and bad smell.
l Connect the pipe securely to avoid water leakage from the joint.
l Insulate the pipe properly to avoid condensation drop.
Joint for VP-20
l Check if the water can flow out properly from both the drain outlet on the indoor unit and the end of
(Prepare on site)
the drain pipe after installation.
l Make sure to make descending slope of greater than 1/100 and do not make up-down bend and/or
trap in the midway. In addition, do not put air vent on the drain pipe. Check if water is drained
out properly from the pipe during commissioning. Also, keep sufficient space for inspection and
maintenance.
- 195 -
water
Power source side terminal block
Earth
Wiring between indoor
and outdoor unit
Remote controller line
Wiring clamp
VP-30 or bigger
than 1/100
Signal side terminal block
herwise it may cause
VRF (KX) series
cover (small size),
amps and part of the 6
apless. 6
PJA012D786
PJA012D781
- 196 -
PJAO12D786
- 197 -
Note : This function is not able to be set with wireless remote controls or simple remote control (RCH-H3).
5
5
7
7
For setting the swing range of other louvers, return to 1 and proceed same procedure respectively.
- 198 -
●Check for refrigerant gas leakage after installation is completed. ● Do not share the drain pipe for indoor unit and GHP (Gas Heat Pump system) outdoor unit.
Toxic exhaust gas would flow into room and it might cause serious damage (some poisoning or deficiency of oxygen) to
If the refrigerant gas leaks into the house and comes in contact with a fan heater, a stove, or an oven, toxic gas is produced.
user’s health and safety.
●Use the specified pipe, flare nut, and tools for R410A. ● Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work.
Using existing parts (R22) could cause the unit failure and serious accident due to explosion of the cooling cycle. If the density of refrigerant exceeds the limit in the event of refrigerant leakage in the small room, lack of oxygen can
●Tighten the flare nut according to the specified method by with torque wrench. occur, which can cause serious accidents.
If the flare nut were tightened with excess torque, it could cause burst and refrigerant leakage after a long period. ● For drain pipe installation, be sure to make descending slope of greater than 1/100, not to make traps,
and not to make air-bleeding.
●Do not put the drainage pipe directly into drainage channels where poisonous gases such as sulfide gas can occur. Check if the drainage is correctly done during commissioning and ensure the space for inspection and maintenance.
Poisonous gases will flow into the room through drainage pipe and seriously affect the user's health and safety. This can also
● Ensure the insulation on the pipes for refrigeration circuit so as not to condense water.
cause the corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
Incomplete insulation could cause condensation and it would wet ceiling, floor, and any other valuables.
●Connect the pipes for refrigeration circuit securely in installation work before compressor is operated. ● Do not install the outdoor unit where is likely to be a nest for insects and small animals.
If the compressor is operated when the service valve is open without connecting the pipe, it could cause explosion and injuries due Insects and small animals could come into the electronic components and cause breakdown and fire. Instruct the user to
to abnormal high pressure in the system. keep the surroundings clean.
●Stop the compressor before removing the pipe after shutting the service valve on pump down work. ● Pay extra attention, carrying the unit by hand.
If the pipe is removed when the compressor is in operation with the service valve open, air would be mixed in the refrigeration circuit Carry the unit with 2 people if it is heavier than 20kg. Do not use the plastic straps but the grabbing place, moving the unit
and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle. by hand. Use protective gloves in order to avoid injury by the aluminum fin.
●Only use prescribed optional parts. The installation must be carried out by the qualified installer. ● Make sure to dispose of the packaging material.
If you install the system by yourself, it can cause serious trouble such as water leaks, electric shocks, fire. Leaving the materials may cause injury as metals like nail and woods are used in the package.
● Do not operate the system without the air filter.
●Do not repair by yourself. And consult with the dealer about repair.
It may cause the breakdown of the system due to clogging of the heat exchanger.
Improper repair may cause water leakage, electric shock or fire.
● Do not touch any button with wet hands.
●Consult the dealer or a specialist about removal of the air conditioner. It could cause electric shock.
Improper installation may cause water leakage, electric shock or fire. ● Do not touch the refrigerant piping with bare hands when in operation.
●Turn off the power source during servicing or inspection work. The pipe during operation would become very hot or cold according to the operating condition, and it could cause a burn or frostbite.
If the power is supplied during servicing or inspection work, it could cause electric shock and injury by the operating fan. ● Do not clean up the air conditioner with water.
●Do not run the unit when the panel or protection guard are taken off. It could cause electric shock.
Touching the rotating equipment, hot surface, or high voltage section could cause an injury to be caught in the machine, to get ● Do not turn off the power source immediately after stopping the operation.
burned, or electric shock. Be sure to wait for more than 5 minutes. Otherwise it could cause water leakage or breakdown.
●Shut off the power before electrical wiring work. ● Do not control the operation with the circuit breaker.
It could cause electric shock, unit failure and improper running. It could cause fire or water leakage. In addition, the fan may start operation unexpectedly and it may cause injury.
- 199 -
31
Blowout opening 19
Accessory item
27 108
Top outlet 47
27
60
Right outlet
690
215 290
For unit hanging For refrigerant pipe For drain pipe For air return grille 100 Rear cover
Drain hose Hose clamp 60 Rear outlet
Flat washer (M10) Paper pattern Pipe cover (large) Pipe cover (small) Strap Fixing bracket Screw Heay insulation Screw Cutout parts
(with clamp)
Wall
※The outlet through which the pipings are taken out is
(mm) available in three directions.
Series type A B
※Pipes can be taken out in 3 directions (rear, right or
8 1 1 1 4 1 1 1 2 1 4 top).
For unit hanging For unit hanging For heat insulation For heat insulation For fixing of pipe For drain pipe For drain hose For fixing of For installing of For drain hose For fixing air 40 to 50type 1070 1022
and adjustment of gas pipe of liquid pipe cover connection mounting drain hose fixing bracket return grille Single Split (PAC) ・ Cut out holes using nippers, etc.
series 60 to 71type 1320 1272
・ Cut out holes to take out pipes along the cutoff line
100 to 140type 1620 1572 on the rear cover.
Accessories 36 to 56type 1070 1022 ・ Cut out the top face cover aligning to the piping
Air return grille
are inside. VRF (KX) series 71type 1320 1272 position.
112 to 140type 1620 1572 ・ When taking pipe out to right-hand side, cut out a
hole along the groove at the inside of side panel.
Pipe position ・ After installing pipes and wires, seal clearances
around pipes and wires with putty, etc. to shut off
235(Liquid piping) Gas dust.
Refrigerant line 135 piping Drain piping (left)
Liquid 75
195(Gas piping)
piping Make sure to install the covers at rear and top in order to
protect the inside of unit from intrusion of dust or
10
protect wires from damages by sharp edges. When
109
taking them out to the right-hand side, remove burrs or
53
53
Unit interior
②Selection of installation location for the indoor unit
271 sharp edges from the cutout.
10 mm slope 110 76
Drain piping
(right)
Haulage Grille upside
① Select the suitable areas to install the unit under approval of the user. Move the box as close to the installation area as possible packed.
・Areas where the indoor unit can deliver hot and cold wind sufficiently. If it must be unpacked, wrap the unit with a nylon sling,
Suggest to the user to use a circulator if the ceiling height is over 3m to and be careful not to damage the unit.
If you need to lay the unit on a floor after unpacking, always (Indoor unit)
avoid warm air being accumulated on the ceiling.
・Areas where there is enough space to install and service. put it with the intake grille facing upward.
・Areas where it can be drained properly. Areas where drain pipe descend- Preparation before instalation
ing slope can be taken.
1. Remove the air return grille. 2. Remove the side panel.
・Areas where there is no obstruction of airflow on both air return grille and air supply port.
Slide stoppers (4 places) of the catches, Remove the screw and detach the
・Areas where fire alarm will not be accidentally activated by the air conditioner.
then pull out the pins ( 4 or 6 places). side panel by sliding it toward the
・Areas where the supply air does not short-circuit. direction indicated by the arrow mark.
Filter
・Areas where it is not influenced by draft air. Side panel screw
Pin
・Areas not exposed to direct sunlight. (1 each on the left and right) (M4)
・Areas where dew point is lower than around 23°C and relative humidity is lower than 80%.
This indoor unit is tested under the condition of JIS (Japan Industrial
Standard) high humidity condition and confirmed there is no problem. Side panel
However, there is some risk of condensation drop if the air conditioner is 3. Remove the hanging plate.
operated under the severer condition than mentioned above. Remove the screw, and then loosen
・Areas where TV and radio stays away more than 1m. (It could cause jamming and noise.) the fixing bolts. Hanging plate
screw
・Areas where any items which will be damaged by getting wet are not placed
Unscrew Indoor Hanging
such as food, table wares, server, or medical equipment under the unit. 8-12mm unit plate fixing
・Areas where there is no influence by the heat which cookware generates. bolts(M8)
Hanging plate Hanging plate
・Areas where not exposed to oil mist, powder and/or steam directly such as above fryer.
・Areas where lighting device such as fluorescent light or incandescent light
doesn’t affect the operation.
④Remote controller
(A beam from lighting device sometimes affects the infrared receiver for the
wireless remote controller and the air conditioner might not work properly.)
Installation of remote controller
② Check if the place where the air conditioner is installed can hold the weight of the unit.
If it is not able to hold, reinforce the structure with boards and beams strong enough Up to two receiver or wired remote controller can be installed in one indoor unit
group.
to hold it. If the strength is not enough, it could cause injury due to unit falling.
③ If there are 2 units of wireless type, keep them away for more than 6m to When both wired and wireless remote controller are used
avoid malfunction due to cross communication. It is necessary to set wired or wireless remote controller as slave.
④ When plural indoor units are installed nearby, keep them away for more than 4 to 5m. (For the method of changing the setting, refer to the installtion
manual attached to remote controller or wireless kit.)
Space for installation and service
When wired remote controller are used only (wireless type)
4000~5000mm or more
It is necessary to remove the line that is connected to the receiver.
Remove signal line connected to the receiver from primary side of
terminal block (X, Y).
ATTENTION
300mm or more
100mm
or more
150mm or more ①Insulate with tape the removed line.
5mm or more ②The LED of that removed connector will not be able to make any
indication.
Obstacle
- 200 -
25 mm or more
45 mm or less
2. Install the suspension bolts in place. Ceiling Bracket
3. Fix with 4 suspension bolts, which can endure load of 500N. Hanging plate
4. Check the measurements given at the right Suspension bolt
figure for the length of the suspension bolts.
5. Fasten the hanging plate onto the suspension bolts. Pipe
<When installed against a ceiling material,> <No ceiling material to install against,>
Air supply
Suspension bolt Suspension bolt
Fasten Hanging plate
Nut
at the
front Washer
end of Unit Ceiling surface Unit (accessory)
an Washer
elon- (accessory) When the pipe is routed through the back.
※Double nuts
gated Hanging plate ※Double nuts
Cut the removed top cover, and install to
hole.
※Please fasten firmly with double nuts. the rear panel instead of rear cover.
6. Install the unit to the hanging plate.
Hanging plate
(1) Slide the unit in from front side to get it
hanged on the hanging plate with the bolts.
(2) Fasten the four fixing bolts (M8: 2
each on the left and right sides) firmly. Screw for
(3) Fasten the two screws (M4: 1 each on hanging
plate (M4)
the left and right sides). Fixing bolts
(M8) Cut
WARNINIG : Hang a side panel on from the
panel side to the rear side and
0~3mm
0~3mm
The drain pipes may face out towards the back to the left, or to the right side.
⑥Refrigerant pipe
Caution
Caution Install the drain pipe according to the installation manual in order to drain properly.
Use the new refrigerant pipe. Imperfection in draining may cause flood indoors and wetting the household goods,etc.
When re-using the existing pipe system for R22 or R407C, pay attention to the following items. Do not put the drain pipe directly into the ditch where toxic gas such as sulfur, the
・Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare parts. other harmful andinflammable gas is generated. Toxic gas would flow into the room and
・Do not use thin-walled pipes. it would cause serious damage to user’s health and safety (some poisoning or deficiency
Use phosphorus deoxidized copper alloy seamless pipe (C1220T specified in JIS H3300) for refrigeration pipe installation. of oxygen). In addition, it may cause corrosion of heat exchanger and bad smell.
In addition, make sure there is no damage both inside and outside of the pipe, and no Connect the pipe securely to avoid water leakage from the joint.
harmful substances such as sulfur, oxide, dust or a contaminant stuck on the pipes. Insulate the pipe properly to avoid condensation drop.
Do not use any refrigerant other than R410A. Check if the water can flow out properly from both the drain outlet on the
Using other refrigerant except R410A (R22 etc.) may degrade inside refrigeration oil. And air getting indoor unit and the end of the drain pipe after installation.
into refrigeration circuit may cause over-pressure and resultant it may result in bursting, etc. Make sure to make descending slope of greater than 1/100 and do not make up-down bend and/or trap
Store the copper pipes indoors and seal the both end of them until they are brazed in order to avoid any dust, dirt in the midway. In addition, do not put air vent on the drain pipe. Check if water is drained out properly
or water getting into pipe. Otherwise it will cause degradation of refrigeration oil and compressor breakdown, etc. from the pipe during commissioning. Also, keep sufficient space for inspection and maintenance.
Use special tools for R410 refrigerant.
Work procedure Work procedure
Heat insulation material
1. Remove the flare nut and blind flanges on the pipe of the indoor unit. 1. Insert drain hose completely to the
※Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving torque to the base, and tighten the drain hose clamp Drain
socket
nut with another spanner in order to avoid unexpected stress to the copper pipe, and then remove them. securely. ( adhesive must not be used.) Drain hose (accessory) VP-20
(prepare on site)
(Gas may come out at this time, but it is not abnormal.) ※ When plumbing on the left side, move the
Clamp (accessory)
Pay attention whether the flare nut pops out. (as the indoor unit is sometimes pressured.) rubber plug and the cylindrical insulating Drain hose
2. Make a flare on liquid pipe and gas pipe, and connect the refrigeration pipes on the indoor unit. materials by the pipe connecting hole on
10mm
・When taking out the pipe to rear or top, install it together with the electric wire ⑧, the left side of the unit to the right side.
Hose clamp
It can be attached
passing them through the attached cover. Beware of a possible outflow of water that may Lowest point from both inside and
outside the unit.
・Seal clearances with putty, etc. to shut off dust. occur upon removal of a drain plug.
※Bend the pipe with as big radius as possible and do not bend the pipe repeatedly. 2. Fix the drain hose at the lowest point with No bumps
In addition, do not twist and crush the pipes. a hose clamp supplied as an accessory. No traps
※Do a flare connection as follows: ※ Give a drain hose a gradient of 10mm To be a descending
Not to be in water
angle
Make sure to loosen the flare nut with holding the nut on pipe side with a spanner as illustrated in the right drawing by
and giving torque to the nut with another spanner in order to avoid unexpected laying it without leaving a slack.
stress to the copper pipe, and then remove them. Take head of electrical cables so that
When fastening the flare nut, align the refrigeration pipe with the center of flare nut, screw they may not run beneath the drain hose.
the nut for 3-4 times by hand and then tighten it by spanner with the specified torque A drain hose must be clamped down with a hose clamp.
mentioned in the table below. Make sure to hold the pipe on the indoor unit securely by a There is a possibility that drain water overflows.
spanner when tightening the nut in order to avoid unexpected stress on the copper pipe. 3. Connect VP-20(prepare on site) to drain hose. (adhesive must not be used.)
3. Cover the flare connection part of the indoor unit with attached insulation material ※ Use commercially available rigid PVC general pipe VP-20 for drain pipe.
after a gas leakage inspection, and tighten both ends with attached straps. 4. Do not to make the up-down bending and trap in the mid-way while assum-
Make sure to insulate both gas pipes and liquid pipes completely. ing that the drain pipes is downhill. (more than 1/100)
※Incomplete insulation may cause dew condensation or water dropping. Never set up air vent.
4. Refrigerant is charged in the outdoor unit. 5. Insulate the drain pipe.
As for the additional refrigerant charge for the indoor unit and piping, refer to the installation Insulate the drain hose clamp with the heat insulation supplied as accessories.
manual attached to the outdoor unit. When the unit is installed in a humid place, consider precautions against
Strap (Accessory) Pipe cover (Accessory)
Pipe diameter Tightening torque N·m dew condensation such as heat insulation for the drain pipe.
ø 6.35 14 to 18 Drain test
ø 9.52 34 to 42
After installation of drain pipe, make sure that drain system work in good
ø 12.7 49 to 61
condition and no water leakage from joint and drain pan.
ø 15.88 68 to 82
Do drain test even if installation of heating season.
ø 19.05 100 to 120 The thickness of insulation should be 20mm or more.
- 201 -
⑧Wiring-out position and wiring connection ⑪How to set the airflow direction
Electrical installation work must be performed according to the installation It is possible to change the movable range of the louver on the air outlet from
manual by an electrical installation service provider qualified by a power the wired remote controller. Once the top and bottom position is set, the louver
provider of the country, and be executed according to the technical will swing within the range between the top and the bottom when swing
standards and other regulations applicable to electrical installation in the operation is chosen. It is also possible to apply different setting to each louver.
country. Note:This function is not able to be set with wireless remote controller or simple remote controll
Be sure to use an exclusive circuit. (RCH-H3).
Use specified cord, fasten the wiring to the terminal securely, and hold the 1. Stop the air conditioner and press SET button and
cord securely in order not to apply unexpected stress on the terminal. LOUVER button simultaneously for three seconds or
Do not put both power source line and signal line on the same route. It may more.
cause miscommunication and malfunction. The following is displayed if the number of the indoor units
Be sure to do D type earth work. connected to the remote controller is one. Go to step 4.
For the details of electrical wiring work, see attached instruction manual for “ ”
1 2 3 X Y
“ ”
Signal cable for
Interconnecting wiring Earth remote controller
Wiring between indoor 4. Press or button.(selection of louver No.) Select the louver No. to be set
Earth Wiring clamp and outdoor unit according to the right figure.
Power source side Signal side [EXAMPLE]
VRF(KX) series terminal block terminal block
Wireless “ ” “ ” “ ”
receiver line “ ”
Check the following items after all installation work completed. set moves from the original position to the lower
Upper
limit position, and goes back to the original position position
again. (This operation is not performed if the indoor
Check if Expected trouble Check
unit and/or indoor unit fan is in operation.) Movable
The indoor and outdoor units are fixed securely? Falling, vibration, noise [Example]
(displayed for two seconds)
range
- 202 -
● Read the “SAFETY PRECAUTIONS” carefully first of all and then strictly follow it during the installation work Using the incorrect one could cause the system failure and fire. Flat washer (M10) Pipe cover (big)
in order to protect yourself. ● Do not use any materials other than a fuse of correct capacity where a fuse should be used.
● The precautionary items mentioned below are distinguished into two levels, and CAUTION . Connecting the circuit by wire or copper wire could cause unit failure and fire.
: Wrong installation would cause serious consequences such as injuries or death. ● Do not install the indoor unit near the location where there is possibility of flammable gas leakages. 8 1
CAUTION : Wrong installation might cause serious consequences depending on circumstances. If the gas leaks and gathers around the unit, it could cause fire. For unit For heat insulation
Both mentions the important items to protect your health and safety so strictly follow them by any means. ● Do not install and use the unit where corrosive gas (such as sulfurous acid gas etc.) or flammable gas (such
hanging of gas pipe
●The meanings of “Marks” used here are as shown on the right: as thinner, petroleum etc.) may be generated or accumulated, or volatile flammable substances are handled.
Never do it under any circumstances. Always do it according to the instruction. It could cause the corrosion of heat exchanger, breakage of plastic parts etc. And inflammable gas could cause fire.
●After completing the installation, do commissioning to confirm there are no abnormalities, and explain to the ● Secure a space for installation, inspection and maintenance specified in the manual.
customers about “SAFETY PRECAUTIONS”, correct operation method and maintenance method (air filter
Insufficient space can result in accident such as personal injury due to falling from the installation place. ②Selection
cleaning, operation method and temperature setting method) with user’s manual of this unit.
Ask your customers to keep this installation manual together with the user’s manual. Also, ask them to hand ● Do not use the indoor unit at the place where water splashes such as laundry. ① Select the sui
over the user’s manual to the new user when the owner is changed. Indoor unit is not waterproof. It could cause electric shock and fire.
・Areas where
● Do not use the indoor unit for a special purpose such as food storage, cooling for precision a circulator if
instrument, preservation of animals, plants, and a work of art.
WARNING It could cause the damage of the items.
・Areas where
・Areas where
● Do not install nor use the system near equipments which generate electromagnetic wave or high harmonics.
●Installation should be performed by the specialist. taken.
Equipments like inverter equipment, private power generator, high-frequency medical equipment, or telecommunication
If you install the unit by yourself, it may lead to serious trouble such as water leakage, electric shock, fire, and injury due to overturn equipment might influence the air conditioner and cause a malfunction and breakdown. Or the air conditioner might ・Areas where
of the unit. influence medical equipments or telecommunication equipments, and obstruct their medical activity or cause jamming. ・Areas where
●Install the system correctly according to these installation manuals. ● Do not install the remote controller at the direct sunlight. ・Areas where
Improper installation may cause explosion, injury, water leakage, electric shock, and fire. It could cause breakdown or deformation of the remote controller. ・Areas where
●Check the density refered by the foumula (accordance with ISO5149). ● Do not install the indoor unit at the place listed below. ・Areas not ex
· Places where flammable gas could leak. · Places where cosmetics or special sprays are ・Areas where
If the density exceeds the limit density, please consult the dealer and installate the ventilation system. frequently used.
· Places where carbon fiber, metal powder or any powder is floated. This indoor u
●Use the genuine accessories and the specified parts for installation. · Place where the substances which affect the air conditioner are generated · Highly salted area such as beach.
such as sulfide gas, chloride gas, acid, alkali or ammonic atmospheres. · Heavy snow area condition and
If parts unspecified by our company are used it could cause water leakage, electric shock, fire, and injury due to overturn of the unit.
· Places exposed to oil mist or steam directly. · Places where the system is affected by drop if the ai
●Ventilate the working area well in case the refrigerant leaks during installation. · On vehicles and ships smoke from a chimney. If there is a p
If the refrigerant contacts the fire, toxic gas is produced. · Places where machinery which generates high harmonics is used. · Altitude over 1000m
20mm thick
●Install the unit in a location that can hold heavy weight. ● Do not install the indoor unit in the locations listed below (Be sure to install the indoor unit ・Areas where
according to the installation manual for each model because each indoor unit has each limitation)
Improper installation may cause the unit to fall leading to accidents. · Locations with any obstacles which can prevent inlet and outlet air of the unit ・Areas where
●Install the unit properly in order to be able to withstand strong winds such as typhoons, and earthquakes. · Locations where vibration can be amplified due to insufficient strength of structure. table wares,
· Locations where the infrared receiver is exposed to the direct sunlight or the strong light beam. (in case of the ・Areas where
Improper installation may cause the unit to fall leading to accidents. infrared specification unit)
· Locations where an equipment affected by high harmonics is placed. (TV set or radio receiver is placed within 5m) ・Areas where
●Do not mix air in to the cooling cycle on installation or removal of the air conditioner.
· Locations where drainage cannot run off safely. ・Areas where
If air is mixed in, the pressure in the cooling cycle will rise abnormally and may cause explosion and injuries.
It can affect performance or function and etc.. the operation
●Be sure to have the electrical wiring work done by qualified electrical installer, and use exclusive circuit. ● Do not put any valuables which will break down by getting wet under the air conditioner. (A beam from
Power source with insufficient capacity and improper work can cause electric shock and fire. Condensation could drop when the relative humidity is higher than 80% or drain pipe is clogged, and it damages user’s belongings. controller an
●Use specified wire for electrical wiring, fasten the wiring to the terminal securely, and hold the cable securely in ● Do not use the base frame for the outdoor unit which is corroded or damaged after a long period of use.
order not to apply unexpected stress on the terminal. It could cause the unit falling down and injury. ② Check if the p
Loose connections or hold could result in abnormal heat generation or fire. ● Pay attention not to damage the drain pan by weld sputter when brazing work is done near the unit. not able to ho
●Arrange the electrical wires in the control box properly to prevent them from rising. Fit the lid of the services If sputter entered into the unit during brazing work, it could cause damage (pinhole) of drain pan and leakage of water. strength is no
panel property. To avoid damaging, keep the indoor unit packed or cover the indoor unit.
Improper fitting may cause abnormal heat and fire. ● Install the drain pipe to drain the water surely according to the installation manual. Space for installat
Improper connection of the drain pipe may cause dropping water into room and damaging user’s belongings.
●Check for refrigerant gas leakage after installation is completed. ●Make installatio
If the refrigerant gas leaks into the house and comes in contact with a fan heater, a stove, or an oven, toxic gas is produced.
● Do not share the drain pipe for indoor unit and GHP (Gas Heat Pump system) outdoor unit.
Toxic exhaust gas would flow into room and it might cause serious damage (some poisoning or deficiency of oxygen) to (Indoor Unit)
●Use the specified pipe, flare nut, and tools for R410A. user’s health and safety. Select either of tw
Using existing parts (R22) could cause the unit failure and serious accident due to explosion of the cooling cycle. ● Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work.
(Case
●Tighten the flare nut according to the specified method by with torque wrench. If the density of refrigerant exceeds the limit in the event of refrigerant leakage in the small room, lack of oxygen can
If the flare nut were tightened with excess torque, it could cause burst and refrigerant leakage after a long period. occur, which can cause serious accidents.
● For drain pipe installation, be sure to make descending slope of greater than 1/100, not to make traps,
●Do not put the drainage pipe directly into drainage channels where poisonous gases such as sulfide gas can and not to make air-bleeding.
occur. Check if the drainage is correctly done during commissioning and ensure the space for inspection and maintenance. Insp
Poisonous gases will flow into the room through drainage pipe and seriously affect the user's health and safety. This can also hol
cause the corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
● Ensure the insulation on the pipes for refrigeration circuit so as not to condense water.
(40
Incomplete insulation could cause condensation and it would wet ceiling, floor, and any other valuables.
●Connect the pipes for refrigeration circuit securely in installation work before compressor is operated.
● Do not install the outdoor unit where is likely to be a nest for insects and small animals. N
If the compressor is operated when the service valve is open without connecting the pipe, it could cause explosion and injuries due Insects and small animals could come into the electronic components and cause breakdown and fire. Instruct the user to
to abnormal high pressure in the system. keep the surroundings clean.
●Stop the compressor before removing the pipe after shutting the service valve on pump down work. ● Pay extra attention, carrying the unit by hand.
If the pipe is removed when the compressor is in operation with the service valve open, air would be mixed in the refrigeration circuit Carry the unit with 2 people if it is heavier than 20kg. Do not use the plastic straps but the grabbing place, moving the unit Notes (a) There m
and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle. by hand. Use protective gloves in order to avoid injury by the aluminum fin.
(b) Install r
●Only use prescribed optional parts. The installation must be carried out by the qualified installer. ● Make sure to dispose of the packaging material.
If you install the system by yourself, it can cause serious trouble such as water leaks, electric shocks, fire. Leaving the materials may cause injury as metals like nail and woods are used in the package. (Case
●Do not repair by yourself. And consult with the dealer about repair. ● Do not operate the system without the air filter.
It may cause the breakdown of the system due to clogging of the heat exchanger.
Improper repair may cause water leakage, electric shock or fire.
● Do not touch any button with wet hands.
●Consult the dealer or a specialist about removal of the air conditioner. It could cause electric shock.
Improper installation may cause water leakage, electric shock or fire.
● Do not touch the refrigerant piping with bare hands when in operation.
●Turn off the power source during servicing or inspection work. The pipe during operation would become very hot or cold according to the operating condition, and it could cause a burn or frostbite.
If the power is supplied during servicing or inspection work, it could cause electric shock and injury by the operating fan. ● Do not clean up the air conditioner with water.
●Do not run the unit when the panel or protection guard are taken off. It could cause electric shock.
Touching the rotating equipment, hot surface, or high voltage section could cause an injury to be caught in the machine, to get ● Do not turn off the power source immediately after stopping the operation.
burned, or electric shock. Be sure to wait for more than 5 minutes. Otherwise it could cause water leakage or breakdown.
●Shut off the power before electrical wiring work. ● Do not control the operation with the circuit breaker.
It could cause electric shock, unit failure and improper running. It could cause fire or water leakage. In addition, the fan may start operation unexpectedly and it may cause injury.
- 203 -
G012D001
○This model is middle static ducted type air conditioning unit. Therefore, do not use this model for direct
blow type air conditioning unit. ③Preparation before installation
●If suspension bolt becomes longer, do reinforcement of earthquake resistant.
①Before installation ○For grid ceiling
When the suspension bolt length is over 500mm, or the gap between the ceiling and roof is
proper earth could
●Install correctly according to the installation manual.
over 700mm, apply earthquake resistant brace to the bolt.
●Confirm the following points:
○In case the unit is hanged directly from the slab and is installed on the ceiling plane which
○Unit type/Power supply specification ○Pipes/Wires/Small parts ○Accessory items
has enough strength.
Accessory item When suspension bolt length is over 1000mm, apply the earthquake resistant brace to the bolt.
connect all
For hanging For refrigerant pipe For drain pipe ●Prepare four (4) sets of suspension bolt, nut and spring washer (M10) on site.
Flat washer (M10) Pipe cover (big) Pipe cover (small) Strap Pipe cover (big) Pipe cover (small) Drain hose Hose clamp
e used.
Suspension Bolt Location
Suspension
e gas leakages. 8 1 1 4 1 1 1 1
bolt (M10)
For unit For heat insulation For heat insulation For pipe For heat insulation For heat insulation For drain pipe For drain hose Accessory parts are stored
hanging of gas pipe of liquid tube cover fixing of drain socket of drain socket connecting mounting inside this suction side. ○ Adhere to the
mable gas (such measurements given
472
Unit
ces are handled. below for the length of
60 mm
Under
the suspension bolts.
uld cause fire.
A
ce. ②Selection of installation location for the indoor unit
UNIT: mm
Multi type 22-56 71, 90 112-160
① Select the suitable areas to install the unit under approval of the user. Single type 50 60, 71 100-140
・Areas where the indoor unit can deliver hot and cold wind sufficiently. Suggest to the user to use A 786 986 1404
cision a circulator if the ceiling height is over 3m to avoid warm air being accumulated on the ceiling.
・Areas where there is enough space to install and service.
・Areas where it can be drained properly. Areas where drain pipe descending slope can be Pipe locations UNIT: mm
high harmonics.
taken.
elecommunication
ditioner might ・Areas where there is no obstruction of airflow on both air return grille and air supply port. Multi type 22-90
r cause jamming. ・Areas where fire alarm will not be accidentally activated by the air conditioner. Single type 50-71
203
174
beach. (PVC pipe)
104
condition and confirmed there is no problem. However, there is some risk of condensation
467
affected by drop if the air conditioner is operated under the severer condition than mentioned above.
29
Refrigerant liquid pipe
If there is a possibility to use it under such a condition, attach additional insulation of 10 to (For natural drainage)
20mm thick for entire surface of indoor unit, refrigeration pipe and drain pipe. Refrigerant gas pipe drain pipe connection VP20 (PVC pipe)
or unit ・Areas where TV and radio stays away more than 1m. (It could cause jamming and noise.)
ch limitation)
・Areas where any items which will be damaged by getting wet are not placed such as food,
table wares, server, or medical equipment under the unit. Multi type 112-160
case of the ・Areas where there is no influence by the heat which cookware generates. Single type 100-140
ced within 5m) ・Areas where not exposed to oil mist, powder and/or steam directly such as above fryer. 635
・Areas where lighting device such as fluorescent light or incandescent light doesn’t affect 468
405
the operation.
ner. (A beam from lighting device sometimes affects the infrared receiver for the wireless remote
user’s belongings. controller and the air conditioner might not work properly.) drain pipe connection VP20
187
g period of use.
145
(PVC pipe)
95
② Check if the place where the air conditioner is installed can hold the weight of the unit. If it is
467
29
e near the unit. not able to hold, reinforce the structure with boards and beams strong enough to hold it. If the
Refrigerant gas pipe
strength is not enough, it could cause injury due to unit falling. (For natural drainage)
eakage of water. Refrigerant liquid pipe drain pipe connection VP20 (PVC pipe)
or more
Note (b)
Hang the unit up. Suspension bolt
d maintenance. Inspection If the measurements between
20
hole Slab M10 nut Washer for M10 the unit and the ceiling hole do
er.
1000 or more
(400x400)
s. not match upon installation, it
150-
200
als.
Unit may be adjusted with the long
20
or more
e, moving the unit Notes (a) There must not be obstacle to draw out fan motor. ( marked area) Adjustment for horizontality
(b) Install refrigerant pipe, drain pipe, and wiring so as not to cross marked area.
(Case 2) From button of unit ○Either use a level vial, or adjust the level according to the method below.
●Adjust so the bottom side of the unit will be leveled with the water surface as
or more
illustrated below.
100
Pipe side
Pour water
A
Water
Inspection surface
or more
0~5mm
B Vinyl hose
- 204 -
(Pipe side)
② Blowout duct ○Use the side fresh air intake hole, or supply ● Do not put the
●Use rectangular duct to connect with unit. through a part of the suction duct. and inflamma
Duct size for each unit is as shown below. serious dama
Fresh air intake through the In addition, it
Single type 50 60-71 100-140 suction duct
Multi type 22-56 71-90 112-140 ● Connect the p
A 682 882 1470 ● Insulate the p
B 172 172 590 [for simultaneous air intake/vent]
(Pipe side)
○Intake air through the suction duct. ● Check if the w
A Air vent hole
(the side cannot be used) of the drain p
● Make sure to
B
and/or trap in
Fresh air intake through the
suction duct drained out p
●Duct should be at their minimum length. inspection an
●We recommend to use sound and heat insulated duct to prevent it from condensation.
(Pipe side)
②Air Vent Work procedure
●Connect duct to unit before ceiling attachment. Air vent hole
○Use the side air vent hole. 1. Make sure to
③ Inlet port
●When shipped the inlet port lies on the back. (always use together with the air intake) drain socket.
●When connecting the duct to the inlet port, remove the air filter if it is fitted to the inlet port. Attach the ho
Fresh air intake through the
●When placing the inlet port to carry out suction from the bottom side, use the following suction duct within 5mm l
procedure to replace the suction duct joint and the bottom plate. ●Do not app
○Insulate the duct to protect it from dew condensation. ●Do not use
Drain socket
⑥Refrigerant pipe
●Remove the screws which fasten the ●Replace the removed bottom plate
bottom plate and the duct joint on the and duct joint. Caution
inlet port side of the unit. ●Use the new refrigerant pipe.
When re-using the existing pipe system for R22 or R407C, pay attention to the following items. Fasten the screw
5 mm left to the
・Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare parts.
Drain socket
・Do not use thin-walled pipes.
●Use phosphorus deoxidized copper alloy seamless pipe (C1220T specified in JIS H3300) for refrigeration pipe installation.
●Fit the duct join with a screw; fit the bottom plate. In addition, make sure there is no damage both inside and outside of the pipe, and no harmful
●Make sure to insulate the duct to prevent dewing on it. Secure with a band, etc. substances such as sulfur, oxide, dust or a contaminant stuck on the pipes. Metal plate
④Install the specific blowout duct in a location where the air will ●Do not use any refrigerant other than R410A.
circulate to the entire room. Using other refrigerant except R410A (R22 etc.) may degrade inside refrigeration oil. And air getting into 2. Prepare a join
●Conduct the installation of the specific blowout hole and the Blowout refrigeration circuit may cause over-pressure and resultant it may result in bursting, etc. end made of
connection of the duct before attaching them to the ceiling. duct
●Store the copper pipes indoors and seal the both end of them until they are brazed in order to avoid any dust, dirt or ※As for drai
●Insulate the area where the duct is secured by a band for dew water getting into pipe. Otherwise it will cause degradation of refrigeration oil and compressor breakdown, etc. ● Make sure
condensation prevention. ●Use special tools for R410 refrigerant. It may cau
⑤Make sure provide an inspection hole on the ceiling. It is indispensable to service elecric
Piping work ● The flexib
equipment, motor, functional components and cleaning of heat exchanger.
Air conditioner main unit
Refrigerant pipe drain pipe
When conducting piping work, make sure to allow the pipes leakage.
to be aligned in a straight line for at least 250 mm, as shown
250mm
(Section where attached in the left illustration. (This is necessary for the drain pump
Ceiling suriace
in a straight line) to function)
Blow outlet Suction duct Suction hole
Blowout duct
(marketed item) (marketed item) Work procedure
Inspection hole (with air filter)
(optional or marketed item)
1. Remove the flare nut and blind flanges on the pipe of the indoor unit.
※ Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving torque to the
nut with another spanner in order to avoid unexpected stress to the copper pipe, and then remove them. 3. Make sure to
Suction grille Suction grille
Bad example of duct work (option) (Locality) (Gas may come out at this time, but it is not abnormal.) and/or trap in
● Pay attention whether the flare nut pops out. (as the indoor unit is sometimes pressured.) ●Pay attent
①If a duct is not provided at the suction side but it is substituted with the space over the ceiling, 2. Make a flare on liquid pipe and gas pipe, and connect the refrigeration pipes on the indoor unit. pipe as clo
humidity in the space will increase by the influence of capacity of ventilation fan, strength of ※Bend the pipe with as big radius as possible and do not bend the pipe repeatedly. In addition, ●Do not set
wind blowing against the out door air louver, weather (rainy day) and others. do not twist and crush the pipes.
a)Moisture in air is likely to condense over the external plates of the unit and to drip on the ※Do a flare connection as follows: 1.5m~
ceiling. Unit should be operated under the conditions as listed in the above table and within ● Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving
the limitation of wind volume. When the building is a concrete structure, especially immedi- torque to the nut with another spanner in order to avoid unexpected stress to the copper Insulation mate
ately after the construction, humidity tends to rise even if the space over the ceiling is not pipe, and then remove them.
Descending
substituted in place of a duct. In such occasion, it is necessary to insulate the entire unit with ● When fastening the flare nut, align the refrigeration pipe with the center of flare nut, screw
glass wool (25mm). (Use a wire net or equivalent to hold the glass wool in place.) the nut for 3-4 times by hand and then tighten it by spanner with the specified torque
b)It may run out the allowable limit of unit operation (Example: When outdoor air temperature mentioned in the table below. Make sure to hold the pipe on the indoor unit securely by a
is 35°C DB, suction air temperature is 27°C WB) and it could result in such troubles as spanner when tightening the nut in order to avoid unexpected stress on the copper pipe. ●When shar
compressor overload, etc.. 3. Cover the flare connection part of the indoor unit with attached insulation material after a gas than one un
c)There is a possibility that the blow air volume may exceed the allowable range of operation below the
leakage inspection, and tighten both ends with attached straps.
addition, se
due to the capacity of ventilation fan or strength of wind blowing against external air louver ●Make sure to insulate both gas pipes and liquid pipes completely.
main drain
so that drainage from be heat exchanger may fall to reach the drain pan but leak outside ※ Incomplete insulation may cause dew condensation or water dropping.
(Example: drip on to the ceiling) with consequential water leakage in the room. 4. Refrigerant is charged in the outdoor unit.
②If vibration damping is not conducted between the unit and the duct, and between the unit and As for the additional refrigerant charge for the indoor unit and piping, refer to the installation
4. Insulate the d
the slab, vibration will be transmitted to the duct and vibration noise may occur. Also, vibration manual attached to the outdoor unit.
● Be sure to
may be transmitted from the unit to the slab. Vibration damping must be performed. Pipe diameter Tightening torque N·m Strap (Accessory) Pipe cover (Accessory)
cause dew
Bad example of duct work
φ 6.35 14 to 18
※ After dra
φ 9.52 34 to 42
Louver to size), th
outdoor air φ 12.7 49 to 61
part of t
φ 15.88 68 to 82
φ 19.05 100 to 120 The thickness of insulation should be 20mm or more.
gapless
For ventilation
- 205 -
Caution Drain up
● Install the drain pipe according to the installation manual in order to drain properly. ● The position for drain pipe outlet can be raised up to 600mm above the ceiling. Use elbows
e fresh air intake hole Imperfection in draining may cause flood indoors and wetting the household goods, etc. for installation to avoid obstacles inside ceiling. If the horizontal drain pipe is too long before
● Do not put the drain pipe directly into the ditch where toxic gas such as sulfur, the other harmful vertical pipe, the backflow of water will increase when the unit is stopped, and it may cause
and inflammable gas is generated. Toxic gas would flow into the room and it would cause overflow of water from the drain pan on the indoor unit. In order to avoid overflow, keep the
serious damage to user’s health and safety (some poisoning or deficiency of oxygen). horizontal pipe length and offset of the pipe within the limit shown in the figure below.
sh air intake through the In addition, it may cause corrosion of heat exchanger and bad smell. 290-325 100 or less
tion duct
● Connect the pipe securely to avoid water leakage from the joint.
● Insulate the pipe properly to avoid condensation drop.
● Check if the water can flow out properly from both the drain outlet on the indoor unit and the end
600 max
nt hole
of the drain pipe after installation.
● Make sure to make descending slope of greater than 1/100 and do not make up-down bend
and/or trap in the midway. In addition, do not put air vent on the drain pipe. Check if water is
h air intake through the
on duct drained out properly from the pipe during commissioning. Also, keep sufficient space for
Otherwise, the construction point makes it same as drain pipe construction.
inspection and maintenance.
l. And air getting into 2. Prepare a joint for connecting VP-20 pipe, adhere and connect the joint to the drain hose (the Outline of bottom drain piping work
g, etc. end made of rigid PVC), and adhere and connect VP-20 pipe (prepare on site). ● If the bottom drain piping can be done with a
o avoid any dust, dirt or ※As for drain pipe, apply VP-20 made of rigid PVC which is on the market. descending gradient (1/50-1/100), it is possible to
sor breakdown, etc. ● Make sure that the adhesive will not get into the supplied drain hose. connect the pipes as shown in the drawing below. Connecting port of top drain pipe
It may cause the flexible part broken after the adhesive is dried up and gets rigid.
● The flexible drain hose is intended to absorb a small difference at installation of the unit or
drain pipes. Intentional bending, expanding may cause the flexible hose broken and water Standard hard polyvinyl
chloride pipes
re to allow the pipes leakage. Connecting port of bottom drain pipes
t 250 mm, as shown Rubber stopper (to be removed)
Insulating material
y for the drain pump
( )
d then remove them. Note: If the unit is run with the connector coupled,
3. Make sure to make descending slope of greater than 1/100 and do not make up-down bend
drain water will be discharged from the upper
and/or trap in the midway.
metimes pressured.) drain pipe joint, causing a water leak.
●Pay attention not to give stress on the pipe on the indoor unit side, and support and fix the
s on the indoor unit. pipe as close place to the unit as possible when connecting the drain pipe.
eatedly. In addition, ●Do not set up air vent.
r to the installation
4. Insulate the drain pipe.
● Be sure to insulate the drain socket and rigid PVC pipe installed indoors otherwise it may
pe cover (Accessory)
cause dew condensation and water leakage.
※ After drainage test implementation, cover the drain socket part with pipe cover (small
size), then use the pipe cover (big size) to cover the pipe cover (small size), clamps and
part of the drain hose, and fix and wrap it with tapes to wrap and make joint part
on should be 20mm or more.
gapless.
PJG012D001
- 206 -
⑧Wiring-out position and wiring connection ⑨External static pressure setting (continued)
● Electrical installation work must be performed according to the installation manual by an Indoor unit fan will run automatically and recognize E.S.P. by itself.
electrical installation service provider qualified by a power provider of the country, and be The operation for automatic E.S.P recognition will last about 6 minutes, and it will be stopped
executed according to the technical standards and other regulations applicable to electrical after recognition is completed.
installation in the country.
Be sure to use an exclusive circuit. Caution
● Use specified cord, fasten the wiring to the terminal securely, and hold the cord securely in · Be sure to execute AUTOMATIC SETTING by remote controller AFTER ducting work is completed.
order not to apply unexpected stress on the terminal. When duct specification is changed after AUTOMATIC SETTING, be sure to execute AUTOMATIC
● Do not put both power source line and signal line on the same route. It may cause miscom- SETTING again after power resetting and turning on again.
munication and malfunction. · Be sure to execute AUTOMATIC SETTING before trial cooling operation.
● For the details of electrical wiring work, see attached instruction manual for electrical wiring (See ELECTRICAL WIRING WORK INSTRUCTION about trial cooling operation)
work. · Before AUTOMATIC SETTING, be sure to check that return air filter in duct is installed and
1. Remove a lid of the control box (2 screws). damper is opened.
2. Hold each wiring inside the unit and fasten them to terminal block securely. Wrong procedure causes excessive air flow or water drop blown out.
3. Fix the wiring with clamps.
4. Install the removed parts back to original place. Notice
· During operation for automatic recognition (the Auto Operation), fan rotates with certain speeds
regardless of set fan speed by remote controller.
· When duct is set with low static pressure (around 10-50Pa), even if indoor unit operate with
higher air flow volume than rated one, but it is not abnormal.
· When you changed operation mode or stop operation with ON/OFF button during Auto Opera-
tion, the Auto operation will be canceled.
· In such case, be sure to execute AUTOMATIC SETTING again according to above procedure.
Signal line Power source line Earth
1. MANUAL SETTING
You can set required E.S.P. by wired remote controller that calculated with the set air flow
rate and pressure loss of the duct connected.
Select No.1-10 (10Pa-100Pa) from following table according to calculation result.
Refer to technical manual for details of air flow characteristic.
Setting No. 1 2 3 4 5 6 7 8 9 10
※ When you set No.11-19 by remote controller, unit will control fan-speed with setting of
No.10 Factory default is at No.5.
Notice
You can NOT set E.S.P by wireless remote controller. E.S.P. button
Caution
Be sure to set E.S.P. according to actual duct connected.
Wrong settings causes excessive air flow volume or water drop blown out.
2. AUTOMATIC SETTING
Indoor unit will recognize E.S.P. by itself automatically and select appropriate fan speed No.1-10.
- 207 -
(a) Remove the control box and the side panel, and remove the screws marked in the circles (2 places) in the figure.
Control box
Side panel
Screw
- 208 -
13 Setting of grill auto mode × × × Simple setting of grill auto mode. RAC unit does not have this function.
14 Ventilation control × × × Air infiltration can be controlled by the indoor unit that RAC unit does not have this function.
has this function.
15 Display of unit number ○ ○ ○ Display address number of remote control. Address setted by SC-BIK-N for RAC
16 Service switch-1: Display of error △ △ △ Display and memorize the error code data that is checked Only error code is used in the RAC unit.
data finally.
Service switch -2 display of
17 operation data △ △ △ Display operation data. RAC unit can be displayed some data.
19 Forced operation of drain pump × △ × Forced operation of drain pump is sent to the indoor unit. Option parts for SRR
21 Quiet mode × × × On timer in order to start quiet mode. RAC unit does not have this function.
Auto address change from remote
22 control × × × Auto address can be changed from remote control. RAC unit does not have this function.
23 Indoor unit's address set of master × × × Adapt controller for 3 pipe system. RAC unit does not have this function.
Turning off signal display of filter sign and sending reset
24 Filter reset × × × RAC unit does not have this function.
signal of operating time.
Clear memory of error code in
25 ○ ○ ○ Reset memory that remote controller has the error code.
remote control
Clear memory of error code in the
26 ○ ○ ○ Reset memory of error for the indoor unit.
indoor unit
27 Clear address in indoor unit × × × Reset memory of address for the indoor unit. RAC unit does not have this function.
29 Function setting △ △ △ It is possible to set the function of remote control and RAC unit can be set a part of function.
indoor unit.
For RAC models, only the range from 18℃ to
30 Setting of temperature range △ △ △ Set Max and Min temperature.
30℃ is available.
External input from CNT terminal can be switched
31 External input ○ ○ ○
between all unit operation and individual operation.
32 Auto adjustment of static pressure × × × Change auto adjustment of static pressure. RAC unit does not have this function.
Displayed part blinks on and off when it recives a
33 Setting of static pressure × × × RAC unit does not have this function.
signal about auto adjustment of static pressure mode.
Displays filter sign via signal from indoor unit when
34 Filter sign × × × RAC unit does not have this function.
counting time achieves target time.
- 209 -
43 Display of demand control operation × × × Display of demand operation from indoor unit. RAC unit does not have this function.
Display of operation on auto Display checking when it receives signal of auto adjusting
44 adjusting static pressure × × × static pressure operation. RAC unit does not have this function.
It is available to select manual setting or automatic setting
45 External static pressure setting × × × for setting external static pressure by remote controller. RAC unit does not have this function.
- 210 -
7 COMPONENT REPLACEMENT
7.1 Models SCM71ZJ-S1, 80ZJ-S1
Fan and fan motor (FMo1)
Screws (For front panel) Screws (For top panel)
1. Loosen 6 screws and remove
the top panel.
2. Loosen 3 screws and remove
the service panel.
3. After removal of service panel,
Loosen a screw.
Screw
Nut
- 211 -
Compressor (CM)
Terminal cover
2. Loosen screws and remove
the cover and the terminal Screws
cover. Cover 〔After removed terminal cover〕
3. Loosen screws and
disconnect all power cables
locally installed
Caution
Be sure to do above work
after turning the power OFF
by breaker.
- 212 -
Compressor (CM)
Screws
〔Side view〕 〔Rear view〕
Rear cover
Disconnect the
connector of
crankcase heater
Front cover
- 213 -
Compressor (CM)
〔Rear view〕
Nuts
- 214 -
Compressor (CM)
Discharge pipe
Suction pipe
Position to be
disconnected
Position to be
disconnected
- 215 -
Screws
〔Side view after lifting〕
- 216 -
U : Pink cable ⑥
V : White cable
W : Gray cable
②Disconnect the faston
connectors of reactotr
which is located just
above the 4-way valve.
Reactor
②
③Disconnect the connector
of fan motor (CNFAN).
①
④Disconnect the connector
U : Pink
of CNSUB. V : White
(Going to Sub PCB) W : Gray
③
⑤Disconnect the connector
of CNTH.
For
Tho-A (Outdoor air temp.)
⑤
Tho-R (Heat exch. temp.)
Tho-D (Discharge pipe temp.)
〔Sub PCB〕
- 217 -
S : White
C-2 : Red
〔Pattern side〕
- 218 -
1.After removing the Main PCB, CNEEV2 ② CNTH ③ CND ⑧ CNC ⑧ CNB ⑧ CNA ⑧ C N 20V ⑦
disconnect all connectors on
Sub PCB.
⑤Disconnect the connector CNEEV1 ① CN20S(RD) ⑥ Grounding cable (G-1) Grounding cable (G-3)
of CNHEAT. CNHEAT(WH) ⑤ CNMAIN ④ Grounding cable (G-2)
(for crankcase heater)
〔Front view〕 〔Side view〕
⑥Disconnect the connector
of CN20S.
(for 4-way valve)
- 219 -
Screws Screws
〔Part side〕
Layout of Sub PCB. CNTH CNEEV2 S-1 (WH) C-1 (RD) CND CNC CNB CNA CN20V
- 220 -
EEV coils
Note:
1) When disconnecting the
connector, be sure to
check the color marked
on the top of coil and
the color of the connector.
GREEN BLUE WHITE RED
2) When replace to a new
coil, be sure to insert the
socket attached to the coil Marking color
to the pipe correctly.
EEVD
GREEN
EEVC
BLUE
EEVB
RED
EEVA
WHITE
Socket
- 221 -
Coil
Screw
- 222 -
Screws
Nut
Grommet
3. Remove the service panel.
Strap
CNFAN1
- 223 -
7. Loosen 4 nuts.
Nuts
Compressor (CM)
Caution
Be sure to do above work
after turning the power OFF
by breaker. Unit A Unit C Unit E
Unit B Unit D Unit F
(125 only)
Side panel
- 224 -
Compressor (CM)
Side panel
4. Loosen screws and remove
the side panel.
Screws
Screws
V
(WH)
U
(RD)
W
(BL)
- 225 -
Compressor (CM)
CNF(PK)
(125 only)
CNE(OR)
CND(OR)
CNCBL)
CNEEV2 CNB(BR)
CNEEV3
CNA(RD)
CNEEV1
10.Remove the control unit. 〔Front view〕 〔Side view〕 〔Control unit removed〕
(Continue)
Screws
- 226 -
Compressor (CM)
11. Remove the partition for 〔Front view〕 〔Side view〕 〔Top view〕
easy replacement work of
compressor according to
following procedure.
- 227 -
Compressor (CM)
〔Front view〕 Crankcase heater 〔Rear view〕
13. Loosen 3 nuts of
compressor fixing bolts.
〔Top view〕
Straps
〔Front view〕
Straps
〔Top view〕
- 228 -
Locking supports
- 229 -
〔Pattern side〕
PK CNEEV4 CNF
(PK)
CNEEV2 CNE
OR
(OR)
CNEEV3
CND
YE
(YE)
CNEEV1
BL CNC
CNS2 (BL)
Note: Be sure to do this work BR CNB
after elapsing 3 minutes CNX2 (BR)
from power OFF. CNA
RD
CNDRM (RD)
CNTRO CNTRI
- 230 -
TB1
Screws
TB3
Locking supports
Disconneced cables
- 231 -
CNI4
6. Pinch the head of locking
supports (8 pieces) and
U V W Connectors IPM
remove the Inverter PCB (RD) (WH) (BL) N3 CNACT1
Power transistor
(PWB2). on the back side (BL)
Noise filter PCB (PCB3 & PCB5) on the back side of the 1st layer
Layout
PCB3
PCB5
Lower
Upper
- 232 -
Noise filter PCB (PWB3) on the back side lower of the 1st layer
PCB3
1. Dismount the 1st layer
according to the procedure Locking support
for control PCB (PWB1) and TB6
Sub PCB (PWB4).
TB5
2. Loosen 5 screws and
disconnect the cables of
TB3 - TB7.
Noise filter PCB (PWB5) on the back side upper of the 1st layer
1. Dismount the 1st layer PCB5
according to the procedure Locking
support
for control PCB (PWB1) and
Sub PCB (PWB4).
TB3
TB5
2. Loosen 5 screws and
disconnect the cables of
TB3 - TB7.
TB4 TB6
Active Filter (LACT) and Diode Stack (DS) on the 2nd layer
Faston connectoes
1. Active Filter
Disconnect the faston
connectors (6 pieces) and
sensor (1 piece). Screw
And then loosen 2 screws
and remove LACT.
- 233 -
EEV coils
M A R K IN G
1. Remove the faulty EEV coil
and disconnect the connector.
EEVF
(125 only)
Note: YELLOW
1) When disconnecting the
connector, be sure to EEVE
check the color marked
on the top of coil and the BLACK
color of the connector.
BLUE
EEVB
RED
EEVA
WHITE
GREEN
BLUE
RED
S ocket
WHITE
BLACK
YELLOW
- 234 -
8 CHECKING PROCEDURE
8.1 Models SCM71ZJ-S1, 80ZJ-S1
<Fan motor>
CNFAN1 on PCB1
WH
OR
BR ④
③
BL ②
①
RD
NO. Output
① 280VDC
② 15VDC
③ 0-6VDC
④ 0-5VDC
<Compressor>
U:Pink
W:Gray
V:White
Resistance 1.154Ω
- 235 -
<EEV A ~ EEV D>
MARKING
EEVD
GREEN
EEVC
BLUE
EEVB
RED
EEVA
WHITE
Input : 12VDC
WH
46Ω
M
RD
46Ω
46Ω 46Ω
OR
YE BL
- 236 -
<Sensor>
Heat exchanger
sensor (Tho-R)
- 237 -
<Main PCB>
R : Black
S : White
C-2 : Red
S-2 : White
Fuse CN20V
- 238 -
<SUB PCB>
CNTH
CN20V
CNA
CNEEV2 CNB
Grounding cable
CNMA1N
CNC
CND
RIN to L-terminal
CNEEV2
SIN to N-terminal
CNHEAT
Grounding cable
- 239 -
CNFAN1 on PCB1
RD
① NO. Output
BL ① 280VDC
BR ② ② 15VDC
③
OR ④ ③ 0-6VDC
WH ④ 0-5VDC
<EEVA - EEVF>
MARKING
Input : 12VDC
EEVF WH
(125 only)
YELLOW 46Ω
M
RD
EEVE 46Ω
46Ω 46Ω
BLACK OR
YE BL
EEVD
GREEN
EEVC
BLUE
EEVB
RED
EEVA
WHITE
<EEV-H>
Input : 12VDC
WH
46Ω
M
RD
46Ω
46Ω 46Ω
OR
YE BL
- 240 -
Heat exchanger
thermistor (Tho-R)
Power transistor
Discharge pipe Suction pipe thermistor (Tho-AF)
temp. thermistor (Tho-D) temp. thermistor (Tho-S)
Resistance(kΩ)
Name Color
0℃ 25℃ 50℃ 90℃
Tho-R Black 16.4 5.0 1.8
Tho-D Black 54.8 5.0
Tho-S Black 16.4 5.0 1.8
Tho-A Yellow 32.8 10.0
Tho-AF Black 5.0
<Compressor>
U
(RD)
Resistance 0.293Ω W V
(BL) (WH)
<Diode module>
① Check a diode module by a mutimeter
set on diode mode.
③ ①
③
④ ②
- 241 -
<Control PCB:PCB1>
CNTH
CNE
CNP1
- 242 - #
<Inverter PCB:PCB2> P2 N2
(RD) (BL) CNI2
P1
(RD)
N1
(BL)
P3
(RD)
U V W N3 CNACT1 CNI4
(BL)
TB5 TB6
TB7
TB4
TB3
- 243 -
CNEEV2 CNE ※2
(OR)
CNEEV3 CND
(YE)
CNEEV1 CNC
(BL)
CNB
CNS2 (BR)
CNX2 CNA
(RD)
CNDRM CNTRO ※1
N, IN
CNTRI
L, IN
TB3
TB5
TB4 TB6
TB7
- 244 -
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.