EDTVN042004

Split Type Air Conditioners


- Cooling Only -

F/ATKA-U Series
EDTVN042004

Split Type
Air Conditioners
F/ATKA-U Series
FTKA25UAVMV RKA25UAVMV
FTKA35UAVMV RKA35UAVMV
ATKA25UAVMV ARKA25UAVMV
Cooling Only
ATKA35UAVMV ARKA35UAVMV
FTKA50UAVMV RKA50UVMV
FTKA60UAVMV RKA60UVMV
1. Power Supply ..........................................................................................3
2. Functions.................................................................................................4
3. Specifications ..........................................................................................5
4. Dimensions .............................................................................................8
4.1 Indoor Unit................................................................................................8
4.2 Outdoor Unit .............................................................................................9
5. Wiring Diagrams....................................................................................11
5.1 Indoor Unit..............................................................................................11
5.2 Outdoor Unit ...........................................................................................12
6. Piping Diagrams....................................................................................14
6.1 Indoor Unit..............................................................................................14
6.2 Outdoor Unit ...........................................................................................15
7. Capacity Tables ....................................................................................17
7.1 Cooling Only...........................................................................................17
7.2 Capacity Correction Factor by the Length of Refrigerant Piping
(Reference) ............................................................................................19
8. Operation Limit......................................................................................20
9. Sound Level ..........................................................................................21
9.1 Measuring Location ................................................................................21
9.2 Indoor Unit..............................................................................................22
9.3 Outdoor Unit ...........................................................................................23
10.Electric Characteristics..........................................................................24
11.Installation Manual ................................................................................25
11.1 FTKA25/35/50/60UAVMV ......................................................................25
11.2 ATKA25/35UAVMV ................................................................................35
12.Operation Manual..................................................................................45
12.1 English....................................................................................................45
12.2 Vietnamese ............................................................................................70
13.Optional Accessories ............................................................................95
13.1 Indoor Unit..............................................................................................95
13.2 Outdoor Unit ...........................................................................................95

Split Type Air Conditioners F/ATKA-U Series 1


EDTVN042004

2 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Power Supply

1. Power Supply
Indoor Unit Outdoor Unit Power Supply
FTKA25UAVMV RKA25UAVMV
FTKA35UAVMV RKA35UAVMV
ATKA25UAVMV ARKA25UAVMV 1 phase, 220 - 230 - 240 V, 50 Hz
ATKA35UAVMV ARKA35UAVMV 1 phase, 220 - 230 V, 60 Hz
FTKA50UAVMV RKA50UVMV
FTKA60UAVMV RKA60UVMV

Note: Power Supply Intake ; Outdoor Unit

Split Type Air Conditioners F/ATKA-U Series 3


Functions EDTVN042004

2. Functions

ARKA25/35UAVMV

ARKA25/35UAVMV
ATKA25/35UAVMV

ATKA25/35UAVMV
FTKA25/35UAVMV

FTKA50/60UAVMV

FTKA25/35UAVMV

FTKA50/60UAVMV
RKA25/35UAVMV

RKA25/35UAVMV
RKA50/60UVMV

RKA50/60UVMV
Category Functions Category Functions

Basic Functions Inverter (with inverter power Health & Deodorizing filter (enzyme blue)
control)   Cleanliness (option)  

Refer to Titanium apatite deodorizing


Operation limit for cooling P. 20 filter (option)  

Operation limit for heating — — Dust collection filter (PM2.5)


 
PAM control —  (option)
Standby electricity saving   Mould proof air filter (prefilter)  
Compressor Oval scroll compressor — — Wipe-clean panel  
Swing compressor   Washable panel — —
Rotary compressor — — Removable drain-pan  
Reluctance DC motor   Mould proof operation  
Comfortable Power-airflow flap   Heating dry operation — —
Airflow
Power-airflow dual flaps — — Good-sleep cooling operation — —
Wide-angle louvres   Odour removing  
Auto-swing (up and down)   Timer Weekly timer — —
Auto-swing (left and right) — — 24-hour ON/OFF timer — —
3D airflow — — Count up-down ON/OFF timer  
Comfort airflow mode Night set mode  
(COANDA panel)  
Worry Free Auto-restart after power failure  
(Reliability &
Comfort Control Auto fan speed   Durability) Self-diagnosis with remo-con  
Indoor unit quiet operation   Wiring error check — —
Outdoor unit quiet operation   Anti-corrosion treatment of
outdoor heat exchanger fins  
Intelligent eye
(auto energy saving) — — Protection net of outdoor unit — —
2-area intelligent eye Low/high voltage shield  
— —
(focus and comfort)
Flexibility Multi-split/split compatible indoor
— —
Hot-start function — — unit
Automatic defrost — — Chargeless 15 m 15 m
Operation Automatic operation Either side drain (right/left)  
— —
(cooling and heating) Power selection — —
Programme dry function   Remote Control Remote control adaptor
(normal open pulse contact)  
Humidity sensor — — (option)
Hybrid cooling — —
(dehumidification control) Remote control adaptor  
(normal open contact) (option)
Fan operation  
Lifestyle Powerful operation HA and Dlll-NET application
— —  
Convenience (non-inverter) (option)
Inverter powerful operation   Wireless LAN adaptor (option)   
Econo mode   Remote Wireless  
Controller
Child lock — — Wired — —
Indoor unit ON/OFF switch  
Signal reception indicator  
0.5°C step room temperature  
setting

16°C minimum temperature


 
setting for cooling mode

Wireless remote controller


(backlight) — —

Wireless remote controller


(luminous button)  

Note:  : Available  : Can be installed inside indoor unit


— : Not available

4 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Specifications

3. Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V
Indoor Unit FTKA25UAVMV ATKA25UAVMV
Model
Outdoor Unit RKA25UAVMV ARKA25UAVMV
kW 2.5 (1.0 ~ 2.9) / 1.25
Capacity
Btu/h 8,500 (3,400 ~ 9,900) / 4,300
Rated (Min. ~ Max.) / Middle
kcal/h 2,150 (860 ~ 2,490) / 1,070
Moisture Removal L/h 1.2
Running Current
A 4.4 / 5.8
Rated / Max.
Power Consumption
W 920 (200 ~ 1,100) / 300
Rated (Min. ~ Max.) / Middle
Power Factor (Rated) % 94.0
COP (Rated) W/W 2.72
CSPF W/W 4.66
Liquid mm  6.4
Piping
 9.5
Connections Gas
mm
Drain mm  16.0
Heat Insulation Both Liquid and Gas Pipes
Max. Interunit Piping Length m 15
Max. Interunit Height Difference m 12
Chargeless m 15
Amount of Additional Charge of
g/m 20
Refrigerant
Indoor Unit FTKA25UAVMV ATKA25UAVMV
Front Panel Colour White
H 9.9 (350)
M m³/min 8.4 (297)
Airflow Rate
L (cfm) 7.1 (251)
SL 6.0 (212)
Type Cross Flow Fan
Fan Motor Output W 27
Speed Steps 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards
Air Filter Removable, Washable, Mildew Proof
Running Current (Rated) A 0.18
Power Consumption (Rated) W 21
Power Factor (Rated) % 53.0
Temperature Control Microcomputer Control
Dimensions (H × W × D) mm 285 × 770 × 226
Packaged Dimensions (H × W × D) mm 320 × 830 × 360
Weight (Mass) kg 8
Gross Weight (Gross Mass) kg 11
Sound
Pressure H / M / L / SL dB(A) 36 / 32 / 27 / 23
Level
Outdoor Unit RKA25UAVMV ARKA25UAVMV
Casing Colour Ivory White
Heat
Fin / Spec. Tube Waffle Fin (PE) /  7 Hi-XD Tube
Exchanger
Type Hermetically Sealed Swing Type
Compressor Model 1YC20JXD
Motor Output W 650
Refrigerant Type FW50DA
Oil Charge L 0.275
Type R-32
Refrigerant
Charge kg 0.41
H m³/min 19.8 (700)
Airflow Rate (cfm)
SL 17.5 (618)
Type Propeller
Fan
Motor Output W 28
Running Current (Rated) A 4.22
Power Consumption (Rated) W 899
Power Factor (Rated) % 96.8
Starting Current A 4.4
Dimensions (H × W × D) mm 418 × 695 × 244
Packaged Dimensions (H × W × D) mm 475 × 793 × 330
Weight (Mass) kg 19
Gross Weight (Gross Mass) kg 22
Sound
Pressure H / SL dB(A) 48 / 45
Level
Drawing No. 3D126542A 3D126545A

Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. The data are based on the conditions shown in the table below. Conversion Formulae
Cooling Piping Length kcal/h = kW × 860
Btu/h = kW × 3412
Indoor ; 27°CDB / 19°CWB cfm = m³/min × 35.3
7.5 m
Outdoor ; 35°CDB / 24°CWB

Split Type Air Conditioners F/ATKA-U Series 5


Specifications EDTVN042004

50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V


Indoor Unit FTKA35UAVMV ATKA35UAVMV
Model
Outdoor Unit RKA35UAVMV ARKA35UAVMV
kW 3.5 (1.2 ~ 3.8) / 1.75
Capacity
Btu/h 11,900 (4,100 ~ 13,000) / 6,000
Rated (Min. ~ Max.) / Middle
kcal/h 3,010 (1,030 ~ 3,270) / 1,500
Moisture Removal L/h 1.7
Running Current
A 5.8 / 7.3
Rated / Max.
Power Consumption
W 1,220 (200 ~ 1,460) / 390
Rated (Min. ~ Max.) / Middle
Power Factor (Rated) % 96.0
COP (Rated) W/W 2.87
CSPF W/W 5.01
Liquid mm  6.4
Piping
 9.5
Connections Gas
mm
Drain mm  16.0
Heat Insulation Both Liquid and Gas Pipes
Max. Interunit Piping Length m 15
Max. Interunit Height Difference m 12
Chargeless m 15
Amount of Additional Charge of
g/m 20
Refrigerant
Indoor Unit FTKA35UAVMV ATKA35UAVMV
Front Panel Colour White
H 10.7 (378)
M m³/min 8.8 (311)
Airflow Rate
L (cfm) 7.1 (251)
SL 6.0 (212)
Type Cross Flow Fan
Fan Motor Output W 27
Speed Steps 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards
Air Filter Removable, Washable, Mildew Proof
Running Current (Rated) A 0.27
Power Consumption (Rated) W 24
Power Factor (Rated) % 40.4
Temperature Control Microcomputer Control
Dimensions (H × W × D) mm 285 × 770 × 226
Packaged Dimensions (H × W × D) mm 320 × 830 × 360
Weight (Mass) kg 8
Gross Weight (Gross Mass) kg 11
Sound
Pressure H / M / L / SL dB(A) 37 / 33 / 28 / 24
Level
Outdoor Unit RKA35UAVMV ARKA35UAVMV
Casing Colour Ivory White
Heat
Fin / Spec. Tube Waffle Fin (PE) /  7 Hi-XD Tube
Exchanger
Type Hermetically Sealed Swing Type
Compressor Model 1YC20HXD
Motor Output W 650
Refrigerant Type FW50DA
Oil Charge L 0.275
Type R-32
Refrigerant
Charge kg 0.49
H m³/min 27.4 (967)
Airflow Rate (cfm)
SL 24.0 (848)
Type Propeller
Fan
Motor Output W 28
Running Current (Rated) A 5.51
Power Consumption (Rated) W 1,196
Power Factor (Rated) % 98.7
Starting Current A 5.8
Dimensions (H × W × D) mm 550 × 658 × 275
Packaged Dimensions (H × W × D) mm 616 × 788 × 359
Weight (Mass) kg 22
Gross Weight (Gross Mass) kg 25
Sound
Pressure H / SL dB(A) 49 / 46
Level
Drawing No. 3D126543A 3D126549A

Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. The data are based on the conditions shown in the table below. Conversion Formulae
Cooling Piping Length kcal/h = kW × 860
Btu/h = kW × 3412
Indoor ; 27°CDB / 19°CWB cfm = m³/min × 35.3
7.5 m
Outdoor ; 35°CDB / 24°CWB

6 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Specifications

50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V


Indoor Unit FTKA50UAVMV FTKA60UAVMV
Model
Outdoor Unit RKA50UVMV RKA60UVMV
kW 5.0 (1.6 ~ 5.4) / 2.5 6.0 (1.4 ~ 6.0) / 3.0
Capacity
Btu/h 17,100 (5,500 ~ 18,400) / 8,500 20,500 (4,800 ~ 20,500) / 10,200
Rated (Min. ~ Max.) / Middle
kcal/h 4,300 (1,380 ~ 4,640) / 2,150 5,160 (1,200 ~ 5,160) / 2,580
Moisture Removal L/h 2.9 3.9
Running Current
A 8.5 / 10.3 9.7 / 12.3
Rated / Max.
Power Consumption
W 1,800 (360 ~ 2,020) / 600 2,060 (370 ~ 2,200) / 685
Rated (Min. ~ Max.) / Middle
Power Factor (Rated) % 96.5 97.0
COP (Rated) W/W 2.78 2.91
CSPF W/W 4.67 4.90
Liquid mm  6.4  6.4
Piping
 12.7  12.7
Connections Gas
mm
Drain mm  16.0  16.0
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Max. Interunit Piping Length m 30 30
Max. Interunit Height Difference m 20 20
Chargeless m 15 15
Amount of Additional Charge of
g/m 20 20
Refrigerant
Indoor Unit FTKA50UAVMV FTKA60UAVMV
Front Panel Colour White White
H 12.9 (455) 13.7 (484)
M m³/min 10.6 (374) 12.1 (427)
Airflow Rate
L (cfm) 8.6 (304) 9.9 (350)
SL 7.1 (251) 8.0 (282)
Type Cross Flow Fan Cross Flow Fan
Fan Motor Output W 27 27
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards
Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof
Running Current (Rated) A 0.34 0.38
Power Consumption (Rated) W 32 39
Power Factor (Rated) % 42.8 46.7
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) mm 285 × 770 × 226 285 × 770 × 226
Packaged Dimensions (H × W × D) mm 320 × 830 × 360 320 × 830 × 360
Weight (Mass) kg 8 8
Gross Weight (Gross Mass) kg 11 11
Sound
Pressure H / M / L / SL dB(A) 44 / 40 / 35 / 29 45 / 42 / 37 / 31
Level
Outdoor Unit RKA50UVMV RKA60UVMV
Casing Colour Ivory White Ivory White
Heat
Fin / Spec. Tube Waffle Fin (PE) /  7 Hi-XD Tube Louvre Fin / Flat Alu Tube
Exchanger
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Compressor Model 1YC36DXD 2YC40AXD
Motor Output W 1,200 1,300
Refrigerant Type FW68DA FW68DA
Oil Charge L 0.35 0.395
Type R-32 R-32
Refrigerant
Charge kg 0.78 0.53
H m³/min 31.7 (1,119) 45.6 (1,610)
Airflow Rate (cfm)
SL 29.9 (1,056) 39.9 (1,409)
Type Propeller Propeller
Fan
Motor Output W 28 50
Running Current (Rated) A 8.16 9.32
Power Consumption (Rated) W 1,768 2,021
Power Factor (Rated) % 98.5 98.6
Starting Current A 8.50 9.70
Dimensions (H × W × D) mm 550 × 675 × 284 595 × 845 × 300
Packaged Dimensions (H × W × D) mm 605 × 798 × 373 660 × 995 × 410
Weight (Mass) kg 26 35
Gross Weight (Gross Mass) kg 30 42
Sound
Pressure H / SL dB(A) 51 / 47 52 / 48
Level
Drawing No. 3D127840 3D127841

Notes: 1. SL: The Quiet fan level of the airflow rate setting.
2. When the airflow rate is set to SL, both indoor and outdoor unit operate in quiet mode. Conversion Formulae
3. The data are based on the conditions shown in the table below. kcal/h = kW × 860
Cooling Piping Length Btu/h = kW × 3412
cfm = m³/min × 35.3
Indoor ; 27°CDB / 19°CWB
7.5 m
Outdoor ; 35°CDB / 24°CWB

Split Type Air Conditioners F/ATKA-U Series 7


Dimensions EDTVN042004

4. Dimensions
4.1 Indoor Unit

FTKA25/35/50/60UAVMV, ATKA25/35UAVMV

3D126535

8 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Dimensions

4.2 Outdoor Unit

RKA25UAVMV, ARKA25UAVMV

3D128437

RKA35UAVMV, ARKA35UAVMV

3D126647

Split Type Air Conditioners F/ATKA-U Series 9


Dimensions EDTVN042004

RKA50UVMV

3D128233

RKA60UVMV

3D122092

10 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Wiring Diagrams

5. Wiring Diagrams
5.1 Indoor Unit

FTKA25/35/50/60UAVMV, ATKA25/35UAVMV

3D107627C

Split Type Air Conditioners F/ATKA-U Series 11


Wiring Diagrams EDTVN042004

5.2 Outdoor Unit

RKA25UAVMV, ARKA25UAVMV

3D125991A

RKA35UAVMV, ARKA35UAVMV

3D125992A

12 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Wiring Diagrams

RKA50UVMV

3D126301

RKA60UVMV

3D111852B

Split Type Air Conditioners F/ATKA-U Series 13


Piping Diagrams EDTVN042004

6. Piping Diagrams
6.1 Indoor Unit
FTKA25/35UAVMV, ATKA25/35UAVMV FTKA50/60UAVMV

4D101847E 4D112625

14 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Piping Diagrams

6.2 Outdoor Unit

RKA25UAVMV, ARKA25UAVMV

3D126572

RKA35UAVMV, ARKA35UAVMV

3D126635

Split Type Air Conditioners F/ATKA-U Series 15


Piping Diagrams EDTVN042004

RKA50UVMV

3D128009

RKA60UVMV

3D122090A

16 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Capacity Tables

7. Capacity Tables
7.1 Cooling Only

FTKA25UAVMV + RKA25UAVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
ATKA25UAVMV + ARKA25UAVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 9.9
BF 0.11

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.46 2.11 0.71 2.35 2.06 0.78 2.23 2.01 0.85 2.28 2.03 0.87 2.21 2.00 0.91 2.10 1.95 0.98
16.0 22 2.57 2.08 0.71 2.46 2.03 0.78 2.34 1.98 0.85 2.40 2.01 0.87 2.33 1.98 0.91 2.21 1.93 0.98
18.0 25 2.68 2.22 0.72 2.57 2.17 0.79 2.46 2.13 0.85 2.51 2.15 0.88 2.44 2.13 0.92 2.33 2.08 0.99
19.0 27 2.73 2.38 0.72 2.62 2.34 0.79 2.51 2.29 0.86 2.57 2.31 0.88 2.50 2.29 0.92 2.38 2.24 0.99
22.0 30 2.90 2.31 0.73 2.79 2.27 0.79 2.68 2.23 0.86 2.74 2.25 0.89 2.67 2.23 0.93 2.56 2.19 0.99
24.0 32 3.01 2.26 0.73 2.90 2.23 0.80 2.79 2.19 0.87 2.86 2.21 0.89 2.79 2.19 0.93 2.67 2.16 1.00

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D126550

FTKA35UAVMV + RKA35UAVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
ATKA35UAVMV + ARKA35UAVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 10.7
BF 0.14

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 3.44 2.62 0.94 3.28 2.54 1.03 3.13 2.47 1.12 3.19 2.50 1.15 3.10 2.45 1.21 2.93 2.37 1.30
16.0 22 3.60 2.58 0.95 3.44 2.50 1.04 3.28 2.43 1.13 3.36 2.47 1.16 3.26 2.42 1.21 3.10 2.35 1.30
18.0 25 3.75 2.71 0.95 3.59 2.64 1.04 3.44 2.57 1.13 3.52 2.61 1.16 3.42 2.57 1.22 3.26 2.50 1.31
19.0 27 3.83 2.86 0.95 3.67 2.80 1.05 3.51 2.74 1.14 3.60 2.77 1.17 3.50 2.73 1.22 3.34 2.66 1.31
22.0 30 4.06 2.77 0.96 3.90 2.71 1.05 3.75 2.65 1.14 3.84 2.69 1.17 3.74 2.65 1.23 3.58 2.59 1.32
24.0 32 4.21 2.70 0.97 4.06 2.64 1.06 3.90 2.59 1.15 4.00 2.63 1.18 3.90 2.59 1.23 3.74 2.54 1.32

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D126551

Split Type Air Conditioners F/ATKA-U Series 17


Capacity Tables EDTVN042004

FTKA50UAVMV + RKA50UVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 12.9
BF 0.11

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 4.92 3.58 1.39 4.69 3.47 1.52 4.47 3.36 1.66 4.56 3.40 1.70 4.42 3.33 1.78 4.19 3.22 1.91
16.0 22 5.14 3.52 1.40 4.91 3.41 1.53 4.69 3.31 1.66 4.79 3.36 1.71 4.65 3.29 1.79 4.42 3.18 1.92
18.0 25 5.36 3.68 1.40 5.13 3.58 1.54 4.91 3.48 1.67 5.02 3.53 1.72 4.88 3.47 1.80 4.65 3.37 1.93
19.0 27 5.47 3.87 1.41 5.24 3.77 1.54 5.02 3.68 1.68 5.14 3.73 1.72 5.00 3.67 1.80 4.77 3.57 1.93
22.0 30 5.80 3.73 1.42 5.58 3.64 1.55 5.35 3.56 1.69 5.49 3.61 1.73 5.35 3.55 1.81 5.11 3.47 1.95
24.0 32 6.02 3.63 1.43 5.80 3.55 1.56 5.57 3.47 1.70 5.72 3.52 1.74 5.58 3.47 1.82 5.34 3.39 1.95

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D127912

FTKA60UAVMV + RKA60UVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)
AFR 13.7
BF 0.18

INDOOR OUTDOOR TEMPERATURE (°CDB)


EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 5.47 3.85 1.53 5.47 3.85 1.72 5.36 3.79 1.90 5.47 3.85 1.94 5.31 3.77 2.04 5.00 3.60 2.18
16.0 22 6.16 4.01 1.60 5.90 3.87 1.75 5.63 3.74 1.90 5.75 3.80 1.95 5.59 3.72 2.05 5.23 3.54 2.18
18.0 25 6.43 4.15 1.61 6.16 4.02 1.76 5.89 3.90 1.91 6.03 3.96 1.96 5.86 3.88 2.06 5.47 3.70 2.18
19.0 27 6.56 4.33 1.61 6.29 4.20 1.77 6.03 4.08 1.92 6.17 4.15 1.97 6.00 4.07 2.06 5.58 3.89 2.18
22.0 30 6.96 4.16 1.63 6.69 4.05 1.78 6.42 3.94 1.93 6.58 4.00 1.98 6.41 3.93 2.07 5.93 3.74 2.18
24.0 32 7.23 4.03 1.64 6.96 3.93 1.79 6.69 3.83 1.94 6.86 3.89 1.99 6.69 3.83 2.08 6.16 3.64 2.18

Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.
2. TC, PI and SHC must be calculated by interpolation using the figures in
BF : Bypass factor the above tables.
EWB : Entering wet bulb temp. (°C) (Figures out of the tables should not be used for calculation.)
3. Capacities are based on the following conditions.
EDB : Entering dry bulb temp. (°C) Corresponding refrigerant piping length : 7.5 m
TC : Total capacity (kW) Level difference : 0 m
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
3D127913

18 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Capacity Tables

7.2 Capacity Correction Factor by the Length of Refrigerant Piping (Reference)


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping —
the distance between the indoor unit and the outdoor unit.

7.2.1 25/35 Class

(R-32)
(%)
100
Capacity correction factor

90

80

5 10 15 (m)

Piping length

7.2.2 50/60 Class

(R-32)
(%)
100
Capacity correction factor

90

80
Range of the refrigerant
additional charge

5 10 15 20 25 30 (m)

Piping length

Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.

Split Type Air Conditioners F/ATKA-U Series 19


Operation Limit EDTVN042004

8. Operation Limit
RKA25/35UAVMV, ARKA25/35UAVMV, RKA50/60UVMV

4D073983S

20 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Sound Level

9. Sound Level
9.1 Measuring Location

Indoor Unit Outdoor Unit

1m 1m

0.8 m
MICROPHONE

MICROPHONE

Notes: 1. Operation sound is measured in an anechoic chamber.


2. The operation sound measuring method is based on JIS standard.

Split Type Air Conditioners F/ATKA-U Series 21


Sound Level EDTVN042004

9.2 Indoor Unit


FTKA25UAVMV, ATKA25UAVMV FTKA35UAVMV, ATKA35UAVMV

4D126553 4D126554

FTKA50UAVMV FTKA60UAVMV

4D127842 4D127839

22 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Sound Level

9.3 Outdoor Unit


RKA25UAVMV, ARKA25UAVMV RKA35UAVMV, ARKA35UAVMV

4D126555 4D126556

RKA50UVMV RKA60UVMV

4D127836 4D127837

Split Type Air Conditioners F/ATKA-U Series 23


Electric Characteristics EDTVN042004

10. Electric Characteristics

Power Supply Compressor OFM IFM


Indoor Unit Outdoor Unit
Hz - Volts Voltage Range MCA MFA RHz RLA W FLA W FLA
50 - 220 3.93 0.29 0.18
50 - 230 Max. 50 Hz, 264 V 3.85 0.28 0.17
Min. 50 Hz, 198 V
FTKA25UAVMV RKA25UAVMV
ATKA25UAVMV ARKA25UAVMV 50 - 240 5.8 15 62 3.65 28 0.28 27 0.17
60 - 220 Max. 60 Hz, 253 V 3.93 0.29 0.18
60 - 230 Min. 60 Hz, 198 V 3.85 0.28 0.17
50 - 220 5.12 0.39 0.27
Max. 50 Hz, 264 V
50 - 230 4.89 0.37 0.27
Min. 50 Hz, 198 V
FTKA35UAVMV RKA35UAVMV
50 - 240 7.3 15 90 4.69 28 0.35 27 0.26
ATKA35UAVMV ARKA35UAVMV
60 - 220 Max. 60 Hz, 253 V 5.12 0.39 0.27
60 - 230 Min. 60 Hz, 198 V 4.89 0.37 0.26
50 - 220 7.75 0.41 0.34
Max. 50 Hz, 264 V
50 - 230 Min. 50 Hz, 198 V 7.36 0.40 0.34
FTKA50UAVMV RKA50UVMV 50 - 240 10.3 15 70 7.08 28 0.39 27 0.33
60 - 220 Max. 60 Hz, 253 V 7.75 0.41 0.34
60 - 230 Min. 60 Hz, 198 V 7.36 0.40 0.33
50 - 220 8.81 0.51 0.38
50 - 230 Max. 50 Hz, 264 V 8.35 0.48 0.37
Min. 50 Hz, 198 V
FTKA60UAVMV RKA60UVMV 50 - 240 12.3 15 86 8.00 50 0.45 27 0.35
60 - 220 Max. 60 Hz, 253 V 8.81 0.51 0.38
60 - 230 Min. 60 Hz, 198 V 8.35 0.48 0.37

Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB
MFA : Max. fuse amps (A) Outdoor temp. 35°CDB
RHz : Rated operating frequency (Hz) 2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
RLA : Rated load amps (A) 4. Instead of fuse, use circuit breaker.
OFM : Outdoor fan motor 5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
IFM : Indoor fan motor detector capable of handling high harmonics must be used in
W : Fan motor rated output (W) order to prevent malfunctioning of the earth leak detector.)
FLA : Full load amps (A)
3D126552
3D127838

24 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

11. Installation Manual


11.1 FTKA25/35/50/60UAVMV

Split Type Air Conditioners F/ATKA-U Series 25


Installation Manual EDTVN042004

26 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

Split Type Air Conditioners F/ATKA-U Series 27


Installation Manual EDTVN042004

28 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

Split Type Air Conditioners F/ATKA-U Series 29


Installation Manual EDTVN042004

30 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

Split Type Air Conditioners F/ATKA-U Series 31


Installation Manual EDTVN042004

32 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

Split Type Air Conditioners F/ATKA-U Series 33


Installation Manual EDTVN042004

3P492258-28S

34 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

11.2 ATKA25/35UAVMV

Split Type Air Conditioners F/ATKA-U Series 35


Installation Manual EDTVN042004

36 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

Split Type Air Conditioners F/ATKA-U Series 37


Installation Manual EDTVN042004

38 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

Split Type Air Conditioners F/ATKA-U Series 39


Installation Manual EDTVN042004

40 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

Split Type Air Conditioners F/ATKA-U Series 41


Installation Manual EDTVN042004

42 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Installation Manual

Split Type Air Conditioners F/ATKA-U Series 43


Installation Manual EDTVN042004

3P492258-31S

44 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

12. Operation Manual


12.1 English

Split Type Air Conditioners F/ATKA-U Series 45


Operation Manual EDTVN042004

46 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 47


Operation Manual EDTVN042004

48 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 49


Operation Manual EDTVN042004

50 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 51


Operation Manual EDTVN042004

52 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 53


Operation Manual EDTVN042004

54 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 55


Operation Manual EDTVN042004

56 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 57


Operation Manual EDTVN042004

58 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 59


Operation Manual EDTVN042004

60 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 61


Operation Manual EDTVN042004

62 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 63


Operation Manual EDTVN042004

64 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 65


Operation Manual EDTVN042004

66 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 67


Operation Manual EDTVN042004

68 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

C: EN_3P492259-19S
C: EN_3P492259-22S

Split Type Air Conditioners F/ATKA-U Series 69


Operation Manual EDTVN042004

12.2 Vietnamese

70 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 71


Operation Manual EDTVN042004

72 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 73


Operation Manual EDTVN042004

74 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 75


Operation Manual EDTVN042004

76 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 77


Operation Manual EDTVN042004

78 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 79


Operation Manual EDTVN042004

80 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 81


Operation Manual EDTVN042004

82 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 83


Operation Manual EDTVN042004

84 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 85


Operation Manual EDTVN042004

86 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 87


Operation Manual EDTVN042004

88 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 89


Operation Manual EDTVN042004

90 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 91


Operation Manual EDTVN042004

92 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Operation Manual

Split Type Air Conditioners F/ATKA-U Series 93


Operation Manual EDTVN042004

C: VN_3P492259-19S
C: VN_3P492259-22S

94 Split Type Air Conditioners F/ATKA-U Series


EDTVN042004 Optional Accessories

13. Optional Accessories


13.1 Indoor Unit

Manual No.
Option Name Model Name
Installation Manual Operation Manual
1 Wireless LAN connecting adaptor 1 BRP072C42 4P518835-2G —
2 Remote control PC-board set BRP067A42 1P518834-1 —
Wiring adaptor for timer clock / remote controller 1 3
3 KRP413BB1S 3P248024-2G —
(normal open pulse contact / normal open contact)
4 Central remote controller 2 DCS302CA61 2P162816-1 3P124623-8D
5 Unified ON/OFF controller 2 DCS301BA61 1P162827-1A 2P167410-1
6 Schedule timer 2 DST301BA61 3P162015-1A 3P124623-5C
Interface adaptor for DIII-NET 1 3P248024-1F
7 (residential air conditioner)
KRP928BB2S
3P248024-3D

8 Deodorizing filter (enzyme blue) (without frame) BAFP094A41 — —


9 Titanium apatite deodorizing filter (without frame) KAF970A46 — —
10 Dust collection filter (PM2.5) (without frame) BAFP046A41 — —
11 Remote controller loss prevention with chain KKF910A4 — —

Notes: 1 Remote control PC-board set (BRP067A42) is also required for each indoor unit.
2 An interface adaptor (KRP928BB2S) is also required for each indoor unit.
3 Timer clock and other devices ; obtained locally.

13.2 Outdoor Unit

Manual No.
Option Name 25 Class 35 Class 50/60 Class
Installation Manual Operation Manual
— KPW937B4 — 4P202735-1 —
1 Air direction adjustment grille
— — KPW937E4 2P286387-1C —
2 Drain plug KKP937A4 — —

Split Type Air Conditioners F/ATKA-U Series 95


Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Specifications, designs and other content appearing in this brochure are current as of February 2020 but subject to change without notice.

c All rights reserved

AK