WIT-PE 500 WITH THREADED ROD (METRIC)

WIT-PE 500
Approved for:
Concrete C20/25 to C50/60, cracked

Suitable for:
Concrete C12/15, Natural stone with dense structure

385 ml 585 ml 1400 ml


Art.no.: Art.no.: Art.no.:
0903480001 0903480003 0903480002 Benefits:
• The prolonged gelling/working time allows
convenient adjustment at higher temperature and with
large embedment depth.
• Its many approvals guarantees optimized load
Galvanized (5 microns): M8 – M39 capacities for threaded rods and rebar.
• Its specially developed chemical composition allows
reliable installation in underwater conditions and
when filled in diamond cored drill holes.
• The low shrinkage of the mortar broadens the
application spectrum in addition for big diameter
Stainless steel - A4 (AISI 316): M8 - M39
fastener elements.

Applications
WIT-PE 500 M

Approvals and Certificates

Description Authority/ Guideline No./date of issue


Laboratory for Assessment
European Technical DIBt, Berlin ETAG 001-T5 ETA-09/0040 / 2013-06-14
Approval
European Technical DIBt, Berlin TR 023 / EC 2 ETA-07/0313 / 2013-05-30
Approval
ICC-ES Evaluation Report ICC AC 308 ESR-2538 / 2012-05-01
Fire resistance IBMB, Braunschweig TR 020 3302/252/08/N13/2009-01-07
Test Report LEED eurofins Leed 2009 EQ c4.1 G15982K / 2012-10-30
VOC Emissions Test report eurofins DEVL 1101903D, DEVL 1104875A 2013-03-13
NSF International NSF International NSF/ANSI Standard61 2013-11-13

68
Basic loading data (for a single anchor)

All data in this section applies to: • Concrete C 20/25, fck,cube = 25 N/mm²,
• Correct setting (See Installation instruction). Concrete C 50/60, fck,cube = 60 N/mm².
• No edge distance and spacing influence. • Temperate range I (min. base material temperature
• Base material thickness, as specified in the table. -40°C, max. long term/short term base material
• Embedment depth, as specified in the table. temperature: +24°C/40°C).
• Anchor material, as specified in the tables, • Dry or wet conditions of drill hole, hammer drilling
steel grade 5.8. • Installation temperature range +5°C to +40°C.

Characteristic resistance

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
Effective anchorage depth hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
Non-cracked concrete
Tensile C20/25 NRk [kN] 18.3 29.0 42.1 70.6 111.9 153.7 187.8 224.0 262.4 302.7 344.9
C50/60 NRk [kN] 18.3 29.0 42.1 77.6 123.1 169.0 206.5 246.5 288.6 333.0 379.4
Shear ≥ C20/25 VRk [kN] 9.2 14.5 21.1 39.2 61.2 88.1 114.8 140.1 173.4 204.2 243.9
Cracked concrete
Tensile C20/25 NRk [kN] 31.1 40.8 64.1 87.1 112.0 140.0
C50/60 NRk [kN] 34.2 44.9 70.5 95.8 123.2 154.0

WIT-PE 500 M
Shear ≥ C20/25 VRk [kN] 21.1 39.2 61.2 88.1 114.8 140.1

Design resistance

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
Effective anchorage depth hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
Non-cracked concrete
Tensile C20/25 NRd [kN] 12.2 19.3 28.1 39.2 53.3 73.2 89.4 106.7 125.0 144.2 164.3
C50/60 NRd [kN] 12.2 19.3 28.1 43.1 58.6 80.5 98.4 117.4 137.5 158.6 180.7
Shear ≥ C20/25 VRd [kN] 7.4 11.6 16.9 31.4 49.0 70.5 91.8 112.1 138.7 163.3 195.2
Cracked concrete
Tensile C20/25 NRd [kN] 17.3 22.7 30.5 41.5 53.3 66.6
C50/60 NRd [kN] 19.0 25.0 33.6 45.6 58.6 73.3
Shear ≥ C20/25 VRd [kN] 16.9 31.4 49.0 70.5 91.8 112.1

69
WIT-PE 500 WITH THREADED ROD (METRIC)
Recommended / Allowable loads1)

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
Effective anchorage depth hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
Non-cracked concrete
Tensile C20/25 Nrec [kN] 8.7 13.8 20.1 28.0 38.1 52.3 63.9 76.2 89.3 103.0 117.3
C50/60 Nrec [kN] 8.7 13.8 20.1 30.8 41.9 57.5 70.3 83.8 98.2 113.3 129.1
Shear ≥ C20/25 Vrec [kN] 5.3 8.3 12.1 22.4 35.0 50.3 65.6 80.1 99.1 116.7 139.4
Cracked concrete
Tensile C20/25 Nrec [kN] 12.3 16.2 21.8 29.6 38.1 47.6
C50/60 Nrec [kN] 13.6 17.8 24.0 32.6 41.9 52.4
Shear ≥ C20/25 Vrec [kN] 12.1 22.4 35.0 50.3 65.6 80.1
1)
Material safety factor yM and safety factor for action y L = 1.4 are included. The material safety factor depends on the failure mode.
WIT-PE 500 M

70
Design Method (simplified)

Simplified version of the design method according ETAG 001, TR 029. Design resistance
according data given in ETA-09/0040, issue 2013-06-14:
• Influence of concrete strength.
• Influence of edge distance.
• Influence of spacing.
• Valid for a group of anchors. (The influencing factors must then be considered for each edge distance and spacing.
The calculated design loads are then on the save side. They will be lower than the exact values according
ETAG 001, Annex C. To avoid this, it is recommended to use the anchor design software of Würth).
• The design method is based on the following simplification: No different loads are acting on individual anchors
(no eccentricity).
• Temperate range I (min. base material temperature -40°C, max. long term/short term base material temperature:
+24°C/40°C).
• Dry or wet conditions of drill hole, hammer drilling.
• Installation temperature range +5°C to +40°C.
• M33, M36, M39 not part of ETA, data based on in-house testing according to guideline.

Tension loading

The decisive design resistance in tension is the lowest value of the following failure modes:

Steel failure:

Combined Pull out and concrete cone failure:

WIT-PE 500 M
Concrete cone failure:

Concrete splitting failure:

Design steel resistance of a single anchor


Anchor type: WIT-PE 500 M

steel grade Thread M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
size
5.8 NRd,s [kN] 12.2 19.3 28.1 52.2 81.6 117.5 153.1 186.9 231.2 272.2 325.3
8.8 NRd,s [kN] 19.5 30.9 44.9 83.6 130.6 188.0 245.0 299.0 369.9 435.6 520.4
10.9 NRd,s [kN] 26.1 41.4 60.2 111.9 174.9 251.8 328.1 400.4 495.4 583.4 697.0
A4-70 NRd,s [kN] 13.7 21.7 31.5 58.6 91.6 132.2 172.3 210.2 260.1 306.3 365.9

71
WIT-PE 500 WITH THREADED ROD (METRIC)
Design combined pull-out and concrete cone resistance of a single anchor

Basic design combined pull-out and concrete cone resistance of a single anchor

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
Non-cracked concrete
N0Rd,p [kN] 16.8 23.6 34.6 48.9 66.1 90.5 116.3 145.4 162.9 195.5 231.0
Cracked concrete
N0Rd,p [kN] 17.3 22.7 30.5 41.5 53.3 66.6

Influence of concrete strength

Concrete strength classes


C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60
(EN 206:2000)
Characteristic compressive strength
of concrete determined by testing fck,cyl [N/mm2] 12 16 20 25 30 35 40 45 50
cylinders1)
WIT-PE 500 M

Characteristic compressive strength of


fck,cube [N/mm2] 15 20 25 30 37 45 50 55 60
concrete determined by testing cube2)
Influencing factor fb,N [-] 0.77 0.89 1.00 1.02 1.04 1.06 1.08 1.09 1.10

1)
strength at 28days of 150mm diameter by 300mm cylinders.
2)
strength at 28days of 150mm cubes.

Influence of embedment depth

Consider the approved range of embedment according to the table


“anchor characteristics”.

72
Characteristic edge distance ccr,p and spacing scr,p

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
scr,p [mm] 226 270 330 375 510 607 683 759 799 872 945
ccr,p [mm] 113 135 165 188 255 304 342 379 400 436 472

Combined pull-out and concrete cone failure - Influence of spacing

Number of
fixing per s/scr,p1) 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 ≥ 1.0
direction

2 fsx,p, fsy,p 0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.90 0.93 0.95 0.98 1.00

3 fsx,p, fsy,p 0.40 0.43 0.47 0.50 0.53 0.57 0.60 0.63 0.67 0.70 0.73 0.77 0.80 0.83 0.87 0.90 0.93 0.97 1.00

4 fsx,p, fsy,p 0.33 0.36 0.40 0.44 0.48 0.51 0.55 0.59 0.63 0.66 0.70 0.74 0.78 0.81 0.85 0.89 0.93 0.96 1.00

5 fsx,p, fsy,p 0.28 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.76 0.80 0.84 0.88 0.92 0.96 1.00

1)
Choose always the lowest value of the spacing s, when there are different spacings in one row.

Combined pull-out and concrete cone failure - Influence of edge distance

WIT-PE 500 M
;

c/ccr,p 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 ≥ 1.0

fcx,1,p 0.73 0.75 0.76 0.78 0.79 0.81 0.82 0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.94 0.96 0.97 0.99 1.00

fcx,2,p
0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.90 0.93 0.95 0.98 1.00
fcy,p

Design concrete cone resistance and splitting resistance of a single anchor

Concrete cone failure:

Concrete splitting failure:

No verification of splitting is required if at least one of the conditions is fulfilled:


a) The edge distance in all directions is for single fasteners and for fastener groups and the
member depth is in both cases.
b) The characteristic resistance for concrete cone failure and pull-out failure is calculated for cracked concrete and
reinforcement resists the splitting forces and limits the crack width to .

73
WIT-PE 500 WITH THREADED ROD (METRIC)
Basic design concrete cone resistance of a single anchor
Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
Non-cracked concrete
N0Rd,c [kN] 20.1 24.0 32.4 39.2 53.3 73.2 89.4 106.7 125.0 144.2 164.3
Cracked concrete
N0Rd,c [kN] 14.3 17.1 23.1 28.0 38.1 52.3 63.9 76.2 89.3 103.0 117.3

Influence of concrete strength

Concrete strength classes


C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60
(EN 206:2000)
Characteristic compressive strength
of concrete determined by testing fck,cyl [N/mm2] 12 16 20 25 30 35 40 45 50
cylinders1)
Characteristic compressive strength of
fck,cube [N/mm2] 15 20 25 30 37 45 50 55 60
concrete determined by testing cube2)
Influencing factor fb,N [-] 0.77 0.89 1.00 1.10 1.22 1.34 1.41 1.48 1.55

1)
strength at 28days of 150mm diameter by 300mm cylinders.
2)
strength at 28days of 150mm cubes.
WIT-PE 500 M

Influence of embedment depth

Consider the approved range of embedment according to the table


“anchor characteristics”.

74
Concrete cone failure
Characteristic edge distance ccr,N and spacing scr,N

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
scr,N [mm] 240 270 330 375 510 630 720 810 900 990 1080
ccr,N [mm] 120 135 165 188 255 315 360 405 450 495 540

Above characteristic spacing and edge distances are given for the typical effective anchorage depth. Calculating for
smaller depths is leading to conservative load capacities. For calculation with bigger depths use the following:
and .

Concrete cone failure - Influence of spacing

Number of
fixing per s/scr,N1) 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 ≥ 1.0
direction

2 fsx, fsy 0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.90 0.93 0.95 0.98 1.00

3 fsx, fsy 0.40 0.43 0.47 0.50 0.53 0.57 0.60 0.63 0.67 0.70 0.73 0.77 0.80 0.83 0.87 0.90 0.93 0.97 1.00

4 fsx, fsy 0.33 0.36 0.40 0.44 0.48 0.51 0.55 0.59 0.63 0.66 0.70 0.74 0.78 0.81 0.85 0.89 0.93 0.96 1.00

5 fsx, fsy 0.28 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.76 0.80 0.84 0.88 0.92 0.96 1.00

WIT-PE 500 M
1)
Choose always the lowest value of the spacing s, when there are different spacings in one row.

Concrete cone failure - Influence of edge distance

c/ccr,N 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 ≥ 1.0

fcx,1 0.73 0.75 0.76 0.78 0.79 0.81 0.82 0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.94 0.96 0.97 0.99 1.00

fcx,2
0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.90 0.93 0.95 0.98 1.00
fcy

75
WIT-PE 500 WITH THREADED ROD (METRIC)
Concrete splitting failure
Characteristic edge distance ccr,sp and spacing scr,sp
Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
scr,sp [mm] 360 420 528 600 816 1008 1152 1296 1440 1584 1728
ccr,sp [mm] 180 210 264 300 408 504 576 648 720 792 864
hmin [mm] 110 120 134 157 210 258 294 330 366 402 438

Above characteristic spacing and edge distances are given for the typical effective anchorage depth. Calculating for
smaller depths is leading to conservative load capacities. For calculation with bigger depths use the following:

and

and according to the table „anchor characteristics“.

Concrete splitting failure - Influence of spacing

Number of
fixing per s/scr,sp1) 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 ≥ 1.0
WIT-PE 500 M

direction

2 fsx,sp, fsy,sp 0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.90 0.93 0.95 0.98 1.00

3 fsx,sp, fsy,sp 0.40 0.43 0.47 0.50 0.53 0.57 0.60 0.63 0.67 0.70 0.73 0.77 0.80 0.83 0.87 0.90 0.93 0.97 1.00

4 fsx,sp, fsy,sp 0.33 0.36 0.40 0.44 0.48 0.51 0.55 0.59 0.63 0.66 0.70 0.74 0.78 0.81 0.85 0.89 0.93 0.96 1.00

5 fsx,sp, fsy,sp 0.28 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.76 0.80 0.84 0.88 0.92 0.96 1.00

1)
Choose always the lowest value of the spacing s, when there are different spacings in one row.

Concrete splitting failure - Influence of edge distance

c/ccr,sp 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 ≥ 1.0

fcx,1, sp 0.73 0.75 0.76 0.78 0.79 0.81 0.82 0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.94 0.96 0.97 0.99 1.00

fcx,2, sp
0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.90 0.93 0.95 0.98 1.00
fcy, sp

76
Concrete splitting failure - Influence of concrete member thickness

h/hmin 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40 2.50 2.60 2.70 2.80 ≥2.90

fh 1.00 1.07 1.13 1.19 1.25 1.31 1.37 1.42 1.48 1.53 1.59 1.64 1.69 1.74 1.79 1.84 1.89 1.94 1.99 2.00

Shear loading

The decisive design resistance in shear is the lowest value of the following failure modes:

Steel failure:

Concrete pry-out failure:

Concrete edge failure:

Design steel resistance of a single anchor

Anchor type: WIT-PE 500 M

steel grade Thread


M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
size
5.8 VRd,s [kN] 7.4 11.6 16.9 31.4 49.0 70.5 91.8 112.1 138.7 163.3 195.2
8.8 VRd,s [kN] 11.7 18.6 27.0 50.2 78.3 112.8 147.0 179.4 221.9 261.4 312.2

WIT-PE 500 M
10.9 VRd,s [kN] 12.2 19.3 28.1 52.2 81.6 117.5 153.1 186.9 231.2 272.2 325.3
A4-70 VRd,s [kN] 8.3 12.8 19.2 35.3 55.1 79.5 103.4 126.1 156.1 183.8 219.5

Design concrete pry-out resistance of a single anchor

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
hef,typ [mm] 80 90 110 125 170 210 240 270 300 330 360
k [-] 2 2 2 2 2 2 2 2 2 2 2

77
WIT-PE 500 WITH THREADED ROD (METRIC)
Design concrete edge resistance

Verification of concrete edge failure may be omitted for single fasteners and groups with an edge distance in all
directions . For anchorages with more than one edge, the resistance for all edges shall be
calculated. The smallest value should be used in the verification.

Basic design concrete edge resistance of a single anchor

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
Non-cracked concrete
V0Rd,c [kN] 5.2 7.5 10.1 16.4 24.3 33.7 40.3 46.3 52.6 59.1 65.7
Cracked concrete
V0Rd,c [kN] 3.7 5.3 7.1 11.6 17.1 23.7 28.3 32.6 37.0 41.6 46.3

Influence of concrete strength

Concrete strength classes


WIT-PE 500 M

C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60


(EN 206:2000)
Characteristic compressive strength of
concrete determined by testing fck,cyl [N/mm2] 12 16 20 25 30 35 40 45 50
cylinders1)
Characteristic compressive strength of
fck,cube [N/mm2] 15 20 25 30 37 45 50 55 60
concrete determined by testing cube2)
Influencing factor fb,V [-] 0.77 0.89 1.00 1.10 1.22 1.34 1.41 1.48 1.55

1)
strength at 28days of 150mm diameter by 300mm cylinders.
2)
strength at 28days of 150mm cubes.

Influence of embedment depth

hef /d 4 5 6 7 8 9 10 11 ≥ 12
fhef,V 0.87 0.91 0.94 0.97 1.00 1.02 1.05 1.07 1.08

Influence of edge distance c1

c1 /d 4 8 12 15 20 30 40 50 60 100 150 200


fc1,V 0.47 1.19 2.05 2.76 4.05 6.96 10.22 13.76 17.54 34.66 59.52 87.35

78
Influence of load direction

α1) 0 10 20 30 40 50 60 70 80 90
fα,V 1.00 1.01 1.05 1.11 1.20 1.34 1.51 1.72 1.92 2.00
1)
For α ≥ 90° the component of the shear load acting away from the edge may be neglected and the verification may
be done with component acting parallel to the edge only.

Influence of spacing

In groups loaded perpendicular to the edge only two adjacent anchors closest and parallel to the edge carry the load.
The smallest spacing should be used for the verification.

s/c11) 0.50 0.60 0.70 0.80 0.90 1.00 1.20 1.40 1.60 1.80 2.00 2.20 2.40 2.60 2.80 3.00
fs,V 1.17 1.20 1.23 1.27 1.30 1.33 1.40 1.47 1.53 1.60 1.67 1.73 1.80 1.87 1.93 2.00
1)
Choose always the lowest value of the spacing s, when there are different spacings in the row closest to the edge.

Influence of second edge distance

WIT-PE 500 M
c2/c11) 1.00 1.10 1.20 1.30 1.40 1.50
fc,V 0.75 0.80 0.85 0.90 0.95 1.00
1)
Distance to the second edge: c1 ≤ c2.

Influence of concrete member thickness

h/c1 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 ≥ 1.50
fh,V 0.26 0.37 0.45 0.52 0.58 0.63 0.68 0.73 0.77 0.82 0.86 0.89 0.93 0.97 1.00

79
WIT-PE 500 WITH THREADED ROD (METRIC)

Structural Verification

Tension

Shear

Combined tension and shear


WIT-PE 500 M

80
Service temperature

Temperature range Base material Maximum long term base Maximum short term base
temperature material temperature material temperature
Temperature range I -40 °C to +40 °C +24 °C +40 °C
Temperature range II -40 °C to +60 °C +43 °C +60 °C
Temperature range III -40 °C to +72 °C +43 °C +72 ° C

Design bond strength for different use categories


Anchor type: WIT-PE 500 M

Non-cracked concrete

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Design bond strength according to ETA-09/0040 / dry and wet concrete / hammer drilling
Temperature range I τRd,ucr [N/mm2] 8.3 8.3 8.3 7.8 6.2 5.7 5.7 5.7 5.2 5.2 5.2
Temperature range II τRd,ucr [N/mm ]
2
5.3 5.3 5.0 4.7 3.8 3.6 3.6 3.6 3.3 3.3 3.3
Temperature range III τRd,ucr [N/mm2] 4.7 4.7 4.4 4.2 3.3 3.3 3.1 3.1 2.9 2.9 2.9
Design bond strength according to ETA-09/0040 / flooded concrete / hammer drilling
Temperature range I τRd,ucr [N/mm2] 7.1 6.7 6.2 4.8 4.5 4.0 3.6 3.3
Temperature range II τRd,ucr [N/mm ]
2
4.5 4.5 4.3 4.0 3.6 3.3 3.1 2.9
Temperature range III τRd,ucr [N/mm2] 4.0 4.0 3.8 3.6 3.3 2.9 2.6 2.6
Design bond strength according to ETA-11/0398 / dry and wet concrete / diamond drilling

WIT-PE 500 M
Temperature range I τRd,ucr [N/mm2] 7.3 5.6 5.6 5.3 5.0
Temperature range II τRd,ucr [N/mm ]
2
4.7 3.6 3.3 3.3 3.1
Temperature range III τRd,ucr [N/mm ]
2
4.0 3.3 3.1 2.8 2.8
Design bond strength according to ETA-11/0398 / flooded concrete / diamond drilling
Temperature range I τRd,ucr [N/mm2] 6.0 5.6 5.3 5.3 4.7
Temperature range II τRd,ucr [N/mm2] 3.7 3.6 3.3 3.3 3.1
Temperature range III τRd,ucr [N/mm ]
2
3.3 3.3 2.8 2.8 2.8

Cracked concrete

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Design bond strength according to ETA-09/0040 / dry and wet concrete / hammer drilling
Temperature range I τRd,cr [N/mm2] 4.2 3.6 2.9 2.6 2.6 2.6
Temperature range II τRd,cr [N/mm ]
2
2.5 2.2 1.7 1.7 1.7 1.7
Temperature range III τRd,cr [N/mm2] 2.2 1.9 1.4 1.4 1.4 1.4
Design bond strength according to ETA-09/0040 / flooded concrete / hammer drilling
Temperature range I τRd,cr [N/mm2] 3.6 2.9 2.4 2.1 1.9 1.9
Temperature range II τRd,cr [N/mm ]
2
2.1 1.9 1.7 1.7 1.7 1.7
Temperature range III τRd,cr [N/mm2] 1.9 1.7 1.4 1.4 1.4 1.4

81
WIT-PE 500 WITH THREADED ROD (METRIC)
Reduction factor for different use categories

Anchor type: WIT-PE 500 M

Non-cracked concrete

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Reduction factor strength according to ETA-09/0040 / dry and wet concrete / hammer drilling
Temperature range I fτ.red 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Temperature range II fτ.red 0.63 0.63 0.60 0.61 0.62 0.63 0.63 0.63 0.64 0.64 0.64
Temperature range III fτ.red 0.57 0.57 0.53 0.54 0.54 0.58 0.54 0.54 0.55 0.55 0.55
Reduction factor according to ETA-09/0040 / flooded concrete / hammer drilling
Temperature range I fτ.red 0.86 0.80 0.74 0.61 0.73 0.71 0.63 0.58
Temperature range II fτ.red 0.54 0.54 0.51 0.52 0.58 0.58 0.54 0.50
Temperature range III fτ.red 0.49 0.49 0.46 0.46 0.54 0.50 0.46 0.46
Reduction factor according to ETA-11/0398 / dry and wet concrete / diamond drilling
Temperature range I fτ.red 0.88 0.67 0.71 0.85 0.88
Temperature range II fτ.red 0.56 0.43 0.43 0.54 0.53
Temperature range III fτ.red 0.48 0.40 0.39 0.45 0.49
Reduction factor according to ETA-11/0398 / flooded concrete / diamond drilling
Temperature range I fτ.red 0.72 0.67 0.68 0.85 0.83
Temperature range II
WIT-PE 500 M

fτ.red 0.44 0.43 0.43 0.54 0.53


Temperature range III fτ.red 0.40 0.40 0.36 0.45 0.49

Cracked concrete

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Reduction factor according to ETA-09/0040 / dry and wet concrete / hammer drilling
Temperature range I fτ.red 1.00 1.00 1.00 1.00 1.00 1.00
Temperature range II fτ.red 0.60 0.62 0.58 0.64 0.64 0.64
Temperature range III fτ.red 0.53 0.54 0.50 0.55 0.55 0.55
Reduction factor according to ETA-09/0040 / flooded concrete / hammer drilling
Temperature range I fτ.red 0.86 0.79 0.83 0.82 0.73 0.73
Temperature range II fτ.red 0.51 0.53 0.58 0.64 0.64 0.64
Temperature range III fτ.red 0.46 0.46 0.50 0.55 0.55 0.55

82
Anchor characteristics

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
hef,min [mm] 60 60 70 80 90 96 108 120 132 144 156
Effective anchorage depth
hef,max [mm] 96 120 144 192 240 288 324 360 396 432 468
Nominal drill hole
d0 [mm] 10 12 14 18 24 28 32 35 37 42 46
diameter
Drill depth h0 / h1 [mm] = hef
Clearance-hole in fixture
df [mm] 9 12 14 18 22 26 30 33 36 39 42
to be attached
Wrench size SW [mm] 13 17 19 24 30 36 41 46 50 55 60
Required torque Tinst [Nm] 10 20 40 80 120 160 180 200 350 500 700
Min. thickness of
hmin [mm] = hef + 30mm ≥ 100mm = hef + 2d0
concrete member
Minimum spacing smin [mm] 40 50 60 80 100 120 135 150 165 180 195
Minimum edge distances cmin [mm] 40 50 60 80 100 120 135 150 165 180 195

WIT-PE 500 M
df
d0

83
WIT-PE 500 WITH THREADED ROD (METRIC)
Mechanical characteristics

Anchor type: WIT-PE 500 M

steel grade Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39
Stressed As [mm²] 37 58 84 157 245 352 459 561 694 817 976
cross section
Section Modulus W [mm³] 31 62 109 277 540 933 1389 1872 2576 3292 4299
Yield strength fy [N/mm2] 400 400 400 400 400 400 400 400 400 400 400
Tensile strength fu [N/mm ] 2
500 500 500 500 500 500 500 500 500 500 500
5.8
Design bending
M0Rd,s [Nm] 15 30 52 133 259 448 667 899 1237 1580 2064
moment
Yield strength fy [N/mm2] 640 640 640 640 640 640 640 640 640 640 640
Tensile strength fu [N/mm ] 2
800 800 800 800 800 800 800 800 800 800 800
8.8
Design bending
M0Rd,s [Nm] 24 48 84 212 415 717 1067 1438 1979 2528 3302
moment
Yield strength fy [N/mm2] 900 900 900 900 900 900 900 900 900 900 900
Tensile strength fu [N/mm ] 1000 1000 1000 1000 1000 1000 1000
2
1000 1000 1000 1000
10.9
Design bending
M0Rd,s [Nm] 25 50 87 221 432 747 1111 1498 2061 2634 3439
moment
Yield strength fy [N/mm2] 450 450 450 450 450 450 450 450 450 450 450
Tensile strength fu [N/mm ] 2
700 700 700 700 700 700 700 700 700 700 700
A4-70
Design bending
M0Rd,s [Nm] 17 34 59 149 292 504 750 1011 1391 1778 2322
WIT-PE 500 M

moment

84
Material specification of anchor

Anchor type: WIT-PE 500 M

Part Designation Material


Steel, zinc plated ≥ 5 μm acc. to EN ISO 4042 or Steel, hot-dip galvanised ≥ 40 μm acc. to EN ISO 1462
Steel, EN 10087 or EN 10263
1 Anchor rod
Property class 5.8, 8.8, 10.9, EN ISO 898-1
Property class 5 (for class 5.8 rod) EN 20898-2
2 Hexagon nut, EN 24032 Property class 8 (for class 8.8 rod) EN 20898-2
Property class 10 (for class 10.9 rod) EN 20898-2
Washer, EN ISO 7089,
3 Steel, zinc plated
EN ISO 7093 or EN ISO 7094
Stainless steel
Material 1.4401 / 1.4571, EN 10088-1
Property class 70 EN ISO 3506
1 Anchor rod
or for
> M24: Property class 50 EN ISO 3506
Material 1.4401 / 1.4571, EN 10088
Property class 70 EN ISO 3506
2 Hexagon nut, EN 24032
or for
> M24: Property class 50 EN ISO 3506
Washer, EN ISO 7089,
3 Material 1.4401 or 1.4571, EN 10088
EN ISO 7093 or EN ISO 7094
High corrosion resistance steel
Material 1.4529 / 1.4565, EN 10088-1:2005,
1 Anchor rod > M24: Property class 50 EN ISO 3506

WIT-PE 500 M
≤ M24: Property class 70 EN ISO 3506
Material 1.4529 / 1.4565, EN 10088,
2 Hexagon nut, EN 24032 > M24: Property class 50 (for class 50 rod)EN ISO 3506
≤ M24: Property class 70 (for class 70 rod)EN ISO 3506
Washer, EN ISO 7089,
3 Material 1.4529 or 1.4565, EN 10088
EN ISO 7093 or EN ISO 7094

85
WIT-PE 500 WITH THREADED ROD (METRIC)
Properties of adhesive

Property Testing method Results

Stability
UV-resistance (sunlight) resistant
Temperature resistance 72 °C
Water resistancy resistant
Water absorption ASTM D 570 0.109 %
Cleaning agents 1% tenside solution: no effects
Physical properties
Flexural strength DIN EN 196-1 after 24 hours: 42 N/mm2
Modulus of Elasticity (Young's UNI EN ISO 178 after 24 hours: 4.11 GPa
Flexural Properties Modulus)
Flexural stress at break UNI EN ISO 178 after 24 hours: 86 MPa
Flexural strain at break UNI EN ISO 178 after 24 hours: 2.0 %
Compressive strength DIN EN 196-1 after 24 hours: ≥ 120 N/mm2
after 7 days: 169 MPa
Compressive strength UNI EN ISO 604
after 2 days: 166 MPa
Compressive Properties
Modulus of Elasticity ASTM D 695 after 24 hours: 5.97 GPa
Yield stress ASTM D 695 after 24 hours: 5129 GPa
Deformation beyond yield point ASTM D 695 3.6 %
WIT-PE 500 M

Tensile strength ASTM D 638 41.7 N/mm2


Tensile properties
Elongation at break ASTM D 638 0.74 %
Dynamic Modulus of Elasticity DIN EN 12504-4 after 24 hours: 10.85 GPa
Shrinkage unidirectional UNI 4285 0.0035 mm/mm
Hardness Shore D /15 ISO 868 after 48 hours: 80
Thermal conductivity Modified transient plane source method 0.48 / 0.41 / 0.54 W/mK
Specific contact resistance IEC 93 4.1 x 1015 Ωcm
DC Resistance or Conductance  Volume resistance ASTM D 257 1.2 x 1012 Ωm
Density DIN 53479 1.41 ± 0.1 g/cm3
Workability features
Watertightness / Impermeability DIN EN 12390-8 after 72 hours at 5bar: 0mm
Open time (10-20°C) 30 min
Curing time (10-20°C) 10 hours
Shelf life 24 months
For information use only. Values are not to be considered as a specification and do not reflect the performance of the system. The given values are
typical values and are subject to change without notice.

86
Working time and curing time

Temperature Gelling - working time Minimum Curing time  Minimum Curing time
of Concrete in dry concrete in wet concrete 
5°C to 9°C 60 min 72 h 142 h
10°C to 19°C 45 min 45 h 90 h
20°C to 29°C 30 min  10 h 20 h
30°C to 39°C 20 min  6 h 12 h
≥ 40°C 12 min  4 h 8h

Filling Quantity

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Nominal drill hole d0 [mm] 10 12 14 18 24 28 32 35 37 42 46


diameter
Drill depth h0 / h1 [mm] = hef
Filling volume per 10mm
[ml] 0.52 0.67 0.83 1.14 2.40 3.00 3.98 4.57 5.00 6.49 7.00
embedment depth
Assumed wastage of 15% included.

WIT-PE 500 M

87
WIT-PE 500 WITH THREADED ROD (METRIC)
Installation instruction

Anchor type: WIT-PE 500 M

Installation Control

Choose the right tools. There is a clearly defined set of tools


for producing a safe fixture: drilling
machine, drill bit, hand-pump, brush,
brush diameter gauge. (See table
„Accessories“)
Check availability of those system tools
before starting.

Drill hole to the required embedment depth with a hammer Working length of drill bit must be
drill set in rotation-hammer mode using an appropriately bigger than the given drill hole
sized carbide drill bit.(for drill bit diameter and drill hole depth.
depth (see table „Anchor characteristics“)

Blow out at least 2x from the back of the bore hole until The compressed air without oil.
return air stream is free of noticeable dust.
If the back of the bore hole is not reached an extension
shall be used.
The hand-pump can be used for anchor sizes up to bore
hole diameter 20 mm. For bore holes larger than 20 mm
WIT-PE 500 M

or deeper 240 mm, compressed air (min. 6 bar) must be


used.

Brush 2x with the specified brush size by inserting the The brush must produce natural
brush to the back of the hole in a twisting motion and resistance as it enters the drill hole -
removing it. if not, the brush is too small and
must be replaced with the proper
brush diameter (use the brush
diameter gauge).

or Blow out at least 2x from the back of the bore hole until
return air stream is free of noticeable dust.
If the back of the bore hole is not reached an extension
shall be used.
The hand-pump can be used for anchor sizes up to bore
hole diameter 20 mm. For bore holes larger than 20 mm
or deeper 240 mm, compressed air (min. 6 bar) must be
used.

Prior to inserting the anchor rod into the filled bore hole, Before use, verify that the anchor
the position of the embedment depth shall be marked on element is dry and free of oil and
the anchor rods. other contaminants.

88
Installation Control

Tightly attach mixing nozzle to cartridge. Only use mixing nozzle and
Place the cartridge into dispensing gun. dispensing gun of the system.
Do not modify the mixing nozzle.

Discard initial adhesive. An initial amount of 10cm


adhesive has to be discarded.
Visual check if resin is evenly in colour.
For every working interruption longer than the
recommended working time as well as for new cartridges,
a new mixing nozzle shall be used.
(see table „Working and cure times“)

Inject the adhesive starting at the back of the hole, slowly Marking the mixing nozzle makes
withdrawing the mixer with each trigger pull. it easier to fill every hole with the
Fill holes approximately 2/3 full, or as required to ensure same volume.
that the annular gap between the anchor and the concrete
is completely filled with adhesive along the embedment
length.
For embedment larger than 190mm an extension nozzle
shall be used.
For overhead and horizontal installation in bore holes
larger than ∅ 20mm a injection adapter and extension
nozzle shall be used.

Press the marked anchor element down to the bottom of If these requirements (excess mortar

WIT-PE 500 M
the hole, turning it slightly while doing so. and the embedment depth) are not
After inserting the anchor element, excess mortar must maintained, the application has to
emerge from the annular gap. be renewed.
For overhead installation fix
embedded part (e.g.wedges).

Do not move or load the anchor until the mortar is fully


cured. (see table „Working and cure times“)

After required curing time, the anchor element can be Check the max. torque by using a
loaded. calibrated torque wrench.
The applied installation torque shall not exceed. (see table
„Anchor characteristic“)

89
WIT-PE 500 WITH THREADED ROD (METRIC)
Accessoires

Anchor type: WIT-PE 500 M

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Nominal drill hole diameter d0 [mm] 10 12 14 18 24 28 32 35 37 42 46

Drill depth h0 / h1 [mm] = hef

Wrench size SW [mm] 13 17 19 24 30 36 41 46 50 55 60

Required torque Tinst [Nm] 10 20 40 80 120 160 180 200 350 500 700

Hammer Drills

H 36-MAS / H24-MLS (SDS-plus)

BMH 32-XE (SDS-Plus)

BMH 40-XES (SDS-Max)

BMH 45-XE (SDS-Max)

Drill Bits

LONGLIFE QUADRO-L (0648 xxx yyy)

LONGLIFE QUADRO-L (0647 0xx yyy)


WIT-PE 500 M

QUADRO-S (0647 7xx yyy)

Brush

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Brush diameter db [mm] 12 14 16 20 26 30 34 37 39 44 48

Brush length lb [mm] 170 200 200 300 300 300


Brush ... 001 ... 002 ... 003 ... 004 ... 005 ... 008 on demand
0905 499 ...
Brush extension 0905 499 111

Brush diameter gauge 0905 499 099

SDS adapter for machine cleaning 0905 499 102

Hex adapter for machine cleaning 0905 499 101

Blow-out (manual)

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Blow-out pump (manual) 0903 990 001


Reducing adapter
... 202
0905 499 ...

90
Compressed-air cleaning

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Jet nozzle 0903 489 217

Thread adapter 0903 489 291

Hose 0699 903 7

Injecting

Thread size M8 M10 M12 M16 M20 M24 M27 M30 M33 M36 M39

Dispensing gun 0891 009

Pneumatic dispenser 385 + 585 0891 017

Pneumatic dispenser 1400 0891 015

Mixer nozzle 0903 488 101

Mixer extension ∅ 10 0903 488 123

Mixer extension ∅ 16 0903 488 122


Injection adapter (repulsion piston) ... 051 ... 052
0903 488 ...

WIT-PE 500 M

91
WIT-PE 500 WITH THREADED ROD (METRIC)

Chemical resistance

Chemical Agent Concentration Resistant Not Resistant


Acetic acid 40 ●
Laitance ●
Acetone 10 ●
Ammonia, aqueous solution 5 ●
Aniline 100 ●
Beer 100 ●
Chlorine all ●
Benzol 100 ●
Boric Acid, aqueous solution ●
Calcium carbonate, suspended in water all ●
Calcium chloride, suspended in water ●
Calcium hydroxide, suspended in water ●
Carbon tetrachloride 100 ●
Caustic soda solution 40 ●
Citric acid all ●
Diesel oil 100 ●
Ethyl alcohol, aqueous solution 50 ●
Formic acid 100 ●
Formaldehyde, aqueous solution 30 ●
Freon ●
Fuel Oil ●
Gasoline (premium grade) 100 ●
Glycol (Ethylene glycol) ●
Hydrochloric acid (Muriatic Acid) conc. ●
Hydrogen peroxide 30 ●
Isopropyl alcohol 100 ●
WIT-PE 500 M

Lactic acid all ●


Linseed oil 100 ●
Lubricating oil 100 ●
Magnesium chloride, aqueous solution all ●
Methanol 100 ●
Motor oil (SAE 20 W-50) 100 ●
Nitric acid 10 ●
Oleic acid 100 ● ●
Perchloroethylene 100 ●
Petroleum 100 ●
Phenol, aqueous solution 8 ●
Phosphoric acid 85 ●
Phosphoric acid 10 ●
Potash lye (Potassium hydroxide, 10% and 40% solution) ●
Potassium carbonate, aqueous solution all ●
Potassium chlorite, aqueous solution all ●
Potassium nitrate, aqueous solution all ●
Sodium carbonate all ●
Sodium Chloride, aqueous solution all ●
Sodium phosphate, aqueous solution all ●
Sodium silicate all ●
Sulfuric acid 30 ●
Tartaric acid all ●
Tetrachloroethylene 100 ●
Toluene ●
Trichloroethylene 100 ●
Turpentine 100 ●
Turpentine 100 ●