Approved for:
Concrete C20/25 to C50/60, non-cracked & cracked
Suitable for:
Concrete C12/15, Natural stone with dense structure
Drilling method
Hammer drill Diamond drill Hollow drill
✓ ✓ ✓
WIT-PE 1000 R
Applications
LEED
tested
All data in this section applies when: • Concrete C 50/60, fck = 60 N/mm2
• Installation is correct (see installation instructions) • Temperature range I (min. base material temperature
• No edge distance and spacing influence -40°C, max long term/short term base material
• Base material thickness and embedment depth are temperature: +24°C/40°C).
according to anchor characteristics • Dry or wet conditions of drill hole, hammer drilling
• Rebar material is according to specifications,
steel grade B500B
• Concrete C 20/25, fck = 20 N/mm2
Characteristic resistance
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Effective anchorage hef [mm]
80 90 110 125 125 170 210 210 270 300
depth
Non-cracked concrete
Tension C20/25 27.5 42.0 56.8 68.8 68.8 109.0 149.7 149.7 218.2 255.6
NRk [kN]
C50/60 27.5 43.5 62.2 84.7 108.7 172.4 236.7 236.7 338.8 404.2
Shear ≥ C20/25 VRk [kN] 13.8 21.7 31.1 42.4 55.3 86.4 124.3 135.0 169.4 221.1
Cracked concrete
Tension C20/25 14.1 19.8 35.2 46.7 48.1 76.3 104.8 104.8 152.8 178.9
NRk [kN]
C50/60 15.5 21.8 38.8 51.4 58.7 99.9 148.0 154.2 222.1 282.2
Shear ≥ C20/25 VRk [kN] 13.8 21.7 31.1 42.4 55.3 86.4 124.3 135.0 169.4 221.1
WIT-PE 1000 R
Design resistance
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Effective anchorage hef [mm]
80 90 110 125 125 170 210 210 270 300
depth
Non-cracked concrete
Tension C20/25 19.6 28.0 37.8 45.8 45.8 72.7 99.8 99.8 145.5 170.4
NRd [kN]
C50/60 19.6 31.0 44.4 60.5 72.5 114.9 157.8 157.8 230.1 269.4
Shear ≥ C20/25 VRd [kN] 9.2 14.5 20.7 28.2 36.9 57.6 82.9 90.0 112.9 147.4
Cracked concrete
Tension C20/25 9.4 13.2 23.5 31.2 32.1 50.9 69.9 69.9 101.8 119.3
NRd [kN]
C50/60 10.3 14.5 25.8 34.3 39.2 66.6 98.7 102.8 148.0 188.0
Shear ≥ C20/25 VRd [kN] 9.2 14.5 20.7 28.2 36.9 57.6 82.9 90.0 112.9 147.4
253
WIT-PE 1000 WITH REBAR
Recommended/allowable loads 1)
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Effective anchorage hef [mm]
80 90 110 125 125 170 210 210 270 300
depth
Non-cracked concrete
Tension C20/25 14.0 20.0 27.0 32.7 32.7 51.9 71.3 71.3 103.9 121.7
Nrec [kN]
C50/60 14.0 22.2 31.7 43.2 51.8 82.1 112.7 112.7 164.3 192.5
Shear ≥ C20/25 Vrec [kN] 6.5 10.3 14.8 20.2 26.3 41.1 59.2 64.3 80.7 105.3
Cracked concrete
Tension C20/25 6.7 9.4 16.8 22.3 22.9 36.3 49.9 49.9 72.7 85.2
Nrec [kN]
C50/60 7,4 10.4 18.5 24.5 28.0 47.6 70.5 73.4 105.7 134.3
Shear ≥ C20/25 Vrec [kN] 6.5 10.3 14.8 20.2 26.3 41.1 59.2 64.3 80.7 105.3
1)
Material safety factor γM and safety factor for action γ L = 1.4 are included. The material safety factor depends on the failure mode.
WIT-PE 1000 R
254
Design method (simplified)
Simplified version of the design method according to Eurocode 2 - Design of concrete structures -
Part 4: Design of fastenings for use in concrete (EN 1992-4):
• Influence factors related to concrete strength, edge distance, spacing and others must be considered when applicable
• Valid for a group of anchors. The influencing factors must then be considered for each edge distance and spacing. The
calculated design resistances are on the safe side. They will be lower than the exact values according to EN 1992-4.
For an economical optimization, we recommend using the anchor design module of the Würth Technical Software II
• The design method is based on the simplification that no different loads are acting on individual anchors
(no eccentricity)
• Temperature range 1 (min. base material temperature -40°C, max. long term/short term base material temperature:
+24°C/40°C)
• Dry or wet conditions of drill hole, hammer drilling (Installation factors might apply for other drilling methods)
• Rebar material according to specifications, steel grade B500B
I. Tension loading
The decisive design resistance in tension is the lowest value of the following failure modes:
2. Pull-out failure NRd,p = N0Rd,p · f b,N · f hef · fsx,p ·fsy,p · fcx,1,p · fcx,2,p · fcy,p · fsus
3. Concrete cone failure NRd,c = N0Rd,c · f b,N · f hef · fsx ·fsy · fcx,1 · fcx, · fcy
WIT-PE 1000 R
4. Concrete splitting failure NRd,sp = N0Rd,sp · f b;N · f hef · fsx,sp · fsy,sp · fcx,1,sp · fcx,2,sp · fcy,sp · f h
Table 1: Design value of steel resistance under tension load NRd,s of a single anchor
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Effective anchorage hef [mm]
80 90 110 125 125 170 210 210 270 300
depth
Design steel resistance N Rd,s [kN] 19.6 31.0 44.4 60.5 79.0 123.4 177.6 192.9 242.0 315.9
255
WIT-PE 1000 WITH REBAR
NRd,p = N0Rd,p · f b,N · f hef · fsx,p ·fsy,p · fcx,1,p · fcx,2,p · fcy,p · fsus
Table 2: Basic design resistance N 0Rd,p in case of combined pull-out and concrete cone failure of a single anchor
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Effective anchorage hef [mm]
80 90 110 125 125 170 210 210 270 300
depth
Non-cracked concrete
Combined pull-out and
N 0Rd,p [kN] 21.4 30.2 44.2 58.6 67.0 113.9 158.3 164.9 237.5 301.6
concrete cone resistance
Cracked concrete
Combined pull-out
N 0Rd,p [kN] 9.4 13.2 23.5 31.2 35.6 60.5 89.7 93.5 134.6 170.9
concrete cone resistance
Spacing scr,p [mm] 234 270 330 375 375 510 630 630 792 900
Edge distance ccr,p [mm] 117 135 165 188 188 255 315 315 396 450
256
b. Influence of embedment depth
Consider the approved range of embedment hef,min ≤ hef ≤ hef,max according to the table „installation parameters“.
c. Influence of spacing
2 fsx,p, fsy,p 0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.85 0.88 0.95 0.98 1.00
3 fsx,p, fsy,p 0.40 0.43 0.47 0.50 0.53 0.57 0.60 0.63 0.67 0.70 0.73 0.77 0.80 0.83 0.80 0.83 0.93 0.97 1.00
4 fsx,p, fsy,p 0.33 0.36 0.40 0.44 0.48 0.51 0.55 0.59 0.63 0.66 0.70 0.74 0.78 0.81 0.78 0.81 0.93 0.96 1.00
5 fsx,p, fsy,p 0.28 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.76 0.80 0.76 0.80 0.92 0.96 1.00
1)
Choose always the lowest value of the spacing s, when there are different spacings in one row
WIT-PE 1000 R
Table 6: Influence of edge distance on combined pull-out and concrete cone resistance
c/ccr,P 0,10 0,15 0,20 0,25 0,30 0,35 0,40 0,45 0,50 0,55 0,60 0,65 0,70 0,75 0,70 0,75 0,90 0,95 ≥1
fcx,1 0.73 0.75 0.76 0.78 0.79 0.81 0.82 0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.91 0.93 0.97 0.99 1.00
fcx,2
0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.85 0.88 0.95 0.98 1.00
fcy
257
WIT-PE 1000 WITH REBAR
Nsus,d = design value of sustained actions (permanent actions & permanent component of variable actions)
NEd = Value of total actions in tension loading at ultimate limit state
Table 7: Influence of sustained loads on combined pull-out and concrete cone resistance
asus 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
fsus 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.90 0.80
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Effective anchorage hef [mm]
80 90 110 125 125 170 210 210 270 300
depth
Non-cracked concrete
Concrete cone resistance N 0Rd,c [kN] 23.5 28.0 37.8 45.8 45.8 72.7 99.8 99.8 145.5 170.4
Cracked concrete
Concrete cone resistance N 0Rd,c [kN] 16.4 19.6 26.5 32.1 32.1 50.9 69.9 69.9 101.8 119.3
Above characteristic spacing and edge distances are given for the typical effective anchorage depths. Calculating for smal-
ler depths leads to conservative load capacities. For calculation with bigger depths, use the following:
258
a. Influence of concrete strength
Consider the approved range of embedment hef,min ≤ hef ≤ hef,max according to the table „anchor characteristics“.
c. Influence of spacing
WIT-PE 1000 R
Table 11: Influence of spacing on concrete cone resistance
Number of
fixing per s/scr,p 1) 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.70 0.75 0.90 0.95 ≥1
direction
2 fsx, fsy 0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.85 0.88 0.95 0.98 1.00
3 fsx, fsy 0.40 0.43 0.47 0.50 0.53 0.57 0.60 0.63 0.67 0.70 0.73 0.77 0.80 0.83 0.80 0.83 0.93 0.97 1.00
4 fsx, fsy 0.33 0.36 0.40 0.44 0.48 0.51 0.55 0.59 0.63 0.66 0.70 0.74 0.78 0.81 0.78 0.81 0.93 0.96 1.00
5 fsx, fsy 0.28 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.76 0.80 0.76 0.80 0.92 0.96 1.00
1)
Choose always the lowest value of the spacing s, when there are different spacings in one row
fcx,1 0.73 0.75 0.76 0.78 0.79 0.81 0.82 0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.91 0.93 0.97 0.99 1.00
fcx,2
0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.85 0.88 0.95 0.98 1.00
fcy
259
WIT-PE 1000 WITH REBAR
Table 13: Design resistance NRd,sp in case of concrete splitting failure of a single anchor
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Effective anchorage hef [mm]
80 90 110 125 125 170 210 210 270 300
depth
Non-cracked concrete
Splitting resistance N 0Rd,sp [kN] 21.4 28.0 37.8 45.8 45.8 72.7 99.8 99.8 145.5 170.4
Above characteristic spacing and edge distances are given for the typical effective anchorage depth. Calculating for
WIT-PE 1000 R
smaller depths leads to conservative load capacities. For calculation with bigger depths, use the following:
and
260
b. Influence of embedment depth
Consider the approved range of embedment hef,min ≤ hef ≤ hef,max according to the table „anchor characteristics“.
c. Influence of spacing
2 fsx,sp , fsy,sp 0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.85 0.88 0.95 0.98 1.00
3 fsx,sp , fsy,sp 0.40 0.43 0.47 0.50 0.53 0.57 0.60 0.63 0.67 0.70 0.73 0.77 0.80 0.83 0.80 0.83 0.93 0.97 1.00
4 fsx,sp , fsy,sp 0.33 0.36 0.40 0.44 0.48 0.51 0.55 0.59 0.63 0.66 0.70 0.74 0.78 0.81 0.78 0.81 0.93 0.96 1.00
5 fsx,sp , fsy,sp 0.28 0.32 0.36 0.40 0.44 0.48 0.52 0.56 0.60 0.64 0.68 0.72 0.76 0.80 0.76 0.80 0.92 0.96 1.00
1)
Choose always the lowest value of the spacing s, when there are different spacings in one row
WIT-PE 1000 R
Table 17: Influence of edge distance on splitting resistance
c/ccr,sp 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.70 0.75 0.90 0.95 ≥1
fcx,1, sp 0.73 0.75 0.76 0.78 0.79 0.81 0.82 0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.91 0.93 0.97 0.99 1.00
fcx,2, sp
0.55 0.58 0.60 0.63 0.65 0.68 0.70 0.73 0.75 0.78 0.80 0.83 0.85 0.88 0.85 0.88 0.95 0.98 1.00
fcy, sp
fh 1.00 1.07 1.13 1.19 1.25 1.31 1.37 1.42 1.48 1.53 1.59 1.64 1.69 1.74 1.79 1.74 1.79 1.94 1.99 2.00
261
WIT-PE 1000 WITH REBAR
The decisive design resistance in shear is the lowest value of the following failure modes:
3. Concrete edge failure VRd,c = V 0Rd,c · fb,V · fhef,V · fs,V · fc1,V · fc2,V · fa · fh
Verification of concrete edge failure may be omitted for single fasteners and groups with an edge distance in all directions
c ≥ max (10 hef ; 60 d). For anchorages with more than one edge, the resistance for all edges shall be calculated. The
smallest value should be used in the verification.
262
Table 21: Design resistance V 0Rd,c in case of concrete edge failure
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Effective anchorage hef [mm]
80 90 110 125 125 170 210 210 270 300
depth
Non-cracked concrete
Basic design edge
V0Rd,c [kN] 2.8 3.6 4.6 5.6 5.8 8.3 12.2 12.2 14.3 17.2
resistance
Cracked concrete
Basic design edge
V0Rd,c [kN] 2.0 2.5 3.2 4.0 4.1 5.9 8.6 8.6 10.2 12.2
resistance
WIT-PE 1000 R
2)
strength at 28 days of 150 mm cubes
c. Influence of spacing
In groups loaded perpendicular to the edge only two adjacent anchors closest and parallel to the edge carry the load.
The smallest spacing should be used for the verification.
263
WIT-PE 1000 WITH REBAR
h/c1 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 ≥ 1.50
fh.V 0.26 0.37 0.45 0.52 0.58 0.63 0.68 0.73 0.77 0.82 0.86 0.89 0.93 0.97 1.00
264
Structural verification
Steel failure
1
of fastener 1)
If NEd and VEd are different for the individual fasteners of the group, the interaction shall
be verified for all fasteners.
or
Failure modes
2
other than steel failure
WIT-PE 1000 R
265
WIT-PE 1000 WITH REBAR
1- Non-cracked concrete
Thread size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
Design bond resistance in non-cracked concrete C20/25 in hammer drilled holes (HD) and compressed air drilled holes (CD)
Temperature
Dry and 10.7 10.7 10.7 10.7 10.7 10.7 10.0 10.0 10.0 10.0
range I
wet
Temperature concrete 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.3 7.3
range II
τRd,ucr [N/mm2]
Temperature
8.9 8.9 8.9 8.9 8.9 8.9 8.3 8.3 8.3 8.3
range I Flooded
Temperature bore hole
6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.1 6.1
range II
WIT-PE 1000 R
Design bond resistance in non-cracked concrete C20/25 in hammer drilled holes with hollow drill bit (HDB)
Temperature
Dry and 9.3 9.3 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7
range I
wet
Temperature concrete 8.0 8.0 8.0 7.3 7.3 7.3 7.3 7.3 7.3 7.3
range II
τRd,ucr [N/mm2]
Temperature
7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2
range I Flooded
Temperature bore hole
6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
range II
Design bond resistance in non-cracked concrete C20/25 in case of compressed air cleaning (CAC)
Temperature
Dry and 9.3 8.7 8.7 8.7 8.0 8.0 7.3 7.3 7.3 7.3
range I
wet
Temperature concrete 7.3 7.3 6.7 6.7 6.7 6.3 6.3 6.3 6.0 6.0
range II
τRd,ucr [N/mm2]
Temperature
7.8 7.2 7.2 7.2 5.7 5.7 5.2 5.2 5.2 5.2
range I Flooded
Temperature bore hole
6.1 6.1 5.6 5.6 4.8 4.5 4.5 4.5 4.3 4.3
range II
266
2- Cracked concrete
Thread size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
Design bond resistance in cracked concrete C20/25 in hammer drilled holes (HD) compressed air drilled holes (CD) and with hollow
drill bit (HDB)
Temperature
Dry and 4.7 4.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7 5.7
range I
wet
Temperature concrete 4.0 4.0 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
range II
τRd,cr [N/mm2]
Temperature
3.9 3.9 4.7 4.7 4.7 4.7 4.7 4.7 4.7 4.7
range I Flooded
Temperature bore hole
3.3 3.3 3.9 3.9 3.9 3.9 3.9 3.9 3.9 3.9
range II
1- Non-cracked concrete
Thread size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
Design bond resistance in non-cracked concrete C20/25 in hammer drilled holes (HD) and compressed air drilled holes (CD)
Temperature
Dry and 10.7 10.7 10.7 10.7 10.7 10.7 10.0 10.0 10.0 10.0
range I
wet
Temperature concrete 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 7.3 7.3
range II
τRd,ucr [N/mm2]
Temperature
8.9 8.9 8.9 8.9 8.9 8.9 8.3 8.3 8.3 8.3
range I Flooded
WIT-PE 1000 R
Temperature bore hole
6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.1 6.1
range II
Design bond resistance in non-cracked concrete C20/25 in hammer drilled holes with hollow drill bit (HDB)
Temperature
Dry and 9.3 9.3 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7
range I
wet
Temperature concrete 8.0 8.0 8.0 7.3 7.3 7.3 7.3 7.3 7.3 7.3
range II
τRd,ucr [N/mm2]
Temperature
7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2 7.2
range I Flooded
Temperature bore hole
6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
range II
Design bond resistance in non-cracked concrete C20/25 in case of compressed air cleaning (CAC)
Temperature
Dry and 9.3 8.7 8.7 8.7 8.0 8.0 7.3 7.3 7.3 7.3
range I
wet
Temperature concrete 7.3 7.3 6.7 6.7 6.7 6.3 6.3 6.3 6.0 6.0
range II
τRd,ucr [N/mm2]
Temperature
7.8 7.2 7.2 7.2 5.7 5.7 5.2 5.2 5.2 5.2
range I Flooded
Temperature bore hole
6.1 6.1 5.6 5.6 4.8 4.5 4.5 4.5 4.3 4.3
range II
267
WIT-PE 1000 WITH REBAR
2- Cracked concrete
Thread size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
Design bond resistance in cracked concrete C20/25 in hammer drilled holes (HD) compressed air drilled holes (CD) and with hollow
drill bit (HDB)
Temperature
Dry and 4.3 4.3 5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
range I
wet
Temperature concrete 3.7 3.7 4.3 4.3 4.3 4.3 4.3 4.3 4.3 4.3
range II
τRd,cr [N/mm2]
Temperature
3.6 3.6 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2
range III Flooded
Temperature bore hole
3.1 3.1 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6
range III
Reduction factors
1- Non-cracked concrete
Thread size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
Reduction factor for non-cracked concrete C20/25 in hammer drilled holes (HD) and compressed air drilled holes (CD)
WIT-PE 1000 R
Temperature
Dry and 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I
wet
Temperature concrete 0.75 0.75 0.75 0.75 0.75 0.75 0.80 0.80 0.73 0.73
range II
τRd,ucr [N/mm2]
Temperature
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I Flooded
Temperature bore hole
0.75 0.75 0.75 0.75 0.75 0.75 0.80 0.80 0.73 0.73
range II
Reduction factor for non-cracked concrete C20/25 in hammer drilled holes with hollow drill bit (HDB)
Temperature
Dry and 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I
wet
Temperature concrete 0.86 0.86 0.92 0.85 0.85 0.85 0.85 0.85 0.85 0.85
range II
τRd,ucr [N/mm2]
Temperature
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I Flooded
Temperature bore hole
0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
range II
Reduction factor for non-cracked concrete C20/25 in case of compressed air cleaning (CAC)
Temperature
Dry and 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I
wet
Temperature concrete 0.79 0.85 0.77 0.77 0.83 0.79 0.86 0.86 0.82 0.82
range II
τRd,ucr [N/mm2]
Temperature
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I Flooded
Temperature bore hole
0.79 0.85 0.77 0.77 0.83 0.79 0.86 0.86 0.82 0.82
range II
268
2- Cracked concrete
Thread size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
Reduction factor for cracked concrete C20/25 in hammer drilled holes (HD) compressed air drilled holes (CD) and with hollow drill bit
(HDB)
Temperature
Dry and 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I
wet
Temperature concrete 0.86 0.86 0.82 0.82 0.82 0.82 0.82 0.82 0.82 0.82
range II
τRd,cr [N/mm2]
Temperature
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I Flooded
Temperature bore hole
0.86 0.86 0.82 0.82 0.82 0.82 0.82 0.82 0.82 0.82
range II
1- Non-cracked concrete
Thread size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
Reduction factor for non-cracked concrete C20/25 in hammer drilled holes (HD) and compressed air drilled holes (CD)
Temperature
Dry and 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I
wet
Temperature concrete 0.75 0.75 0.75 0.75 0.75 0.75 0.80 0.80 0.73 0.73
range II
τRd,ucr [N/mm2]
Temperature
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I Flooded
WIT-PE 1000 R
Temperature bore hole
0.75 0.75 0.75 0.75 0.75 0.75 0.80 0.80 0.73 0.73
range II
Reduction factor for non-cracked concrete C20/25 in hammer drilled holes with hollow drill bit (HDB)
Temperature
Dry and 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I
wet
Temperature concrete 0.86 0.86 0.92 0.85 0.85 0.85 0.85 0.85 0.85 0.85
range II
τRd,ucr [N/mm2]
Temperature
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I Flooded
Temperature bore hole
0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
range II
Reduction factor for non-cracked concrete C20/25 in case of compressed air cleaning (CAC)
Temperature
Dry and 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I
wet
Temperature concrete 0.79 0.85 0.77 0.77 0.83 0.79 0.86 0.86 0.82 0.82
range II
τRd,ucr [N/mm2]
Temperature
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I Flooded
Temperature bore hole
0.79 0.85 0.77 0.77 0.83 0.79 0.86 0.86 0.82 0.82
range II
269
WIT-PE 1000 WITH REBAR
2- Cracked concrete
Thread size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
Reduction factor for cracked concrete C20/25 in hammer drilled holes (HD) compressed air drilled holes (CD) and with hollow drill bit
(HDB)
Temperature
Dry and 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range I
wet
Temperature concrete 0.85 0.85 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87
range II
τRd,cr [N/mm2]
Temperature
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
range III Flooded
Temperature bore hole
0.85 0.85 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87
range III
Mechanical characteristics
Steel
Rebar size Ø8 Ø10 Ø12 Ø14 Ø16 Ø20 Ø24 Ø25 Ø28 Ø32
grade
Stressed cross section As [mm2] 50 79 113 154 201 314 452 491 616 804
Section modulus W [mm ]
3
50 98 170 269 402 785 1357 1534 2155 3217
Yield strength fy [N/mm ] 2
460 460 460 460 460 460 460 460 460 460
Tensile strength fu [N/mm2] 483 483 483 483 483 483 483 483 483 483
460A
WIT-PE 1000 R
Design bending M0Rd,s [Nm] 19 38 66 104 155 303 524 593 833 1243
moment
Yield strength fy [N/mm2] 460 460 460 460 460 460 460 460 460 460
Tensile strength fu [N/mm ] 2
497 497 497 497 497 497 497 497 497 497
460B
Design bending M 0
Rd,s [Nm] 20 39 68 107 160 312 540 610 857 1279
moment
Yield strength fy [N/mm2] 500 500 500 500 500 500 500 500 500 500
fu
B500B Tensile strength [N/mm ] 550 550 550 550 550 550 550 550 550 550
2
Design bending M 0
Rd,s [Nm] 22 43 75 118 177 345 597 675 948 1415
moment
270
Material specifications
WIT-PE 1000 R
271
WIT-PE 1000 WITH REBAR
Chemical resistance
Stability
UV-resistance (sunlight) resistant
Temperature resistance 72°C
Water resistance resistant
Physical properties
Flexural properties Flexural strength after 24 hours: 66,0 N/mm2
DIN EN 196-1
Compressive properties Compressive strength after 24 hours:122 N/mm2
Tensile strength 44,2 N/mm2
Tensile properties Coefficient of elasticity DIN EN ISO 527-2 6,300 N/mm2
Mean strain at fracture 1,0 %
Shrinkage DIN 52450 ≤ 1,4 ‰
Shore-hardness A 99,4
DIN EN ISO 868
Shore-hardness D 86,1
Density Weighing ≤ 1,50 kg/dm3
Thermal conductivity 0,50 W/mK
DIN EN 993-15
Specific heat capacity 1,350 J/Kg K
Electrical resistance DIN IEC 93 8,0 . 1012 Ω
Workability features
Water tightness /
DIN EN 12390-8 0 mm
WIT-PE 1000 R
impermeability
Working time (20°C) 3 min
Curing time (20°C) 30 mins
Shelf-life 18 months
For information use only. Values are not to be considered as a specification and do not reflect the performance of the system. The given values are typical
values and are subject to change without notice.
Gelling –
Temperature of base material Min. curing time – dry conditions1)
working time
0°C to 4°C 90 min 144 h
5°C to 9°C 80 min 48 h
10°C to 14°C 60 min 28 h
15°C to 19°C 40 min 18 h
20°C to 24°C 30 min 12 h
25°C to 34°C 12 min 9h
35°C to 39°C 8 min 6h
+40°C 8 min 4h
1)
for wet base material the curing time must be doubled
273
WIT-PE 1000 WITH REBAR
Installation parameters
hmin
h0
hef
WIT-PE 1000 R
d0
274
A) Bore hole drilling
WIT-PE 1000 R
a minimum
of noticeable dust. If theofbore
twohole
times until return
ground air stream
is not reached is free of shall be
an extension
In case of aborted drill hole, the drill hole shall be filled with morta
used. noticeable dust. If the bore hole ground is not reached an
Attention! Standing water in the bore hole must be removed
43677 extension shallbefore
be used.cleaning.
2b. Check brush diameter. Brush the hole with an appropriate sized wire brush >
2b.
db,min be Checkofbrush
a minimum diameter.
two times. Brushhole
theground
If the cleaning.
bore hole with anreached
is not appropriate
with the
B1) Bore hole
Attention! cleaning
Standing water in the bore hole must removed before
sized
brush, a brush wire brush
extension shall >bedused.
b,min
a minimum of two times. If the
bore hole ground is not reached with the brush, a brush
B1) Bore
CAC: holeforcleaning
Cleaning dry, wet and water-filled bore 2c.
holesFinally
with all
blowdiameter
extension in non-cracked
shall
the hole clean be used.
again and cracked
with compressed air (min.concrete
6 bar) a minimum of
two2c.
times until return air stream is free of noticeable dust. If the bore hole ground
11623390 Finally blow the hole clean again with compressed air
CAC: Cleaning for dry, wet and water-filled bore holes iswith
not reached,
2a. an extension
all Starting
diameter from
(min. 6 bar)
shall
a the
be used.
in non-cracked
bottom
minimum
and cracked
or back
of two times of
concrete
untilthe boreairhole,
return streamblow the hole
compressed air (min. 6 bar) a minimum of two
is free of noticeable dust. If the bore hole ground is not times until return a
After cleaning, the bore hole has to be protected against re-contamination in an appropriate way until dispensing
2a.
the mortar in the bore hole. If necessary, the cleaning has to
reached,
Starting
of be an
from
noticeable extension
the
repeateddust.bottom shall
orbe
If thebefore
directly
used.
back of the
bore dispensing
hole groundbore hole,
not blow
is mortar.
the In-the an
reached holeexte
cl
flowing water must no contaminate the bore hole again. used. compressed air (min. 6 bar) a minimum of two times until return air
of noticeable dust. If the bore hole ground is not reached an exten
B2) Bore hole cleaning
2b. used.Check brush diameter. Brush the hole with an appropriate sized
db,min a minimum of two times. If the bore hole ground is not reac
Check
brush,brush
a brush2b.
diameter. Brush
extension thebehole
shall with an appropriate sized w
used.
db,min a minimum of two times. If the bore hole ground is not reache
2c. brush,
Finallyablow
brushthe
extension shallagain
hole clean be used.
with compressed air (min. 6 ba
two times until return air stream is free of noticeable dust. If the b
11623390 2c. Finally blow the hole
is not reached, clean again
an extension shallwith
be compressed
used. air (min. 6 bar)
two times until return air stream is free of noticeable dust. If the bor
11623390 is not reached, an extension shall
After cleaning, the bore hole has to be protected against re-contamination in be
anused.
appropriate way until
the mortar in the bore hole. If necessary, the cleaning has to be repeated directly before dispensing the
After cleaning,
flowing the bore
water must hole has to be
no contaminate theprotected
bore holeagainst
again.re-contamination in an appropriate way until d
the mortar in the bore hole. If necessary, the cleaning has to be repeated directly before dispensing
275the m
flowing water must no contaminate the bore hole again.
B2) Bore hole cleaning
Rinsing again with water until clear w
the mortar in the bore hole. If necessary, the cleaning has to be repeated directl
Check the brush diameter. Brush the
used
2c. Rinsing again with water until clear water comes out.
2a.
2b.
2c.
2a.
2b.
2c.
3a.
2b. Check the brush diameter. Brush the hole with an appropriate sized wire brush >
db,min a minimum of two times in a twisting motion. If the bore hole ground is not
B2) Bore hole cleaning reached with the brush, a brush extension must be used.
2a.
11623390
a twisting motion. If the bore hole ground is not reached
43708
with the brush, a brush extension must be used.
43674 (change to brush)
2c. Rinsing again with water until clear water comes out.
2a. Starting from the bottom or back of the bore hole, blow the hole cle
43674
Attention! Standing (change
water to brush)
in the bore hole must be removed compressed air (min. 6
before proceeding tobar) a minimum of two times until return air
cleaning.
2a. from Starting from the bottom or bore
backhole,
of theblow
borethehole,
of noticeable dust. If the bore hole ground is not reached an extens
Starting the bottom or back of the hole clean with 2a.
used
compressed blow the hole
air (min. clean
6 bar) with compressed
a minimum of two timesairuntil
(min. 6 bar)
return air stream is free
Attention! Standing water in the bore hole must be removed
a minimum before
of two proceeding
times until return air to cleaning.
stream is
of noticeable dust. If the bore hole ground is not reached an extensionfree of shall be
2a.
2b.
used Check noticeable
Starting fromdust.
brush If the bore
the bottom
diameter. orhole
Brush theground
back isbore
of thewith
hole notan reached
hole, an thesized
blow
appropriate hole wir
cle
extension shall be used.
dcompressed air (min.
b,min a minimum 6 bar)
of two times.a Ifminimum
the boreofhole
twoground
times until return
is not air
reache
2b. Check brush
2b. brush,
of diameter.
Check brushBrush
noticeable
a brush dust. the
diameter. hole
If the
extension withthe
Brush
bore
shall an appropriate
hole
hole
be with an is
ground
used. sized
notwire
appropriatebrush >an extens
reached
db,min a minimum
sized of two
wire times.
brush > If then bore
d a hole ground
minimum of twois times.
not reached
If the with the
used b,mi
brush, a brush
boreextension shallisbenot
hole ground used.
reached with the brush, a brush
2c. Finally blowshall
extension the behole clean again with compressed air (min. 6 bar)
used.
2c.
2b. Check
Finally two
blowtimes
brush
until
the hole
diameter.
return
clean againair
Brush
stream
with
theishole
compressedfreeairwith
of(min.an6 appropriate
noticeable dust. Ifsized
bar) a minimum the wir
of bore
11623390 two d
2c.timesb,min a
Finally
until minimum
blow
return airthe of
stream two
holeis times.
clean
free If
again
of the
with
noticeable
is not reached, an extension shall be used. bore hole
compressed
dust. If the ground
air
bore is
hole not
groundreache
11623390 brush,
(min.aan
is not reached, 6brush
bar) aextension
shall beofshall
minimum
extension be used.
two times
used. until return air stream
is free of noticeable dust. If the bore hole ground is not
After cleaning, the bore hole has to be protected against re-contamination
reached, an extension
After cleaning, the bore hole has to be protected against re-contamination shall
in an bein an appropriate
used.
appropriate
way until di
way until dispensing
the mortar in in
the 2c. Finally blow the repeated
hole clean again with before
compressed air (min. 6 bar)
the mortar thebore
bore hole.
hole. IfIfnecessary,
necessary,the the cleaning
cleaning has tohas to be
be repeated directly
directly before dispensing dispensing
the mortar. In- the m
After cleaning, the bore hole has to be protected against re-contamination in an air
two times until return appropriate way
stream is free until dis- dust. If the bore
of noticeable
flowing water
flowing water must
mustno contaminate
no contaminate thethe bore
bore holehole
again.again.
pensing the mortar in 11623390
the bore hole. If necessary, the cleaning hasreached,
to be repeated directly
shallbefore dispensing
WIT-PE 1000 R
43708
43708
43708 3b.
3b. Prior
Priorto to
inserting
insertingthe
thereinforcing barinto
reinforcing bar intothethefilled
filled bore hole, the pos
bore
hole, the position
embedment depth of the be
shall embedment
marked depth shall tape)
(e.g. with be on the reinforcin
marked (e.g. with tape) on the reinforcing bar. After that,
that,insert
insert
thethe
barbar in empty
in the the empty hole
hole to to hole
verify verifyand hole and depth lv. The
depth
should
lv. The anchor should be free of dirt, grease, oil and material.
be free of dirt, grease, oil and other foreign
other foreign material.
11623372
3c. Prior to dispensing into the bore hole, squeeze out separately the m
shows a consistent grey or red color (minimum of three full strokes)
non-uniformly mixed adhesive components.
276
grease, oil and other foreign material.
1013039
D) Filling the bore hole
3c. Prior to dispensing into the bore hole, squeeze out separately
3c. Prior to dispensing into the bore hole, squeeze out separately the mortar u
1013039 shows a consistent grey or red color (minimum of three full str
shows a consistent grey or red color (minimum of three full strokes) and d
non-uniformly
non-uniformly mixed mixed
adhesive adhesive components.
components.
3c. Prior to dispensing into the bore hole, squeeze out separately the mortar u
shows a consistent grey or red color (minimum of three full strokes) and d
3c.3c.non-uniformly
PriorPrior to dispensing
to dispensing into
mixeduntil
into
thethe
adhesive
bore
bore hole,squeeze
hole,
components.
squeezeout
outseparately
separa- the morta
shows telya the mortar
consistent greyit or
shows
red acolor
consistent grey or
(minimum of red color
three full strokes) and
(minimum of three full strokes) and discard non-uniformly
1251356
1013039
non-uniformly mixed adhesive
mixed adhesive components. components.
1251356
1251356
D) Filling the bore hole
D) Filling the bore hole 4. Starting from the bottom or back of the cleaned bore hole, fil
1251356
1251356 adhesive until the level mark at the mixer extension is visible a
4. Starting hole. from the bottom or back of the cleaned bore hole, fill the hole up
For embedment larger than 190 mm, an extension nozz
D)
D) Filling
Filling
D) Filling the hole
the bore bore hole approximately two-thirds with adhesive. Slowly withdraw the static mixing
4.4. as
Slowly
Starting from
withdraw
the bottom
the static
or or
back
mixing nozzle.bore Using a fill piston plugw
theStarting
hole fillsfromto avoid
the creating
bottom airofpockets.
back thethecleaned
of borehole,
If the bottom
cleaned or back
hole, theofhole
the
4. hole the
Starting
adhesive mortar
from
isfillnot untilthe
reached, helps
thebottom
level
an tooravoid
markbackat
appropriate creating
of
the the
mixer
extension air
cleaned pockets.
bore
extension
nozzle hole,
is fill
visible
must be the
at hole
the
used. top
Obseupo
the hole with adhesive until the level mark at the mixer
approximately
hole.For Foroverhead
extension
gel-/working embedmenttwo-thirds
and
is visible
times. with
larger
at the adhesive.
horizontal
thanof 190
top Slowly
theinstallation
mm,For
hole. withdraw
and bore
an embedment
extension the static
nozzleholes mixing
deep
shall be
as thepiston
Slowly hole
larger fills
than
plug
withdraw to190
avoid
themm,
and creating
the
static airnozzle.
anappropriate
extension
mixing pockets.
nozzle
mixerIf the
shall
Using bottom
abe used. or
extension
piston back
must
plug of use
be
during thein
11623387 hole isSlowly withdrawan
not reached, theappropriate
static mixingextension
nozzle. Using
nozzlea piston
must be used. Obse
working
the mortar helps times to avoid creating air pockets.
plug during injection of the mortar helps to avoid creating
gel-/working times.
3b.
For overhead
air pockets.and horizontal installation and bore holes deeper than 2
3c.
11623387
Piston
pistonplugs
plug
For and
and mixer
overhead the nozzle extensions
andappropriate
horizontal shall
andbebore
mixer extension
installation used
must for
be the
holes following
used. Observe
11623387
applications:
deeper
working than 240 mm, a piston plug and the appropriate
times
grease, oil and other foreign material.
the empty hole to verify hole and depth lv. The anchor should be free of dirt,
embedment depth shall be marked on the anchor rod. After that, insert the rod in
non-uniformly mixed adhesive components.
shows a consistent grey or red color (minimum of three full strokes) and discard
Prior to dispensing into the bore hole, squeeze out separately the mortar until it
Prior to inserting the anchor rod into the filled bore hole, the position of the
11623387 mixer extension must be used. Observe the gel-/working
Piston•times.
plugsHorizontal
and mixerassembly
nozzle extensions
(horizontalshall be used
direction) andforground
the following
erection
applications:(vertical downwards direction): Drill bit-Ø d0 ≥ 18 mm and
embedment depth hef > 250 mm
11623386 •• Horizontal assembly
Overhead assembly (vertical
(horizontal direction)
upwards and ground
direction): erection
Drill bit-Ø d0
(vertical downwards direction): Drill bit-Ø d0 ≥ 18 mm and
D) Setting the rebar mm
11623386 embedment depth hef > 250 mm
11623386 5a. Push
• the reinforcing
Overhead bar(vertical
assembly into theupwards
bore hole while turning
direction): sligh
Drill bit-Ø d0
E) Setting the rebar
D) Setting the rebar distribution
mm of the adhesive until the embedment depth is reac
WIT-PE 1000 R
D) Setting the rebar 5a. 5a. Pushbe thefree
Push reinforcing
the of dirt, bar intointo
grease,
reinforcing bar the
oilthebore hole
orbore
other
hole while
whileturning
foreign slightly to ensur
material.
turning
11623386 slightly to
distribution of ensure positiveuntil
the adhesive distribution of the adhesive
the embedment depthuntil
is reached. The b
the embedment
be free depth isorreached. The barmaterial.
should be free
5a. Push the of dirt, grease,
anchor rod intooil
the boreother foreign
hole while turning slightly to ensure pos
of dirt, grease, oil or other foreign material.
D) Setting the rebar distribution of the adhesive until the embedment depth is reached. The rod
be free of dirt, grease, oil or other foreign material.
5a. Push the anchor rod into the bore hole while turning slightly to ensure pos
11623371
5b. distribution of the adhesive
After inserting the anchor,untilthe
theannular
embedmentgap depth
between is reached. The rod
the anchor rod
11623371
5b.beconcrete,
5b.
free
Beofsure
dirt,inthat
grease,
case oil
a or
theofbar isother
push foreign
inserted
through material.
ininstallation,
the bore hole until theto embe
in addition
Be sure that the bar is inserted in the bore hole until the
the fi
5b. the
sure concrete
Becompletely
that the
embedment filled
barsurface
mark with and
atmortar.
isisinserted
the inthat
Be
concrete excess
thesure
bore that
surface mortar
holetheuntil
and is visible
anchor
thatthe rod isatinserted
embedment themato
11623376 thehole untilrequirements
excess
concrete
these the
mortarembedment
surfaceis visible
and arethatmark
at the top
excess
not is at
of the concrete
the
mortar
maintained, hole. If these
is visible surface
at the top
the application and that
ofhas he
the to
these requirements
is horizontal
visible
requirements are
at theandtop not
are maintained,
ofnot If the
themaintained, application
hole.installation,
thesetherequirementshas tohas
application aretonot
bemainta
renew
overhead
be renewed. For horizontal and overhead installation, fix
fix embedded part (e.g
horizontal
application and part
embeddedhas
overhead
to(e.g. installation,
be with
renewed.
wedges). Forfixoverhead
embedded part (e.g. with
installation, wed
fix embe
11623376
(e.g. with wedges).
11623375
11623370
11623370
5c. Observe gelling time t . Attend that the gelling time can
5c. Allow the adhesive to cure gel to the specified time prior to applying a
5c.5c. Observe
Observe gelling
vary according
torque. gelling time
to tthe
time base tgelmaterial
. Attendtemperature.
that the gelling
Do not time can vary
gel. Attend that the gelling time can vary accordin
move Do not the
or load movebaror load
until full the anchor
curing until
time tcure hasit elapsed.
is fully cured.
base material temperature. Do not move or load the load
base material temperature. Do not move or the full
bar until barcuring
until
has elapsed.
has elapsed.
34372275
34372275
34372275 277
WIT-PE 1000 WITH REBAR
Filling Quantity
Rebar size Ø8 Ø 10 Ø 12 Ø 14 Ø 16 Ø 20 Ø 24 Ø 25 Ø 28 Ø 32
Nominal drill hole d0 [mm]
12 14 16 18 20 25 32 32 35 40
diameter
Drill depth h 0 / h1 [mm] = lv
Filling volume per
10mm embedment [ml] 0.81 1.01 1.21 1.43 1.66 2.59 4.85 4.47 5.07 6.62
depth
Assumed waste of 15 % included.
WIT-PE 1000 R
278
279
WIT-PE 1000 R