org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ®
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2022 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 29
ESR-4757 | Most Widely Accepted and Trusted Page 2 of 29
3.2 Materials: 3.2.4.3 Ductility: In accordance with ACI 318-19 and ACI
318-14 2.3 or ACI 318-11 D.1, as applicable, in order for a
3.2.1 Würth WIT-PE 1000 Adhesive: Würth WIT-PE 1000
steel anchor element to be considered ductile, the tested
adhesive is an injectable two-component epoxy adhesive.
elongation must be at least 14 percent and reduction of area
The two components are kept separate by means of a
must be at least 30 percent. Steel elements with a tested
labeled dual-cylinder cartridge. The two components
elongation less than 14 percent or a reduction of area less
combine and react when dispensed through a static mixing
than 30 percent, or both, are considered brittle.
nozzle, supplied by Würth, which is attached to the
Specifications and physical properties of various steel
cartridge. Würth WIT-PE 1000 is available in
materials are provided for threaded rods in Table 2 and for
14.8-ounce (440 mL), 20-ounce (585 mL) and 47-ounce
reinforcing bars in Table 3 of this report. Where values are
(1400 mL) cartridges. Each cartridge label is marked with
nonconforming or unstated, the steel must be considered
the adhesive expiration date. The shelf life, as indicated by
brittle.
the expiration date, applies to an unopened cartridge stored
in a dry, dark, and cool environment, in accordance with the 3.2.4.4 Steel Reinforcing Bars for use in Post-Installed
MPII, as illustrated in Figure 5 of this report. Reinforcing Bar Connections: Steel reinforcing bars used
in post-installed reinforcing bar connections are deformed
3.2.2 Hole Cleaning Equipment: reinforcing bars (rebar), as depicted in Figure 4. Tables 20
3.2.2.1 Standard Equipment: Hole cleaning equipment is and 21 summarize reinforcing bar size ranges. The
comprised of steel wire brushes supplied by Adolf Würth embedded portions of reinforcing bars must be straight, and
GmbH & Co. KG, and air blowers which are shown in Figure free of mill scale, rust and other coatings that may impair the
1 of this report. The Würth dust extraction system shown in bond with the adhesive. Reinforcing bars must not be bent
Figure 1 of this report removes dust with a HEPA dust after installation except as set forth in ACI 318-19 Section
extractor during the hole drilling and cleaning operation. 26.6.3.2 (b), ACI 318-14 Section 26.6.3.1 (b) or ACI 318-11
Section 7.3.2, as applicable, with the additional condition
3.2.2.2 Würth Hollow Drill Bit System: The Würth hollow that the bars must be bent cold, and heating of reinforcing
drill bit system shown in Figure 1 is comprised of Heller bars to facilitate field bending is not permitted.
Duster Expert Hollow drill bit with carbide tips conforming to
ANSI B212.15 attached to a class M vacuum that has a 3.3 Concrete:
minimum air flow rating of 90cfm (150m3/h, 42I/s). The Normal-weight concrete must comply with Sections 1903
vacuum dust extractor system removes the drilling dust and 1905 of the IBC. The specified compressive strength of
during the drilling operation, eliminating the need for the concrete must be from 2,500 psi to 8,500 psi
additional hole cleaning. (17.2 MPa to 58.6 MPa) [minimum of 24 MPa is required
under ADIBC Appendix L, Section 5.1.1].
3.2.3 Dispensers: Würth WIT-PE 1000 adhesive must be
dispensed with manual dispensers, pneumatic dispensers, 4.0 DESIGN AND INSTALLATION
or electric powered dispensers supplied by Adolf Würth 4.1 Strength Design:
GmbH & Co. KG.
4.1.1 General: The design strength of anchors under the
3.2.4 Steel Anchor Elements: 2021 IBC, as well as the 2021 IRC must be determined in
3.2.4.1 Threaded Steel Rods for use in Post-Installed accordance with ACI 318-19 and this report. The design
Anchor Applications: Threaded steel rods must be clean strength of anchors under the 2018 and 2015 IBC, as well
and continuously threaded (all-thread) in diameters as the 2018 and 2015 IRC, must be determined in
described in Tables 4 and 12 and Figure 5 of this report. accordance with ACI 318-14 and this report. The design
Specifications for grades of threaded rod, including the strength of anchors under the 2012 and 2009 IBC, as well
mechanical properties, and corresponding nuts and as the 2012 and 2009 IRC, must be determined in
washers, are included in Table 2 of this report. Carbon steel accordance with ACI 318-11 and this report.
threaded rods must be furnished with a minimum The strength design of anchors must comply with ACI 318-
0.0002-inch-thick (0.005 mm) zinc electroplated coating 19 17.5.1.2 or ACI 318-14 17.3.1 or 318-11 D.4.1, as
complying with ASTM B633 SC1 or a minimum applicable, except as required in ACI 318-19 17.10 or ACI
0.0021-inch-thick (0.053 mm) mechanically deposited zinc 318-14 17.2.3 or ACI 318-11 D.3.3, as applicable.
coating complying with ASTM B695, Class 55. The stainless
Design parameters are provided in Tables 4 through 21 of
steel threaded rods must comply with Table 2 of this report.
this report. Strength reduction factors, φ, as given in ACI
Steel grades and types of material (carbon, stainless) for the
318-19 17.5.3, ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as
washers and nuts must match the threaded rods. Threaded
applicable, must be used for load combinations calculated
steel rods must be clean, straight and free of indentations or
in accordance with Section 1605.1 of the 2021 IBC or
other defects along their length. The embedded end may be
Section 1605.2 of the 2018, 2015, 2012 and 2009 IBC, ACI
flat cut or cut on the bias to a chisel point.
318-19 and ACI 318-14 5.3 or ACI 318-11 9.2, as
3.2.4.2 Steel Reinforcing Bars for use in Post-Installed applicable.
Anchor Applications: Steel reinforcing bars must be
Strength reduction factors, φ, as given in ACI 318-11 D.4.4
deformed reinforcing bars as described in Table 3 of this
must be used for load combinations calculated in
report. Tables 8 and 16 and Figure 5 summarize reinforcing
accordance with ACI 318-11 Appendix C.
bar size ranges. The embedded portions of reinforcing bars
must be clean, straight, and free of mill scale, rust, mud, oil 4.1.2 Static Steel Strength in Tension: The nominal
and other coatings (other than zinc) that may impair the static steel strength of a single anchor in tension, Nsa, in
bond with the adhesive. Reinforcing bars must not be bent accordance with ACI 318-19 17.6.1.2, ACI 318-14 17.4.1.2
after installation except as set forth in ACI 318-19 Section or ACI 318-11 D.5.1.2, as applicable, and the associated
26.6.3.2 (b), ACI 318-14 Section 26.6.3.1 (b) or ACI 318-11 strength reduction factors, φ, in accordance with ACI 318-19
Section 7.3.2, as applicable, with the additional condition 17.5.3, ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as
that the bars must be bent cold, and heating of reinforcing applicable, are provided in Tables 4, 8, 12 and 16 of this
bars to facilitate field bending is not permitted. report for the corresponding anchor steel.
ESR-4757 | Most Widely Accepted and Trusted Page 3 of 29
4.1.3 Static Concrete Breakout Strength in Tension: made for increased concrete compressive strength as noted
The nominal static concrete breakout strength of a single in the footnotes to the corresponding tables and this section.
anchor or group of anchors in tension, Ncb or Ncbg, must be Bond strengths must also be multiplied by the factor Κwf
calculated in accordance with ACI 318-19 17.6.2, ACI 318- where holes are water-filled at the time of anchor installation
14 17.4.2 or ACI 318-11 D.5.2, as applicable, with the (flooded).
following addition: The bond strength values in Tables 6, 7, 10, 11, 14, 15
The basic concrete breakout strength of a single anchor in and 18 of this report correspond to concrete compressive
tension, Nb, must be calculated in accordance with ACI 318- strength f′c equal to 2,500 psi (17.2 MPa). For concrete
19 17.6.2.2, ACI 318-14 17.4.2.2 or ACI 318-11 D.5.2.2, as compressive strength, f′c between 2,500 psi and 8,000 psi
applicable, using the values of kc,cr and kc,uncr as provided in (17.2 MPa and 55 MPa), the tabulated characteristic bond
Tables 5, 9, 13 and 17 of this report. Where analysis strength may be increased by a factor of (f’c / 2,500)0.10 for
indicates no cracking in accordance with ACI 318-19 hammer drill (or Würth Hollow drill bit). For diamond core
17.6.2.5, ACI 318-14 17.4.2.6 or ACI 318-11 D.5.2.6, as drilled, the tabulated characteristic bond strength may be
applicable, Nb must be calculated using kc,uncr and Ψc,N = increased by a factor of (f’c / 2,500)0.20 [For SI:
1.0. For anchors in lightweight concrete see ACI 318-19 (f'c / 17.2)0.10 or (f'c / 17.2)0.20 respectively] [minimum of
17.2.4, ACI 318-14 17.2.6 or ACI 318-11 D.3.6, as 24 MPa is required under ADIBC Appendix L, Section 5.1.1].
applicable. The value of f′c used for calculation must be Where applicable, the modified bond strength values must
limited to 8,000 psi (55 MPa) in accordance with ACI 318- be used in lieu of τk,cr and τk,uncr in ACI 318-19 Equations
19 17.3.1, ACI 318-14 17.2.7 or ACI 318-11 D.3.7, as (17.6.5.1.2b) and (17.6.5.2.1) or ACI 318-14 Equations
applicable. Additional information for the determination of (17.4.5.1d) and (17.4.5.2) or ACI 318-11 Equations (D-21)
nominal bond strength in tension is given in Section 4.1.4 of and (D-22), as applicable.
this report. The resulting nominal bond strength must be multiplied by
4.1.4 Static Bond Strength in Tension: The nominal the associated strength reduction factor φd, φws or Κwf ·φwf,
static bond strength of a single adhesive anchor or as applicable.
group of adhesive anchors in tension, Na or Nag, must 4.1.5 Static Steel Strength in Shear: The nominal static
be calculated in accordance with ACI 318-19 17.6.5, ACI steel strength of a single anchor in shear as governed by
318-14 17.4.5 or ACI 318-11 D.5.5, as applicable. the steel, Vsa, in accordance with ACI 318-19 17.7.1.2, ACI
Bond strength values (τk,cr, τk,uncr) are a function of 318-14 17.5.1.2 or ACI 318-11 D.6.1.2, as applicable, and
concrete compressive strength, concrete state (cracked, the strength reduction factor, φ, in accordance with ACI 318-
uncracked), installation conditions (dry concrete, water- 19 17.5.3, ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as
saturated concrete, water-filled holes), hole drilling method applicable, are given in Tables 4, 8, 12 and 16 of this report
(hammer drilling, including Würth hollow drill bit, diamond for the corresponding anchor steel.
core drilling) and concrete substrate temperature range. 4.1.6 Static Concrete Breakout Strength in Shear: The
Special inspection level is qualified as periodic for all nominal static concrete breakout strength of a single anchor
anchors except as described in Section 4.4 of this report or group of anchors in shear, Vcb or Vcbg, must be calculated
(the selection of continuous special inspection level does in accordance with ACI 318-19 17.7.2, ACI 318-14 17.5.2 or
not provide an increase in anchor category or associated ACI 318-11 D.6.2, as applicable, based on information given
strength reduction factor for design). The following table in Tables 5, 9, 13 and 17 in this report.
summarizes the requirements:
The basic concrete breakout strength of a single anchor in
shear, Vb, must be calculated in accordance with ACI 318-
COMPRESSIVE
STRENGTH
STRENGTH
DRILLING /
CLEAING
METHOD
ASSOCIATED
STATE
STRENGTH
INSTALLATION 16 for the corresponding anchor steel in lieu of da (2021,
REDUCTION
CONDITIONS
FACTOR 2018, 2015, 2012 and 2009 IBC). In addition, hef must be
substituted for ℓe. In no case shall ℓe exceed 8d. The value of
f'c shall be limited to a maximum of 8,000 psi (55 MPa) in
Dry concrete φd
accordance with ACI 318-19 17.3.1, ACI 318-14 17.2.7 or
Hammer drill (or Würth Hollow
Water-saturated
Cracked
(flooded)
anchors in shear, Vcp or Vcpg, shall be calculated in
Dry concrete φd accordance with ACI 318-19 17.7.3, ACI 318-14 17.5.3 or
Uncracked
Dry concrete
4.1.9 Minimum Member Thickness hmin, Anchor
Uncracked
For anchors that will be torqued during installation, the requirements of ACI 318-11 D.4.1.1, the anchor design
maximum torque, Tmax, must be reduced for edge distances tensile strength shall be calculated from ACI 318-11
less than the values given in Tables 5 and 13, as applicable. D.3.3.4.4.
Tmax is subject to the edge distance, cmin, and anchor
The following exceptions apply to ACI 318-11 D.3.3.5.2:
spacing, smin, and shall comply with the following
requirements: 1. For the calculation of the in-plane shear strength of
anchor bolts attaching wood sill plates of bearing or
INSTALLATION TORQUE SUBJECT TO EDGE DISTANCE
non-bearing walls of light-frame wood structures to
NOMINAL MINIMUM MINIMUM MAXIMUM foundations or foundation stem walls, the in-plane shear
ANCHOR EDGE ANCHOR TORQUE, strength in accordance with ACI 318-11 D.6.2 and D.6.3
SIZE, DISTANCE, SPACING, Tmax need not be computed and ACI 318-11 D.3.3.5.3 need not
D cmin smin apply provided all of the following are satisfied:
5
/8 in. to 1 in. 1.1. The allowable in-plane shear strength of the
1.75 in. (45 mm) anchor is determined in accordance with AF&PA NDS
M16 to M27
5d 0.45·Tmax
Table 11E for lateral design values parallel to grain.
11/4 in. 1.2. The maximum anchor nominal diameter is 5/8 inch
2.75 in. (70 mm)
M30 (16 mm).
For values of Tmax, see Figure 5 of this report. 1.3. Anchor bolts are embedded into concrete a
minimum of 7 inches (178 mm).
4.1.10 Critical Edge Distance cac and ψcp,Na: The
modification factor, ψcp,Na, must be determined in 1.4. Anchor bolts are located a minimum of 13/4 inches
accordance with ACI 318-19 17.6.5.5, ACI 318-14 17.4.5.5 (45 mm) from the edge of the concrete parallel to the
or ACI 318-11 D.5.5.5, as applicable, except as noted length of the wood sill plate.
below: 1.5. Anchor bolts are located a minimum of 15 anchor
For all cases where cNa/cac<1.0, ψcp,Na determined from diameters from the edge of the concrete perpendicular
ACI 318-19 Eq. 17.6.5.5.1b, ACI 318-14 Eq. 17.4.5.5b or to the length of the wood sill plate.
ACI 318-11 Eq. D-27, as applicable, need not be taken less 1.6. The sill plate is 2-inch or 3-inch nominal thickness.
than cNa/cac. For all other cases, ψcp,Na shall be taken as 1.0.
2. For the calculation of the in-plane shear strength of
The critical edge distance, cac must be calculated anchor bolts attaching cold-formed steel track of bearing or
according to Eq. 17.6.5.5.1c for ACI 318-19, Eq. 17.4.5.5c non-bearing walls of light-frame construction to foundations
for ACI 318-14 or Eq. D-27a for ACI 318-11, in lieu of ACI or foundation stem walls, the in-plane shear strength in
318-19 17.9.5, ACI 318-14 17.7.6 or ACI 318-11 D.8.6, as accordance with ACI 318-11 D.6.2 and D.6.3 need not be
applicable. computed and ACI 318-11 D.3.3.5.3 need not apply
τ 0.4 provided all of the following are satisfied:
h
cac =hef ∙ � k, uncr� ∙ �3.1 - 0.7 �
1160 hef 2.1. The maximum anchor nominal diameter is 5/8 inch
(Eq. 17.6.5.5.1c for ACI 318-19 or Eq. 17.4.5.5c for ACI (16 mm).
318-14 or Eq. D-27a for ACI 318-11) 2.2. Anchors are embedded into concrete a minimum
where of 7 inches (178 mm).
h 2.3. Anchors are located a minimum of 13/4 inches
� � need not be taken as larger than 2.4; and (45 mm) from the edge of the concrete parallel to the
hef
length of the track.
τk,uncr = the characteristic bond strength stated in the tables
2.4. Anchors are located a minimum of 15 anchor
of this report whereby τk,uncr need not be taken as larger
diameters from the edge of the concrete perpendicular
than:
to the length of the track.
𝑘𝑘𝑢𝑢𝑢𝑢𝑢𝑢𝑢𝑢�ℎ𝑒𝑒𝑒𝑒𝑓𝑓𝑐𝑐′ 2.5. The track is 33 to 68 mil designation thickness.
𝜏𝜏𝑘𝑘,𝑢𝑢𝑢𝑢𝑢𝑢𝑢𝑢 = Eq. (4-1)
𝜋𝜋∙𝑑𝑑𝑎𝑎
Allowable in-plane shear strength of exempt anchors,
4.1.11 Requirements for Seismic Design Categories C, parallel to the edge of concrete, shall be permitted to be
D, E and F: In structures assigned to Seismic Design determined in accordance with AISI S100 Section
Category C, D, E or F under the IBC or IRC, anchors must E3.3.1.
be designed in accordance with ACI 318-19 17.10, ACI 318-
3. In light-frame construction, bearing or nonbearing walls,
14 17.2.3 or ACI 318-11 D.3.3, as applicable.
shear strength of concrete anchors less than or equal to 1
The nominal steel shear strength, Vsa, must be adjusted inch [25 mm] in diameter attaching a sill plate or track to
by αV,seis as given in Tables 4, 8, 12 and 16 for the foundation or foundation stem wall need not satisfy ACI 318-
corresponding anchor steel. The nominal bond strength τκ,cr 11 D.3.3.5.3(a) through (c) when the design strength of the
must be adjusted by αN,seis as given in Tables 6 and 14 for anchors is determined in accordance with ACI 318-11
threaded rods, and Tables 10 and 18 for reinforcing bars. D.6.2.1(c).
As an exception to ACI 318-11 Section D.3.3.4.2: 4.2 Strength Design of Post-Installed Reinforcing
Anchors designed to resist wall out-of-plane forces with Bars:
design strengths equal to or greater than the force 4.2.1 General: The design of straight post-installed
determined in accordance with ASCE 7 Equation 12.11-1 or deformed reinforcing bars must be determined in
12.14-10 shall be deemed to satisfy Section ACI 318-11 accordance with ACI 318 rules for cast-in-place reinforcing
D.3.3.4.3(d). bar development and splices and this report. Examples of
Under ACI 318-11 D.3.3.4.3(d), in lieu of requiring the typical applications for the use of post-installed reinforcing
anchor design tensile strength to satisfy the tensile strength bars are illustrated in Figure 4 of this report.
ESR-4757 | Most Widely Accepted and Trusted Page 5 of 29
5/
4.2.2 Determination of bar development length ld: and M16 through 11/4-inch and M30 diameter
8-inch
Values of ld must be determined in accordance with the ACI threaded steel rods, and No. 5 and ø16 through No. 10 and
318 development and splice length requirements for straight ø32, steel reinforcing bars, installed in the specified hole
cast-in-place reinforcing bars. diameter, and attached to the mixing nozzle and extension
Exceptions: tube supplied by Würth as described in Figure 5 in this
report. For installation with the 3/8-inch, 1/2-inch, M8, M10
1. For uncoated and zinc-coated (galvanized) post- and M12 diameter threaded steel rods, and No. 3, No. 4, ø8,
installed reinforcing bars, the factor Ψe shall be taken as ø10 and ø12 steel reinforcing bars only, a piston plug is not
1.0. For all other cases, the requirements in ACI 318-19 required.
Table 25.4.2.5, ACI 318-14 Table 25.4.2.4 or ACI 318-
11 Section 12.2.4 (b) shall apply. Installation of anchors in horizontal or upwardly inclined
orientations shall be fully restrained from movement
2. When using alternate methods to calculate the throughout the specified curing period through the use of
development length (e.g. anchor theory), the applicable temporary wedges, external supports, or other methods.
factors for post-installed anchors generally apply. Where temporary restraint devices are used, their use shall
4.2.3 Minimum Member Thickness, hmin, Minimum not result in impairment of the anchor shear resistance.
Concrete Cover, cc,min, Minimum Concrete Edge 4.4 Special Inspection:
Distance, cb,min, Minimum Spacing, sb,min: For post-
installed reinforcing bars, there is no limit on the minimum Periodic special inspection must be performed where
member thickness. In general, all requirements on concrete required in accordance with Section 1705.1.1 and Table
cover and spacing applicable to straight cast-in-bars 1705.3 of the 2021, 2018, 2015 and 2012 IBC, 1704.4 and
designed in accordance with ACI 318 shall be maintained. 1704.15 of the 2009 IBC and this report. The special
inspector must be on the jobsite initially during anchor
For post-installed reinforcing bars installed at embedment installation to verify the anchor type, adhesive expiration
depths greater than 20d (hef > 20d), the minimum concrete date, anchor dimensions, concrete type, concrete
cover shall be as follows: compressive strength, hole dimensions, hole cleaning
REBAR SIZE MINIMUM CONCRETE procedures, anchor spacing, edge distances, concrete
COVER, cc,min thickness, anchor embedment, tightening torque, and
db ≤ No. 6 1 3/16 in. (30mm) adherence to the manufacturer’s printed installation
instructions.
No. 6 < db ≤ No. 11 1 9 /16 in. (40 mm)
The special inspector must verify the initial installations of
The following requirements apply for minimum concrete each type and size of adhesive anchor by construction
edge and spacing for hef > 20d: personnel on site. Subsequent installations of the same
Required minimum edge distance for post-installed anchor type and size by the same construction personnel
reinforcing bars (measured from the center of the bar): are permitted to be performed in the absence of the special
inspector. Any change in the anchor product being installed
cb,min = do/2 + cc,min
or the personnel performing the installation requires an
Required minimum center-to-center spacing between post- initial inspection. For ongoing installations over an extended
installed bars: period, the special inspector must make regular inspections
sb,min = do + cc,min to confirm correct handling and installation of the product.
Required minimum center-to-center spacing from existing Continuous special inspection of adhesive anchors
(parallel reinforcing: installed in horizontal or upwardly inclined orientations to
resist sustained tension loads must be performed in
sb,min = db/2 (existing reinforcing) + do/2 + cc,min
accordance with ACI 318-19 26.13.3.2e, ACI 318-14
4.2.4 Design Strength in Seismic Design Categories C, 17.8.2.4, 26.7.1(h) and 26.13.3.2 (c) or ACI 318-11 D.9.2.4,
D, E and F: In structures assigned to Seismic Category C, as applicable.
D, E or F under the IBC or IRC, design of straight post-
Under the IBC, additional requirements as set forth in
installed reinforcing bars must consider the provisions of
Sections 1705, 1706 or 1707 must be observed, where
ACI 318-19 or ACI 318-14 Chapter 18 or ACI 318-11
applicable.
Chapter 21, as applicable.
4.3 Installation 5.0 CONDITIONS OF USE
Installation parameters are illustrated in Figure 5 of this The Würth WIT-PE 1000 Adhesive Anchor and Post
report. Installation must be in accordance with ACI 318-19 Installed Reinforcing Bar Connection System described in
26.7.2, ACI 318-14 17.8.1 and 17.8.2 or ACI 318-11 D.9.1 this report complies with, or is a suitable alternative to what
and D.9.2. Anchor locations must comply with this report is specified in, those codes listed in Section 1.0 of this
and the plans and specifications approved by the code report, subject to the following conditions:
official. Installation of the Würth WIT-PE 1000 Adhesive 5.1 Würth WIT-PE 1000 adhesive anchors and post-
Anchor System must conform to the manufacturer’s printed installed reinforcing bars must be installed in
installation instructions included in each unit package as accordance with the manufacturer's printed installation
described in Figure 5 of this report. instructions included with each cartridge and provided
The adhesive anchor system may be installed in in Figure 5 of this report.
downwards, horizontally and upwardly inclined orientation 5.2 Anchors [3/8-, 1/2-, 5/8-, 3/4-, 7/8-, 1-, and 11/4-inch
applications (e.g. overhead). If the bottom or back of the fractional diameter and M8, M10, M12, M16, M20,
bore hole is not reached with the mixing nozzle, a mixer M24, M27 and M30 metric diameter threaded steel
extension tube, supplied by Würth must be attached to the rods, and No. 3 through No. 10 fractional size and ø8,
mixing nozzle as described in Figure 5 of this report. ø10, ø12, ø14, ø16, ø20, ø25, ø28 and ø32 metric
Additionally, horizontal or upwardly inclined orientation steel reinforcing bars] described in this report must be
applications of all bore hole depths, and downwards installed in cracked and uncracked normal-weight
applications with a bore hole depth of more than 10 inch concrete having a specified compressive strength f′c =
(250 mm) are to be installed using piston plugs for the 2,500 psi to 8,500 psi (17.2 MPa to 58.6 MPa)
ESR-4757 | Most Widely Accepted and Trusted Page 6 of 29
[minimum of 24 MPa is required under ADIBC 5.13 Use of zinc-plated carbon steel threaded rods or steel
Appendix L, Section 5.1.1]. reinforcing bars is limited to dry, interior locations.
Adhesive anchors with 3/8-, 1/2-, 5/8-, 3/4-, 7/8-, 1-, 5.14 Use of hot-dipped galvanized carbon steel and
and 11/4-inch fractional diameter, and M8, M10, M12, stainless steel rods is permitted for exterior exposure
M16, M20, M24, M27 and M30 metric diameter or damp environments.
threaded steel rods and No. 3 through No. 10 fractional
size and ø8, ø10, ø12, ø14, ø16, ø20, ø25, ø28 and 5.15 Steel anchoring materials in contact with preservative-
ø32 metric size steel reinforcing bars drilled with treated and fire-retardant-treated wood shall be of zinc-
diamond core bits are used in uncracked normal- coated steel or stainless steel. The minimum coating
weight concrete only, to resist static, wind or weights for zinc-coated steel shall be in accordance
earthquake (IBC Seismic Design Categories A and B with ASTM A153.
only) tension and shear loads. Use is limited to normal- 5.16 Periodic special inspection must be provided in
weight concrete with a specified compressive strength, accordance with Section 4.4 in this report. Continuous
f′c = 2,500 psi to 8,500 psi (17.2 MPa to 58.6 MPa) special inspection for anchors installed in horizontal
[minimum of 24 MPa is required under ADIBC or upwardly inclined orientations to resist sustained
Appendix L, Section 5.1.1]. tension loads must be provided in accordance with
5.3 The values of f′c used for calculation purposes must not Section 4.4 of this report.
exceed 8,000 psi (55 MPa). 5.17 Installation of anchors and post-installed reinforcing
5.4 Anchors and post-installed reinforcing bars must be bars in horizontal or upwardly inclined orientations to
installed in concrete base materials in holes predrilled resist sustained tension loads must be performed by
in accordance with the instructions provided in Figure personnel certified by an applicable certification
5 of this report. program in accordance with ACI 318-19 26.7.2(e), ACI
318-14 17.8.2.2 or 17.8.2.3 or ACI 318-11 D.9.2.2 or
5.5 Loads applied to the anchors must be adjusted in
D.9.2.3, as applicable.
accordance with Section 1605.2 of the IBC for strength
design. 5.18 Würth WIT-PE 1000 adhesive anchors and post-
5.6 In structures assigned to Seismic Design Categories installed reinforcing bars may be used to resist tension
C, D, E, and F under the IBC or IRC, anchor strength and shear forces in floor, wall for overhead installations
must be adjusted in accordance with Section 4.1.11 of into concrete with a temperature between 40°F and
this report. 104°F (5°C and 40°C) for threaded rods and rebar.
5.7 Würth WIT-PE 1000 adhesive anchors are permitted to 5.19 Anchors and post-installed reinforcing bars shall not be
be installed in concrete that is cracked or that may be used for installations where the concrete temperature
expected to crack during the service life of the anchor, can vary from 40°F (5°C) or less to 80°F (27°C) or
subject to the conditions of this report. higher within a 12-hour period. Such applications may
include but are not limited to anchorage of building
5.8 Strength design values are established in accordance façade systems and other applications subject to direct
with Section 4.1 of this report.
sun exposure.
5.9 Minimum anchor spacing and edge distance as well as
minimum member thickness must comply with the 5.20 Würth WIT-PE 1000 adhesive is manufactured in
values described in this report. Willich, Germany, under a quality control program with
inspections by ICC-ES.
5.10 Prior to anchor installation, calculations and details
demonstrating compliance with this report must be 6.0 EVIDENCE SUBMITTED
submitted to the code official. The calculations and
Data in accordance with the ICC-ES Acceptance Criteria for
details must be prepared by a registered design
Post-installed Adhesive Anchors in Concrete (AC308),
professional where required by the statutes of the
dated June 2019, editorially revised March 2021, which
jurisdiction in which the project is to be constructed.
incorporates requirements in ACI 355.4-11 and ACI 355.4-
5.11 Anchors and post-installed reinforcing bars are not 19 for use in cracked and uncracked concrete.
permitted to support fire-resistive construction. Where
not otherwise prohibited by the code, Würth WIT-PE 7.0 IDENTIFICATION
1000 adhesive anchors are permitted for installation in 7.1 Würth WIT-PE 1000 adhesive is identified by
fire-resistive construction provided that at least one of packaging labeled with the manufacturer's name (Adolf
the following conditions is fulfilled: Würth GmbH & Co. KG) and address, anchor name,
• Anchors and post-installed reinforcing bars are used the lot number, the expiration date, and the evaluation
to resist wind or seismic forces only. report number (ESR-4757). Threaded rods, nuts,
washers, and deformed reinforcing bars are standard
• Anchors and post-installed reinforcing bars that
steel anchor elements and must conform to applicable
support gravity load–bearing structural elements are
national or international specifications as set forth in
within a fire-resistive envelope or a fire-resistive
Tables 2 and 3 of this report.
membrane, are protected by approved fire-resistive
materials, or have been evaluated for resistance to 7.2 The report holder’s contact information is as follows:
fire exposure in accordance with recognized
ADOLF WÜRTH GmbH & CO. KG
standards.
REINHOLD-WÜRTH-STRASSE 12-17
• Anchors and post-installed reinforcing bars are used 74653 KÜNZELSAU
to support nonstructural elements. GERMANY
5.12 Since an ICC-ES acceptance criteria for evaluating +49 (7940) 15 0
data to determine the performance of adhesive www.wuerth.de
anchors subjected to fatigue or shock loading is info@wuerth.de
unavailable at this time, the use of these anchors under
such conditions is beyond the scope of this report.
ESR-4757 | Most Widely Accepted and Trusted Page 7 of 29
Concrete Strength - Npn, Nsb, Nsbg, Ncb, Ncbg, Vcb, Vcbg, Vcp, Vcpg Table 5 Table 13
Concrete Strength - Npn, Nsb, Nsbg, Ncb, Ncbg, Vcb, Vcbg, Vcp, Vcpg Table 9 Table 17
2
Bond Strength - Na, Nag Tables 10 and 11 Tables 18 and 19
Determination of development length for post-installed reinforcing
Table 20 Table 21
bar connections
1
Ref. ACI 318-19 17.5.2, ACI 318-14 17.3.1.1 or 318-11 D.4.1.1, as applicable.
2
See Section 4.1.4 of this evaluation report.
MINIMUM SPECIFIED
MINIMUM
YIELD STRENGTH REDUCTION
THREADED ROD SPECIFIED ELONGATION, SPECIFICATION
0.2 futa/fya OF AREA,
SPECIFICATION ULTIMATE MIN. PERCENT11 FOR NUTS12
PERCENT OFFSET, MIN. PERCENT
STRENGTH, futa
fya
ASTM A1932 ASTM A194 /
psi 125,000 105,000
Grade B7 1.19 16 50 A563
(MPa) (862) (724)
all sizes Grade DH
ASTM A563
ASTM F568M6 Class 5.8 psi 72,500 58,000
1.25 10 35 Grade DH
(equivalent to ISO 898-1) (MPa) (500) (400)
DIN 934 (8-A2K)13
ISO 898-17 MPa 500 400 EN ISO 4032
1.25 22 -
Class 5.8 (psi) (72,500) (58,000) Grade 6
ISO 898-17 MPa 800 640 EN ISO 4032
1.25 12 52
Class 8.8 (psi) (116,000) (92,800) Grade 8
ASTM F5938 CW1 psi 100,000 65,000
3 1.54 20 -
/8 to 5/8 in. (316) (MPa) (690) (450) ASTM F594 Alloy
8 Group 1, 2 or 3
STAINLESS STEEL
Würth
FIGURE 1—WÜRTH DUST REMOVAL DRILLING SYSTEM WITH HEPA DUST EXTRACTOR OPTIONS
THREADED ROD
REINFORCING BAR
TABLE 4—STEEL DESIGN INFORMATION FOR U.S. CUSTOMARY UNIT THREADED ROD1
Nominal Rod Diameter (inch)
DESIGN INFORMATION Symbol Units 3/ 1/ 5/ 3/ 7/
8 2 8 4 8 1 11/4
in. 0.375 0.500 0.625 0.750 0.875 1.000 1.250
Threaded rod O.D. d
(mm) (9.5) (12.7) (15.9) (19.1) (22.2) (25.4) (31.8)
in.² 0.0775 0.1419 0.2260 0.3345 0.4617 0.6057 0.9691
Threaded rod effective cross-sectional area Ase
(mm²) (50) (92) (146) (216) (298) (391) (625)
lb 4,495 8,230 13,110 19,400 26,780 35,130 56,210
ASTM A36/F1554,
Nsa
Nominal strength as governed by steel (kN) (20.0) (36.6) (58.3) (86.3) (119.1) (156.3) (250.0)
strength (for a single anchor)
Grade 36
Grade 105
Grade B7
strength (for a single anchor) lb 5,810 10,640 16,950 25,085 34,625 45,425 72,680
Vsa
(kN) (25.9) (47.3) (75.4) (111.6) (154.0) (202.1) (323.3)
Reduction factor for seismic shear αV,seis - 0.73
Strength reduction factor for tension2 φ - 0.75
Strength reduction factor for shear2 φ - 0.65
lb 9,300 17,030 27,120 40,140 55,405 72,685 101,755
Nsa
Nominal strength as governed by steel (kN) (41.4) (76.2) (120.9) (178.8) (246.7) (323.7) (450.0)
ASTM A449
strength (for a single anchor) lb 5,580 10,220 16,270 24,085 33,240 43,610 61,055
Vsa
(kN) (24.8) (45.7) (72.5) (107.3) (148) (194.2) (270.0)
Reduction factor for seismic shear αV,seis - 0.73
Strength reduction factor for tension2 φ - 0.75
Strength reduction factor for shear2 φ - 0.65
lb 5,620 10,290 16,385 24,250 33,470 43,910 70,260
Nsa
Nominal strength as governed by steel (kN) (25) (46) (73) (108) (149) (195.5) (312.5)
ASTM F568M
Nominal strength as governed by steel (kN) (34.5) (63.1) (100.5) (126.5) (174.6) (229.0) (366.4)
strength (for a single anchor)
Stainless
Nsa
Grade B8/B8M2,
Nominal strength as governed by steel (kN) (32.8) (60.3) (95.6) (141.5) (195.2) (256.1) (409.4)
strength (for a single anchor)
Class 2B
TABLE 5—CONCRETE BREAKOUT DESIGN INFORMATION FOR U.S. CUSTOMARY UNIT THREADED ROD1
Nominal Rod Diameter (inch)
DESIGN INFORMATION Symbol Units
3/ ½ 5/ 3/ 7/ 1 11/4
8 8 4 8
TABLE 6—BOND STRENGTH DESIGN INFORMATION FOR U.S. CUSTOMARY UNIT THREADED ROD IN HOLES
DRILLED WITH A HAMMER DRILL AND CARBIDE BIT (OR WÜRTH HOLLOW CARBIDE DRILL BIT)1
Nominal Rod Diameter (inch)
DESIGN INFORMATION Symbol Units
3/ 1/ 5/ 3/ 7/ 1 11/4
8 2 8 4 8
3 3 1 1 1
in. 2 /8 2 /4 3 /8 3 /2 3 /2 4 5
Minimum embedment hef,min
(mm) (60) (70) (79) (89) (89) (102) (127)
in. 71/2 10 121/2 15 171/2 20 25
Maximum embedment hef,max
(mm) (191) (254) (318) (381) (445) (508) (635)
Temperature range
110°F / 176°F2,3
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
Water-filled holes
Strength reduction factor φwf - 0.45
Modification factor for water
Κwf - 1.0
filled holes
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
TABLE 7—BOND STRENGTH DESIGN INFORMATION FOR U.S. CUSTOMARY UNIT THREADED ROD IN HOLES
DRILLED WITH A CORE DRILL AND DIAMOND CORE BIT 1
Nominal Rod Diameter (inch)
DESIGN INFORMATION Symbol Units
3/ 1/ 5/ 3/ 7/ 1 11/4
8 2 8 4 8
3 3 1 1 1
in. 2 /8 2 /4 3 /8 3 /2 3 /2 4 5
Minimum embedment hef,min
(mm) (60) (70) (79) (89) (89) (102) (127)
in. 71/2 10 121/2 15 171/2 20 25
Maximum embedment hef,max
(mm) (191) (254) (318) (381) (445) (508) (635)
Temperature
range C:
176°F2,3
122°F /
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
Water-saturated Anchor category − - 1 2
Concrete Strength reduction factor φws - 0.65 0.55
SPCAC4 cleaning
Anchor category − - 3
Water-filled holes
Strength reduction factor φwf - 0.45
Modification factor for water
Κwf - 1.0 0.99 0.96 0.95 0.93 0.90
filled holes
1
Bond strength values correspond to concrete compressive strength f'c = 2,500 psi [minimum of 24 MPa is required under ADIBC Appendix L, Section 5.1.1]. For
concrete compressive strength, f'c between 2,500 psi and 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c / 2500)0.2 [For SI:
(f'c / 17.2)0.2]. See Section 4.1.4 of this report.
2
Characteristic bond strengths are for sustained loads including dead and live loads. For load combinations consisting of short-term loads only such as wind, bond
strengths may be increased by 4 percent for temperature range C.
3
Short term elevated concrete temperatures are those that occur over brief intervals, e.g. as result of diurnal cycling. Long term concrete temperatures are roughly
constant over significant periods of time.
Temperature range C: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
4
SPCAC: see Figure 5
ESR-4757 | Most Widely Accepted and Trusted Page 13 of 29
TABLE 8—STEEL DESIGN INFORMATION FOR U.S. CUSTOMARY UNIT REINFORCING BARS 1
Nominal Bar Size
DESIGN INFORMATION Symbol Units
No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10
in. 0.375 0.500 0.625 0.750 0.875 1.000 1.125 1.250
Reinforcing bar O.D. d
(mm) (9.5) (12.7) (15.9) (19.1) (22.2) (25.4) (28.6) (31.8)
Reinforcing bar effective cross- in.² 0.110 0.200 0.310 0.440 0.600 0.790 1.000 1.270
Ase
sectional area (mm²) (71) (129) (200) (284) (387) (510) (645) (819)
Nominal strength as lb 9,900 18,000 27,900 39,600 54,000 71,100 90,000 114,300
Nsa
governed by steel (kN) (44.0) (80.1) (124.1) (176.0) (240.0) (316.0) (400.0) (508.0)
ASTM A615, A767, A996
strength (for a single lb 5,940 10,800 16,740 23,760 32,400 42,660 54,000 68,580
anchor) Vsa
(kN) (26.4) (48.0) (74.5) (105.7) (144.1) (189.8) (240.2) (305.0)
Grade 60
steel strength (for a single lb 5,280 9,600 14,880 21,120 28,800 37,920 48,000 60,960
anchor) Vsa
(kN) (23.5) (42.7) (66.2) (93.9) (128.1) (168.7) (213.5) (271.2)
Reduction for seismic
αV,seis ---- 0.76
shear
Strength reduction factor
φ ---- 0.75
φ for tension2
Strength reduction factor
φ ---- 0.65
φ for shear2
lb 6,600 12,000 18,600 26,400
Nominal strength as Nsa
(kN) (29.4) (53.4) (82.7) (117.4)
governed by steel strength
ASTM A615 Grade 40
(for a single anchor) lb 3,960 7,200 11,160 15,840 In accordance with ASTM A615,
Vsa
(kN) (17.6) (32.0) (49.6) (70.5) Grade 40 bars are furnished only in sizes No. 3
through No. 6
Reduction factor for
αV,seis - 0.76
seismic shear
TABLE 9—CONCRETE BREAKOUT DESIGN INFORMATION FOR U.S. CUSTOMARY UNIT REINFORCING BARS1
Nominal Bar Size
DESIGN INFORMATION Symbol Units
No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No.10
Effectiveness factor for cracked in-lb 17
kc,cr
concrete (SI) (7)
Effectiveness factor for in.-lb. 24
kc,uncr
uncracked concrete (SI) (10)
in. 17/8 21/2 31/8 33/4 43/8 5 55/8 61/4
Min. anchor spacing smin
(mm) (48) (64) (79) (95) (111) (127) (143) (159)
in. 15/8 13/4 2 23/8 21/2 23/4 3 31/4
Min. edge spacing4 cmin
(mm) (41) (44) (51) (60) (64) (70) (76) (82)
in. hef + 11/4
Min. member thickness hmin hef + 2d0 3
(mm) (hef + 30)
Critical edge spacing – splitting
cac - See Section 4.1.10 of this report.
(for uncracked concrete)2
Critical anchor spacing –
sac - 2∙cac
splitting
Strength reduction factor for
tension, concrete failure modes, φ - 0.65
Condition B2
Strength reduction factor for
shear, concrete failure modes, φ - 0.70
Condition B2
1
Additional setting information is described in Figure 5, installation instructions.
2
The strength reduction factor applies when the load combinations from the IBC or ACI 318 are used and the requirements of ACI 318-19 17.5.3, ACI 318-14
17.3.3(c) or ACI 318-11 D.4.3(c), as applicable, for Condition B (supplement reinforcement not present) are met. For installations where complying reinforcement
can be verified, the applicable strength reduction factors described in ACI 318-19 17.5.3, ACI 318-14 17.3.3(c) or ACI 318-11 D.4.3(c), as applicable, may be used
for Condition A (supplement reinforcement present). If the load combinations of ACI 318-11 Appendix C are used, the appropriate strength reduction factor must
be determined in accordance with ACI 318-11 D.4.4(c) for Condition B (supplement reinforcement not present).
3
d0 = hole diameter.
4
The edge distances, cmin less than the values given in the table may be reduced subject to the anchor spacing, smin in accordance with Section 4.1.9.
ESR-4757 | Most Widely Accepted and Trusted Page 15 of 29
TABLE 10—BOND STRENGTH DESIGN INFORMATION FOR U.S. CUSTOMARY UNIT REINFORCING BARS
IN HOLES DRILLED WITH A HAMMER DRILL AND CARBIDE BIT (OR WÜRTH HOLLOW CARBIDE DRILL BIT)1
Nominal Rod Diameter (inch)
DESIGN INFORMATION Symbol Units
No.3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10
in. 23/8 23/4 31/8 31/2 31/2 4 41/2 5
Minimum embedment hef,min
(mm) (60) (70) (79) (89) (89) (102) (114) (127)
in. 71/2 10 121/2 15 171/2 20 221/2 25
Maximum embedment hef,max
(mm) (191) (254) (318) (381) (445) (508) (572) (635)
Temperature range
110°F / 176°F2,3
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
CAC4 cleaning
Concrete Strength reduction factor φws - 0.65
Anchor category − - 3
Strength reduction factor φwf - 0.45
Water-filled holes
Modification factor for water
Κwf - 1.0
filled holes
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
Water-saturated Anchor category − - 2
HDB4 cleaning
Concrete Strength reduction factor φws - 0.55
Anchor category − - Not 3
applicable
Water-filled holes
Strength reduction factor φwf - 0.45
Modification factor for water
Κwf - 0.86 0.91 0.95 1
filled holes
Reduction factor for seismic tension αN,seis - 1 0.98 0.97 0.95 0.92
1
Bond strength values correspond to concrete compressive strength f'c = 2,500 psi [minimum of 24 MPa is required under ADIBC Appendix L, Section 5.1.1]. For
concrete compressive strength, f'c between 2,500 psi and 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c / 2500)0.1 [For SI: (f'c
/ 17.2)0.1]. See Section 4.1.4 of this report.
2
Characteristic bond strengths are for sustained loads including dead and live loads. For load combinations consisting of short-term loads only such as wind, bond
strengths may be increased by 10 percent for temperature range A and B and by 16 percent for temperature range C.
3
Short term elevated concrete temperatures are those that occur over brief intervals, e.g. as result of diurnal cycling. Long term concrete temperatures are roughly
constant over significant periods of time.
Temperature range A: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 110°F (43°C);
Temperature range B: Maximum short term temperature = 153°F (67°C), maximum long term temperature = 110°F (43°C);
Temperature range C: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
4
CAC: compressed air cleaning see Figure 5; HDB: cleaning during drilling action with hollow drill bit system
ESR-4757 | Most Widely Accepted and Trusted Page 16 of 29
TABLE 11—BOND STRENGTH DESIGN INFORMATION FOR U.S. CUSTOMARY UNIT REINFORCING BARS
IN HOLES DRILLED WITH A CORE DRILL AND DIAMOND CORE BIT 1
Nominal Rod Diameter (inch)
DESIGN INFORMATION Symbol Units
No.3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10
in. 23/8 23/4 31/8 31/2 31/2 4 41/2 5
Minimum embedment hef,min
(mm) (60) (70) (79) (89) (89) (102) (114) (127)
in. 71/2 10 121/2 15 171/2 20 221/2 25
Maximum embedment hef,max
(mm) (191) (254) (318) (381) (445) (508) (572) (635)
Temperature
range C:
176°F2,3
122°F /
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
Water-saturated Anchor category − - 2
Concrete Strength reduction factor φws - 0.55
SPCAC4 cleaning
Anchor category − - 3
Water-filled holes
Strength reduction factor φwf - 0.45
Modification factor for water
Κwf - 0.90
filled holes
1
Bond strength values correspond to concrete compressive strength f'c = 2,500 psi [minimum of 24 MPa is required under ADIBC Appendix L, Section 5.1.1]. For
concrete compressive strength, f'c between 2,500 psi and 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c / 2500)0.2 [For SI: (f'c
/ 17.2)0.2]. See Section 4.1.4 of this report.
2
Characteristic bond strengths are for sustained loads including dead and live loads. For load combinations consisting of short-term loads only such as wind, bond
strengths may be increased by 4 percent for temperature range C.
3
Short term elevated concrete temperatures are those that occur over brief intervals, e.g. as result of diurnal cycling. Long term concrete temperatures are roughly
constant over significant periods of time.
Temperature range C: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
4
SPCAC: see Figure 5
ESR-4757 | Most Widely Accepted and Trusted Page 17 of 29
strength (for a single kN 11.0 14.5 25.3 47.1 73.5 105.9 137.7 168.3
anchor) Vsa
( lb ) (2,470) (3,260) (5,684) (10,586) (16,519) (23,801) (30,948) (37,826)
Reduction factor for
αV,seis - 0.78
seismic shear
Strength reduction
φ - 0.65
factor for tension2
Strength reduction
φ - 0.60
factor for shear2
Nominal strength as kN 29.3 46.4 67.4 125.6 196 282.4 367.2 448.8
Nsa
governed by steel ( lb ) (6,582) (10,428) (15,157) (28,229) (44,051) (63,470) (82,528) (100,868)
ISO 898-1 Class 8.8
strength (for a single kN 17.6 23.0 40.5 75.4 117.6 169.4 220.3 269.3
anchor) Vsa
( lb ) (3,949) (5,216) (9,094) (16,937) (26,431) (38,082) (49,517) (60,521)
Reduction factor for
αV,seis - 0.78
seismic shear
Strength reduction
φ - 0.65
factor for tension2
Strength reduction
φ - 0.60
factor for shear2
Nominal strength as kN 25.6 40.6 59 109.9 171.5 247.1 229.5 280.5
Nsa
governed by steel ( lb ) (5,760) (9,125) (13,263) (24,700) (38,545) (55,536) (51,580) (63,043)
A4 stainless steel3
strength (for a single kN 15.4 20.3 35.4 65.9 102.9 148.3 137.7 168.3
anchor) Vsa
ISO 3506-1,
TABLE 14—BOND STRENGTH DESIGN INFORMATION FOR METRIC THREADED ROD IN HOLES
DRILLED WITH A HAMMER DRILL AND CARBIDE BIT (OR WÜRTH HOLLOW CARBIDE DRILL BIT)1
Nominal Rod Diameter (inch)
DESIGN INFORMATION Symbol Units
M8 M10 M12 M16 M20 M24 M27 M30
mm 60 60 70 80 90 96 108 120
Minimum embedment hef,min
( in.) (2.4) (2.4) (2.8) (3.1) (3.5) (3.8) (4.3) (4.7)
mm 120 200 240 320 400 480 540 600
Maximum embedment hef,max
( in.) (4.7) (7.9) (9.4) (12.6) (15.7) (18.9) (21.3) (23.6)
Temperature range
110°F / 176°F2,3
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
CAC4 cleaning
Concrete Strength reduction factor φws - 0.65
Anchor category − - 3
Strength reduction factor φwf - 0.45
Water-filled holes
Modification factor for water
Κwf - 1.0
filled holes
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
Water-saturated Anchor category − - 2
HDB4 cleaning
Concrete Strength reduction factor φws - 0.55
Anchor category − - Not applicable
3
Water-filled holes
Strength reduction factor φwf - 0.45
Modification factor for water
Κwf - 0.86 0.91 0.96 1
filled holes
Reduction factor for seismic tension αN,seis - 1 0.99 0.98 0.96 0.94 0.93
1
Bond strength values correspond to concrete compressive strength f'c = 2,500 psi [minimum of 24 MPa is required under ADIBC Appendix L, Section 5.1.1]. For
concrete compressive strength, f'c between 2,500 psi and 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c / 2500)0.1 [For SI: (f'c
/ 17.2)0.1]. See Section 4.1.4 of this report.
2
Characteristic bond strengths are for sustained loads including dead and live loads. For load combinations consisting of short-term loads only such as wind, bond
strengths may be increased by 10 percent for temperature range A and B and by 16 percent for temperature range C.
3
Short term elevated concrete temperatures are those that occur over brief intervals, e.g. as result of diurnal cycling. Long term concrete temperatures are roughly
constant over significant periods of time.
Temperature range A: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 110°F (43°C);
Temperature range B: Maximum short term temperature = 153°F (67°C), maximum long term temperature = 110°F (43°C);
Temperature range C: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
4
CAC: compressed air cleaning see Figure 5; HDB: cleaning during drilling action with hollow drill bit system
ESR-4757 | Most Widely Accepted and Trusted Page 19 of 29
TABLE 15—BOND STRENGTH DESIGN INFORMATION FOR METRIC THREADED ROD IN HOLES
DRILLED WITH A CORE DRILL AND DIAMOND CORE BIT 1
Nominal Rod Diameter (inch)
DESIGN INFORMATION Symbol Units
M8 M10 M12 M16 M20 M24 M27 M30
mm 60 60 70 80 90 96 108 120
Minimum embedment hef,min
( in.) (2.4) (2.4) (2.8) (3.1) (3.5) (3.8) (4.3) (4.7)
mm 120 200 240 320 400 480 540 600
Maximum embedment hef,max
( in.) (4.7) (7.9) (9.4) (12.6) (15.7) (18.9) (21.3) (23.6)
Temperature
range C:
176°F2,3
122°F /
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
Water-saturated Anchor category − - 1 2
Concrete Strength reduction factor φws - 0.65 0.55
SPCAC4 cleaning
Anchor category − - 3
Water-filled holes
Strength reduction factor φwf - 0.45
Modification factor for water
Κwf - 1.0 0.99 0.96 0.94 0.92 0.91
filled holes
1
Bond strength values correspond to concrete compressive strength f'c = 2,500 psi [minimum of 24 MPa is required under ADIBC Appendix L, Section 5.1.1]. For
concrete compressive strength, f'c between 2,500 psi and 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c / 2500)0.2 [For SI: (f'c
/ 17.2)0.2]. See Section 4.1.4 of this report.
2
Characteristic bond strengths are for sustained loads including dead and live loads. For load combinations consisting of short-term loads only such as wind, bond
strengths may be increased by 4 percent for temperature range C.
3
Short term elevated concrete temperatures are those that occur over brief intervals, e.g. as result of diurnal cycling. Long term concrete temperatures are roughly
constant over significant periods of time.
Temperature range C: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
4
SPCAC: see Figure 5
anchor) Vsa
( lb ) (3,709) (5,843) (8,414) (11,453) (14,959) (23,373) (36,521) (45,812) (59,836)
Reduction factor for
αV,seis - 0.75
seismic shear
Strength reduction
φ - 0.65
factor for tension2
Strength reduction
φ - 0.60
factor for shear2
1
Values provided for common bar material types based on specified strengths and calculated in accordance with ACI 318-19 Eq. 17.6.1.2 and Eq. 17.7.1.2b or ACI
318-14 Eq. 17.4.1.2 and Eq. 17.5.1.2b or ACI 318-11 Eq. (D-2) and Eq. (D-29), as applicable.
2
The tabulated value of φ applies when the load combinations of Section 1605.1 of the 2021 IBC or Section 1605.2 of the 2018, 2015, 2012 and 2009 IBC, ACI
318-19 and ACI 318-14 5.3 or ACI 318-11 9.2, as applicable, as set forth in ACI 318-19 17.5.3 or ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, are used.
If the load combinations of ACI 318-11 Appendix C are used, the appropriate value of φ must be determined in accordance with ACI 318-11 D.4.4.
ESR-4757 | Most Widely Accepted and Trusted Page 20 of 29
mm 35 40 45 50 50 60 70 75 85
Min. edge spacing4 cmin
( in.) (13/8) (15/8) (13/4) (2) (2) (23/8) (23/4) (3) (31/8)
mm hef + 30
Min. member thickness hmin hef + 2d0 3
( in.) (hef + 11/4)
Critical edge spacing –
splitting (for uncracked cac - See Section 4.1.10 of this report.
concrete)2
Strength reduction factor for 0.65
tension, concrete failure φ -
modes, Condition B2
Strength reduction factor for 0.70
shear, concrete failure modes, φ -
Condition B2
1
Additional setting information is described in Figure 5, installation instructions.
2
The strength reduction factor applies when the load combinations from the IBC or ACI 318 are used and the requirements of ACI 318-19 17.5.3, ACI 318-14
17.3.3(c) or ACI 318-11 D.4.3(c), as applicable, for Condition B (supplement reinforcement not present) are met. For installations where complying reinforcement
can be verified, the applicable strength reduction factors described in ACI 318-19 17.5.3, ACI 318-14 17.3.3(c) or ACI 318-11 D.4.3(c), as applicable, may be used
for Condition A (supplement reinforcement present). If the load combinations of ACI 318-11 Appendix C are used, the appropriate strength reduction factor must
be determined in accordance with ACI 318-11 D.4.4(c) for Condition B (supplement reinforcement not present).
3
d0 = hole diameter.
4
The edge distances, cmin less than the values given in the table may be reduced subject to the anchor spacing, smin in accordance with Section 4.1.9.
ESR-4757 | Most Widely Accepted and Trusted Page 21 of 29
110°F / 176°F2,3
Characteristic bond strength in uncracked psi 2,070 2,055 2,040 2,025 2,010 1,985 1,945 1,925 1,895
τk,uncr
concrete (N/mm²) (14.3) (14.2) (14.1) (14.0) (13.9) (13.7) (13.4) (13.3) (13.1)
A:
Characteristic bond strength in cracked psi 1,345 1,345 1,740 1,735 1,725 1,690 1,650 1,620 1,605
τk,cr
concrete (N/mm²) (9.3) (9.3) (12.0) (12.0) (11.9) (11.7) (11.4) (11.2) (11.1)
110°F / 153°F2,3
Characteristic bond strength in uncracked psi 2,380 2,365 2,345 2,330 2,315 2,280 2,235 2,210 2,180
Temperature
τk,uncr
concrete (N/mm²) (16.4) (16.3) (16.2) (16.1) (15.9) (15.7) (15.4) (15.2) (15.0)
range B:
Characteristic bond strength in cracked psi 1,550 1,550 2,000 1,995 1,985 1,945 1,900 1,865 1,845
τk,cr
concrete (N/mm²) (10.7) (10.7) (13.8) (13.7) (13.7) (13.4) (13.1) (12.8) (12.7)
122°F / 176°F2,3
Characteristic bond strength in uncracked psi 1,945 1,930 1,920 1,905 1,890 1,865 1,830 1,810 1,780
Temperature
τk,uncr
concrete (N/mm²) (13.4) (13.3) (13.2) (13.1) (13.0) (12.8) (12.6) (12.5) (12.3)
range C:
Characteristic bond strength in cracked psi 1,340 1,340 1,635 1,630 1,620 1,590 1,550 1,525 1,505
τk,cr
concrete (N/mm²) (9.2) (9.2) (11.3) (11.2) (11.2) (10.9) (10.7) (10.5) (10.4)
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
Water-filled holes
Strength reduction factor φwf - 0.45
Modification factor for water
Κwf - 0.86 0.91 0.96 1
filled holes
Reduction factor for seismic tension αN,seis - 1 0.99 0.98 0.96 0.94 0.93
1
Bond strength values correspond to concrete compressive strength f'c = 2,500 psi [minimum of 24 MPa is required under ADIBC Appendix L, Section 5.1.1]. For
concrete compressive strength, f'c between 2,500 psi and 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c / 2500)0.1 [For SI: (f'c
/ 17.2)0.1]. See Section 4.1.4 of this report.
2
Characteristic bond strengths are for sustained loads including dead and live loads. For load combinations consisting of short-term loads only such as wind, bond
strengths may be increased by 10 percent for temperature range A and B and by 16 percent for temperature range C.
3
Short term elevated concrete temperatures are those that occur over brief intervals, e.g. as result of diurnal cycling. Long term concrete temperatures are roughly
constant over significant periods of time.
Temperature range A: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 110°F (43°C);
Temperature range B: Maximum short term temperature = 153°F (67°C), maximum long term temperature = 110°F (43°C);
Temperature range C: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
4
CAC: compressed air cleaning see Figure 5; HDB: cleaning during drilling action with hollow drill bit system.
ESR-4757 | Most Widely Accepted and Trusted Page 22 of 29
176°F2,3
122°F /
Characteristic bond strength in uncracked psi 1,670 1,605 1,560 1,520 1,483 1,430 1,375 1,350 1,320
τk,uncr
concrete (N/mm²) (11.5) (11.1) (10.7) (10.5) (10.2) (9.8) (9.5) (9.3) (9.1)
Anchor category − - 1
Dry Concrete
Strength reduction factor φd - 0.65
Water-saturated Anchor category − - 2
SPCAC4 Concrete Strength reduction factor φws - 0.55
cleaning
Anchor category − - 3
Water-filled holes
Strength reduction factor φwf - 0.45
Modification factor for water
Κwf - 0.90
filled holes
1
Bond strength values correspond to concrete compressive strength f'c = 2,500 psi [minimum of 24 MPa is required under ADIBC Appendix L, Section 5.1.1]. For
concrete compressive strength, f'c between 2,500 psi and 8,000 psi, the tabulated characteristic bond strength may be increased by a factor of (f'c / 2500)0.2 [For SI: (f'c
/ 17.2)0.2]. See Section 4.1.4 of this report.
2
Characteristic bond strengths are for sustained loads including dead and live loads. For load combinations consisting of short-term loads only such as wind, bond
strengths may be increased by 4 percent for temperature range C.
3
Short term elevated concrete temperatures are those that occur over brief intervals, e.g. as result of diurnal cycling. Long term concrete temperatures are roughly
constant over significant periods of time.
Temperature range C: Maximum short term temperature = 176°F (80°C), maximum long term temperature = 122°F (50°C).
4
SPCAC: see Figure 5
ESR-4757 | Most Widely Accepted and Trusted Page 23 of 29
TABLE 20—DEVELOPMENT LENGTH FOR U.S. CUSTOMARY UNIT REINFORCING BARS IN HOLES DRILLED
WITH A HAMMER DRILL AND CARBIDE BIT (OR WÜRTH HOLLOW CARBIDE DRILL BIT) OR A CORE DRILL AND DIAMOND CORE
BIT 1, 2, 4, 5, 6
Bar size
Symbol
Units
DESIGN Criteria Section of
INFORMATION Reference Standard #3 #4 #5 #6 #7 #8 #9 #10
Nominal reinforcing in. 0.375 0.500 0.625 0.750 0.875 1.000 1.125 1.250
db ASTM A615/A706
bar diameter (mm) (9.5) (12.7) (15.9) (19.1) (22.2) (25.4) (28.6) (31.8)
in2 0.11 0.20 0.31 0.44 0.60 0.79 1.00 1.27
Nominal bar area Ab ASTM A615/A706
(mm2) (71.3) (126.7) (197.9) (285.0) (387.9) (506.7) (644.7) (817.3)
Development length in. 12.0 14.4 18.0 21.6 31.5 36.0 40.5 45.0
ACI 318-14 25.4.2.3
for fy = 60 ksi and f’c =
ld or
2,500 psi (normal
ACI 318-11 12.2.3
weight concrete)3 (mm) (304.8) (365.8) (457.2) (548.6) (800.1) (914.4) (1028.7) (1143)
Development length in. 12.0 12.0 14.2 17.1 24.9 28.5 32.0 35.6
ACI 318-14 25.4.2.3
for fy = 60 ksi and f’c =
ld or
4,000 psi (normal
ACI 318-11 12.2.3 (mm) (304.8) (304.8) (361.4) (433.7) (632.5) (722.9) (812.8) (904.2)
weight concrete) 3
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897 MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi
1
Development lengths valid for static, wind, and earthquake loads (SDC A and B).
2
Development lengths in SDC C through F must comply with ACI 318-19 and ACI 318-14 Chapter 18 or ACI 318-11 Chapter 21 and section 4.2.4 of this report.
3
fy and f’c used in this table are for example purposes only. For sand-lightweight concrete, increase development length by 33%, unless the provisions of ACI 318-
19 25.4.2.5, ACI 318-14 25.4.2.4 or ACI 318-11 12.2.4 (d) are met to permit λ > 0.75.
c b + K tr
4
= 2.5 , ψt = 1.0, ψe = 1.0, ψs = 0.8 for db ≤ #6, 1.0 for db > #6.
d
b
5
Minimum f’c of 24 MPa is required under ADIBC Appendix L, Section 5.1.1
6
Calculations may be performed for other steel grades per ACI 318-11 Chapter 12 or ACI 318-14 and ACI 318-19 Chapter 25.
Bar size
Criteria Section of
Symbol
Units
Development length for fy mm 305 348 417 556 871 1087 1392
ACI 318-14 25.4.2.3
= 72.5 ksi and f’c = 2,500
ld or
psi (normal weight
ACI 318-11 12.2.3
concrete) 3 (in.) (12.0) (13.7) (16.4) (21.9) (34.3) (42.8) (54.8)
Development length for fy mm 305 305 330 439 688 859 1100
ACI 318-14 25.4.2.3
= 72.5 ksi and f’c = 4,000
ld or
psi (normal weight
ACI 318-11 12.2.3 (in.) (12.0) (12.0) (13.0) (17.3) (27.1) (33.8) (43.3)
concrete) 3
For SI: 1 inch ≡ 25.4 mm, 1 lbf = 4.448 N, 1 psi = 0.006897 MPa.
For pound-inch units: 1 mm = 0.03937 inches, 1 N = 0.2248 lbf, 1 MPa = 145.0 psi
1
Development lengths valid for static, wind, and earthquake loads (SDC A and B).
2
Development lengths in SDC C through F must comply with ACI 318-19 and ACI 318-14 Chapter 18 or ACI 318-11 Chapter 21 and section 4.2.4 of this report.
3
fy and f’c used in this table are for example purposes only. For sand-lightweight concrete, increase development length by 33%, unless the provisions of ACI 318-
19 25.4.2.5, ACI 318-14 25.4.2.4 or ACI 318-11 12.2.4 (d) are met to permit λ > 0.75.
c b + K tr
4
= 2.5 , ψt = 1.0, ψe = 1.0, ψs = 0.8 for db < 20mm, 1.0 for db ≥ 20mm.
d
b
5
Minimum f’c of 24 MPa is required under ADIBC Appendix L, Section 5.1.1
6
Calculations may be performed for other steel grades per ACI 318-11 Chapter 12 or ACI 318-14 and ACI 318-19 Chapter 25.
ESR-4757 | Most Widely Accepted and Trusted Page 24 of 29
(B)
(A)
(C)
www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ®
DIVISION: 03 00 00—CONCRETE
Section: 03 16 00—Concrete Anchors
DIVISION: 05 00 00—METALS
Section: 05 05 19—Post-Installed Concrete Anchors
REPORT HOLDER:
EVALUATION SUBJECT:
WÜRTH WIT-PE 1000 ADHESIVE ANCHOR AND POST-INSTALLED REINFORCING BAR CONNECTION SYSTEM IN
CRACKED AND UNCRACKED CONCRETE
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2022 ICC Evaluation Service, LLC. All rights reserved. Page 28 of 29
ICC-ES Evaluation Report ESR-4757 FBC Supplement
Reissued May 2022
This report is subject to renewal May 2023.
www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council ®
DIVISION: 03 00 00—CONCRETE
Section: 03 16 00—Concrete Anchors
DIVISION: 05 00 00—METALS
Section: 05 05 19—Post-Installed Concrete Anchors
REPORT HOLDER:
EVALUATION SUBJECT:
WÜRTH WIT-PE 1000 ADHESIVE ANCHOR AND POST-INSTALLED REINFORCING BAR CONNECTION SYSTEM IN
CRACKED AND UNCRACKED CONCRETE
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2022 ICC Evaluation Service, LLC. All rights reserved. Page 29 of 29