Project

Reference code
Design office FOR ANCHOR BOLT CAPACITY ONLY
Person in charge
Construction Office
Person in charge

Base material Installation


Stand-off with grouting 20 mm
Cracked Concrete
Rotational Restraint 2.0
Thickness of base material 300 mm
Strength Class C25/30
fck,cube 30 N/mm2 Anchor plate
Short term temp 40 °C Assumed rigid plate
Long term temp 24 °C Thickness of the plate 16 mm
Plate shape Custom geometry

Plate vertex Anchors Position

Vertex x y Anchor x y Slotted -x Slotted -y


1 -125.0 -150.0 1 -75.0 100.0
2 -125.0 150.0 2 75.0 100.0
3 125.0 150.0 3 -75.0 -100.0
4 125.0 -150.0 4 75.0 -100.0

= Slotted

Profile
Selected Profile RECT. HOLLOW 100x150x5
Eccentricity X: 0.0 mm
Y: 0.0 mm
Profile rotation 0.0°

DESIGN CONCRETE
08/08/2019 Page: 1 / 9
v. 4.0.3.454 - Database engine 216.30.2316085211
Project

Reference code
Design office
Person in charge
Construction Office
Person in charge

Selected Products
Anchor (name) MIT600RE, Steel 8.8
Approval ETA-09/0340
Size M20
Article code

- Mungo Pure Epoxy MIT600RE can be found in the cartridge of;


-MIT600RE 385ml (Article code 1710001)
-MIT600RE 585ml (Article code 1710010)
-MIT600RE 1400ml (Article code 1710012)

Anchor data
d Anchor/thread diameter: 20.0 mm tfix Thickness of fixture: 16.0 mm
dnom Outside diameter of anchor: 20.0 mm SW Spanner: 0.0 mm
d0 Drill hole diameter: 24.0 mm Tinst Max setting torque 120.0 Nm
h1 Depth of drilled hole: 175.0 mm Use category, concrete Dry/Wet Bore Hole
hnom Setting depth: 170.0 mm
hef Effective anchorage depth: 170.0 mm Minimum stud lenght L 209.0 mm
df Diameter of clearance hole in fixture: 22.0 mm

PRODUCT
MIT600RE Pure Epoxy. European Technical Approval Option 1 for cracked and non-cracked concrete with anchor rod and with rebar
used as anchor. Fire resistance test certification F30-F120. VOC free according to Swiss legislation and certified A+ according to
DEVL 1101903D / DEVL 1104875A. LEED - Test Report. Certification for drinking water Systems. The anchor may also be used under
seismic influence for performance category C1 + C2. Application also in damp and water-filled drill holes. Indoor (zinc plated) and
outdoor (stainless steel) applications.

DESIGN CALCULATION
This calculation is based on specific values exclusively for the product above.

DESIGN CONCRETE
08/08/2019 Page: 2 / 9
v. 4.0.3.454 - Database engine 216.30.2316085211
Project

Reference code
Design office
Person in charge
Construction Office
Person in charge

Any changes to the brand or physical conditions for design will require a recalculation of the anchor design.

ANCHOR PLATE
The design program assumes, in accordance with EOTA TR029, that the anchor plate does not deform as a result of applied actions.
Thus, and in accordance with EOTA TR029, the anchor plate shall be sufficiently stiff and its design should be carried out according
to standards for steel structures ensuring elastic behaviour.

INSTALLATION
All conditions of the European Technical Approval (ETA) and Mungo technical publications shall be complied with in all detail.
The load values are valid only if the installation has been carried out correctly.

ATTENTION
The loads as well as the installation data can vary. Please consult our website www.mungo.swiss to download the newest version.

Input Data
Tension Bending Reinforcement
NSd,Z 0.00 kN MSd,X -11.70 kN·m Diameter 11 mm
Shear MSd,Y 0.00 kN·m Distance rebars 200 mm
VSd,X 0.00 kN Torsion Distance stirrups 200 mm
VSd,Y 9.70 kN MSd,Z 0.00 kN·m Edge reinforcement No
Edges
CXp ∞ mm
CXn ∞ mm
CYp ∞ mm
CYn ∞ mm

DESIGN CONCRETE
08/08/2019 Page: 3 / 9
v. 4.0.3.454 - Database engine 216.30.2316085211
Project

Reference code
Design office
Person in charge
Construction Office
Person in charge

Calculated design loads on anchor(s)

Tension force Shear force Shear force (x) Shear force (y)
Anchor
[kN] [kN] [kN] [kN]
1 0.00 2.42 0.00 2.42
2 0.00 2.42 0.00 2.42
3 25.99 2.42 0.00 2.42
4 25.99 2.42 0.00 2.42

Resultant tension force: 51.98 [kN]


Resultant compression force: 51.98 [kN]
Resultant shear force: 9.70 [kN]

Calculation of Utilizations according to: TECHNICAL REPORT TR029


(β- is the ratio between design load and design resistance)

Calculation of Utilisations - Tension loads

Tension - Steel Failure

NRk,s γM,s NRd,s NSd βN,s


Anchor
[kN] [-] [kN] [kN] [%]

196.00 1.50 130.67 1 0.00 0.0%

2 0.00 0.0%

3 25.99 19.9%

4 25.99 19.9%

Tension - Combined Failure

NRk,p = N0Rk,p · ψA,Np · ψs,Np · ψg,Np · ψec,Np · ψre,Np

Setting depth: lb Effective anchorage depth: hef

τRk τRk,ucr ψc d hef scr,Np ccr,Np k fck,cube γNrkp


[N/mm2] [N/mm2] [-] [mm] [mm] [mm] [mm] [-] [N/mm²] [-]
6.0 13.0 1.020 20.0 170 510 263 2.0 30 2.1

The anchors are divided into 1 group

DESIGN CONCRETE
08/08/2019 Page: 4 / 9
v. 4.0.3.454 - Database engine 216.30.2316085211
Project

Reference code
Design office
Person in charge
Construction Office
Person in charge

Group N0R,kp Ac,N A0c,n ψs,Np hef scr,Np ccr,Np c-x c+x c-y c+y
Anchor
No. [kN] [mm²] [mm²] [-] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

1 [3, 4] 65.37 336,600 260,100 1.000 170 510 255 6,000 6,000 6,000 6,200

Group sm ψg,Np ψre,Np eNp,x eNp,y ψec,Np NRk,p NRd,p NSd βNp
Anchor
No. [mm] [-] [-] [mm] [mm] [-] [kN] [kN] [kN] [%]

1 [3, 4] 150.0 1.071 1.000 0.0 0.0 1.000 90.62 43.15 51.98 120.4%

Tension - Concrete Cone Failure


NRk,c=N0Rk,c · ψA,N · ψs,N · ψre,N · ψec,N

hef scr,N ccr,N fck,cube γMc


[mm] [mm] [mm] [N/mm²] [-]
170 510 255 30 2.1

The anchors are divided into 1 group

Verification performed with three or more edges cmax < ccr

Group N0Rk,c Ac,N A0c,N hef scr,N ccr,N c-x c+x c-y c+y
Anchor
No. [kN] [mm²] [mm²] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

1 [3, 4] 87.41 336,600 260,100 170 510 255 6,000 6,000 6,000 6,200

Group ψs,N ψre,N eN,x eN,y ψec,N NRk,c NRd,c Nsd βN,c
Anchor
No. [-] [-] [mm] [mm] [-] [kN] [kN] [kN] [%]

1 [3, 4] 1.000 1.000 0.0 0.0 1.000 113.12 53.87 51.98 96.5%

Tension - Splitting Failure

As the calculation is performed for cracked concrete, no proof for splitting failure is required.

DESIGN CONCRETE
08/08/2019 Page: 5 / 9
v. 4.0.3.454 - Database engine 216.30.2316085211
Project

Reference code
Design office
Person in charge
Construction Office
Person in charge

Calculation of Utilisations - Shear loads


Shear - Steel Failure Without Lever Arm

VRk,s γMs VRd,s


[kN] [-] [kN]

98.00 1.25 78.40

1 2 3 4

Vsd [kN] 2.42 2.42 2.42 2.42

βV,s [ % ] 3.1% 3.1% 3.1% 3.1%

Shear - Steel Failure With Lever Arm

l αm M0R,ks
[ mm ] [-] [ Nm ]

38.00 2.00 519.00

1 2 3 4

VR,ks [kN] 27.32 27.32 21.88 21.88

VRd,s [kN] 21.85 21.85 17.51 17.51

Vsd [kN] 2.42 2.42 2.42 2.42

βV,sla [ % ] 11.1% 11.1% 13.9% 13.9%

Shear - Pryout Failure(NRk,c)


NRk,c=N0Rk,c · ψA,N · ψs,N · ψre,N · ψec,V,cp

VRk,cp=k · NRk,c

hef scr,N ccr,N fck,cube k γMc


[mm] [mm] [mm] [N/mm²] [-] [-]
170 510 255 30 2.0 1.5

The anchors are divided into 1 group

Group N0Rk,c Ac,N A0c,N ψs,N ψre,N c-x c+x c-y c+y
Anchor
No. [kN] [mm2] [mm2] [-] [-] [mm] [mm] [mm] [mm]

DESIGN CONCRETE
08/08/2019 Page: 6 / 9
v. 4.0.3.454 - Database engine 216.30.2316085211
Project

Reference code
Design office
Person in charge
Construction Office
Person in charge

1 [1, 2, 3, 4] 87.41 468,600 260,100 1.000 1.000 6,000 6,000 6,000 6,000

Group eN,x eN,y ψec,N NRk,c VRk,cp VRd,cp VSd βV,cp


Anchor
No. [mm] [mm] [-] [kN] [kN] [kN] [kN] [%]

1 [1, 2, 3, 4] 0.0 0.0 1.000 157.48 314.96 209.97 9.70 4.6%

Shear - Pryout Failure(NRk,p)


NRk,p=N0Rk,p · ψA,Np · ψs,Np · ψgN,p · ψre,Np · ψec,V,cp

VRk,cp=k · NRk,p

hef τRk,ucr scr,Np ccr,Np d τRk ψc k γMc


[mm] [N/mm2] [mm] [mm] [mm] [N/mm2] [-] [-] [-]
170 13.0 510.0 255.0 20.0 6.0 1.020 2.0 1.5

The anchors are divided into 1 group

Group N0Rk,p Ap,N A0p,N sm ψg,Np c-x c+x c-y c+y


Anchor
No. [kN] [mm ] 2
[mm2] [-] [-] [mm] [mm] [mm] [mm]

1 [1, 2, 3, 4] 65.37 468,600 260,100 175.0 1.156 6,000 6,000 6,000 6,000

Group ψs,N ψre,N en,x en,y ψec,N NRk,c VRk,cp VRd,cp VSd βV,cp
Anchor
No. [-] [-] [mm] [mm] [-] [kN] [kN] [kN] [kN] [%]
[1, 2, 3,
1 1.000 1.000 0.0 0.0 1.000 136.09 272.18 181.46 9.70 5.3%
4]

Shear - Concrete Edge Failure

As all edges are greater than 10 hef and 60 d, the proof for concrete edge failure is omitted.

Combined tension and shear

Anchor Tension (βN) Shear (βV) Condition Utilisation Status

Steel 3 19.9% 13.9% β = β2N + β2V 5.9%

Concrete 3 120.4% 5.3% β = (βN + βV) / 1.2 104.8%

DESIGN CONCRETE
08/08/2019 Page: 7 / 9
v. 4.0.3.454 - Database engine 216.30.2316085211
Project

Reference code
Design office
Person in charge
Construction Office
Person in charge
Anchor

βN,s βN,p βN,comb βN,c βN,sp βV,s βV,sla βV,cp βV,c βN,s,max βV,s.max βN,c,max, βV,c,max,E βcombi,c,E βcombi,S,E
E

1 0.0% 0.0% 0.0% 0.0% 0.0% 3.1% 11.1% 5.3% 0.0% 0.0% 11.1% 0.0% 5.3% 1.2% 1.2%

2 0.0% 0.0% 0.0% 0.0% 0.0% 3.1% 11.1% 5.3% 0.0% 0.0% 11.1% 0.0% 5.3% 1.2% 1.2%

3 19.9% 0.0% 120.4% 96.5% 0.0% 3.1% 13.9% 5.3% 0.0% 19.9% 13.9% 120.4% 5.3% 104.8% 5.9%

4 19.9% 0.0% 120.4% 96.5% 0.0% 3.1% 13.9% 5.3% 0.0% 19.9% 13.9% 120.4% 5.3% 104.8% 5.9%

βN,s,max = βN,s
βV,s,max = max ( βV,s , βV,sla )

βN,c,max,E = max ( βN,p , βN,c , βN,sp , βN,comb )


βV,c,max,E = max ( βV,cp , βV,c )
βcombi,s,E = β2N,s + β2V,s
βcombi,c,E = min[ ( β1.5N,c,max,E + β1.5V,c,max,E), ( βN,c,max,E + βV,c,max,E ) / 1.2 ]

With consideration of related anchors and separation of steel and concrete failure

RESULT
Anchor(s) is rejected as the decisive utilization exceeds the allowed capacity

REMARKS
The verification of anchor design cases covered by ETAG 001 or TR29 is performed according to the selected Guideline. The
verification of anchor design cases non-covered by guidelines is based on the selected Guideline. Further information can be
found inside ACP Design Guides. The loads acting on anchors are evaluated according to the theory of elasticity, assuming
that the anchor plate does not deform under the design actions. To ensure the validity of this assumption the anchor plate
shall be sufficient stiff. The user must verify this condition, since the base plate stiffness is not automatically calculated by the
software. The transfer of loads from anchors into base material must be verified in accordance with ETAG 001 Annex C or
TR29 Section 7. The design method is valid only for clearance hole in the fixture with a diameter not larger than the values
given in ETAG 001 Annex C or TR29 Table 4.1.

IMPORTANT NOTICE
The data input to this software, and the relative results, must be checked by the user under the responsibility of an engineer
experienced in anchorages and concrete work. This is to ensure there are no errors and all data is complete and accurate and
complies with all rules and regulations for the actual conditions and application.
The data contained in this software relates only to the product illustrated therein and is based on principles, formulas and
safety regulations according to the existing guidelines for anchorages into concrete, together with the knowledge of the
manufacturer.
The user must comply with these principles. The user is solely responsible for the data entered into the program and any
errors or omissions are the responsibility of the user. The user must ensure that the most current version of the program is

DESIGN CONCRETE
08/08/2019 Page: 8 / 9
v. 4.0.3.454 - Database engine 216.30.2316085211
Project

Reference code
Design office
Person in charge
Construction Office
Person in charge

installed by way of the auto-updating function offered by the manufacturer.


The user must update the program when instructed to do so.
The aim of the program is to act as a calculation aid and to assist in complying with current regulations and guidelines,
without any guarantee of suitability for any specific application.

DESIGN CONCRETE
08/08/2019 Page: 9 / 9