You are on page 1of 12

Hilti PROFIS Engineering 3.0.

85

www.hilti.in
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

Specifier's comments:

1 Anchor Design
1.1 Input data

Anchor type and diameter: HIT-RE 500 V4 + HAS-U 5.8 M12


Return period (service life in years): 50
Item number: 2223823 HAS-U 5.8 M12x160 (element) / 2287553
HIT-RE 500 V4 (adhesive)
Effective embedment depth: hef,act = 100.0 mm (hef,limit = - mm)
Material: 5.8
Evaluation Service Report: ETA 20/0541
Issued I Valid: 04/09/2021 | -
Proof: Design Method Extended ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0.0 mm (no stand-off); t = 12.0 mm

Anchor plate
CBFEM
: lx x ly x t = 350.0 mm x 350.0 mm x 12.0 mm;

Profile: Circular Hollow Sections India, 219.1x8; (L x W x T) = 219.1 mm x 219.1 mm x 8.0 mm


Base material: 2
cracked concrete, M 25, fc,cube = 25.00 N/mm ; h = 150.0 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting according to EOTA TR 029, 5.2.2.6 present.

CBFEM
- The anchor calculation is based on a component-based Finite Element Method (CBFEM)

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

1.1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = -35.000; Vx = 0.000; Vy = 0.000; no no 2
Mx = 1.500; My = 1.500; Mz = 0.000;

1.2 Load case/Resulting anchor forces y


5

Anchor reactions [kN] 6 4


Tension force: (+Tension, -Compression)
Tension
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 0.006 -0.003 -0.006
2 0.000 0.007 0.005 -0.005 7 x 3
3 0.000 0.007 0.006 0.003
4 0.000 0.005 -0.000 0.005
5 0.000 0.003 -0.003 0.001 Compression
6 0.345 0.001 0.000 -0.000 8 2
7 0.000 0.003 -0.001 0.003
1
8 0.000 0.005 -0.005 0.000

resulting tension force in (x/y)=(-95.5/95.5): 0.345 [kN]


resulting compression force in (x/y)=(45.0/-45.5): 35.976 [kN]

Anchor forces are calculated based on a component-based Finite Element Method (CBFEM)

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

1.3 Tension load (EOTA TR 029, Section 5.2.2)

Load [kN] Capacity [kN] Utilization bN [%] Status


Steel Strength* 0.345 28.133 2 OK
Combined pullout-concrete cone failure** 0.345 27.646 2 OK
Concrete Breakout Failure** 0.345 24.000 2 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

1.3.1 Steel Strength

N
NSd £ NRd,s = Rk,s EOTA TR 029, Table 5.2.2.1
gM,s

NRk,s [kN] gM,s NRd,s [kN] NSd [kN]


42.200 1.500 28.133 0.345

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

1.3.2 Combined pullout-concrete cone failure

N
NSd £ NRd,p = Rk,p EOTA TR 029, Table 5.2.2.1
gM,p
0 Ap,N
NRk,p = NRk,p · 0
· y s,Np · y g,Np · y ec1,Np · y ec2,Np · y re,Np EOTA TR 029, Eq. (5.2)
Ap,N
0
NRk,p = p · d · hef · t Rk EOTA TR 029, Eq. (5.2a)
0
Ap,N = scr, Np · scr,Np EOTA TR 029, Eq. (5.2b)
0.5
t Rk,ucr
scr,Np = 20 · d · (
7.5 )
£ 3 · hef EOTA TR 029, Eq. (5.2c)
s
ccr,Np = cr,Np EOTA TR 029, Eq. (5.2d)
2
c
y s,Np = 0.7 + 0.3 · 1.00 EOTA TR 029, Eq. (5.2e)
ccr,Np £
0,5
y g,Np
0
= y g,Np - (s s )
cr,Np
· (y g,Np - 1) ³ 1.00
0
EOTA TR 029, Eq. (5.2f)
1,5
0
y g,Np = √n - (√n - 1) · (k · √dh · t· f ef
Rk

ck,cube
) ³ 1.00 EOTA TR 029, Eq. (5.2g)
1
y ec1,Np = 1.00 EOTA TR 029, Eq. (5.2h)
2 · ec1,N £
1+
scr,Np
1
y ec2,Np = 1.00 EOTA TR 029, Eq. (5.2h)
2 · ec2,N £
1+
scr,Np
h
y re,Np = 0.5 + ef £ 1.00 EOTA TR 029, Eq. (5.2i)
200

2 0 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,25 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm]
90,000 90,000 18.00 300.0 150.0 ∞
0
yc t Rk,cr [N/mm ]
2
k y g,Np y g,Np
1.000 11.00 2.300 1.000 1.000

ec1,N [mm] y ec1,Np ec2,N [mm] y ec2,Np y s,Np y re,Np


0.0 1.000 0.0 1.000 1.000 1.000
0
NRk,p [kN] NRk,p [kN] gM,p NRd,p [kN] NSd [kN]
41.469 41.469 1.500 27.646 0.345

Group anchor ID
6

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

1.3.3 Concrete Breakout Failure

N
NSd £ NRd,c = Rk,c EOTA TR 029, Table 5.2.2.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N EOTA TR 029, Eq. (5.3)
Ac,N
0 1,5
NRk,c = k1 · √fck,cube · hef EOTA TR 029, Eq. (5.3a)
0
Ac,N = scr,N · scr,N EOTA TR 029, Eq. (5.3b)
c
y s,N = 0.7 + 0.3 · 1.00 EOTA TR 029, Eq. (5.3c)
ccr,N £
hef
y re,N = 0.5 + 1.00 EOTA TR 029, Eq. (5.3d)
200 £
1
y ec1,N = 1.00 EOTA TR 029, Eq. (5.3e)
2 · ec1,N £
1+
scr,N
1
y ec2,N = 1.00 EOTA TR 029, Eq. (5.3e)
2 · ec2,N £
1+
scr,N

2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm]
90,000 90,000 150.0 300.0

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
k1 NRk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.200 36.000 1.500 24.000 0.345

Group anchor ID
6

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

1.4 Shear load (EOTA TR 029, Section 5.2.3)

Load [kN] Capacity [kN] Utilization bV [%] Status


Steel Strength (without lever arm)* 0.007 20.256 1 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength* 0.007 18.644 1 OK
Concrete edge failure in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

1.4.1 Steel Strength (without lever arm)

V
VSd £ VRd,s = Rk,s EOTA TR 029, Table 5.2.3.1
gM,s

VRk,s [kN] gM,s VRd,s [kN] VSd [kN]


25.320 1.250 20.256 0.007

1.4.2 Pryout Strength (Concrete Breakout Strength controls)

V
VSd £ VRd,cp = Rk,cp EOTA TR 029, Table 5.2.3.1
gM,c,p
VRk,cp = k · min (NRk,p; NRk,c) EOTA TR 029, Eq. (5.7), (5.7a)
0 A
NRk,c = NRk,c · 0c,N · y s,N · y re,N · y ec1,N · y ec2,N EOTA TR 029, Eq. (5.3)
Ac,N
0 1,5
NRk,c = k1 · √fck,cube · hef EOTA TR 029, Eq. (5.3a)
0
Ac,N = scr,N · scr,N EOTA TR 029, Eq. (5.3b)
c
y s,N = 0.7 + 0.3 · 1.00 EOTA TR 029, Eq. (5.3c)
ccr,N £
hef
y re,N = 0.5 + 1.00 EOTA TR 029, Eq. (5.3d)
200 £
1
y ec1,N = 1.00 EOTA TR 029, Eq. (5.3e)
2 · ec1,V £
1+
scr,N
1
y ec2,N = 1.00 EOTA TR 029, Eq. (5.3e)
2 · ec2,V £
1+
scr,N

2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k-factor k1
34,957 90,000 150.0 300.0 2.000 7.200

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
NRk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
36.000 1.500 18.644 0.007

Group anchor ID
2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

1.5 Combined tension and shear loads (EOTA TR 029, Section 5.2.4)
Steel failure

bN bV a Utilization bN,V [%] Status


0.014 0.000 1.500 1 OK

a a
bN + bV £ 1.0

1.6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates as per current regulations (ETAG 001/Annex C, EOTA
TR029, etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor
plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above.
The proof if the rigid base plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Characteristic bond resistances depend on short- and long-term temperatures.
• Edge reinforcement is not required to avoid splitting failure
• The anchor design methods in PROFIS Engineering require rigid anchor plates, as per current regulations (AS 5216:2021, ETAG 001/Annex
C, EOTA TR029 etc.). This means that the anchor plate should be sufficiently rigid to prevent load re-distribution to the anchors due to
elastic/plastic displacements. The user accepts that the anchor plate is considered close to rigid by engineering judgment."
• The characteristic bond resistances depend on the return period (service life in years): 50

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

1.7 Installation data

Anchor plate, steel: E 165 (Fe 290); E = 200,000.00 N/mm ; fyk = 165.00
2 Anchor type and diameter: HIT-RE 500 V4 + HAS-U 5.8
N/mm
2 M12
Profile: Circular Hollow Sections India, 219.1x8; (L x W x T) = 219.1 mm x Item number: 2223823 HAS-U 5.8 M12x160 (element) /
219.1 mm x 8.0 mm 2287553 HIT-RE 500 V4 (adhesive)
Hole diameter in the fixture: df = 14.0 mm Maximum installation torque: 40 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 14.0 mm
Hole depth in the base material: 100.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 130.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required

Hilti HAS-U threaded rod with HIT-RE 500 V4 injection mortar with 100 mm embedment h_ef, M12, Steel galvanized, Hammer drilled
installation per ETA 20/0541

1.7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • Torque wrench
the hole
• Proper diameter wire brush

y
175.0 175.0
39.5 40.0

6 4
175.0
95.5

7 3
x
95.5

175.0

8 2
40.0 39.5

40.0 39.5 95.5 95.5 39.5 40.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 0.0 -135.0 - - - - 5 0.0 135.0 - - - -
2 95.5 -95.5 - - - - 6 -95.5 95.5 - - - -
3 135.0 0.0 - - - - 7 -135.0 0.0 - - - -
4 95.5 95.5 - - - - 8 -95.5 -95.5 - - - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

2 Anchor plate rigidity check

2.1 Input data


Anchor plate: Shape: Circular
lx x ly x t = 350.0 mm x 1,000.0 mm x 12.0 mm
Calculation: Anchor Plate Rigidity Check
Material: E 165 (Fe 290); Fy = 165.00 N/mm²; εlim = 5.00%
Anchor type and size: HIT-RE 500 V4 + HAS-U 5.8 M12, hef = 100.0 mm
Anchor stiffness: The anchor is modeled considering stiffness values determined from load displacement curves tested in an
independent laboratory. Please note that no simple replacement of the anchor is possible as the anchor
stiffness has a major impact on the load distribution results.
Design method: IS800-based design using component-based FEM
Stand-off installation: eb = 0.0 mm (No stand-off); t = 12.0 mm
Profile: 219.1x8; (L x W x T x FT) = 219.1 mm x 219.1 mm x 8.0 mm x -
Material: E 165 (Fe 290); Fy = 165.00 N/mm²; εlim = 5.00%
Eccentricity x: 0.0 mm
Eccentricity y: 0.0 mm
Base material: Cracked concrete; M 25; fc,cube = 25.00 N/mm²; h = 150.0 mm; E = 30,000.00 N/mm²; G = 12,500.00
N/mm²; v = 0.20
Welds (profile to anchor plate): Type of redistribution: Plastic
Mesh size: Number of elements on edge: 8
Min. size of element: 10.0 mm
Max. size of element: 50.0 mm

2.2 Anchor plate classification


Results below are displayed for the decisive load combinations: Combination 1
Anchor tension forces Equivalent rigid anchor plate (CBFEM) Component-based Finite Element Method
(CBFEM) anchor plate design
Anchor 1 0.000 kN 0.000 kN
Anchor 2 0.000 kN 0.000 kN
Anchor 3 0.000 kN 0.000 kN
Anchor 4 0.000 kN 0.000 kN
Anchor 5 0.000 kN 0.000 kN
Anchor 6 0.809 kN 0.345 kN
Anchor 7 0.000 kN 0.000 kN
Anchor 8 0.000 kN 0.000 kN

User accepted to consider the selected anchor plate as rigid by his/her engineering judgement. This means the anchor design guidelines can
be applied.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

2.3 Warnings
● By using the CBFEM calculation functionality of PROFIS Engineering you may act outside the applicable design codes and your specified
anchor plate may not behave rigid. Please, validate the results with a professional designer and/or structural engineer to ensure suitability
and adequacy for your specific jurisdiction and project requirements.
● The anchor is modeled considering stiffness values determined from load displacement curves tested in an independent laboratory.
Please note that no simple replacement of the anchor is possible as the anchor stiffness has a major impact on the load distribution
results.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

3 Summary of results
Load combination Max. utilization Status
Anchors Combination 1 2% OK

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11
Hilti PROFIS Engineering 3.0.85

www.hilti.in
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - May 27, 2023 Date: 27/05/2023
Fastening point:

4 Remarks; Your Cooperation Duties


● Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,
formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc.,
that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be
conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based
essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the
relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and
cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility.
The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and
the relevance of the results or suitability for a specific application.
● You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you
do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the
Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery
of lost or damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

12

You might also like