Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HST3 M16 hef2
Return period (service life in years): 50
Item number: 2105858 HST3 M16x135 35/15
Effective embedment depth: hef,act = 85.0 mm (hef,limit = - mm), hnom = 98.0 mm
Material:
Evaluation Service Report: ETA 98/0001
Issued I Valid: 11/3/2022 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 12.0 mm
R 2 2
Anchor plate : E 250 (Fe 410 W) A; E = 200,000.00 N/mm ; fyk = 250.00 N/mm ; gMs = 1.100
lx x ly x t = 400.0 mm x 500.0 mm x 12.0 mm; (Recommended plate thickness: not calculated)
Profile: ISMB, ISMB 200; (L x W x T x FT) = 200.0 mm x 100.0 mm x 5.7 mm x 10.8 mm
Base material: 2
uncracked concrete, M 25, fc,cyl = 20.00 N/mm ; h = 300.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: diamond cored hole, Installation condition: Dry
Reinforcement: reinforcement spacing < 150 mm (any Ø) or < 100 mm (Ø <= 10 mm)
with longitudinal edge reinforcement d >= 12.0 [mm] + close mesh (stirrups, hangers) s <= 100.0
[mm]

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.83

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = 0.000; Vx = 33.000; Vy = 0.000; no no 98
Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces y


3 4

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 8.250 8.250 0.000
2 0.000 8.250 8.250 0.000 x
3 0.000 8.250 8.250 0.000
4 0.000 8.250 8.250 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm ]
2
1 2
resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]
resulting compression force in (x/y)=(0.0/0.0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.83

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* N/A N/A N/A N/A
Concrete Breakout Failure** N/A N/A N/A N/A
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.83

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 8.250 44.240 19 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 16.500 126.415 14 OK
Concrete edge failure in direction x+** 33.000 33.746 98 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
55.300 1.000 55.300 1.250 44.240 8.250

4.2 Pryout Strength

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
hef
y re,N = 0.5 + 1.00 EN 1992-4, Eq. (7.5)
200 £
1
y ec1,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eV,1 £
1+ ( scr,N )
1
y ec2,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eV,2 £
1+ ( scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
102,000 65,025 127.5 255.0 3.410 20.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 0.994 0.925 1.000
0
k1 NRk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
11.000 38.551 1.500 126.415 16.500

Group anchor ID
3, 4

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.83

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

4.3 Concrete edge failure in direction x+

V
VEd £ VRd,c = Rk,c EN 1992-4, Table 7.2
gM,c
0 Ac,V
VRk,c = kT · VRk,c · 0
· y s,V · y h,V · y a,V · y ec,V · y re,V EN 1992-4, Eq. (7.40)
Ac,V
0 a b 1,5
VRk,c = k9 · dnom · lf · √fck · c1 EN 1992-4, Eq. (7.41)
0,5
a = 0.1 · () lf
c1
EN 1992-4, Eq. (7.42)
0,2

= 0.1 · (
c )
d nom
b EN 1992-4, Eq. (7.43)
1
0 2
Ac,V = 4.5 · c1 EN 1992-4, Eq. (7.44)
c2
y s,V = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.45)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 EN 1992-4, Eq. (7.46)
1
y ec,V = £ 1.00 EN 1992-4, Eq. (7.47)
1+ ( 2 · eV
3 · c1 )
y a,V = √(cos a ) + (10.5 · sin a )
V
2
V
2 ³ 1.00 EN 1992-4, Eq. (7.48)

lf [mm] dnom [mm] k9 a b 2


fc,cyl [N/mm ]
85.0 16.00 2.400 0.082 0.066 20.00
2 0 2
c1 [mm] Ac,V [mm ] Ac,V [mm ]
125.0 140,625 70,312

y s,V y h,V y a,V ec,V [mm] y ec,V y re,V


1.000 1.000 1.000 0.0 1.000 1.000
0
VRk,c [kN] kT gM,c VRd,c [kN] VEd [kN]
25.310 1.0 1.500 33.746 33.000

5 Displacements (highest loaded anchor)


Short term loading:

NSk = 0.000 [kN] dN = 0.0000 [mm]


VSk = 6.111 [kN] dV = 0.8316 [mm]
dNV = 0.8316 [mm]
Long term loading:

NSk = 0.000 [kN] dN = 0.0000 [mm]


VSk = 6.111 [kN] dV = 1.2377 [mm]
dNV = 1.2377 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.83

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.83

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

7 Installation data
2
Anchor plate, steel: E 250 (Fe 410 W) A; E = 200,000.00 N/mm ; fyk = 250.00 Anchor type and diameter: HST3 M16 hef2
2
N/mm
Profile: ISMB, ISMB 200; (L x W x T x FT) = 200.0 mm x 100.0 mm x 5.7 mm x Item number: 2105858 HST3 M16x135 35/15
10.8 mm
Hole diameter in the fixture: df = 18.0 mm Maximum installation torque: 110 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 108.0 mm
Drilling method: Core drilled Minimum thickness of the base material: 140.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.
Setting: Machine torqueing with SIW 6AT-A22 and SI-AT-A22 module

Hilti HST3 stud anchor with 85 mm embedment, M16 hef2, Steel galvanized, installation per ETA 98/0001

7.1 Recommended accessories

Drilling Cleaning Setting


• Diamond core rig • Manual blow-out pump • Hilti SIW 6AT-A22 + SI AT-A22
• Torque wrench
• Hammer

20.0
y
200.0 200.0
50.0

3 4
250.0
400.0

x
250.0

1 2
50.0

125.0 150.0 125.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -75.0 -200.0 125.0 275.0 - -
2 75.0 -200.0 275.0 125.0 - -
3 -75.0 200.0 125.0 275.0 - -
4 75.0 200.0 275.0 125.0 - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.83

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

8 Drilling and installation

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.83

www.hilti.group/content/hilti/CP/XX/en.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: SAURAV Date: 2/2/2023
Fastening point:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan