Hilti PROFIS Engineering 3.0.

89

www.hilti.com.kw
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200 + HAS-U 8.8 M20
Item number: 2237092 HAS-U 8.8 M20x300 (element) / 2045030
HIT-HY 200-A (adhesive)
Effective embedment depth: hef,act = 200.0 mm (hef,limit = - mm)
Material: 8.8
Evaluation Service Report: ESR-3187
Issued I Valid: 1.05.2021 | 1.03.2022
Proof: Design Method ACI 318-08 / Chem
Stand-off installation: without clamping (anchor); restraint level (anchor plate): 2.00; eb = 20.0 mm; t = 10.0 mm
2
Hilti Grout: CB-G EG, epoxy, fc,Grout = 120.00 N/mm
Anchor plate :
R lx x ly x t = 220.0 mm x 220.0 mm x 10.0 mm; (Recommended plate thickness: not calculated)

Profile: I profile, ; (L x W x T x FT) = 203.0 mm x 204.0 mm x 7.0 mm x 11.0 mm


Base material: cracked concrete, C35/45, fc' = 5,076 psi; h = 500.0 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) no

Application also possible with HVU2 + HAS-U 8.8 M20 under the selected boundary conditions.
More information in section Alternative fastening data of this report.

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.89

www.hilti.com.kw
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

1.1 Design results


Case Description Forces [kN] / Moments [kNm] Seismic Max. Util. Anchor [%]
1 Combination 1 N = -7.000; Vx = 45.000; Vy = 0.000; no 64
Mx = 0.000; My = 0.000; Mz = 0.000;
Nsus = 0.000; Mx,sus = 0.000; My,sus = 0.000;

2 Load case/Resulting anchor forces y

Anchor reactions [kN] 3 4


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 11.250 11.250 0.000
2 0.000 11.250 11.250 0.000 x
3 0.000 11.250 11.250 0.000 Compression
4 0.000 11.250 11.250 0.000

max. concrete compressive strain: 0.00 [‰] 1 2


max. concrete compressive stress: 0.14 [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(110.0/110.0): 7.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* N/A N/A N/A N/A
Bond Strength** N/A N/A N/A N/A
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.89

www.hilti.com.kw
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 11.250 56.400 20 OK
Steel failure (with lever arm)* 11.250 17.807 64 OK
Pryout Strength (Concrete Breakout 45.000 239.991 19 OK
Strength controls)**
Concrete edge failure in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength

Vsa = ESR value refer to ICC-ES ESR-3187


f Vsteel ³ Vua ACI 318-08 Eq. (D-2)

Variables
Ase,V [mm ]
2
futa [N/mm ]
2
aV,seis
245 800.00 0.700

Calculations
Vsa [kN]
117.500

Results
Vsa [kN] f steel f eb f Vsa [kN] Vua [kN]
117.500 0.600 0.800 56.400 11.250

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.89

www.hilti.com.kw
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

4.2 Steel failure (with lever arm)

M aM · M s
Vs = bending equation for stand-off
Lb

Ms = Ms
0
(1 - fNN )
ua

sa
resultant flexural resistance of anchor
0
Ms = (1.2) (S) (fu,min) characteristic flexural resistance of anchor

( N
1 - f ua
Nsa ) reduction for tensile force acting simultaneously with a shear force on the anchor
3
p(d)
S = elastic section modulus of anchor bolt at concrete surface
32
Lb = z + (n)(d0) internal lever arm adjusted for spalling of the surface concrete
f VM
s ³ Vua ACI 318-08 Eq. (D-2)

Variables
aM fu,min [N/mm ]
2
Nua [kN] f Nsa [kN] z [mm] n d0 [mm]
2.00 800.00 0.000 127.400 25.0 0.500 20.0

Calculations

0
Ms [kNm] (1 - fNN )
ua

sa Ms [kNm] Lb [mm]
0.519 1.000 0.519 35.0

Results
M
Vs [kN] f steel f VM
s [kN] Vua [kN]
29.678 0.600 17.807 11.250

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.89

www.hilti.com.kw
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

4.3 Pryout Strength (Concrete Breakout Strength controls)

Vcpg = kcp [(AA ) y Nc

Nc0
ec,N y ed,N y c,N y cp,N Nb ] ACI 318-08 Eq. (D-31)
f Vcpg ³ Vua ACI 318-08 Eq. (D-2)
ANc see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
2
ANc0 = 9 hef ACI 318-08 Eq. (D-6)

( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-08 Eq. (D-9)
1+
3 hef

y ed,N = 0.7 + 0.3 (1.5h


c
) £ 1.0 a,min

ef
ACI 318-08 Eq. (D-11)

= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-08 Eq. (D-13)
c ac ac

Nb = kc l √f'c h1.5
ef ACI 318-08 Eq. (D-7)

Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 200.0 0.0 0.0 ∞

'
y c,N cac [mm] kc l fc [psi]
1.000 343.9 17 1 5,076

Calculations
ANc [mm ]
2
ANc0 [mm ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
518,400 360,000 1.000 1.000 1.000 1.000 119.043

Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
342.844 0.700 239.991 45.000

5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the
potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or
where pullout or pryout strength governs.
• ACI 318 does not specifically address anchor bending when a stand-off condition exists. PROFIS Engineering calculates a shear load
corresponding to anchor bending when stand-off exists and includes the results as a shear Design Strength!
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• The present version of the software does not account for special design provisions for overhead applications. Refer to related approval (e.g.
section 4.1.1 of the ICC-ESR 2322) for details.
• For additional information about ACI 318 strength design provisions, please go to
https://submittals.us.hilti.com/PROFISAnchorDesignGuide/

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.89

www.hilti.com.kw
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.89

www.hilti.com.kw
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

6 Installation data
Anchor type and diameter: HIT-HY 200 + HAS-U 8.8 M20
Profile: I profile, ; (L x W x T x FT) = 203.0 mm x 204.0 mm x 7.0 mm x 11.0 Item number: 2237092 HAS-U 8.8 M20x300 (element) /
mm 2045030 HIT-HY 200-A (adhesive)
Hole diameter in the fixture: df = 22.0 mm Maximum installation torque: 150 Nm
Plate thickness (input): 10.0 mm Hole diameter in the base material: 22.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 200.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 244.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required

M20 Hilti HAS-U Carbon steel threaded rod with Hilti HIT-HY 200

6.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • Torque wrench
the hole
• Proper diameter wire brush

y
110.0 110.0
50.0

3 4
110.0
120.0

x
110.0

1 2
50.0

50.0 120.0 50.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -60.0 -60.0 - - - -
2 60.0 -60.0 - - - -
3 -60.0 60.0 - - - -
4 60.0 60.0 - - - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.89

www.hilti.com.kw
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

7 Alternative fastening
7.1 Alternative fastening data

Anchor type and diameter: HVU2 + HAS-U 8.8 M20


Item number: 2223887 HAS-U 8.8 M20x260 (element) / 2164509
HVU2 M20x170 (capsule)
Effective embedment depth: hef,act = 170.0 mm, hnom = 170.0 mm
Material: 8.8
Evaluation Service Report: ESR-4372
Issued I Valid: 1.06.2022 | 1.06.2024
Proof: Design Method ACI 318-08 / Chem
Stand-off installation: without clamping (anchor); restraint level (anchor plate): 2.00; eb = 20.0 mm; t = 10.0 mm
2
Hilti Grout: CB-G EG, epoxy, fc,Grout = 120.00 N/mm
Anchor plate :
R lx x ly x t = 220.0 mm x 220.0 mm x 10.0 mm; (Recommended plate thickness: not calculated)

Profile: I profile, ; (L x W x T x FT) = 203.0 mm x 204.0 mm x 7.0 mm x 11.0 mm


Base material: cracked concrete, C35/45, fc' = 5,076 psi; h = 500.0 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry, Installation direction: vertical downward
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Seismic loads (cat. C, D, E, or F) no

Max. Utilization with HVU2 + HAS-U 8.8 M20: 64 %


Fastening meets the design criteria!

7.2 Installation data

Anchor type and diameter: HVU2 + HAS-U 8.8 M20


Profile: I profile, ; (L x W x T x FT) = 203.0 mm x 204.0 mm x 7.0 mm x 11.0 Item number: 2223887 HAS-U 8.8 M20x260 (element) /
mm 2164509 HVU2 M20x170 (capsule)
Hole diameter in the fixture: df = 22.0 mm Maximum installation torque: 150 Nm
Plate thickness (input): 10.0 mm Hole diameter in the base material: 22.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 170.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 220.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required

M20 Hilti HAS-U Karbon çeliği Dişli rod ile Hilti HVU2

7.2.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • HVA square drive shafts
• Properly sized drill bit accessories to blow from the bottom of • Torque wrench
the hole
• Proper diameter wire brush

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.89

www.hilti.com.kw
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: A1-11-PC-C03___20231129 Date: 29.11.2023
Fastening point:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan