Hilti PROFIS Engineering 3.0.

83

www.hilti.com.hk
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200-R + Rebar 25mm
Return period (service life in years): 50
Item number: not available (element) / 2045036 HIT-HY 200-R
(adhesive)
Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 440.0 mm (hef,limit = - mm)
Material: B500B
Evaluation Service Report: ETA 12/0084
Issued I Valid: 10/12/2021 | -
Proof: Based on Engineering judgement SOFA BOND - based on ETAG BOND testing with a load factor 2
and global safety factor 3
Stand-off installation: without clamping (anchor); restraint level (anchor plate): 2.00; eb = 120.0 mm; t = 30.0 mm
2
Hilti Grout: , multipurpose, fc,Grout = 45.00 N/mm
Anchor plate :
R lx x ly x t = 400.0 mm x 400.0 mm x 30.0 mm; (Recommended plate thickness: 25.0 mm)

Profile: Pipe, ; (L x W x T) = 165.0 mm x 165.0 mm x 8.0 mm


Base material: 2
cracked concrete, C35, fc,cube = 35.00 N/mm ; h = 700.0 mm, Temp. short/long: 40/24 °C
Installation: automatic cleaned drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = -3.400; Vx = 4.400; Vy = 0.000; no no 89
Mx = 0.000; My = 19.500; Mz = 0.000;

2 Load case/Resulting anchor forces y


3 4

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 29.151 1.113 1.113 -0.012
2 0.000 1.114 1.114 0.015 x
3 28.267 1.087 1.087 -0.012 Tension Compression
4 0.605 1.087 1.087 0.009

max. concrete compressive strain: 0.11 [‰]


max. concrete compressive stress: 3.32 [N/mm ]
2
1
resulting tension force in (x/y)=(-158.3/5.7): 58.023 [kN] 2
resulting compression force in (x/y)=(167.9/5.4): 61.423 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

3 Tension load (Based on EOTA TR 029, Section 5.2.2 FOS = 3)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 29.151 90.000 33 OK
Combined pullout-concrete cone failure** 58.023 93.627 62 OK
Concrete Breakout Failure** 58.023 75.976 77 OK
Splitting failure** 58.023 75.939 77 OK

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

NRk,s [kN] gM,s NRd,s [kN] NSd [kN]


270.000 3.000 90.000 29.151

3.2 Combined pullout-concrete cone failure


2 0 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,25 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm]
660,720 400,000 12.00 632.5 316.2 204.5
0
yc t Rk,cr [N/mm ]
2
k y g,Np y g,Np
1.034 7.24 2.300 1.362 1.120

ec1,N [mm] y ec1,Np ec2,N [mm] y ec2,Np y s,Np y re,Np


82.7 0.793 52.9 0.857 0.894 1.000
0
NRk,p [kN] NRk,p [kN] gM,p NRd,p [kN] NSd [kN]
250.180 280.880 3.000 93.627 58.023

Group anchor ID
1, 3, 4

3.3 Concrete Breakout Failure


2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm]
1,517,819 1,587,600 660.0 1,320.0
' ' '
hef [mm] ccr,N [mm] scr,N [mm]
420.0 630.0 1,260.0

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


82.7 0.884 52.9 0.923 0.797 1.000
0
k1 NRk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.200 366.641 3.000 75.976 58.023

Group anchor ID
1, 3, 4

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

3.4 Splitting failure


0 2
Ac,N [mm ]
2
Ac,N [mm ] ccr,sp [mm] scr,sp [mm] y h,sp
1,517,819 1,587,600 764.0 1,528.0 1.245
' ' '
hef [mm] ccr,sp [mm] scr,sp [mm]
362.8 630.0 1,260.0

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1


82.7 0.884 52.9 0.923 0.797 1.000 7.200
0
NRk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
294.385 3.000 75.939 58.023

Group anchor ID
1, 3, 4

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

4 Shear load (Based on EOTA TR 029, Section 5.2.3 FOS = 3)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* N/A N/A N/A N/A
Steel failure (with lever arm)* 1.113 3.092 36 OK
Pryout Strength** 4.400 206.913 3 OK
Concrete edge failure in direction x+** 4.400 36.885 12 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel failure (with lever arm)

l [mm] aM
147.5 2.00
0 0
NSd / NRd,s 1 - NSd / NRd,s MRk,s [kNm] MRk,s = MRk,s (1 - NSd/ NRd,s) [kNm]
0.324 0.676 1.012 0.684
M M
VRk,s = aM * MRk,s / l [kN] gMs,b,V VRd,s [kN] VSd [kN]
9.277 3.000 3.092 1.113

4.2 Pryout Strength (Concrete Breakout Strength controls)


2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k-factor
1,580,237 1,267,876 660.0 1,320.0 2.000
' ' '
hef [mm] ccr,N [mm] scr,N [mm]
375.3 563.0 1,126.0

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N


0.0 1.000 3.5 0.994 0.809 1.000
0
NRk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
309.736 3.000 206.913 4.400

Group anchor ID
1-4

4.3 Concrete edge failure in direction x+

lf [mm] dnom [mm] k1 a b


300.0 25.00 1.700 0.080 0.056
' 2 0 2
c1 [mm] c1 [mm] Ac,V [mm ] Ac,V [mm ]
563.0 466.7 764,750 980,000

y s,V y h,V y a,V ec,V [mm] y ec,V y re,V


0.788 1.000 1.000 1.1 0.998 1.000
0
VRk,c [kN] gM,c VRd,c [kN] VSd [kN]
180.315 3.000 36.885 4.400

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

5 Combined tension and shear loads (Based on EOTA TR 029, Section 5.2.4 FOS = 3)
Steel failure

bN bV a Utilization bN,V [%] Status


0.764 0.360 1.500 89 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 21.594 [kN] dN = 0.0687 [mm]


VSk = 0.824 [kN] dV = 0.0247 [mm]
dNV = 0.0730 [mm]
Long term loading:

NSk = 21.594 [kN] dN = 0.1000 [mm]


VSk = 0.824 [kN] dV = 0.0412 [mm]
dNV = 0.1081 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• Your design has selected filled holes. Please ensure that there is a proper method to fill the annular gap between the fixture and HIT-HY
200-R + Rebar 25mmand contact Hilti in case of any questions.
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Characteristic bond resistances depend on short- and long-term temperatures.
• The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100:1998, etc.) is the responsibility of the user
• An SLS-check is not performed for SOFA and has to be provided by the user!
• The characteristic bond resistances depend on the return period (service life in years): 50

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

8 Anchor plate stress check


Scope: For the loads / load combinations applied on the anchor plate, an anchor plate stress check is performed (based on the results of a FE
calculation). This stress check contains normal stresses resulting from bending moments in two directions. The user is responsible to select
an anchor plate thickness that meets the requirement per guideline for a rigid anchor plate (to ensure that the assumed load distribution is
(1)
correct). A detailed description can be found in Mallée.

(1)
Mallée, R.; Riemann, H. (1990): Ankerplattenbefestigungen mit Hinterschnittdübeln,
Bauingenieur 65 (1990), S. 49 - 57, Springer VDI-Verlag, 1990
Mallée, R.; Burkhardt, F. (1999): Befestigungen von Ankerplatten mit Dübeln, Beton und
Stahlbetonbau 94, Heft 12, S. 502 - 511, Ernst & Sohn Verlag, 1999

8.1 Base material properties

Steel type: GB Q235


2
Yield stress: fy = 205.00 [N/mm ]
Partial safety factor: gm,s = 1.000
2
Ultimate strength: fu = 370.00 [N/mm ]
2
Young's modulus: Es = 205,000.00 [N/mm ]
Poisson ratio: n = 0.3

8.2 Results

Relevant load combination: LC 01

Stress distribution s 11

2
172.53 [N/mm ]

2
-64.84 [N/mm ]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

Stress distribution s 22

2
75.86 [N/mm ]

2
-134.76 [N/mm ]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

Deformations (z-direction)
0.4 [mm]

-0.3 [mm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

9 Installation data
2 2
Anchor plate, steel: GB Q235; E = 205,000.00 N/mm ; fyk = 205.00 N/mm Anchor type and diameter: HIT-HY 200-R + Rebar 25mm
Profile: Pipe, ; (L x W x T) = 165.0 mm x 165.0 mm x 8.0 mm Item number: not available (element) / 2045036 HIT-HY
200-R (adhesive)
Hole diameter in the fixture: df = 25.0 mm Maximum installation torque: -
Plate thickness (input): 30.0 mm Hole diameter in the base material: 32.0 mm
Recommended plate thickness: 25.0 mm Hole depth in the base material: 440.0 mm
Drilling method: SafeSet - automatic cleaning Minimum thickness of the base material: 504.0 mm
Cleaning: Automatically performed while drilling

Rebar with HIT-HY 200 injection mortar with 440 mm embedment h_ef, 25mm, SAFEset - automatic cleaning installation per ETA 12/0084,
with annular gaps filled with Hilti Filling set or any suitable gap solutions

9.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Dispenser including cassette and mixer
• Properly sized drill bit for SAFEset - • For deep installations, a piston plug is
automatic cleaning (TE-CD / TE-YD) necessary
• Vacuum cleaner • Filling set
• Torque wrench

y
200.0 200.0
37.0

3 4
200.0
313.0

x
200.0

1
12.0

2
38.0

38.0 255.0 67.0 38.0

Coordinates Anchor [mm] 2.0

Anchor x y c-x c+x c-y c+y


1 -162.0 -150.0 563.0 887.0 575.0 517.5
2 162.0 -162.0 887.0 563.0 563.0 529.5
3 -160.0 163.0 565.0 885.0 888.0 204.5
4 95.0 163.0 820.0 630.0 888.0 204.5

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11
Hilti PROFIS Engineering 3.0.83

www.hilti.com.hk
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Jan 19, 2023 (1) Date: 14/2/2023
Fastening point:

10 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan