Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-RE 500 V4 + HAS-U 5.8 M12
Return period (service life in years): 50
Item number: 2223821 HAS-U 5.8 M12x110 (element) / 2287553
HIT-RE 500 V4 (adhesive)
Effective embedment depth: hef,opti = 70.0 mm (hef,limit = 220.0 mm)
Material: 5.8
Evaluation Service Report: ETA 20/0541
Issued I Valid: 09/06/2023 | -
Proof: Design Method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0.0 mm (no stand-off); t = 10.0 mm
Anchor plate :
R lx x ly x t = 250.0 mm x 250.0 mm x 10.0 mm; (Recommended plate thickness: not calculated)
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
3 4
Anchor forces are calculated based on the assumption of a rigid anchor plate.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
N
NSd £ NRd,s = Rk,s EOTA TR 029, Table 5.2.2.1
gM,s
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
N
NSd £ NRd,p = Rk,p EOTA TR 029, Table 5.2.2.1
gM,p
0 Ap,N
NRk,p = NRk,p · 0
· y s,Np · y g,Np · y ec1,Np · y ec2,Np · y re,Np EOTA TR 029, Eq. (5.2)
Ap,N
0
NRk,p = p · d · hef · t Rk EOTA TR 029, Eq. (5.2a)
0
Ap,N = scr, Np · scr,Np EOTA TR 029, Eq. (5.2b)
0.5
t Rk,ucr
scr,Np = 20 · d · (
7.5 )
£ 3 · hef EOTA TR 029, Eq. (5.2c)
s
ccr,Np = cr,Np EOTA TR 029, Eq. (5.2d)
2
c
y s,Np = 0.7 + 0.3 · 1.00 EOTA TR 029, Eq. (5.2e)
ccr,Np £
0,5
y g,Np
0
= y g,Np - (s s )
cr,Np
· (y g,Np - 1) ³ 1.00
0
EOTA TR 029, Eq. (5.2f)
1,5
0
y g,Np = √n - (√n - 1) · (k · √dh · t· f ef
Rk
ck,cube
) ³ 1.00 EOTA TR 029, Eq. (5.2g)
1
y ec1,Np = 1.00 EOTA TR 029, Eq. (5.2h)
2 · ec1,N £
1+
scr,Np
1
y ec2,Np = 1.00 EOTA TR 029, Eq. (5.2h)
2 · ec2,N £
1+
scr,Np
h
y re,Np = 0.5 + ef £ 1.00 EOTA TR 029, Eq. (5.2i)
200
2 0 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,25 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm]
148,225 44,100 18.00 210.0 105.0 100.0
0
yc t Rk,cr [N/mm ]
2
k y g,Np y g,Np
1.000 11.00 2.300 1.000 1.000
Group anchor ID
1-4
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
N
NSd £ NRd,c = Rk,c EOTA TR 029, Table 5.2.2.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N EOTA TR 029, Eq. (5.3)
Ac,N
0 1,5
NRk,c = k1 · √fck,cube · hef EOTA TR 029, Eq. (5.3a)
0
Ac,N = scr,N · scr,N EOTA TR 029, Eq. (5.3b)
c
y s,N = 0.7 + 0.3 · 1.00 EOTA TR 029, Eq. (5.3c)
ccr,N £
hef
y re,N = 0.5 + 1.00 EOTA TR 029, Eq. (5.3d)
200 £
1
y ec1,N = 1.00 EOTA TR 029, Eq. (5.3e)
2 · ec1,N £
1+
scr,N
1
y ec2,N = 1.00 EOTA TR 029, Eq. (5.3e)
2 · ec2,N £
1+
scr,N
2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm]
148,225 44,100 105.0 210.0
Group anchor ID
1-4
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
V
VSd £ VRd,s = Rk,s EOTA TR 029, Table 5.2.3.1
gM,s
V
VSd £ VRd,cp = Rk,cp EOTA TR 029, Table 5.2.3.1
gM,c,p
VRk,cp = k · min (NRk,p; NRk,c) EOTA TR 029, Eq. (5.7), (5.7a)
0 A
NRk,c = NRk,c · 0c,N · y s,N · y re,N · y ec1,N · y ec2,N EOTA TR 029, Eq. (5.3)
Ac,N
0 1,5
NRk,c = k1 · √fck,cube · hef EOTA TR 029, Eq. (5.3a)
0
Ac,N = scr,N · scr,N EOTA TR 029, Eq. (5.3b)
c
y s,N = 0.7 + 0.3 · £ 1.00 EOTA TR 029, Eq. (5.3c)
ccr,N
hef
y re,N = 0.5 + 1.00 EOTA TR 029, Eq. (5.3d)
200 £
1
y ec1,N = 1.00 EOTA TR 029, Eq. (5.3e)
2 · ec1,V £
1+
scr,N
1
y ec2,N = 1.00 EOTA TR 029, Eq. (5.3e)
2 · ec2,V £
1+
scr,N
2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k-factor k1
148,225 44,100 105.0 210.0 2.000 7.200
Group anchor ID
1-4
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
V
VSd £ VRd,c = Rk,c EOTA TR 029, Table 5.2.3.1
gM,c
0 Ac,V
VRk,c = VRk,c · 0
· y s,V · y h,V · y a,V · y ec,V · y re,V EOTA TR 029, Eq. (5.8)
Ac,V
0 a b 1,5
VRk,c = k1 · dnom · hef · √fck,cube · c1 EOTA TR 029, Eq. (5.8a)
0,5
a = 0.1 · ( ) hef
c1
EOTA TR 029, Eq. (5.8b)
0,2
= 0.1 · (
c )
d nom
b EOTA TR 029, Eq. (5.8c)
1
0 2
Ac,V = 4.5 · c1 EOTA TR 029, Eq. (5.8d)
c2
y s,V = 0.7 + 0.3 · 1.00 EOTA TR 029, Eq. (5.8e)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 EOTA TR 029, Eq. (5.8f)
√
1
2
y a,V =
(cos aV) +
2
(sin2.5a )
V ³ 1.00 EOTA TR 029, Eq. (5.8g)
1
y ec,V = 1.00 EOTA TR 029, Eq. (5.8h)
2 · ec,V £
1+
3 · c1
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
a a
bN + bV £ 1.0
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Characteristic bond resistances depend on short- and long-term temperatures.
• Edge reinforcement is not required to avoid splitting failure
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
8 Installation data
Anchor plate, steel: E 165 (Fe 290); E = 200,000.00 N/mm ; fyk = 165.00
2 Anchor type and diameter: HIT-RE 500 V4 + HAS-U 5.8
N/mm
2 M12
Profile: ISLB, ISLB 125; (L x W x T x FT) = 125.0 mm x 75.0 mm x 4.4 mm x Item number: 2223821 HAS-U 5.8 M12x110 (element) /
6.5 mm 2287553 HIT-RE 500 V4 (adhesive)
Hole diameter in the fixture: df = 14.0 mm Maximum installation torque: 40 Nm
Plate thickness (input): 10.0 mm Hole diameter in the base material: 14.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 70.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required
Hilti HAS-U threaded rod with HIT-RE 500 V4 injection mortar with 70 mm embedment h_ef, M12, Steel galvanized, Hammer drilled
installation per ETA 20/0541
y
125.0 125.0
35.0
3 4
125.0
180.0
x
125.0
1 2
35.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.87
www.hilti.in
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - Aug 30, 2023 Date: 30/08/2023
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10