Effective Roof area Calculation for Each Down Take pipe


Width Of Roof Ah1 = 14.000 M
Downspout spacing Lr1 = 49.750 M Design of Gravity Drainage System Inside Buildings : As Per
Roof Height Av1 = 4.444 M
Width Of Roof Ah2 = 0.000 M BS-EN-12056-3:2000
Downspout spacing Lr2 = 0.000 M Notes: 1. Provide Roof and Wall Sheeting area per Downspout spacings
Roof Height Av2 = 0.000 M 2. Risk Factors for Eave gutter 1 and Non Eave Gutters 2 considered in design.
Wall area calculation 2. Vertical downspouts are assumed to flow at 0.33 fillings.
Wall Height Awh1 = 1.500 M 3. Header Pipe is designed at End of Horizontal Pipe, pipe size can be reduced at upstream end.
Length of wall Lw1 = 49.750 M 4. If non circular section used for Downspouts, equivalent c/s area circular pipe dia to be used in calculations
Wall Height Awh2 = 0.000 M 5.In Colebrook-White Formula roughness co efficient 0.15mm used
Length of wall Lw1 = 0.000 M 6. Header Pipe assumed to have slope on 1 in 300
7. Gutters are designed as level gutters ( 3 mm/m or less. Slope).
Rain water Intensity I = 31.000 mm/h 8. Gutters are designed to carry 0.9 * Cross sectional area.
9. free board is provided for Valley and Parapet Gutters and no free board for eave gutters considered.
L = Length of Gutter(Verti., Pipe Dist.) = 29.875 M 11.In Header pipe systems Tapered outlet considered with sizes, Do>1.5di; Lt > Do
Proposed Gutter Size: Required Flow Capacity Design Flow Capacity Check MBMA calculation check
Width Of Gutter Sole S = 0.250 M Eave Gutter = 7.27 L/S Eave Gutter = 23.68 L/S Safe Downspout spacing (Ds) based on Gutter capacity: = 92.901 m
Height Of Gutter Total Z = 0.250 M Valley Gutter = 7.27 L/S Valley Gutter = 16.95 L/S Safe Downspout spacing (Ds) based on Verti, pipe capacity: = 100.972 m
Design Width of water flowing T = 0.250 M
Capacity of Vertical Rainwater pipes
Down Take Pipe Size Di (mm) = 160 mm Design Capacity = 37.52 L/S Safe

Header Pipe Design:


D =Inside diameter if 1 Pipe used = 160 mm Required Header Flow Capacity = 7.27 L/S
D =Inside diameter if 2 Pipe used = 0 mm Design Capacity Of Header With 1 pipe = 9.62 L/S Safe with 1 pipe Project No: SIPL-PEB-1484
Number Of Vertical Pipes in Sys.. = 1 Nos. Design Capacity Of Header With 2 pipe #DIV/0! #DIV/0! Date: 23-Nov-22
Prep. by M.Rajan